ps1 PDF
ps1 PDF
Code: EE61
No.of Hrs.: 35
SUBJECT EXPERTS:
Dr. MS Raviprakasha, Professor of E&EE, MCE, Hassan
Dr. GK Purushothama, Professor of E&EE, MCE, Hassan
Dr. K Umarao, Prof. & HOD of E&EE, RNSIT, Bangalore
LECTURE SCHEDULE:
Dr. MS Raviprakasha: Chapters # 1, 2 & 4 (Introduction,
Representation of Power systems, Sym. 3-phase faults & Unsym.
Faults Part I): (14 Hrs.) (Plus 3 concluding Sessions)
Dr. GK Purushothama: Chapter # 3 (Sym. Components &
Unsym. Faults-Part II): (13 hrs.)
Dr. K Umarao: Chapter # 5 (Stability Studies): (08 Hrs.)
PROGRAMME SCHEDULE:
14 Hrs. (8 + 6 Hrs.) of Class by Dr. MS Raviprakasha, MCE,
Hassan
13 Hrs. (9 + 4 Hrs.) of Class by Dr. GK Purushothama, MCE,
Hassan
3 Classes per week: Mon (2 pm), Thu (11 am) & Fri (11 am)
CONTENTS (CHAPTER-WISE)
Chapter 1
REPRESENTATION OF POWER SYSTEMS
Chapter 2
SYMMETRICAL THREE PHASE FAULTS
Chapter 3
SYMMETRICAL COMPONENTS
Chapter 4
UNSYMMETRICAL FAULTS
Chapter 5
STABILITY STUDIES
TEXTS/ REFERENCES:
1.
2.
3.
4.
PREREQUISITE SUBJECTS:
1. DC and Synchronous Machines
2. Transmission and distribution
3. Transformers and induction machines
TOPICS
SUB-TOPICS
Representation of
1.
Power systems
- SLD/ OLD
- React./ Imp. Diagram
- per unit Systems
Electric Power
2.
System
- Generation - Machines
- Transmission Trans- Distribution formers
- Utilization Tariffs
3. Fault studies
- Sym. Faults
- Sym. Components
- Seq. Imps. / Networks
- Unsymmetrical Faults
4. System Stability
- SSS, TS, DS
- Angle Stability
- Solution of Equations
- EAC, Clarkes Diagram
5.
- Incidence Matrices
- Frames of Reference
- Singular/ NS Transformations
- Network Matrices
- Node Elimination
- ZBUS Building
6.
Present Scenario
No.
SUB-TOPICS
TOPICS
7.
Reactive Power
Management
- Importance of VArs
- Compensation Devices,
Sizing, Placement,
Design, Optimality,
- VAr Dispatch
- VAr Co-ordination
8.
Gen. Expansion
Planning
- Optimality
- Load Prediction: Short,
Medium and Long Term
Forecasting
9.
Operation and
Control
10.
System
Reliability
- Requirements
- Methods
- Unit Commitment
- Parallel Operation
- Optimal Load Dispatch
- Constraints
12. Instrumentation
- CTs, PTs
- SCADA
- Bad Data Elimination
- Security/ Cont. Studies
Future Trends
No.
TOPICS
SUB-TOPICS
14.
Voltage Stability
- Importance
- Angle/ Voltage stability
- P- Vs. Q- |V| Analysis
- Proximity Indices
- WBOV
15.
Power System
Simulators
- Requirements
- Control Blocks
- Data-Base Definition
16.
Energy Auditing
- Deregulation
17.
Demand Side
Management
18.
Renewable Energy
- The Paradigm
19.
Sparsity Oriented
Programming
- Sparsity: YBUS
- Ordering Schemes
- LU- Factorization: Fills
- Pivoting
- UD Table Storage
20.
Recent Computer
Applications
CHAPTER 1
REPRESENTATION OF POWER SYSTEMS
[CONTENTS: One line diagram, impedance diagram, reactance diagram, per unit
quantities, per unit impedance diagram, formation of bus admittance &
impedance matrices, examples]
Example system
Consider for illustration purpose, a sample example power system and data as under:
Generator 1: 30 MVA, 10.5 KV, X= 1.6 ohms, Generator 2: 15 MVA, 6.6 KV, X=
1.2 ohms, Generator 3: 25 MVA, 6.6 KV, X= 0.56 ohms, Transformer 1 (3-phase):
15 MVA, 33/11 KV, X=15.2 ohms/phase on HT side, Transformer 2 (3-phase): 15
MVA, 33/6.2 KV, X=16.0 ohms/phase on HT side, Transmission Line: 20.5 ohms per
phase, Load A: 15 MW, 11 KV, 0.9 PF (lag); and Load B: 40 MW, 6.6 KV, 0.85 PF
(lag). The corresponding SLD incorporating the standard symbols can be shown as in
figure 2.
10
It is observed here, that the generators are specified in 3-phase MVA, L-L voltage and
per phase Y-equivalent impedance, transformers are specified in 3-phase MVA, L-L
voltage transformation ratio and per phase Y-equivalent impedance on any one side and
the loads are specified in 3-phase MW, L-L voltage and power factor.
Example system
As per the list of assumptions as above and with reference to the system of figure 2, the
impedance diagram can be obtained as shown in figure 3.
11
Note: These impedance & reactance diagrams are also refered as the Positive Sequence
Diagrams/ Networks.
12
In an electrical power system, the parameters of interest include the current, voltage,
complex power (VA), impedance and the phase angle. Of these, the phase angle is
dimensionless and the other four quantities can be described by knowing any two of
them. Thus clearly, an arbitrary choice of any two base values will evidently fix the other
base values.
Normally the nominal voltage of lines and equipment is known along with the complex
power rating in MVA. Hence, in practice, the base values are chosen for complex power
(MVA) and line voltage (KV). The chosen base MVA is the same for all the parts of the
system. However, the base voltage is chosen with reference to a particular section of the
system and the other base voltages (with reference to the other sections of the systems,
these sections caused by the presence of the transformers) are then related to the chosen
one by the turns-ratio of the connecting transformer.
If Ib is the base current in kilo amperes and Vb, the base voltage in kilovolts, then the base
MVA is, Sb = (VbIb). Then the base values of current & impedance are given by
Base current (kA), Ib = MVAb/KVb
= Sb/Vb
(1.1)
(1.2)
(1.3)
In 3-phase systems, KVb is the line-to-line value & MVAb is the 3-phase MVA. [1-phase
MVA = (1/3) 3-phase MVA].
Changing the base of a given pu value:
It is observed from equation (3) that the pu value of impedance is proportional directly to
the base MVA and inversely to the square of the base KV. If Zpunew is the pu impedance
required to be calculated on a new set of base values: MVAbnew & KVbnew from the
already given per unit impedance Zpuold, specified on the old set of base values,
MVAbold & KVbold , then we have
(1.4)
On the other hand, the change of base can also be done by first converting the given pu
impedance to its ohmic value and then calculating its pu value on the new set of base
values.
Merits and Demerits of pu System
Following are the advantages and disadvantages of adopting the pu system of
computations in electric power systems:
Merits:
13
The pu value is the same for both 1-phase and & 3-phase systems
The pu value once expressed on a proper base, will be the same when refereed to
either side of the transformer. Thus the presence of transformer is totally
eliminated
The variation of values is in a smaller range 9nearby unity). Hence the errors
involved in pu computations are very less.
Usually the nameplate ratings will be marked in pu on the base of the name plate
ratings, etc.
Demerits:
If proper bases are not chosen, then the resulting pu values may be highly absurd
(such as 5.8 pu, -18.9 pu, etc.). This may cause confusion to the user. However,
this problem can be avoided by selecting the base MVA near the high-rated
equipment and a convenient base KV in any section of the system.
(1.5)
(1.6)
14
(1.7)
Of the various network matrices refered above, the bus admittance matrix (YBUS) and the
bus impedance matrix (ZBUS) are determined for a given power system by the rule of
inspection as explained next.
Rule of Inspection
Consider the 3-node admittance network as shown in figure5. Using the basic branch
relation: I = (YV), for all the elemental currents and applying Kirchhoffs Current Law
principle at the nodal points, we get the relations as under:
At node 1: I1 =Y1V1 + Y3 (V1-V3) + Y6 (V1 V2)
At node 2: I2 =Y2V2 + Y5 (V2-V3) + Y6 (V2 V1)
At node 3: 0 = Y3 (V3-V1) + Y4V3 + Y5 (V3 V2)
(1.8)
These are the performance equations of the given network in admittance form and they
can be represented in matrix form as:
I1
(Y1+Y3 +Y6)
I2
-Y6
-Y3
-Y6
-Y3
V1
(Y2+Y5 +Y6)
-Y5
V2
-Y5
(Y3 +Y4+Y5)
V3
(1.9)
In other words, the relation of equation (9) can be represented in the form
IBUS = YBUS EBUS
(1.10)
Where, YBUS is the bus admittance matrix, IBUS & EBUS are the bus current and bus
voltage vectors respectively.
By observing the elements of the bus admittance matrix, YBUS of equation (9), it is
observed that the matrix elements can as well be obtained by a simple inspection of the
given system diagram:
15
Diagonal elements: A diagonal element (Yii) of the bus admittance matrix, YBUS, is equal
to the sum total of the admittance values of all the elements incident at the bus/node i,
Off Diagonal elements: An off-diagonal element (Yij) of the bus admittance matrix, YBUS,
is equal to the negative of the admittance value of the connecting element present
between the buses I and j, if any.
This is the principle of the rule of inspection. Thus the algorithmic equations for the rule
of inspection are obtained as:
Yii = yij
(j = 1,2,.n)
Yij = - yij
(j = 1,2,.n)
(1.11)
For i = 1,2,.n, n = no. of buses of the given system, yij is the admittance of element
connected between buses i and j and yii is the admittance of element connected between
bus i and ground (reference bus).
Bus impedance matrix
In cases where, the bus impedance matrix is also required, then it cannot be formed by
direct inspection of the given system diagram. However, the bus admittance matrix
determined by the rule of inspection following the steps explained above, can be inverted
to obtain the bus impedance matrix, since the two matrices are inter-invertible. Note: It
is to be noted that the rule of inspection can be applied only to those power systems that
do not have any mutually coupled elements.
