Fault Currents
Fault Currents
Whereas the Parliament of India has set out to provide a practical regime of right to
information for citizens to secure access to information under the control of public authorities,
in order to promote transparency and accountability in the working of every public authority,
and whereas the attached publication of the Bureau of Indian Standards is of particular interest
to the public, particularly disadvantaged communities and those engaged in the pursuit of
education and knowledge, the attached public safety standard is made available to promote the
timely dissemination of this information in an accurate manner to the public.
1 +, 1 +
01 ' 5
Jawaharlal Nehru
! $ ' +-
Satyanarayan Gangaram Pitroda
! > 0 B
BharthariNtiatakam
( Reaffirmed 2002 )
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Indian Standard
FOREWORD
This Indian
Standard
which
is identical
with IEC Pub 909 ( 1988 ) Short-circuit
current
calculation
in three-phase
A. C. systems,
issued
by the International
Electrotechnicai
Commission
( IEC ) was adopted by the Bureau of lndian Standards
on the recommendations
of
the Electrical
Installations
Sectional
Committee
(ET 20) and approval
of the Eiectrotechnicai
Division
Council.
An important
criterion
for the proper selection
of a circuit-breaker
or any other fault protective devices for use at a point in an electrical
circuit
is the information
on maximum
fault
current likely at that point.
The electromagnetic,
mechanical
and thermal
stresses which a
switchgear
and the associated
apparatus
have to uithstand
depends on the fault current.
Proper
selection
of breaking and withstand
capacities
play a major role in the health
of the electrical
installations.
Realizing
this need and to provide uniform.guide
for calculation
of short-circuit
currents,
IS 5728 was brought out in 1970.
considerable
more information
have been
Subsequent
to the preparation
of this standard,
collated
the world over on calculation
of fault iaveis under different and specific circumstances.
There was also a need to simplify calculation
techniques
in a practical
way commensurate
with
the modern arithmatic
tools available
to engineers
in the form of computers,
digital
transient
network analysers,
etc.
With an objective
to establish
a general,
practicable
and concise
procedure
for short-circuit
current
calculations
IS 5728 has been taken up for revision,
aligning
its contents
with IEC 909 ( 1988 ).
On the publication
CROSS
of this standard,
stand
superseded.
REFERENCES
International
Standard
131 : Electric
441 : Switchgear.
of the effects
bands for
preferred
electrical
voltages
vocabulary:
1
( Part
I51 : Electrical
Voltage
including
IS 1985 Eiectrotechnicai
eiectrotechnicai
IS 12360 : 1988
instalia.ions
and frequency
voltages
i
J
( Part
57 ) : 1982 Electric
circuits
17 ) : 1989 Switchgear
and
magnetic
and controlgear
of
the cflticts
of
IS 13234:1992
IEC Pub 909 (1988)
CONTENTS
Clause
1.
scope ................................................
2.
Object. ......................................
............................................
3.
Definitions.
4.
Symbols, subscripts and superscripts ...............................
..........................................
4.1
Symbols.
.........................................
4.2
Subscripts.
........................
4.3
Superscripts.
5.
6.
7.
8.
9.
_ ...............
9
10
.......................
SYSTEMSwrrn SHORT-CIRCUITS
CURRENTS
HAVINGNOA.C. COMFONENI
DECAY
( FAR-FROM-GENERATOR
SHORTCIRCUITS)
General...............................................l4
.....................................
Short-circuit parameters.
8.1
Balanced short circuit ...................................
8.2
Unbalanced short circuit ..................................
8.3
Short-circuit impedances ..................................
8.4
Conversion of impedances, currents and voltages .....................
Calculation of short-circuit currents. ...............................
9.1
Calculation method for balanced short circuits. ......................
9.2
Calculation method for line-to-line and line-to-earth short circuits
9.3
The minimum short-circuit currents ............................
SECTION
Two -
......
......
Calculation
14
14
14
15
22
22
22
26
29
..............................................
