HVAC Calculations Mixed Air Calculator Humidification and Reheat

This document contains calculations for an air handling unit (AHU) for a commercial office building project. It calculates the mixed air temperature and humidity ratio based on supply air flow, return air flow, and outdoor air flow rates and conditions. It then determines the humidification needed to meet the winter indoor humidity ratio and calculates the reheat needed to lower the supply air temperature to the desired setpoint. The reheat load is calculated to be approximately 4.7 kW.

Uploaded by

esagcojr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
559 views

HVAC Calculations Mixed Air Calculator Humidification and Reheat

This document contains calculations for an air handling unit (AHU) for a commercial office building project. It calculates the mixed air temperature and humidity ratio based on supply air flow, return air flow, and outdoor air flow rates and conditions. It then determines the humidification needed to meet the winter indoor humidity ratio and calculates the reheat needed to lower the supply air temperature to the desired setpoint. The reheat load is calculated to be approximately 4.7 kW.

Uploaded by

esagcojr
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 1

HVAC Calculations

Project Name:
Subject:
Project Number:

Commercial Office Building


AHU X-X
XXX

Mixed Air Calculator


Supply Air CFM

1,000

CFM

R.A.
900

Temps. (F)
Winter
Summer

CFM
%
90.0%

O.A.
100

65
75

Humidity Ratios (gr/lbm air)


Winter
40
Summer
53

%
10.0%

Mixed

23
98

60.8
77.3

0
70

36.0
54.7

Humidification
Humidity Ratios
Winter Mixed Air
Winter Indoor Air
Difference

36.0
40.0
4.0

(gr/lbm air)
(gr/lbm air)
(gr/lbm air)

Specific Volume

13.4

(ft^3/lbm air)

1,000

ft^3
min

4.0 gr
lbm air

lbm air
13.4 ft^3

60 min
hr

lbm H2O
7000 gr

2.6

lbm H2O
hr

Reheat
Supply Air Temp
Mixed Air Temp.
Reheat =

55.0
77.3
22.3 F x

F
F
1,000

CFM

1.085

Btuh
24,196

Watts
7,089

kW
7.1

*Correction Factor =

0.66

Btuh*
15,969

281921966.xls