1.7 Examples
I EXAMPLES ON RULE OF INSPECTION:
Problem #1: Obtain the bus admittance matrix for the admittance network shown aside
by the rule of inspection
YBUS =
16 -8 -4
-8 24 -8
-4 -8 16
Problem #2: Obtain YBUS and ZBUS matrices for the impedance network shown aside by
the rule of inspection. Also, determine YBUS for the reduced network after eliminating the
eligible unwanted node. Draw the resulting reduced system diagram.
16
YBUS =
-9.8 5 4
5 -16 10
4 10 -14
ZBUS = YBUS-1
YBUSNew = YA-YBYD-1YC
YBUS =
-8.66 7.86
7.86 -8.86
17
= j 1.0256 pu.
18
Problem #2:
Draw the per unit reactance diagram for the system shown in figure below. Choose a base
of 11 KV, 100 MVA in the generator circuit.
Solution:
19
The one line diagram with the data is considered as shown in figure.
Selection of base quantities:
100 MVA, 11 KV in the generator circuit(Given); the voltage bases in other sections are:
11 (115/11.5) = 110 KV in the transmission line circuit and 110 (6.6/11.5) = 6.31 KV in
the motor circuit.
Calculation of pu values:
XG = j 0.1 pu, Xm = j 0.2 (100/90) (6.6/6.31)2 = j 0.243 pu.
Xt1 =Xt2 = j 0.1 (100/50) (11.5/11)2 = j 0.2185 pu.
Xt3 =Xt4 = j 0.1 (100/50) (6.6/6.31)2 = j 0.219 pu.
Xlines = j 20 (100/1102) = j 0.1652 pu.
Eg = 1.000 pu, Em = (6.6/6.31) = 1.04500 pu
Thus the pu reactance diagram can be drawn as shown in figure P2(b).
Problem #3:
A 30 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 15%. The
generator supplies 2 motors through a step-up transformer - transmission line stepdown transformer arrangement. The motors have rated inputs of 20 MVA and 10 MVA at
12.8 KV with 20% sub transient reactance each. The 3-phase transformers are rated at 35
MVA, 13.2 KV- /115 KV-Y with 10 % leakage reactance. The line reactance is 80
ohms. Draw the equivalent per unit reactance diagram by selecting the generator ratings
as base values in the generator circuit.
20
Solution:
The one line diagram with the data is obtained as shown in figure P3(a).
21
Problem #4:
A 33 MVA, 13.8 KV, 3-phase generator has a sub transient reactance of 0.5%. The
generator supplies a motor through a step-up transformer - transmission line step-down
transformer arrangement. The motor has rated input of 25 MVA at 6.6 KV with 25% sub
transient reactance. Draw the equivalent per unit impedance diagram by selecting 25
MVA (3), 6.6 KV (LL) as base values in the motor circuit, given the transformer and
transmission line data as under:
Step up transformer bank: three single phase units, connected Y, each rated 10 MVA,
13.2/6.6 KV with 7.7 % leakage reactance and 0.5 % leakage resistance;
Transmission line: 75 KM long with a positive sequence reactance of 0.8 ohm/ KM and a
resistance of 0.2 ohm/ KM; and
Step down transformer bank: three single phase units, connected Y, each rated 8.33
MVA, 110/3.98 KV with 8% leakage reactance and 0.8 % leakage resistance;
Solution:
The one line diagram with the data is obtained as shown in figure P4(a).
22
23
2. A 100 MVA, 33 KV, 3-phase generator has a sub transient reactance of 15%. The
generator supplies 3 motors through a step-up transformer - transmission line stepdown transformer arrangement. The motors have rated inputs of 30 MVA, 20 MVA and
50 MVA, at 30 KV with 20% sub transient reactance each. The 3-phase transformers are
rated at 100 MVA, 32 KV- /110 KV-Y with 8 % leakage reactance. The line has a
reactance of 50 ohms. By selecting the generator ratings as base values in the generator
circuit, determine the base values in all the other parts of the system. Hence evaluate the
corresponding pu values and draw the equivalent per unit reactance diagram.
[Answers: XG = j 0.15, Xm1 = j 0.551, Xm2 = j 0.826, Xm3 = j 0.331, Eg1=1.0 00, Em1 = Em2
= Em3 = 0.9100, Xt1 = Xt2 = j 0.0775 and Xline = j 0.39 all in per unit]
3. A 80 MVA, 10 KV, 3-phase generator has a sub transient reactance of 10%. The
generator supplies a motor through a step-up transformer - transmission line step-down
transformer arrangement. The motor has rated input of 95 MVA, 6.3 KV with 15% sub
transient reactance. The step-up 3-phase transformer is rated at 90 MVA, 11 KV-Y /110
KV-Y with 10% leakage reactance. The 3-phase step-down transformer consists of three
single phase Y- connected transformers, each rated at 33.33 MVA, 68/6.6 KV with 10%
leakage reactance. The line has a reactance of 20 ohms. By selecting the 11 KV, 100
MVA as base values in the generator circuit, determine the base values in all the other
parts of the system. Hence evaluate the corresponding pu values and draw the equivalent
per unit reactance diagram.
[Answers:
4. For the three-phase system shown below, draw an impedance diagram expressing all
impedances in per unit on a common base of 20 MVA, 2600 V on the HV side of the
transformer. Using this impedance diagram, find the HV and LV currents.
24
25
CHAPTER 2
SYMMETRICAL THREE PHASE FAULTS
2.1 Preamble
in practice, any disturbance in the normal working conditions is termed as a FAULT. The
effect of fault is to load the device electrically by many times greater than its normal
rating and thus damage the equipment involved. Hence all the equipment in the fault line
should be protected from being overloaded. In general, overloading involves the increase
of current up to 10-15 times the rated value. In a few cases, like the opening or closing of
a circuit breaker, the transient voltages also may overload the equipment and damage
them.
In order to protect the equipment during faults, fast acting circuit breakers are put in the
lines. To design the rating of these circuit breakers or an auxiliary device, the fault
current has to be predicted. By considering the equivalent per unit reactance diagrams,
the various faults can be analyzed to determine the fault parameters. This helps in the
protection and maintenance of the equipment.
Faults can be symmetrical or unsymmetrical faults. In symmetrical faults, the fault
quantity rises to several times the rated value equally in all the three phases. For example,
a 3-phase fault - a dead short circuit of all the three lines not involving the ground. On the
other hand, the unsymmetrical faults may have the connected fault quantities in a random
way. However, such unsymmetrical faults can be analyzed by using the Symmetrical
Components. Further, the neutrals of the machines and equipment may or may not be
grounded or the fault may occur through fault impedance. The three-phase fault involving
ground is the most severe fault among the various faults encountered in electric power
systems.
2.2 Transients on a transmission line
Now, let us Consider a transmission line of resistance R and inductance L supplied by an
ac source of voltage v, such that v = Vm sin (t+) as shown in figure 1. Consider the
short circuit transient on this transmission line. In order to analyze this symmetrical 3phase fault, the following assumptions are made:
The supply is a constant voltage source,
The short circuit occurs when the line is unloaded and
26
v = Vm sin (t+)
= iR + L (di/dt)
(2.1)
and
i = Im sin (t+-)
(22.)
Where
(2.3)
Thus
(2.4)
-1
Consider the performance equation of the circuit of figure 1 under circuit as:
iR + L (di/dt) = 0
i.e.,
(R/L + d/dt)i = 0
(2.5)
In order to solve the equation (5), consider the complementary function part of the
solution as: CF = C1 e(-t/)
(2.6)
Where (= L/R) is the time constant and C1 is a constant given by the value of steady
state current at t = 0. Thus we have,
C1 = -is(0)
= - [Vm/Z] sin (-)
= [Vm/Z] sin (-)
(2.7)
(2.8)
Thus the total current under short circuit is given by the solution of equation (1) as
[combining equations (4) and (8)],
27
i =is +it
= [2V/Z] sin (t+-) + [2V/Z] sin (-) e(-R/L)t
(2.9)
Thus, is is the sinusoidal steady state current called as the symmetrical short circuit
current and it is the unidirectional value called as the DC off-set current. This causes the
total current to be unsymmetrical till the transient decays, as clearly shown in figure 2.
(2.10)
now, since the resistance of the transmission line is very small, the impedance angle ,
can be taken to be approximately equal to 900. Hence, we have
imm = [2V/Z] cos + [2V/Z]
(2.11)
28
This value is maximum when the value of is equal to zero. This value corresponds to
the short circuiting instant of the voltage wave when it is passing through zero. Thus the
final expression for the maximum momentary current is obtained as:
imm = 2 [2V/Z]
(2.12)
Thus it is observed that the maximum momentary current is twice the maximum value of
symmetrical short circuit current. This is refered as the doubling effect of the short circuit
current during the symmetrical fault on a transmission line.
(2.13)
Where Xd is called as the direct axis synchronous reactance of the synchronous machine.
Consider now a sudden three-phase short circuit of the synchronous generator on no-load.
The machine experiences a transient in all the 3 phases, finally ending up in steady state
conditions.
(2.14)
29
Where Xd is called as the sub-transient reactance of the synchronous machine. Here, the
equivalent resistance of the damper winding is more than that of the rotor field winding.
Hence, the time constant of the damper field winding is smaller. Thus the damper field
effects and the eddy currents disappear after a few cycles.
(2.15)
30
The currents and reactances during the three zones of period are related as under in terms
of the intercepts on the oscillogram (oa, ob and oc are the y-intercepts as indicated in
figure 6):
RMS value of the steady state current = I = [oa/2] = [Eg/Xd]
RMS value of the transient current = I = [ob/2] = [Eg/Xd]
RMS value of the sub transient current = I = [oc/2] = [Eg/Xd]
(2.16)
31
Also shown in figure 7, are the circuit models to be used for short circuit current
calculations when a fault occurs at the terminals of the generator, for sub-transient current
and transient current values. The induced emf values used in these models are given by
the expressions as under:
Eg = Vt + j ILXd = Voltage behind syn. reactance
Eg= Vt + j ILXd = Voltage behind transient reactance
Eg= Vt + j ILXd = Voltage behind subtr. Reactance
(2.17)
The synchronous motors will also have the terminal emf values and reactances. However,
then the current direction is reversed. During short circuit studies, they can be replaced by
circuit models similar to those shown in figure 7 above, except that the voltages are given
by the relations as under:
Em = Vt - j ILXd = Voltage behind syn. reactance
Em= Vt - j ILXd = Voltage behind transient reactance
Em= Vt - j ILXd = Voltage behind subtr. Reactance
(2.18)
The circuit models shown above for the synchronous machines are also very useful while
dealing with the short circuit of an interconnected system.