10. General.
11. Short-circuit parameters ......................................
..........................................
11.1 General
11.2 Balanced short circuit. ...................................
11.3 Unbalanced short circuit ..................................
Appendix
3
3
4
7.
7
8
8
_ ........
of short-circuit
.........
30
30
30
32
32
33
33
37
37
37
37
48
48
:z
49
53
53
53
53
54
IS 13234 : 1992
IEC Pub 909 ( 1988 )
1.
Scope
This standard is applicable to the calculation
currents:
in low-voltage
three-phase
of short-circuit
a.c. systems,
at
Object
The object of this standard is to establish a general, practicable and concise procedure
leading to conservative results with sufficient accuracy. For this purpose, an equivalent voltage
source at the short-circuit location is considered, as described under Clause 6. This does not
exclude the use of special methods, for example the superposition method, adjusted to
particular circumstances, if they give at least the same precision.
Short-circuit currents and short-circuit impedances may also be determined by system tests,
by measurement on a network analyzer, or with a digital computer. In existing low-voltage
systems it is possible to determine the short-circuit impedance on the basis of measurements at
the location of the prospective short circuit considered.
The calculation of the short-circuit impedance based on the rated data of the electrical
equipment and the topological arrangement of the system has the advantage of being possible
both for existing systems and for systems at the planning stage.
There are two different
magnitude:
short-circuit
short-circuit
current
currents
to be calculated
which determines
which differ
in their
the maximum
equipment;
the minimum short-circuit current which can be a basis, for example, for the selection of
fuses and for the setting of protective devices and for checking the run-up of motors.
One has to distinguish between:
currents
deliberately
decay (far-from-generator
created
under controlled
An application guide, dealing with non-meshed low-voltage three-phase a.c. systems and a
technical report on the derivation of the parameters and various calculation factors of this
standard are under consideration.
( IEC
page 7 )
IS 13234 : 1992
IEC Pub 909 ( 1988 )
3.
Definitions
For the purpose of this standard, the following definitions apply. Reference is made to the
International Electrotechnical Vocabulary (IEV) [IEC Publication 501 when applicable.
3.1
Short circuit
3.3
The current that would flow if the short circuit were replaced by an ideal connection of
negligible impedance without any change of the supply.
Note. - The current in a three-phase short circuit is assumed to be made simultaneously in all poles. Investigations
of non-simultaneous short circuits, which can lead to higher aperiodic components of short-circuit current,
are beyond the scope of this standard.
3.7
D. C. (aperiodic)
component
u, r,:
The mean value between the top and bottom envelope of a short-circuit current decaying
from an initial value to zero according to Figures 1 and 12.
3.8
W page9 )
IS13234:1992
IEC Pub 909 ( 1988 )
3.9
3.10
3.11
3.12
3.13
3.14
3.15
3.16
operating
3.17
the subtransient
behaviour of generators
and motors.
3.18
of prospective
( IEC
page 11)
IS 13234: 1992
IEC Pub 909( 1988)
Near-to-generator
3.19
short circuit
A short circuit to which at least one synchronous machine contributes a prospective irqitial
symmetrical short-circuit current which is more than twice the generators rated current, or a
short circuit to which synchronous and asynchronous motors contribute more than 5% of the
initial symmetrical short-circuit current I;: without motors (see Clause 10).
Short-circuit
3.20
3.20.1
impedances
Positive-sequence
at the short-circuit
shorf-circuit
location
_(,,
of u three-phase
Z
impedance
a.c. system
3.20.2
short-circuit
z,_,, o f a three-phase
impedance
a.(:. system
3.20.3
short-circuit
impedance
_(,,,
Z sf a three-phrse
location
location
a.c. system
The impedance of the zero-sequence system as viewed from the short-circuit location (see
Sub-clause 8.3.1 and Figure 4c, page 27). It includes three times the neutral-to-earth
impedance 3 ZNE.
