earthingFAQ PDF
earthingFAQ PDF
27/07/2012
max 30
max 30
max 10
c) Combined TX/RMU maximum 10 ohms per electrode where 2 electrodes exist per
TX/RMU site. When HV and LV earths are combined the final installation shall be no
greater than 1 ohm.
2) Do we drill additional rods at Pillars to get to the minimum combined earth reading
of <1ohm?
Yes, this can be done only if <1ohm combined earthing cannot be met. This does not
eliminate the requirement of achieving maximum 10ohm at each electrode of a TX or RMU
site. It may be necessary to drill at pillars where the LV network (of new subdivision) is
sparse i.e. less than 20 pillars. Refer also to Q6.
Where additional rods are drilled at a pillar to achieve <1ohm combined earthing, the pillar
shall be marked DEEP EARTH. The label will be fitted inside the pillar, be non
conductive and be indelible. The deep earth will then form an integral part of the new
installation and relocation of that pillar needs to account for the deep earth. The Deep
Earth shall be marked on the As Constructed drawing. A deep earth depth is typically
30m.
3) Can we install counterpoise earthing, i.e. install an earth cable (bare or insulated)
between the transformer site and another electrode further away from the site?
No. The reason for this is earth potential rise can transfer voltages into adjacent
equipment and/or services. Our preference is to use the cable screens (neutrals) that are
insulated and connect them to deep earths at pillars.
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Page 1 of 7
5) How many connections are required from the terminal bar and the earth electrodes?
Refer to the drawings showing on next page. The Terminal Bar (defined in AS/NZS
3000:2007, Section K.11.4.4) of the transformer consists of 2 parts that are
interconnected i.e. LV bar and HV bar. The reason for having an interconnection
(Combined HV & LV link is factory fitted earth cable) is to allow for separate HV and LV
earthing if deemed absolutely necessary. With a single Terminal Bar this would not be
possible.
There are 2 connections to the earth electrodes, which also couple as a grading ring.
Electrode 1 (max.
10 ohms)
Electrode 2 (max.
10 ohms)
MEN Link
3 separate
connections
2 separate connections to
earthing conductor leading to
earth electrodes
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Page 2 of 7
CMEN Areas
EQUIPMENT
Local Earth Area
ITEM
Requirements CMEN
Standard
Pole-Mounted
Distribution
Transformer
LV Earth Requirement
Area
MEN
Connect all
items to 30
max local earth
and area
CMEN.
N/A
Ground
Connect all
Mounted URD items to 10
Substation
max local earth
and area
CMEN.
N/A
N/A
N/A
HV Switch
Poles
Country
Connect all
1 Connect all items to
items to 10
max 10 max local earth
max local
earth and area
CMEN.
6) What are the steps and process to achieve earthing for a TX that complies with the
standards?
There are two options for achieving electrode and system earthing resistance
requirements. One option is to install the earth equipment on site until the requirements
are achieved. The process for this is given in the table below. The other option is to
engage an Earthing Consultant before the subdivision is installed to undertake an earthing
design to determine the extent of earthing works required for the site that satisfies safe
touch, step and transfer potential criteria.
For both cases field measurements must be made to prove the network impedances.
Note: the earthing requirement for combination RMU and TX site is the same as a standalone TX site.
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Page 3 of 7
Step
Description
Responsibility
Developer/
installer
6.
7.
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Developer/
installer
Developer/
installer
Developer/
installer
Developer
/Earthing
Consultant
Western Power
Developer
/Earthing
Consultant
Page 4 of 7
8) What length of earth test lead should be used to measure the electrode
resistance?
Most testers adopt the Fall-of-Potential method using a Current probe (C) and a Potential
probe (P) that is placed 62% the distance of probe C from the earth electrode under test.
When earth testing with Megger, if depth of the electrode is I, then the test probe P of the
earth tester must be placed at minimum (or further) 2xI from the earth electrode and the
C probe must be 3.2xI from the earth electrode (in that ratio where P probe is 62% the
distance between the earth electrode and C probe). This ensures an accurate earth
resistance measurement, otherwise the measurement will result in higher resistance
readings due to summation of the zones of influence of the earth electrode and the C
probe. Refer to arrangement below.
EXAMPLE - if rods have been drilled to 10m (I) then probe P must be at a minimum (or
more) 20m (2 x I) from earth electrode and probe C must be 32m (3.2 x I) from earth
electrode.
Probe P
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Probe C
Page 5 of 7
Below is a guide of test lead lengths required to test electrodes of various depths, which
should be followed to achieve correct earth resistance readings. The test lead length is
not limited to 320m, where the test equipment is capable of longer lengths.
ELECTRODE DEPTH
<15m
15 - 30m
30 - 45m
45 - 60m
60 - 75m
75 - 100m
30m
60m
90m
120m
150m
200m
50m
100m
150m
190m
240m
320m
9) Are the earthing standards changing and how will this impact construction?
Yes, the standards are changing such that AS3000:2000 is being revised and could be
issued as AS3000:2007 (release date is uncertain at this stage). The section on HV
earthing has been retained at present but will be superseded by AS2067, which is also
being revised at present. All HV earthing standards will reside in the new version of
AS2067, which does not define resistance values to be achieved but instead defines
touch voltage limits that are applied to a risk assessment as shown in the flowchart. This
means earthing systems need to be designed to meet the specific risk criteria for a
particular site and depends on:
a) Earth fault current and duration
b) Soil resistivity
c) Level of LV interconnection
d) Other factors
It is envisaged that each design drawing will have on it a resistance value that needs to
be achieved and any other remedial earthing work required to ensure touch voltage limits
are satisfied, all of which are derived by undertaking a level of earthing design.
Standard resistance values of 30ohm, 10ohm and 1ohm may not exist.
MEN
Connection
DMS#: 4031787v7
File#: AM/96/S4(28)V1
MEN
Link
Page 6 of 7
Body impedance at
power frequency see
IEC 60479
Add
bare hand to earthing
path resistance and if
applicable individual
protection equipment
Add
bare foot to earthing
resistance and if
applicable individual
protection equipment
Fault/Human contact
coincidence likelihood
Fibrillation probability
(if present at time of fault)
Societal acceptable
shock safety level
DMS#: 4031787v7
File#: AM/96/S4(28)V1
Page 7 of 7