2.6 Examples
Problem #1: A transmission line of inductance 0.1 H and resistance 5 is suddenly
short circuited at t = 0, at the far end of a transmission line and is supplied by an ac
source of voltage v = 100 sin (100t+150). Write the expression for the short circuit
current, i(t). Find the approximate value of the first current maximum for the given
values of and . What is this value for =0, and =900? What should be the instant of
short circuit so that the DC offset current is (i)zero and (ii)maximum?
32
Solution:
Figure P1.
Consider the expression for voltage applied to the transmission system given by
v = Vm sin(t+) = 100 sin (100t+150)
Thus we get: Vm = 100 volts; f = 50 Hz and
= 150.
or
= 80.9570
= - 9.0430.
33
Solution:
Consider the SLD with the data given in the problem statement. The base values are
selected as under:
Figure P2(a)
Selection of bases:
Sb = 25 MVA (common); Vb = 11 KV (Gen. circuit)- chosen so that then Vb = 66 KV
(line circuit) and Vb = 6.6 KV (Motor circuit).
Pu values:
Xg=j0.2 pu, Xt1=Xt2=j0.1 pu; Xm1=Xm2=Xm3=j0.25(25/5)=j1.25 pu; Xline=j0.15 pu.
Since the system is operating at no load, all the voltages before fault are 1 pu.
Considering the pu reactance diagram with the faults at P, we have:
Figure P2(b)
Current to be interrupted by circuit breaker A = 1.0 /j[0.2+0.1+0.15+0.1]
= - j 1.818 pu = - j 1.818 (25/[3(11)]) = - j 1.818 (1.312) KA = 2.386 KA
And Current to be interrupted by breaker B = 1/j1.25 = - j 0.8 pu
= - j0.8 (25/[3(6.6)]) = - j0.8 (2.187) KA = 1.75 KA.
34
Problem #3: Two synchronous motors are connected to a large system bus through a
short line. The ratings of the various components are: Motors(each)= 1 MVA, 440 volts,
0.1 pu reactance; line of 0.05 ohm reactance and the short circuit MVA at the bus of the
large system is 8 at 440 volts. Calculate the symmetrical short circuit current fed into a
three-phase fault at the motor bus when the motors are operating at 400 volts.
Solution:
Consider the SLD with the data given in the problem statement. The base values are
selected as under:
Figure P3.
Sb = 1 MVA; Vb = 0.44 KV (common)- chosen so that Xm(each)=j0.1 pu, Em = 1.000,
Xline=j0.05 (1/0.442) = j 0.258 pu and Xlarge-system -= (1/8) = j 0.125 pu.
Thus the prefault voltage at the motor bus; Vt = 0.4/0.44 = 0.90900,
Short circuit current fed to the fault at motor bus (If = YV);
If = [0.125 + 0.258]-1 + 2.0 }0.909 = [20.55 pu] [1000/(3(0.4))]
= 20.55 (1.312) KA = 26.966 KA.
Problem #4: A generator-transformer unit is connected to a line through a circuit
breaker. The unit ratings are: Gen.: 10 MVA, 6.6 KV, Xd = 0.1 pu, Xd = 0.2 pu and Xd
= 0.8 pu; and Transformer: 10 MVA, 6.9/33 KV, Xl = 0.08 pu; The system is operating
on no-load at a line voltage of 30 KV, when a three-phase fault occurs on the line just
beyond the circuit breaker. Determine the following:
(i) Initial symmetrical RMS current in the breaker,
(ii) Maximum possible DC off-set current in the breaker,
(iii) Momentary current rating of the breaker,
(iv) Current to be interrupted by the breaker and the interrupting KVA and
(v) Sustained short circuit current in the breaker.
Solution:
35
Consider the base values selected as 10 MVA, 6.6 KV (in the generator circuit) and
6.6(33/6.9) = 31.56 KV(in the transformer circuit). Thus the base current is:
Ib = 10 / [3(31.56)] = 0.183 KA
The pu values are: Xd = 0.1 pu, Xd = 0.2 pu and Xd = 0.8 pu; and XTr = 0.08 (6.9/6.6)2
= 0.0874 pu; Vt = (30/31.6) = 0.9500 pu.
Initial symmetrical RMS current = 0.9500 / [0.1 + 0.0874] = 5.069 pu = 0.9277 KA;
Maximum possible DC off-set current = 2 (0.9277) = 1.312 KA;
Momentary current rating = 1.6(0.9277) = 1.4843 KA; (assuming 60% allowance)
Current to be interrupted by the breaker (5 Cycles) = 1.1(0.9277) = 1.0205 KA;
Interrupting MVA = 3(30) (1.0205) = 53.03 MVA;
Sustained short circuit current in the breaker = 0.9500 (0.183) / [0.8 + 0.0874]
= 0.1959 KA.
2. A generator (rated: 25MVA, 12. KV, 10%) supplies power to a motor (rated: 20 MVA,
3.8 KV, 10%) through a step-up transformer (rated:25 MVA, 11/33 KV, 8%),
transmission line (of reactance 20 ohms) and a step-down transformer (rated:20 MVA,
33/3.3 KV, 10%). Write the pu reactance diagram. The system is loaded such that the
motor is drawing 15 MW at 0.9 leading power factor, the motor terminal voltage being
3.1 KV. Find the sub-transient current in the generator and motor for a fault at the
generator bus.
[Answer: Ig = 9.337 KA; Im = 6.9 KA]
3. A synchronous generator feeds bus 1 and a power network feed bus 2 of a system.
Buses 1 and 2 are connected through a transformer and a line. Per unit reactances of the
components are: Generator(bus-1):0.25; Transformer:0.12 and Line:0.28. The power
network is represented by a generator with an unknown reactance in series. With the
generator on no-load and with 1.0 pu voltage at each bus, a three phase fault occurring on
bus-1 causes a current of 5 pu to flow into the fault. Determine the equivalent reactance
of the power network.
[Answer: X = 0.6 pu]
4. A synchronous generateor, rated 500 KVA, 440 Volts, 0.1 pu sub-transient reactance is
supplying a passive load of 400 KW, at 0.8 power factor (lag). Calculate the initial
symmetrical RMS current for a three-phase fault at the generator terminals.
[Answer: Sb=0.5 MVA; Vb=0.44 KV; load=0.836.90; Ib=0.656 KA; If=6.97 KA]
36
2.
3.
4.
5.
b)
c)
Pulsating in nature
d)
Rotating in nature
b)
Reduce hunting
c)
d)
Zn2
b)
Zn
c)
3 Zn
d)
An ineffective value
b)
c)
d)
b)
c)
d)
37
3.1 INTRODUCTION
Power systems are large and complex three-phase systems. In the normal operating
conditions, these systems are in balanced condition and hence can be represented as an
equivalent single phase system. However, a fault can cause the system to become
unbalanced. Specifically, the unsymmetrical faults: open circuit, LG, LL, and LLG faults
cause the system to become unsymmetrical. The single-phase equivalent system method
of analysis (using SLD and the reactance diagram) cannot be applied to such
unsymmetrical systems. Now the question is how to analyze power systems under
unsymmetrical conditions? There are two methods available for such an analysis:
Kirchhoffs laws method and Symmetrical components method.
The method of symmetrical components developed by C.L. Fortescue in 1918 is a
powerful technique for analyzing unbalanced three phase systems. Fortescue defined a
linear transformation from phase components to a new set of components called
symmetrical components. This transformation represents an unbalanced three-phase
system by a set of three balanced three-phase systems. The symmetrical component
method is a modeling technique that permits systematic analysis and design of threephase systems. Decoupling a complex three-phase network into three simpler networks
reveals complicated phenomena in more simplistic terms.
Consider a set of three-phase unbalanced voltages designated as Va, Vb, and Vc.
According to Fortescue theorem, these phase voltages can be resolved into following
three sets of components.
1. Positive-sequence components, consisting of three phasors equal in magnitude,
displaced from each other by 1200 in phase, and having the same phase sequence as
the original phasors, designated as Va1, Vb1, and Vc1
2. Negative-sequence components, consisting of three phasors equal in magnitude,
displaced from each other by 1200 in phase, and having the phase sequence opposite
to that of the original phasors, designated as Va2, Vb2, and Vc2
3. Zero-sequence components, consisting of three phasors equal in magnitude, and with
zero phase displacement from each other, designated as Va0, Vb0, and Vc0
Since each of the original unbalanced phasors is the sum of its components, the
original phasors expressed in terns of their components are
Va = Va1 + Va2 + Va0
Vb = Vb1 + Vb2 + Vb0
Vc = Vc1 + Vc2 + Vc0
(3.1)
38
The synthesis of a set of three unbalanced phasors from the three sets of symmetrical
components is shown in Figure1.
(3.2)
39
If the operator a is applied to a phasor twice in succession, the phasor is rotated through
2400. Similarly, three successive applications of a rotate the phasor through 3600.
To reduce the number of unknown quantities, let the symmetrical components of
Vb and Vc can be expressed as product of some function of the operator a and a
component of Va. Thus,
Vb1 = a 2 Va1
Vb2 = a Va2
Vb0 = Va0
Vc1 = a Va1
Vc2 = a 2 Va2
Vc0 = Va0
Using these relations the unbalanced phasors can be written as
Va = Va0 + Va1 + Va2
Vb = Va0 + a 2Va1 + a Va2
Vc = Va0 + a Va1 + a 2Va2
(3.3)
In matrix form,
va
1 1
v 1 a 2
b
vc
1 a
Let
va
Vp vb ;
vc
1
a
a 2
va 0
v
a1
va 2
va 0
Vs va1 ;
va 2
(3.4)
1 1
A 1 a 2
1 a
1
a
a 2
(3.5)
1 1 1
A 1 a a 2
1 a 2 a
With these definitions, the above relations can be written as
1
1
3
Vp = A Vs;
Vs = A-1Vp
(3.6)
(3.7)
(3.8)
Since the sum of three balanced voltages is zero, the zero-sequence component voltage in
a balanced three-phase system is always zero. Further, the sum of line voltages of even an
unbalanced three-phase system is zero and hence the corresponding zero-sequence
component of line voltages.