Short-circuit
3.20.4
impedance
Zk of u three-phase
a.c. system
Short-circuit
3.21.1
impedances
Positive-sequence
of electrical
short-circuit
short-circuit
short-circuit
equipment
impedance
zC,) of electrical
equipment
lndex of symbol z,, , may be omitted if there is no possibility of confusion with the negative-sequence
zero-sequence short-circuit impedances.
Negative-sequence
3.21.2
short-circuit
impedance
+,
of electrical
and the
equipment
The ratio of the line-to-neutral voltage to the short-circuit current of the cor_responding
phase of electrical equipment when fed by a symmetrical negative-sequence
system of voltages
(see Sub-clause 8.3.2).
Zero-sequence
3.21.3
short-circuit
impedance
&,
of electrical
equipment
The ratio of the line-to-earth voltage to the short-circuit current of one phase of electrical
equipment when fed by an a.c. voltage source, if the three @aralltf phase &nifu&rsBle
L&WI.
for the outgoing current and a fourth line and/or earth is joint return (see Sub-clause 8.3.2).
3.22
Subtransient
reuctance
X; of a synchronous
machine
The effective reactance at the moment of short circuit. For the calculation
currents the saturated value of xl: is taken.
of short-circuit
Note. - When the reactance X; in ohms is divided by the rated impedance ZrG = U$, I S,o of the synchronous
machine, the result in per unit is represented by a small letter xb = A.:/ &.
(IEC~page
13)
6
IS 13234 : 1992
IEC Pub 909 ( 1988 )
3.23
Note. - The time t,,, is the sum of the shortest possible operating time of an instantaneous relay and the shortest
opening time of a circuit breaker. It does not take into account adjustable time delays oftripping devices.
4.
are underlined,
All equations are written without specifying units. The symbols represent quantities
possessing both numerical values and dimensions that are independent of units, provided a
coherent unit system is chosen, for example. the International System of Units (SI).
4.1
Symbols
A
C
CU,l$3
f
lb
Ik
I kP
$
or &
ILit
iDC
P
K
P krT
4
al
R resp. r
RG
S
s:
tr
tmm
4
un
ur
Ukr
4
XA resp. Xi
X d sat
Z resp. 2
%
31)
32)
30)
tl
IS 13234 : 1992
IEC Pub 909 ( 1988)
x
1
P
&3
e
p
4.2
Subscripts
(1)
(2)
UJ)
f
k or k3
kl
k2
k2E resp. kE2E
max
min
n
r
rsl
t
AT
B
E
F
CJ
HV
LV
L
LR
Ll, L2, L3
$
MV
N
P
PSU
Q
T
4.3
Superscripts
n
I
Positive-sequence
component
Negative-sequence
component
Zero-sequence component
Fictitious
Three-phase short circuit
Line-to-earth short circuit, line-to-neutral short circuit
Line-to-line short circuit without earth connection
Line-to-line short circuit with earth connection. line current respectively
Maximum
Minimum
Nominal value (IEV 151-04-01)
Rated value (IEV 151-04-03)
Resulting
Transformed value
Auxiliary transformer
Busbar
Earth
Fault, short-circuit location
Generator
High-voltage, high-voltage winding of a transformer
Low-voltage, low-voltage winding of a transformer
Line
Locked rotor
Line 1, 2. 3 of a three-phase system
Asynchronous motor or group of asynchronous motors
Without motor
Medium-voltage, medium-voltage winding of a transformer
Neutral of a three-phase a.c. system
Terminal, pole
Power-station unit (generator and transformer)
Feeder connection point
Transformer
earth current
IS 13234: 1992
IEC Pub 909 ( 1988 )
Current
t
Decaying
(aperiodic1 component
ice
c
Time
Bottom
envelope
r,
lp
I,
= steady-state short-cirtiit current
iDc = decaying (aperiodic) component of short-circuit current
A
= initial value of the aperiodic component ioc
Calculation assumptions
A complete calculation of short-circuit currents should give the currents as a function of time
at the short-circuit location from the initiation of the short circuit up to its end, corresponding
to the instantaneous value of the voltage at the beginning of short circuit (see Figures 1 and 12,
pages 19 and 63).