40
NUMERICAL EXAMPLES
Example 1 : The line currents in a 3-ph 4 wire system are Ia = 100<300; Ib = 50<3000;
Ic = 30<1800. Find the symmetrical components and the neutral current.
Solution:
Ia0
Ia1
Ia2
In
= 1/3(Ia + Ib + Ic)
= 27.29 < 4.70 A
= 1/3(Ia + a Ib + a2Ic) = 57.98 < 43.30 A
= 1/3(Ia + a2 Ib + a Ic) = 18.96 < 24.90 A
= Ia + Ib + Ic = 3 Ia0 = 81.87 <4.70 A
Example 2: The sequence component voltages of phase voltages of a 3-ph system are:
Va0 = 100 <00 V; Va1 = 223.6 < -26.60 V ; Va2 = 100 <1800 V. Determine the phase
voltages.
Solution:
Va = Va0 + Va1 + Va2
= 223.6 <-26.60 V
Vb = Va0 + a2Va1 + a Va2 = 213 < -99.90 V
Vc = Va0 + a Va1 + a2 Va2 = 338.6 < 66.20 V
Example 3: The two seq. components and the corresponding phase voltage of a 3-ph
system are Va0 =1<-600 V; Va1=2<00 V ; & Va = 3 <00 V. Determine the other phase
voltages.
Solution:
Va = Va0 + Va1 + Va2
Va2 = Va Va0 Va1 = 1 <600 V
Vb = Va0 + a2Va1 + a Va2 = 3 < -1200 V
Vc = Va0 + a Va1 + a2 Va2 = 0 V
Example 4: Determine the sequence components if Ia =10<600 A; Ib =10<-600 A; Ic =
10 <1800 A.
Solution:
Ia0 = 1/3(Ia + Ib + Ic)
=0A
Ia1 = 1/3(Ia + a Ib + a2Ic) = 10<600 A
Ia2 = 1/3(Ia + a2 Ib + a Ic) = 0 A
Observation: If the phasors are balanced, two sequence components will be zero.
Example 5: Determine the sequence components if Va = 100 <300 V;
<1500 V & Vc = 100 <-900 V.
Vb
100
Solution:
Va0 = 1/3(Va + Vb + Vc)
=0V
Va1 = 1/3(Va + a Vb + a2Vc) = 0 V
Va2 = 1/3(Va + a2 Vb + a Vc) = 100<300 V
Observation: If the phasors are balanced, two sequence components will be zero.
41
Example 6: The line b of a 3-ph line feeding a balanced Y-load with neutral grounded is
open resulting in line currents: Ia = 10<00 A & Ic = 10<1200 A. Determine the sequence
current components.
Solution:
Ib = 0 A.
Ia0 = 1/3(Ia + Ib + Ic)
Ia1 = 1/3(Ia + a Ib + a2Ic)
Ia2 = 1/3(Ia + a2 Ib + a Ic)
= 3.33<600 A
= 6.66<00 A
= 3.33<-600 A
Ic = 0 A; Ia = 10<00 A. Ib = 10<1200 A
Ia0 = 1/3(Ia + Ib + Ic)
= 0A
Ia1 = 1/3(Ia + a Ib + a2Ic) = 5.78<-300 A
Ia2 = 1/3(Ia + a2 Ib + a Ic) = 5.78< 300 A
Note: The zero-sequence components of line currents of a delta load (3-ph 3-wire) system
are zero.
3.3 POWER IN TERMS OF SYMMETRICAL COMPONENTS
The power in a three-phase system can be expressed in terms of symmetrical components
of the associated voltages and currents. The power flowing into a three-phase system
through three lines a, b and c is
S = P + j Q = Va Ia* + Vb Ib* + Vc Ic *
(3.9)
where Va , Vb and Vc are voltages to neutral at the terminals and Ia , Ib, and Ic are the
currents flowing into the system in the three lines. In matrix form
S va
vb
I a
v Ib
I c
c
Va
Vb
Vc
I a
I
b
I c
Thus
S = [A V]T [AI]*
Using the reversal rule of the matrix algebra
S = VT AT A* I*
Noting that AT = A and a and a 2 are conjugates,
42
S va 0
va1
1 1
va 2 1 a 2
1 a
1
a
a 2
1 1
1 a
1 a 2
I a0
1
a I a1
a
I a 2
S 3 va 0
va1 va 2
I a0
I a1
I a 2
(3.10)
Here, 3Va0Ia0, 3Va1Ia1 and 3Va2Ia2 correspond to the three-phase power delivered to the
zero-sequence system, positive-sequence system, and negative-sequence system,
respectively. Thus, the total three-phase power in the unbalanced system is equal to the
sum of the power delivered to the three sequence systems representing the three-phase
system.
3.4 PHASE SHIFT OF COMPONENTS IN Y- TRANSFORMER BANKS
The dot convention is used to designate the terminals of transformers. The dots are placed
at one end of each of the winding on the same iron core of a transformer to indicate that
the currents flowing from the dotted terminal to the unmarked terminal of each winding
produces an mmf acting in the same direction in the magnetic circuit. In that case, the
voltage drops from dotted terminal to unmarked terminal in each side of the windings are
in phase.
The HT terminals of three-phase transformers are marked as H1, H2 and H3 and the
corresponding LT side terminals are marked X1, X2 and X3. In Y-Y or - transformers,
the markings are such that voltages to neutral from terminals H1, H2, and H3 are in phase
with the voltages to neutral from terminals X1, X2, and X3, respectively. But, there will
be a phase shift (of 300) between the corresponding quantities of the primary and
secondary sides of a star-delta (or delta-star) transformer. The standard for connection
and designation of transformer banks is as follows:
1. The HT side terminals are marked as H1, H2 and H3 and the corresponding LT side
terminals are marked X1, X2 and X3.
2. The phases in the HT side are marked in uppercase letters as A, B, and C. Thus for
the sequence abc, A is connected to H1, B to H2 and C to H3. Similarly, the phases in
the LT side are marked in lowercase letters as a, b and c.
3. The standard for designating the terminals H1 and X1 on transformer banks requires
that the positive-sequence voltage drop from H1 to neutral lead the positive sequence
voltage drop from X1 to neutral by 300 regardless of the type of connection in the HT
43
and LT sides. Similarly, the voltage drops from H2 to neutral and H3 to neutral lead
their corresponding values, X2 to neutral and X3 to neutral by 30 0.
44
Va1 = +j VA1
Ia1 = +j IA1
Va2 = -j VA2
Ia1 = -j IA2
(3.11)
Where each voltage and current is expressed in per unit. Although, these relations are
obtained for Y- transformer with Y connection in the HT side, they are valid even
when the HT side is connected in and the LT side in Y.
NUMERICAL EXAMPLES
Example 8: Three identical resistors are Y-connected to the LT Y-side of a delta-star
transformer. The voltages at the resistor loads are |Vab| = 0.8 pu., |Vbc|=1.2 pu., and
|Vca|=1.0 pu. Assume that the neutral of the load is not connected to the neutral of the
transformer secondary. Find the line voltages on the HT side of the transformer.
Solution:
Assuming an angle of 1800 for Vca, find the angles of other voltages
Vab = 0.8<82.80 pu
Vbc = 1.2<-41.40 pu
Vca = 1.0<1800 pu
The symmetrical components of line voltages are
Vab0 = 1/3 (Vab +Vbc + Vca) = 0
Vab1 = 1/3 (Vab +aVbc + a2Vca) = 0.985<73.60 V
Vab1 = 1/3 (Vab +a2Vbc + aVca) = 0.235<220.30 V
Since Van1 = Vab1<-300 and Van2 = Vab2<300
Van1 = 0.985<73.60-300
= 0.985<43.60 pu (L-L base)
Van2 = 0.235<220.30+300
= 0.235<250.30 pu(L-L base)
Since each resistor is of 1.0<0 pu. Impedance,
Ian1 = (Van1/Z) = 0.985<43.60 pu.
45
Consider the network shown in Figure. Assuming that there is no mutual impedance
between the impedances Za, Zb, and Zc, the voltage drops Vaa, vbb, and Vcc can be
expressed in matrix form as
46
Vaa ' Z a
V 0
bb '
Vcc ' 0
0
Zb
0
0
0
Z c
Ia
I
b
I c
(3.12)
0
Zb
0
0
I a0
0 A I a1
I a 2
Z c
(3.13)
Vaa2 = Za Ia2;
Vaa0 = Za Ia0
(3.14)
47
NUMERICAL EXAMPLES
Example 9: A Y-connected source with phase voltages Vag = 277<00, Vbg = 260<-1200
and Vcg = 295<1150 is applied to a balanced load of 30<400 /phase through a line of
impedance 1<850 . The neutral of the source is solidly grounded. Draw the sequence
networks of the system and find source currents.
Solution:
Va0 = 15.91<62.110 V
Va1 = 277.1<-1.70 V
Va2 = 9.22<216.70 V
Y eq. of load = 10<400 /phase
Zline = 1<850 .
Zneutral = 0
Ia0 = 0<00 A
Ia1 = 25.82<-45.60 A
Ia2 = 0.86<172.80 A
Ia = 25.15<-46.80 A
Ib = 25.71<196.40 A
Ic = 26.62<73.80 A
48
49
impedance, which is generally denoted as Z2. The impedance of a circuit to zerosequence currents alone is called the impedance to zero-sequence current or simply zerosequence impedance, which is generally denoted as Z0. In the analysis of an
unsymmetrical fault on a symmetrical system, the symmetrical components of the
unbalanced currents that are flowing are determined. Since in a balanced system, the
components currents of one sequence cause voltage drops of like sequence only and are
independent of currents of other sequences, currents of any one sequence may be
considered to flow in an independent network composed of the generated voltages, if any,
and impedances to the current of that sequence only.