In most practical cases a determination like this is not necessary. Depending on the
application of the results, it is of interest to know the r.m.s. value of the symmetrical a.c.
component and the peak value ip of the short-circuit current following the occurrence of-a short
circuit. The value ipdepends on the time constant of the decaying aperiodic component and the
frequencyf, that is on the ratio R/X or X/R of the short-circuit impedance zk, and is nearly
reached if the short circuit starts at zero voltage.
In meshed networks there are several time constants. That is why it is not possible to give an
easy exact method of calculating ip -and z&. Special methods to calculate ip with sufficient
accuracy are given in Sub-clause 9.1.3.2.
For the determination of the asymmetrical short-circuit breaking current the decaying
aperiodic component iDC of the short-circuit current as shown in Figures 1 or 12 may be
calculated with sufficient accuracy by:
where:
4
R/X
=
=
=
=
IS 13234 : 1992
IEC Pub 909 ( 1988)
In meshed networks according to Sub-clause 9.1.3.2 - Method A - the right hand side of
eyuation( 1) should be multiplied by 1.15. According to Sub-clause 9.1.3.2 - Method B - the
equivalent frequency should be selected as follows:
2JFft
-fJf
<2JE
<5X
<lOJr
c25Jr
0.27
0.15
0.092
0.055
where f = 50 Hz or 60 Hz.
Furthermore, the calculation of maximum and minimum short-circuit currents is based on
the following simplifications:
1) For the duration of the short circuit there is no change in the number of circuits involved,
that is, a three-phase short circuit remains three phase and a line-to-earth short circuit
remains line-to-earth during the time of short circuit.
2) Tap changers of the transformers are assumed to be in main position.
3) Arc resistances are not taken into account.
While these assumptions are not strictly true for the power systems considered,
recommended short-circuit calculations have acceptable accuracy.
the
For balanced and unbalanced short circuits as shown in Figure 2, page 23, it is useful to calculate the short-circuit currents by the method of symmetrical components (see Subclause 8.2).
6.
10
IS 13234 : 1992
IEC Pub 909 ( 1988 )
d)
Short-circuit
!i;2E
current
a)
b)
c)
d)
FIG. 2. -
Branch short-circuit
currents
in conductors
and earth
Characterization of short circuits and their currents. The direction of current arrows
is chosen arbitrarily.
Finally high-voltage transformers in many cases are equipped with regulators and tap
changers operating under load flow conditions, whereas transformers feeding low-voltage
systems have normally only a few taps, for example + 2.5% or + 4%. The actual regulator or
tap changer position of transformers in the case of far-from-generator short circuits may be
disregarded without unacceptable loss of accuracy by use of this method.
The modelling of the system equipment by means of impedances according to Sub-clauses
8.3.2 and 11.5.3 applies in conjunction with the equivalent voltage source at the short-circuit
location irrespective of whether a far-from-generator short-circuit according to Section One or
a near-to-generator short-circuit according to Section Two is involved.
Figure 3, page 25, shows an example of the equivalent voltage source at the short-circuit
location F as the sole active voltage of the system in the case of a low+oltage system fed by a
single transformer. All other active voltages in the system are assumed to be zero. Thus the
network feeder in Figure 3a, page 25, is represented only by its internal impedance Zo (see
Sub-clause 8.3.2.1). Parallel admittances (e. g. line capacitances and passive loads) are not to
be considered when calculating short-circuit currents in accordance~with Figure 3b, page 25.