The single-phase equivalent circuit consisting of the impedances to currents of any one
sequence only is called the sequence network of that particular sequence. Thus, the
sequence network corresponding to positive-sequence current is called the positivesequence network. Similarly, the sequence network corresponding to negative-sequence
current is called negative-sequence network, and that corresponding to zero-sequence
current is called zero-sequence network. The sequence networks are interconnected in a
particular way to represent various unsymmetrical fault conditions. Therefore, to
calculate the effect of a fault by the method of symmetrical components, it is required to
determine the sequence networks.
3.7 SEQUENCE NETWORKS OF UNLOADED GENERATOR
Consider an unloaded generator which is grounded through a reactor as shown in Figure.
When a fault occurs, unbalanced currents depending on the type of fault will flow
through the lines. These currents can be resolved into their symmetrical components. To
draw the sequence networks of this generator, the component voltages/currents,
component impedances are to be determined. The generated voltages are of positivesequence only as the generators are designed to supply balanced three-phase voltages.
Hence, positive-sequence network is composed of an emf in series with the positivesequence impedance. The generated emf in this network is the no-load terminal voltage to
neutral, which is also equal to the transient and subtransient voltages as the generator is
not loaded. The reactance in this network is the subtransient, transient, or synchronous
reactance, depending on the condition of study.
50
The negative- and zero-sequence networks are composed of only the respective sequence
impedances as there is no corresponding sequence emf. The reference bus for the
positive- and negative-sequence networks is the neutral of the generator.
The current flowing in the impedance Zn between neutral and ground is 3I a0 as shown in
Fig. 3.6. Thus the zero-sequence voltage drop from point a to the ground, is given by: (Ia0Zg0 3Ia0Zn), where Zg0 is the zero-sequence impedance of the generator. Thus the
zero-sequence network, which is single-phase equivalent circuit assumed to carry only
one phase, must have an zero-sequence impedance of Zo = (Zg0 +3Zn).
From the sequence networks, the voltage drops from point a to reference bus (or ground)
are given by
Va1 = Ea - Ia1Z1
Va2 =
- Ia2Z2
Va0 =
- Ia0 Z0
(3.15)
51
Eq. 3.15 applicable to any unloaded generator are valid for loaded generator under steady
state conditions. These relations are also applicable for transient or subtransient
conditions of a loaded generator if Eg or Eg is substituted for Ea.
52
53
1. Case 1: Y-Y Bank with one neutral grounded: If either one of the neutrals of a Y-Y
bank is ungrounded, zero-sequence current cannot flow in either winding ( as the
absence of a path through one winding prevents current in the other). An open circuit
exists for zero-sequence current between two parts of the system connected by the
transformer bank.
2. Case 2: Y-Y Bank with both neutral grounded: In this case, a path through
transformer exists for the zero-sequence current. Hence zero-sequence current can
flow in both sides of the transformer provided there is complete outside closed path
for it to flow. Hence the points on the two sides of the transformer are connected by
the zer0-sequence impedance of the transformer.
54
55
4. Case 4: Y- Bank with ungrounded Y: In this case, there is no path for zerosequence current. The zero-sequence impedance is infinite and is shown by an open
circuit.
5. Case 5: - Bank: In this case, there is no return path for zero-sequence current. The
zero-sequence current cannot flow in lines although it can circulate in the windings.
6. The zero-sequence equivalent circuits determined for the individual parts separately
are connected according to the SLD to form the complete zero-sequence network.
Procedure to draw the sequence networks
The sequence networks are three separate networks which are the single-phase equivalent
of the corresponding symmetrical sequence systems. These networks can be drawn as
follows:
1. For the given condition (steady state, transient, or subtransient), draw the reactance
diagram (selecting proper base values and converting all the per unit values to the
selected base, if necessary). This will correspond to the positive-sequence network.
2. Determine the per unit negative-sequence impedances of all elements (if the values of
negative sequence is not given to any element, it can approximately be taken as equal
to the positive-sequence impedance).
Draw the negative-sequence network by
replacing all emf sources by short circuit and all impedances by corresponding
negative-sequence impedances in the positive-sequence network.
3. Determine the per unit zero-sequence impedances of all the elements and draw the
zero-sequence network corresponding to the grounding conditions of different
elements.
NUMERICAL EXAMPLES
Example 10: For the power system shown in the SLD, draw the sequence networks.
56
EXERCISE PROBLEM: For the power system shown in the SLD, draw the sequence
networks.
57
4.1 PREAMBLE
The unsymmetrical faults will have faulty parameters at random. They can be analyzed
by using the symmetrical components. The standard types of unsymmetrical faults
considered for analysis include the following (in the order of their severity):
Further the neutrals of various equipment may be grounded or isolated, the faults can
occur at any general point F of the given system, the faults can be through a fault
impedance, etc. Of the various types of faults as above, the 3- fault involving the ground
is the most severe one. Here the analysis is considered in two stages as under: (i) Fault at
the terminals of a Conventional (Unloaded) Generator and (ii) Faults at any point F, of a
given Electric Power System (EPS).
Consider now the symmetrical component relational equations derived from the three
sequence networks corresponding to a given unsymmetrical system as a function of
sequence impedances and the positive sequence voltage source in the form as under:
Va0 = - Ia0Z0
Va1 = Ea - Ia1Z1
Va2 = - Ia2Z2
(4.1)
These equations are refered as the sequence equations. In matrix Form the sequence
equations can be considered as:
Va0
0
Va1 = Ea
Va2
0
Z0 0 0
0 Z1 0
0 0 Z2
Ia0
Ia1
Ia2
(4.2)
This equation is used along with the equations i.e., conditions under fault (c.u.f.), derived
to describe the fault under consideration, to determine the sequence current Ia1 and hence
the fault current If, in terms of Ea and the sequence impedances, Z1, Z2 and Z0. Thus
during unsymmetrical fault analysis of any given type of fault, two sets of equations as
follows are considered for solving them simultaneously to get the required fault
parameters:
Equations for the conditions under fault (c.u.f.)
58
Equations for the sequence components (sequence equations) as per (4.2) above.
4.2 SINGLE LINE TO GROUND FAULT ON A CONVENTIONAL (UNLOADED)
GENERATOR
A conventional generator is one that produces only the balanced voltages. Let Ea, nd Ec
be the internally generated voltages and Zn be the neutral impedance. The fault is
assumed to be on the phasea as shown in figure 4.1. Consider now the conditions under
fault as under:
c.u.f.:
Ib = 0; Ic = 0;
and Va = 0.
(4.3)
Now consider the symmetrical components of the current Ia with Ib=Ic=0, given by:
Ia0
1 1 1
Ia1 = (1/3) 1 a a2
Ia2
1 a2 a
Solving (4.4) we get,
Ia
0
0
(4.4)
(4.5)
Z0 0
0 Z1
0
0
Ia1
Ia1
59
Va2
Z2
Ia1
(4.6)
Or in other words,
Ia1 = [Ea/(Z1 + Z2 + Z0)]
(4.7)
.
Figure 4.2 Connection of sequence networks for LG Fault
on phase a of a Conventional Generator
The equation (4.7) derived as above implies that the three sequence networks are
connected in series to simulate a LG fault, as shown in figure 4.2. Further we have the
following relations satisfied under the fault conditions:
1.
2.
3.
4.
5.
6.
7.
8.
9.
60
10. If Zn = , then Z0 = , i.e., the zero sequence network is open so that then,
If=Ia=0.
4.3 LINE TO LINE FAULT ON A CONVENTIONAL GENERATOR
(4.8)
Now consider the symmetrical components of the voltage Va with Vb=Vc, given by:
Va0
Va1
Va2
1 1 1
= (1/3) 1 a a2
1 a2 a
Va
Vb
Vb
(4.9)
(4.10)
Further, consider the symmetrical components of current Ia with Ib=-Ic, and Ia=0; given
by:
Ia0
Ia1
Ia2
1 1 1
= (1/3) 1 a a2
1 a2 a
0
Ib
-Ib
(4.11)
61
(4.12)
Using equation (4.10) and (4.12) in (4.2), and since Va0 = 0 ( Ia0 being 0), we get,
0
0
Z0 0 0
0
Va1 = Ea 0 Z1 0
Ia1
Va1
0
0 0 Z2
-Ia1
Pre-multiplying equation (4.13) throughout by [0 1 -1], we get,
(4.13)
(4.14)
62
10. Since Ia0=0, the presence of absence of neutral impedance does not make any
difference in the analysis.
4.4
DOUBLE LINE
GENERATOR
TO
GROUND
FAULT
ON
CONVENTIONAL
(4.15)
Now consider the symmetrical components of the voltage with Vb=Vc=0, given by:
Va0
1 1 1
Va1 = (1/3) 1 a a2
Va2
1 a2 a
Solving (4) we get,
Va
0
0
(4.16)
(4.17)
Z0 0 0
0 Z1 0
0 0 Z2
Ia0
Ia1
Ia2
(4.18)
63
1/Z0
-1
Z =
1/Z1
1/Z2
(4.19)
We get,
-1
Va1
0
Z0 0 0
-1
-1
Va1 = Z Ea Z 0 Z1 0
Va1
0
0 0 Z2
Ia0
Ia1
Ia2
(4.20)
Using the identity: Va1= (Ea Ia1Z1) in equation (4.19), pre-multiplying throughout by [1
1 1] and finally adding, we get,
Ea/Z0 - Ia1(Z1/Z0) + (Ea/Z1)- Ia1 + Ea/Z2 - Ia1(Z1/Z2) = (Ea/Z1) (Ia0+Ia1+Ia2)
= (Ea/Z1) - Ia
= (Ea/Z1)
(4.21)
(4.22)
Ia1 = {Ea/ [Z1+Z2Z0/(Z2+Z0)]}; Ia2= -Ia1Z0/(Z2 + Z0) and Ia0 = -Ia1Z2/(Z2 + Z0),
Fault current If: Ia0=(1/3)(Ia+Ib+Ic) = (1/3)(Ib+Ic) = If/3, Hence If = 3Ia0
Ia = 0, Vb=Vc=0 and hence Va1=Va2=Va0=Va/3
Fault phase voltages;Vb = Vc = 0
Sound phase voltage; Va = Va1+Va2+Va0 = 3Va1;
Fault phase powers are VbIb* = 0, and VcIc* = 0, since Vb=Vc=0
64
4.5
THREE PHASE
GENERATOR
TO
GROUND
FAULT
ON
CONVENTIONAL
(4.23)
Now consider the symmetrical components of the voltage with Va=Vb=Vc= 0, given by:
Va0
Va1
Va2
1 1 1
= (1/3) 1 a a2
1 a2 a
0
0
0
(4.24)
65
(4.25)
Thus we have
Va1 = Ea1 Ia1Z1
(4.26)
(4.27)
The equation (4.26) derived as above implies that, to simulate the 3-phase ground fault,
the three sequence networks are connected such that the negative and zero sequence
networks are absent and only the positive sequence network is present, as shown in figure
4.8. Further the fault current, If in case of a 3-phase ground fault is given by
If = Ia1= Ia = (Ea/Z1)
(4.28)
It is to be noted that the presence of a neutral connection without or with a neutral
impedance, Zn will not alter the simulated conditions in case of a three phase to ground
fault.