11
IS 13234 : 1992
IEC Pub 909 ( 1988 )
The equivalent voltage source cU, I \I 3 (see Sub-clause 3.15) at the short-circuit location Fis
composed of the voltage factor c, the nominal system voltage U, and 43: The voltage factor cis
different for the calculation of maximum or minimum short-circuit currents. If there are no
national standards, it seems adequate to choose a voltage factor c according to Table I,
considering that the highest voltage in a normal system does not differ, on average, by more
than + 5% (LV) or + 10% (HV) approximately from the nominal voltage.
a)
rotating
load
a) System diagram.
b) Equivalent
FIG. 3. -
system)
12
IS 13234: 1992
IEC Pub 909 ( 1988 )
a)
b)
FIG. 4. -
F.
TABLE I
Voltage
factor
c
Voltage factor c for the calculation of
Nominal voltage
Low voltage
1OOVto1OOOV
(IEC Publication 38, Table I)
a) 230 V I400 V
b) Other voltages
c,,,
Crnin
1.00
1.05
0.95
1.00
Medium voltage
> 1 kVto35kV
(IEC Publication 38, Table III)
High voltage
> 35 kV to 230 kV
(IEC Publication 38, Table IV)
Note. - cU, should not exceed the highest voltage U,,, for equipment of power systems.
13
(JEC
page 27)
IS 13234: 1992
IEC Pub 909 ( 1988)
(2b)
(2c)
SECTION
7.
General
This section refers to short circuits where there is no change for the duration of~the short
circuit inthe voltage or voltages that caused the short-circuit current to develop (i. e. a quasistationary voltage condition), nor any significant change in the impedance of the circuit (i. e.
constant and linear impedances).
Therefore, the prospective (available) short-circuit
the following two components:
-
as the sum of
Figure 1, page 19, gives schematically the general course of the short-circuit current in the
case of a far-from-generator
short circuit. The symmetrical a.c. components Ziand Zkare r.m.s.
values and are nearly equal in magnitude.
This assumption is generally satisfied in power systems fed from extended high-voltage
systems through transformers, that is in the case of a far-from-generator
short circuit.
Single-fed short-circuits supplied by a transformer according to Figure 3, page 25, may a
priori be regarded as far-from-generator
short circuits if Xr,v 3 2 Xo, with Xo, to be calculated
in accordance with Sub-clause 8.3.2.1 and Xr,v in accordance with Sub-clause 8.3.2.2.
8.
8.1
Short-circuit parameters
Bulanced short circuit
The
Figure
values
simple
In calculating the short-circuit current, it is sufficient to take into account only the positive2 asseenfromthefaultlocation
(see Sub-clause8.3.1).
sequence short-circuit impedanceZtl, = _k
Details of calculation
8.2
(asymmetrical)
line-to-line
line-to-line
line-to-earth
(IEC page 29 )
14
IS 13234 : 1992
IEC Pub 909 ( 1988 )
As a rule, the three-phase short-circuit current is the largest. In the event of a short circuit
near to a transformer with neutral earthing or a neutral-earthing transformer, the line-to-earth
short-circuit current may be greater than the three-phase short-circuit current. This applies in
particular to transformers of vector group Yz, Dy and Dz when earthing the y- or z-winding on
the low voltage side of the transformer.
In three-phase systems the calculation of the current values resulting from unbalanced short
circuits is simplified by the use of the method of symmetrical components which requires the
calculation of three independent
system components,
avoiding any coupling of mutual
impedances.
Using this method, the currents in each line are found by superposing
symmetrical component systems:
-
positive-sequence
current L(t),
- negative-sequence
current &,
- zero-sequence current I(O).
Taking the line Ll as reference,
a=-_+j-
L(l)
42)
a 42)
r,2
a2 L(l)
lL3
g i(1)
+ a2
: J3;
42)
(34
L(O)
I(O)
(3c)
a2=-
T-j+i:i
(4)
symmetrical
component
(see Sub-
The method of the symmetrical components postulates that the system impedances are
balanced, for example in the case of transposed lines. The results of the short-circuit calculation
have an acceptable accuracy also in the case of untransposed lines.
8.3
Short-circuit impedances
For the purpose of this standard, one has to make a distinction between short-circuit
impedances at the short-circuit location F and short-circuit impedances of individual electrical
equipment. According to the calculation with symmetrical components positive-sequence,
negative-sequence
and zero-sequence short-circuit impedances shall be considered.
8.3.1
15
(EC
page 31)
IS 13234: 1992
IEC Pub 909 ( 1988)
phase order is applied to the short-circuit location F. When calculating short-circuit currents in
accordance with Clause 9, all line capacitances and parallel admittances of non-rotating loads
are neglected.
The values of positive-sequence
and negative-sequence
impedances can differ from each
other on!y in the case of rotating machines. In this section, where far-from-generator
short
circuits are calculated, it is generally allowed to take &) = z(r).
The zero-sequence short-circuit impedance &,) at the short-circuit location F is obtained
according to Figure 4c, page 27, if an a.c. voltage is applied between the short-circuited lines
and the common returns (e. g. earth system, neutral conductor, earth wires, cable sheaths,
cable armouring).
When calculating unbalanced short-circuit currents in medium or high-voltage systems and
applying an equivalent voltage source at the short-circuit location, the line zero-sequence
capacitances and zero-sequence parallel admittances of non-rotating loads are to be considered
for isolated neutral systems and resonant earthed systems.
Neglecting the line zero-sequence capacitances in earthed neutral systems leads to results
which are higher than the real values of the short-circuit currents. The deviation depends on
several parameters of the system, for example the length of the line between transformers with
neutral earthing.
In low-voltage systems, line capacitances
be neglected.
short-circuit
of non-rotating
loads can
d)
Ito1
e
!lOl
31101
G
l-
I(O)
+ YCOI
4 Transformer
b) Transformer
cl
4
FIG. 5. -
Measuring of zero-sequence
(examples).
short-circuit
16
impedances
of electrical
equipment
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Short-circuit impedances
8.3.2
of electrical equipment
In network feeders, transformers, overhead lines, cables, reactors and similar equipment,
positive-sequence
and negative-sequence
short-circuit impedances are equal:
31)
&!m
41)
32)
32)
1 L(2)
8.3.2.1
the zero-sequence
short-circuit impedances differ from the positive-sequence
impedances: -.$ may be larger than, equal to or smaller than &).
Network feeders
If a short circuit in accordance with Figure 6a, page 35, is fed from a network in which only
the initial symmetrical short-circuit power S{o or the initial symmetrical short-circuit current
Iio at the feeder connection point Q is known, then the equivalent impedance Zo of the
network (positive-sequence
short-circuit impedance) at the feeder connection point Q should
be determined by:
ZQ
= CRQ =
c&Q
(54
L-3 riQ
a) Without transformer.
b) With transformer.
FIG. 6. -
17
IS 13234 : 1992
IEC Pub 909 ( 1988 )
If a short circuit in accordance with Figure 6b, page 35, is fed by a transformer from a medium
or high-voltage network in which only the initial symmetrical short-circuit power slC,oor the
initial symmetrical short-circuit current Zioat the feeder connection point Q is known, then the
equivalent impedance Zo, referred to the low-voltage side of the transformer
may be
determined by:
1
c@o
ZQl =
Sk0
cunQ
=
t2r
vi3
p.
t,
where:
u nQ
s;,
initial symmetrical
short-circuit
point Q
f;Q
initial symmetrical
short-circuit
tf
rated transformation
point Q
point Q
In the case of high-voltage feeders with nominal voltages above 35 kV fed by overhead lines,
the equivalent impedance ZQ may be considered as a reaCtanCe,
i. e. ZQ
= 0 + jxQ.
In other
cases, if no accurate value is known for the resistance RQ of network feeders, one may
substitute RQ = 0.1 Xo where Xo = 0.995 Zo.
The initial symmetrical short-circuit power YiQ or the initial symmetrical short-circuit
current &Q on the high-voltage side of the Nsupply transformers shall be given by the supply
company.
In general, the equivalent zero-sequence short-circuit impedance of network feeders is not
required for calculations, In special cases, however, it may be necessary to consider this
impedance.