4.6 UNSYMMETRICAL FAULTS ON POWER SYSTEMS
In all the analysis so far, only the fault at the terminals of an unloaded generator have
been considered. However, faults can also occur at any part of the system and hence the
power system fault at any general point is also quite important. The analysis of
unsymmetrical fault on power systems is done in a similar way as that followed thus far
for the case of a fault at the terminals of a generator. Here, instead of the sequence
impedances of the generator, each and every element is to be replaced by their
corresponding sequence impedances and the fault is analyzed by suitably connecting
them together to arrive at the Thevenin equivalent impedance if that given sequence.
Also, the internal voltage of the generators of the equivalent circuit for the positive
66
sequence network is now Vf (and not Ea), the pre-fault voltage to neutral at the point of
fault (PoF) (ref. Figure 4.9).
Z0 0 0
0 Z1 0
0 0 Z2
Ia0
Ia1
Ia2
(4.29)
(4.30)
67
(4.32)
(4.33)
68
It is observed that a single conductor fault is similar to a LLG fault at the fault point F of
the system considered.
(ii) Two Conductor Open Fault: consider the phases b and c under open condition so
that then the conditions under fault are:
Ib = Ic = 0; Vaa = 0
The derived conditions are:
Ia1 = Ia2 = Ia0 = Ia/3 and
Vaa1 = Vaa2 = Vaa0 = 0
(4.35)
These relations suggest a series combination of the three sequence networks as shown in
fig. 4.12. It is observed that a double conductor fault is similar to a LG fault at the fault
point F of the system considered.
Figure 4.12
69
(iii) Three Conductor Open Fault: consider all the three phases a, b and c, of a 3-phase
system conductors be open. The conditions under fault are:
Ia + Ib + Ic = 0
The derived conditions are:
Ia1 = Ia2 = Ia0 = 0 and
Va0 = Va2 = 0 and Va1 = Vf
(4.36)
These relations imply that the sequence networks are all open circuited. Hence, in a strict
analystical sense, this is not a fault at all!
4.8
All the faults considered so far have comprised of a direct short circuit from one or two
lines to ground. The effect of impedance in the fault is found out by deriving equations
similar to those for faults through zero valued neutral impedance. The connections of the
hypothetical stubs for consideration of faults through fault impedance Zf are as shown in
figure 4.13.
Fig
ure 4.13
70
Let phases b and c be on fault at F through Zf,, so that then, the c.u.f. would be:
Ia = 0 and Vb = Vc = 0
Hence the derived conditions under fault would be:
Va1 = Va2 = Va0 = (Va/3)
Ia1 = {Vf / [Z1+Z2(Z0+3Zf)/(Z2+Z0+3Zf)]}
Ia2= -Ia1(Z0+3Zf)/(Z2+Z0+3Zf); Ia0 = -Ia1Z2/(Z2+(Z0+3Zf) and
If = 3Ia0
(4.39)
(iv) Three Phase Fault at any point F of a given Power system through Zf
Let all the 3 phases a, b and c be on fault at F, through Zf so that the c.u.f. would be: Va =
IaZf ; Hence the derived conditions under fault would be: Ia1 = [Vf /(Z1+Zf); The
connections of the sequence networks for all the above types of faults through Zf are as
shown in figure 4.14.
LG Fault
LLG Fault
LL Fault
3-Ph. Fault
71
Figure 4.15
4.9
EXAMPLES
Example-1: A three phase generator with constant terminal voltages gives the following
currents when under fault: 1400 A for a line-to-line fault and 2200 A for a line-to-ground
fault. If the positive sequence generated voltage to neutral is 2 ohms, find the reactances
of the negative and zero sequence currents.
Solution: Case a) Consider the conditions w.r.t. the LL fault:
Ia1 = [Ea1/(Z1 + Z2)]
If = Ib = - Ic = 3 Ia1
=3 Ea1 / (Z1 + Z2) or
(Z1 + Z2) = 3 Ea1 / If
i.e., 2 + Z2 = 3 [2000/1400]
Solving, we get,
Z2 = 0.474 ohms.
Z0 = 0.253 ohms.
72
Xn = 4.235 ohms.
Case b: Consider the fault current expression for LLG fault given by:
If = 3Ia0 = 3 { -Ia1X2/(X2 + X0+3Xn)}= 2.0,
where, Ia1 = {Ea/ [X1+X2(X0+3Xn)/(X2+X0+3Xn)]}
Substituting and solving for Xn we get,
Xn = 0.078 pu
= 0.47 ohms.
Example-4: A three phase 50 MVA, 11 kV generator is subjected to the various faults
and the surrents so obtained in each fault are: 2000 A for a three phase fault; 1800 A for a
line-to-line fault and 2200 A for a line-to-ground fault. Find the sequence impedances of
the generator.
Solution: Case a) Consider the conditions w.r.t. the three phase fault:
If = Ia = Ia1 = Ea1/Z1
i.e., 2000 = 11000/ (3Z1)
Solving, we get,
73
74
5.1 INTRODUCTION
Power system stability of modern large inter-connected systems is a major problem for
secure operation of the system. Recent major black-outs across the globe caused by
system instability, even in very sophisticated and secure systems, illustrate the problems
facing secure operation of power systems. Earlier, stability was defined as the ability of a
system to return to normal or stable operation after having been subjected to some form
of disturbance. This fundamentally refers to the ability of the system to remain in
synchronism. However, modern power systems operate under complex interconnections,
controls and extremely stressed conditions. Further, with increased automation and use of
electronic equipment, the quality of power has gained utmost importance, shifting focus
on to concepts of voltage stability, frequency stability,
The IEEE/CIGRE Joint Task Force on stability terms and conditions have proposed the
following definition in 2004: Power System stability is the ability of an electric power
system, for a given initial operating condition, to regain a state of operating equilibrium
after being subjected to a physical disturbance, with most system variables bounded, so
that practically the entire system remains intact.
The Power System is an extremely non-linear and dynamic system, with operating
parameters continuously varying. Stability is hence, a function of the initial operating
condition and the nature of the disturbance. Power systems are continually subjected to
small disturbances in the form of load changes. The system must be in a position to be
able to adjust to the changing conditions and operate satisfactorily. The system must also
withstand large disturbances, which may even cause structural changes due to isolation of
some faulted elements.
A power system may be stable for a particular (large) disturbance and unstable for
another disturbance. It is impossible to design a system which is stable under all
75
The high complexity of stability problems has led to a meaningful classification of the
power system stability into various categories. The classification takes into account the
main system variable in which instability can be observed, the size of the disturbance and
the time span to be considered for assessing stability.
76
Small single (or small disturbance) rotor angle stability: It is the ability of the power
system to maintain synchronism under small disturbances. In this case, the system
equation can be linearized around the initial operating point and the stability depends
only on the operating point and not on the disturbance. Instability may result in
(i) A non oscillatory or a periodic increase of rotor angle
(ii) Increasing amplitude of rotor oscillations due to insufficient damping.
The first form of instability is largely eliminated by modern fast acting voltage regulators
and the second form of instability is more common. The time frame of small signal
stability is of the order of 10-20 seconds after a disturbance.
Large-signal rotor angle stability or transient stability: This refers to the ability of
the power system to maintain synchronism under large disturbances, such as short circuit,
line outages etc. The system response involves large excursions of the generator rotor
angles. Transient stability depends on both the initial operating point and the disturbance
parameters like location, type, magnitude etc. Instability is normally in the form of a
periodic angular separation. The time frame of interest is 3-5 seconds after disturbance.
The term dynamic stability was earlier used to denote the steady-state stability in the
presence of automatic controls (especially excitation controls) as opposed to manual
controls. Since all generators are equipped with automatic controllers today, dynamic
stability has lost relevance and the Task Force has recommended against its usage.
Voltage stability refers to the ability of a power system to maintain steady voltages at all
buses in the system after being subjected to a disturbance. It depends on the ability of the
system to maintain equilibrium between load demand and load supply. Instability results
in a progressive fall or rise of voltages of some buses, which could lead to loss of load in
an area or tripping of transmission lines, leading to cascading outages. This may
eventually lead to loss of synchronism of some generators.
The cause of voltage instability is usually the loads. A run-down situation causing voltage
instability occurs when load dynamics attempt to restore power consumption beyond the
77
Large disturbance voltage stability: It refers to the systems ability to maintain steady
voltages following large disturbances; It requires computation of the non-linear response
of the power system to include interaction between various devices like motors,
transformer tap changers and field current limiters. Short term voltage stability involves
dynamics of fast acting load components and period of interest is in the order of several
seconds. Long term voltage stability involves slower acting equipment like tap-changing
transformers and generator current limiters. Instability is due to loss of long-term
equilibrium.
Frequency stability refers to the ability of a power system to maintain steady frequency
following a severe disturbance, causing considerable imbalance between generation and
load. Instability occurs in the form of sustained frequency swings leading to tripping of
generating units or loads. During frequency swings, devices such as under frequency load
shedding, generator controls and protection equipment get activated in a few seconds.