Transformers
8.3.2.2
Ukr
100%
RT=
zr = RT + jX,
V2rT
&T
URr
___.
V2
-=- IT
100%
&T
P krT
3&
where:
u rr
I rT
SrT
P krT
Ukr
rated short-circuit
llRr
The necessary data may be taken from rating plates or obtained from the manufacturer.
The resistive component
current.
can be calculated
IS 13234 : 1992
IEC Pub POP ( 1988 )
The ratio X/R generally increases with transformer size. For large transformers
the
resistance is so small that the impedance may be assumed to consist only of reactance when
calculating short-circuit current magnitude. Resistance must be considered if the peak shortcircuit current $, or the decaying aperiodic component ioc is to be calculated.
The zero-sequence short-circuit impedances &r = RcOjT+ jXcOITof transformers
or more windings may be obtained from the manufacturer.
Note. -
with two
It is sufficient for transformers with tap-changers to determine Zr in accordance with formula (6) for the
main position and to convert the impedances, currents and voltages according to Sub-clause 8.4 using the
rated transformation ratio t, correspondingto
the tap-changer in the main position.
Special considerations
-
a single fed short-circuit current is calculated and the short-circuit current has the same direction as the
operational current before the short-circuit occurs (short circuit on the low-voltage side of one transformer
or parallel transformers with tap changers according to Figure 3, page 25, or Figure 6b, page 35),
ratio of a transformer
is considerably
100%
ITA
SrT,4~
100%
ITA
SrT,4C
u2
UkrBC
ZBC
(side C open)
(94
(side B open)
(9b)
(side A open)
(9c)
u2
UkrAC
AC =
short-circuit impedances
by the three short-circuit
u2
UkrAB
ZAB
voltage in the
100%
rTA
LS~TBC
(104
(lob)
1
zc
-j-
@AC
+ ZBC
ZAB)
WC)
where:
u rTA
rated voltage
s il
SrlA(
s rTH(
UkrAH
AH
rated short-circuit
u krB(
rated short-circuit
IS 13234 : 1992
IEC Pub 909 ( 1988 )
8.3.2.3
The positive-sequence
short-circuit impedances zL = RL + jXL may be calculated from the
conductor data, such as the cross sections and the centre-distances of the conductors.
For measurement of the zero-sequence short-circuit impedances &) = RCo)+ jX(,,, see Subclause 8.3.2 and Figure 5d, page 33. Sometimes it is possible to calculate the zero-sequence
impedances with the ratios RCOjL/RL
et XcojL/XL.
The impedances &),_ and &_ of low-voltage and high-voltage cables depend on national
techniques andstandards
and may be taken from text-books or manufacturers data.
The effective resistance per unit length R,_ of overhead lines at the medium conductor
temperature 20 C may be calculated from the nominal cross section q,, and the resistivity Q:
R,=
__!_
(11)
qn
with:
1
52mm
___
m
for copper
Q mm
~
m
for aluminium
Q mm
~
m
eYi
=34
and
=31
a)
b)
side
a) Denotation
of winding connections.
FIG. 7. - Three-winding
(IEC
page 41)
20
transformer
system).
(example).
IS 13234 : 1992
IEC-Pub 909 ( 1988 )
The reactance per unit length Xr for overhead lines may be calculated, assuming
transposition, from:
fPQ
0.25
-+ln12
where:
d = :dr, rz dLz L3dL3 r, geometric mean distance between conductors,
r = radius of a single conductor.
; nrRi4, with the bundle radius R
n = number of bundled
conductors;
In
the
case
of
conductor
respectively
bundles,
is
to
be
substituted
by
n = 1
8.3.2.4
0.25
WW
Iz
0.25
+ ln-
d
r
(124
Q/km
The positive-sequence, the negative-sequence and the zero-sequence short-circuit impedances are equal, assuming geometric symmetry. Short-circuit current limiting reactors shall be
treated as a part of the short-circuit impedance.