However, devices such as prime mover energy supply systems and load voltage
regulators respond after a few minutes. Hence, frequency stability could be a short-term
or a long-term phenomenon.
78
Since a synchronous machine is a rotating body, the laws of mechanics of rotating bodies
are applicable to it. In rotation we first define the fundamental quantities. The angle m is
defined, with respect to a circular arc with its center at the vertex of the angle, as the ratio
of the arc length s to radius r.
m =
s
r
(5.1)
d m
dt
(5.2)
d m d 2 m
dt
dt 2
(5.3)
The torque on a body due to a tangential force F at a distance r from axis of rotation is
given by
T=rF
(5.4)
(5.5)
The unit of torque is N-m. When torque is applied to a body, the body experiences
angular acceleration. Each particle experiences a tangential acceleration a r , where r
is the distance of the particle from axis of rotation. The tangential force required to
accelerate a particle of mass dm is
dF = a dm = r dm
(5.6)
(5.7)
(5.8)
I = r dm
(5.9)
2
It is called the moment of inertia of the body. The unit is Kg m . If the torque is
assumed to be the result of a number of tangential forces F, which act at different points
of the body
T=rF
Now each force acts through a distance, ds = r d m and the work done is F . ds i.e.,
79
dW = F r d m = dm T
and
W = T dm
(5.10)
dW
d m
(5.11)
T=
Thus the unit of torque may also be Joule per radian. The power is defined as rate of
doing work. Using (5.11)
P=
d W T d m
T m
dt
dt
(5.12)
(5.13)
1
1
2
I m = M m
2
2
(5.14)
The laws of rotation developed in section.3 are applicable to the synchronous machine.
From(.5.8)
I = T
or
I d 2 m
T
d t2
(5.15)
Here T is the net torque of all torques acting on the machine, which includes the shaft
torque (due to prime mover of a generator or load on a motor), torque due to rotational
losses (friction, windage and core loss) and electromagnetic torque.
It also shows the corresponding torque for a motor with respect to the
direction of rotation.
80
(a) Generator
(b) Motor
(5.16)
m m sm t
(5.17)
81
d m d m
sm
dt
dt
d 2 m
d 2 m
dt 2
dt 2
(5.18)
d 2 m
= Ta = Tm Te N-m
I
dt 2
(5.19)
d 2 m
= m ( Tm Te ) N-m
m I
dt 2
(5.20)
d 2 m
M
Pm Pa
dt 2
(5.21)
where M is the angular momentum, also called inertia constant, Pm is shaft power input
less rotational losses, Pe is electrical power output corrected for losses and Pa is the
acceleration power. M depends on the angular velocity m , and hence is strictly not a
constant, because m deviates from the synchronous speed during and after a
disturbance. However, under stable conditions m does not vary considerably and M can
be treated as a constant. (21) is called the Swing equation. The constant M depends on
the rating of the machine and varies widely with the size and type of the machine.
Another constant called H constant (also referred to as inertia constant) is defined as
stored kinetic energy in mega joules
at sychronous speed
H=
MJ / MVA
Machine rating in MVA
(5.22)
H falls within a narrow range and typical values are given in Table 5.1. If the rating of the
machine is G MVA, from (5.22) the stored kinetic energy is GH Mega Joules. From
(5.14)
82
GH =
1
M s m MJ
2
(5.23)
or
M=
2 GH
s m
MJ-s/mech rad
(5.24)
s m d t 2
G
G
(5.25)
pu
(5.26)
p
Here s is the synchronous speed in electrical rad/s ( s s m ) and Pa is
2
acceleration power in per unit on same base as H. For a system with an electrical
frequency f Hz, (5.26) becomes
H d 2
Pa Pm Pe pu
f dt 2
(5.27)
pu
(5.28)
when is in electrical degrees. Equations (5.27) and (5.28) also represent the swing
equation. It can be seen that the swing equation is a second order differential equation
which can be written as two first order differential equations:
2H d
Pm Pe
s dt
d
s
dt
pu
(5.29)
(5.30)
In which , s and are in electrical units. In deriving the swing equation, damping
has been neglected.
83
Table 5.1
Type of machine
H (MJ/MVA)
96
3600 rpm
74
3600 rpm
43
23
24
Non condensing
Water wheel generator
Synchronous condenser
Large
Small
2.0
In defining the inertia constant H, the MVA base used is the rating of the machine. In a
multi machine system, swing equation has to be solved for each machine, in which case,
a common MVA base for the system has to chosen. The constant H of each machine must
be consistent with the system base.
Let
G
system
Gmach
on both sides we get
Gsystem
2 H d 2 m Pm Pe
Gmach
dt
s
m
Gmach
G
system
(5.31)
2 H system d 2 m
Pm Pe pu (on system base)
s m
dt 2
where H system = H
Gmach
Gsystem
(5.32)
84
The swing equations for two machines on a common system base are:
2H1 d 2 1
Pm1 Pe1 pu
s d t 2
(5.33)
2H 2 d 2 2
Pm 2 Pe 2 pu
s d t 2
(5.34)
Now 1 2 (since they swing together). Adding (5.33) and (5.34) we get
2 H eq d 2
Pm Pe pu
s d t 2
(5.35)
Where H eq H 1 H 2
Pm Pm1 Pm 2
Pe Pe1 Pe 2
The relation (5.35) represents the dynamics of the single equivalent machine.
For any two non coherent machines also (5.33) and (5.34) are valid. Subtracting (5.34)
from (33) we get
2 d 2 1 2 d 2 2 Pm1 Pe 1 Pm 2 Pe 2
s d t 2 s d t 2
H1
H2
Multiplying both sides by
H1 H 2
H1 H 2
(5.36)
we get
85
2
s
2
H 1 H 2 d 1 2 Pm1 H 2 Pm 2 H 1 Pe1 H 2 pe 2 H 1
H1 H 2
H1 H 2
d t2
H1 H 2
i.e
d 2 12
2
H 12
Pm12 Pe12
s
d t2
where
H 12
(5.37)
H1 H 2
H1 H 2
Pm12
p m1 H 2 p m 2 H 1
H1 H 2
Pe12
pe1 H 2 pe 2 H 1
H1 H 2
From (5.37) it is obvious that the swing of a machine is associated with dynamics of
other machines in the system. To be stable, the angular differences between all the
machines must decrease after the disturbance. In many cases, when the system loses
stability, the machines split into two coherent groups, swinging against each other. Each
coherent group of machines can be replaced by a single equivalent machine and the
relative swing of the two equivalent machines solved using an equation similar to (5.37),
from which stability can be assessed.
The acceleration power is given by Pa = Pm Pe. Hence, under the condition that Pm is a
constant, an accelerating machine should have a power characteristic, which would
increase Pe as increases.
This would reduce Pa and hence the acceleration and help in maintaining stability. If on
the other hand, Pe decreases when increases, Pa would further increase which is
detrimental to stability. Therefore,
P
must be positive for a stable system. Thus the
86
(ii)
(iii)
Effect of voltage regulating loop during the transient is neglected i.e the
excitation is assumed to be a constant.
As discussed in section 4, the powerangle relationship plays a vital role in the solution
of the swing equation.
87
Ia = Armature current
Ra = Armature resistance
xd = Direct axis reactance
The power output of the generator is given by the real part of E g Ia* .
Ia
E g Vt 0
Ia
Neglecting Ra,
(5.38)
Ra jx d
E g Vt 0
jxd
E g 90 Vt 90
P = R E g
xd
xd
E g cos 90
2
xd
E g Vt cos 90
xd
E g Vt sin
xd
(5.39)
(Note- R stands for real part of). The graphical representation of (9.39) is called the
power angle curve and it is as shown in Fig 5.3.
The maximum power that can be transferred for a particular excitation is given by
E g Vt
xd
at = 90o.
88
Power output
Ed I d Eq I q
(5.40)
E d Vt sin ;
E q Vt cos
E g Eq
I a sin
Id
Iq
xd
Ed
I a cos
xq
(5.41)
E g Vt sin
xd
Vt x d x q sin 2
2
2 xd xq
(5.42)
89
the relation (5.42) gives the steady state power angle relationship for a salient pole
machine. The second term does not depend on the excitation and is called the reluctance
power component. This component makes the maximum power greater than in the
classical model. However, the angle at which the maximum power occurs is less than 90o.
In Fig. 5.5, the infinite bus voltage is taken as reference and is the angle between E g and
Eb. The generator is assumed to be connected to the infinite bus through a lossless line of
reactance xe. The power transferred (using classical model) is given by
P=
E g Eb
x d xe
sin
(5.43)
E g Eb
x d xe
sin
Eb
xq
2 xd xe xq xe
sin 2
(5.44)
90
An important measure of performance is the steady state stability limit, which is defined
as the maximum power that can be transmitted in steady state without loss of
synchronism, to the receiving end. If transient analysis is required, respective transient
quantities namely E g , x d and x q are used in (5.43) and (5.44) to calculate the power
output.
Transient stability is the ability of the system to remain stable under large disturbances
like short circuits, line outages, generation or load loss etc. The evaluation of the transient
stability is required offline for planning, design etc. and online for load management,
emergency control and security assessment. Transient stability analysis deals with actual
solution of the nonlinear differential equations describing the dynamics of the machines
and their controls and interfacing it with the algebraic equations describing the
interconnections through the transmission network.
Since the disturbance is large, linearized analysis of the swing equation (which describes
the rotor dynamics) is not possible. Further, the fault may cause structural changes in the
network, because of which the power angle curve prior to fault, during the fault and post
fault may be different (See example 9.8). Due to these reasons, a general stability criteria
for transient stability cannot be established, as was done in the case of steady state
stability (namely PS > 0). Stability can be established, for a given fault, by actual solution
of the swing equation. The time taken for the fault to be cleared (by the circuit breakers)
is called the clearing time. If the fault is cleared fast enough, the probability of the system
remaining stable after the clearance is more. If the fault persists for a longer time,
likelihood of instability is increased.
Critical clearing time is the maximum time available for clearing the fault, before the
system loses stability. Modern circuit breakers are equipped with auto reclosure facility,
wherein the breaker automatically recloses after two sequential openings. If the fault still
persists, the breakers open permanently. Since most faults are transient, the first reclosure
91
is in general successful. Hence, transient stability has been greatly enhanced by auto
closure breakers.
Some common assumptions made during transient stability studies are as follows:
1. Transmission line and synchronous machine resistances are neglected. Since
resistance introduces a damping term in the swing equation, this gives
pessimistic results.
2. Effect of damper windings is neglected which again gives pessimistic results.
3. Variations in rotor speed are neglected.
4. Mechanical input to the generator is assumed constant. The governor control
loop is neglected. This also leads to pessimistic results.
5. The generator is modeled as a constant voltage source behind a transient
reactance, neglecting the voltage regulator action.
6. Loads are modeled as constant admittances and absorbed into the bus
admittance matrix.
The above assumptions, vastly simplify the equations. A digital computer program for
transient stability analysis can easily include more detailed generator models and effect of
controls, the discussion of which is beyond the scope of present treatment. Studies on the
transient stability of an SMIB system, can shed light on some important aspects of
stability of larger systems. One of the important methods for studying the transient
stability of an SMIB system is the application of equal-area criterion.
92
d t
0
dt
some time after the fault is cleared in a stable system and
d
> 0, for a long time after
dt
d 2
Pm Pe Pa
dt 2
d 2 Pa
dt 2 M
Multiplying both sides by 2
2
d
, we get
dt
d d 2
d Pa
2
2
dt dt
dt M
d t dt
dt M
93
2
d
M
dt
2
or
dt
For stability
P d
a
2
M
P d
(5.45)
d
0 , some time after fault is cleared. This means
dt
P d
a
(5.46)
The integral gives the area under the Pa curve. The condition for stability can be, thus
stated as follows: A SMIB system is stable if the area under the Pa curve, becomes
zero at some value of . This means that the accelerating (positive) area under P a
curve, must equal the decelerating (negative) area under Pa curve. Application of
equal area criterion for several disturbances is discussed next.
Fig.5.7
SMIB System
Pe Pmax sin
Pmax
Eg V
x d xe
Under steady state Pm = Pe. Let the machine be initially operating at a steady state angle
o, at synchronous speed s, with a mechanical input Pmo, as shown in Fig.5.8 ( point a).
94
If there is a sudden step increase in input power to Pm1 the accelerating power is positive
(since Pm1 > Pmo) and power angle increases. With increase in , the electrical power P e
increases, the accelerating power decreases, till at = 1, the electrical power matches the
new input Pm1. The area A1, during acceleration is given by
A1 =
P
0
m1
Pe d
(5.47)
At b, even though the accelerating power is zero, the rotor is running above synchronous
speed. Hence, and Pe increase beyond b, wherein Pe < Pm1 and the rotor is subjected to
deceleration. The rotor decelerates and speed starts dropping, till at point d, the machine
reaches synchronous speed and = max. The area A2, during deceleration is given by
A2 =
max
(5.48)
By equal area criterion A1 = A2. The rotor would then oscillate between 0 and max at its
natural frequency. However, damping forces will reduce subsequent swings and the
machine finally settles down to the new steady state value 1 (at point b). Stability can be
maintained only if area A2 at least equal to A1, can be located above Pm1. The limiting
case is shown in Fig.5.9, where A2 is just equal to A1.
95
Here max is at the intersection of Pe and Pm1. If the machine does not reach synchronous
speed at d, then beyond d, Pe decreases with increase in , causing to increase
indefinitely. Applying equal area criterion to Fig.5.9 we get
A1 = A2.
From (5.47) and (5.48) we get
(5.49)
Equation (5.49) is a non-linear equation in max and can be solved by trial and error or by
using any numerical method for solution of non-linear algebraic equation (like NewtonRaphson, bisection etc). From solution of max, Pm1 can be calculated. Pm1 Pmo will give
the maximum possible increase in mechanical input before the machine looses stability.
Example 1: A 50Hz, 4 pole turbo alternator rated 150 MVA, 11 kV has an inertia
constant of 9 MJ / MVA. Find the (a) stored energy at synchronous speed (b) the rotor
acceleration if the input mechanical power is raised to 100 MW when the electrical load
is 75 MW, (c) the speed at the end of 10 cycles if acceleration is assumed constant at the
initial value.
96
Solution:
(a)
(b)
Pa = Pm Pe = 100 75 = 25 MW
M=
GH
1350
0.15 MJ s /e
180 f 180 50
0.15
d2
25
d t2
Acceleration
d 2
25
166.6 e/s2
2
0.15
dt
= 166.6
2
m/s2
P
= 166.6
2
1
rps /s
P
360
= 166.6
2
1
60 rpm/s
P
360
= 13.88 rpm/s
* Note e = electrical degree; m = mechanical degree; P=number of poles.
(c) 10 cycles =
10
0 .2 s
50
NS = Synchronous speed =
120 50
1500 rpm
4
Rotor speed at end of 10 cycles = NS + 0.2 = 1500 + 13.88 0.2 = 1502.776 rpm.
Example 2: Two 50 Hz generating units operate in parallel within the same plant, with
the following ratings: Unit 1: 500 MVA, 0.8 pf, 13.2 kV, 3600 rpm: H = 4 MJ/MVA;
Unit 2: 1000 MVA, 0.9 pf, 13.8 kV, 1800 rpm: H = 5 MJ/MVA. Calculate the equivalent
H constant on a base of 100 MVA.
Solution:
H 1system H 1 mach
G1 mach
Gsystem
H 2 system H 2 mach
G2 mach
Gsystem
= 4
500
20 MJ/MVA
100
= 5
1000
50 MJ/MVA
100
97
H eq H 1 H 2 = 20 + 50 = 70 MJ/MVA
This is the equivalent inertia constant on a base of 100 MVA and can be used when the
two machines swing coherently.
Example 3: Obtain the power angle relationship and the generator internal emf for (i)
classical model (ii) salient pole model with following data: xd = 1.0 pu : xq = 0.6 pu : Vt
= 1.0 pu : Ia = 1.0 pu at upf
Solution:
(i) Classical model: The phasor diagram is shown in Fig P3.
E g Vt I a x d
2
= tan 1
1.414
Ia xd
1 .0
= tan 1
45
Vt
1 .0
Eg = 1.414 45 .
(ii) Salient pole: From Fig (5), we get using (41a) to (41d)
Eg = Eq + Id xd = Vt cos + Id xd
= Vt cos + Ia sin xd
98
Vt sin Ia cos xq = 0
Substituting the given values we get
0 = sin 0.6 cos
We thus have two simultaneous equations.
Eg = cos + sin
0 = sin 0.6 cos
Solving we get = 30.96o
Eg = 1.372 pu
If the excitation is held constant, then from (42)
P = 1.372 sin + 0.333 sin 2
Example 4: Determine the steady state stability limit of the system shown in Fig 8, if Vt
= 1.0 pu and the reactances are in pu.
Fig. P4 Example 4
Solution:
Current I =
j1.0
j 1 .0
Eg Vt j 1.0 ( I )
99
= 1
2 cos 1 = 0
= cos-1 0.5 = 60o
E g = 2 sin 60o = 1.732
1.732 1.0
0.866 pu
1 .0 1 .0
Fig . P5 Example 6
(a) X = 0.4 +
0.35
= 0.575 pu
2
100
Pmax =
E g Eb
X
1 .2 1 .0
2.087 pu
0.575
o sin 1
Pe
0 .8
sin 1
22.54 .
Pmax
2.087
H
5 .2
Without damping s = j
PS
1.927
j
M
0.0331
PS
1.927
=
= 7.63 rad/sec = 1.21 Hz
M
0.0331
(a) n =
(b) =
D
2
1
0.14
M PS
2
1
= 0.277
0.0331 1.927
1
1
= 1.892 s
4
n
0.277 7.63
o
1
= 22.54 o
e nt sin d t
8.59
1 0.277
101
Fig.P6
(ii)
(iii)
Solution:
(i)
(ii)
If a short circuit occurs in the middle of the line, the network equivalent
can be draw as shown in Fig. 12a.
102
The network is reduced by converting the delta to star and again the resulting star to delta
as shown in Fig P7a, P7b and P7c.
Fig.P7b
Fig.P7c
103
1 .2 1 .0
= 0.744 ;
1.55
Pe = 0.744 sin
1 .2 1 .0
= 1.6
0.75
Pe = 1.6 sin
Example 8: A generator supplies active power of 1.0 pu to an infinite bus, through a
lossless line of reactance xe = 0.6 pu. The reactance of the generator and the connecting
transformer is 0.3 pu. The transient internal voltage of the generator is 1.12 pu and
infinite bus voltage is 1.0 pu. Find the maximum increase in mechanical power that will
not cause instability.
Solution:
Pmax =
1.12 1.0
= 1.244 pu
0 .9
o = sin-1
1 .0
= 53.47o = 0.933 rad.
1.244
The above can be solved by NR method since it is of the form f(max) = K. Applying N
R method, at any iteration r, we get
(r )
max
=
df
d max
(r )
K f max
df
r
d max
(r )
(r )
max
o cos max
(r )
( r 1)
(r )
(r )
max
max
max
(r )
iteratively till max
. Here K = cos o = 0.595. The computations are shown in table
(1)
P8, starting from an initial guess max
= 1.745 rad.
104
Table P8
Interaction
r
(r )
max
df
d max
(r )
(r )
f max
(r )
max
( r 1)
max
1.745 0.1407
0.626
0.22
1.965
1.965
0.396
0.568
0.068
1.897
1.897
0.309
0.592
0.0097 1.887
1.887 0.2963
0.596
0.0033 1.883
(r )
Since max
is sufficient by small, we can take
105
d 21 Pm1 Pe1
P P
m e
2
dt
M1
M1
d 2 2 Pm 2 Pe 2
P P
e m
2
dt
M2
M2
Simplifying, we get
d 2 (1 2 ) M 1 M 2
( Pm Pe )
dt 2
M1 M 2
or
d 2
Pm Pe
dt 2
M eq
where Meq =
M 1M 2
M1 M 2
= 1 2
Pe
E1 E 2
x d 1 xe x d 2
sin
This relation is identical to that of an SMIB system in form and can be used to determine
the relative swing (1 2) between the two machines to assess the stability.
------------------------
106