8.3.2.5
Motors
s 0.01 ri
(13)
where:
%M
ri
= short-circuit
of the short-circuit
21
(IEC
page 43)
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Conversion of impedances, ,,currents and voltages
8.4
When calculating short-circuit currents in systems with different voltage levels, it is necessary
to convert impedances, currents and voltages from one level to the other (e. g. see Figure 3b,
page 25). For per unit or other similar unit systems no conversion is necessary, if these systems
are coherent.
The impedances of the equipment in superimposed or subordinated networks are to be
divided or multiplied by the square of the rated transformation ratio tr or in special cases by the
square of the transformation ratio t, corresponding to the actual position if it is known.
Voltages and currents are to be converted by the rated transformation ratio t, or t.
9.
9.1
9.1.1
9.1.1.1
In accordance with Figure 3, page 25, the three-phase initial symmetrical short-circuit
current Pl; becomes:
where:
=
dJ,t,-3
equivalent
+ x, + x,
z,=,Rz,+Xz,
= sum of series-connected
reactances
= short-circuit
impedance
Resistances of the order of Rk < 0.3Xk may be neglected. The impedance of the system
feeder got = R, + jXQt, referred to the voltage of that transformer side-where the short circuit
occurs, 1sto be calculated according to equations (5a) and (5b)and additional information in
Sub-clause 8.3.2.1.
The scope of Section One supports the following equation:
Zk = Zb = fI,
9.1.1.2
(15)
Because the short circuit is fed by a series circuit, the peak short-circuit current can be
expressed by:
ip = x Jz
I$
(16)
IS 13234 : 1992
IEC Pub 909 ( 1988 )
b)
a)
1.6
t
K
02
0.6
0-4
R/X
0.8
1.0
1.2
0.5
18
20
50
100
X/R -
FIG. 8. -
The factor x for the ratios R/X and X/R is taken from Figure 8.
The factor x may also be calculated
by the approximate
equation:
9.1.2
9.1.2.1
The initial symmetrical short-circuit current &, the symmetrical breaking current Z,,and the
steady-state short-circuit current Z, at the short-circuit location F, fed from sources which are
not meshed with one another in accordance with Figure 9, page 49, may be composed of the
various separate branch short-circuit currents which are independent of each other:
r{ = rj,, + rj,
(17)
short-
Note. - The short-circuit current at the short-circuit location F is the phasor sum of the branch short-circuit currents.
In most cases the phase angles of-the branch short-circuit currents are nearly the same. The short-circuit
current at F is then equal to the algebraic sum of the branch short-circuit currents.
Impedances between the short-circuit location F and the busbar B, where the branch shortcircuit currents flow together as shown in Figure 9, may be neglected if they are smaller than
0.05 U,,l(,, 3 flin), where Zi, is the initial symmetrical short-circuit current on the busbar
determined by equation (17) with a three-phase busbar short circuit. In all other cases,
calculations are made in accordance with Sub-clause 9.1.3.
23
200
IS 13234 : 1992
IEC Pub 909 (
1988)
9.1.2.2
The peak short-circuit current i, at the short-circuit location F, fed from sources which are
not meshed with one another in accordance with Figure 9, may be composed of the branch
short-circuit currents ipTl and ipT2:
.
Ip = lpT1 +
Ql
02
(19)
.%b2
T2
Tl
FIG. 9. -
[pT2
System diagram illustrating a short circuit fed ~from several sources which are
independent of one another. (In some cases the impedance between busbar B and
the short-circuit location F may be neglected.)
9.1.3
9.1.3.1
In accordance with the example shown in Figure 10, page 51, the equivalent voltage source
cU, / ; 3 is established at the short-circuit location as the only active voltage in the network.
The calculation is to be carried out in accordance with Sub-clause 8.3.1, especially with Figure 4a, page 27 (positive-sequence
short-circuit impedance at the short-circuit location F). It is
generally necessary to ascertain the short-circuit impedance Zk = z(r), by network transformation (e. g. series connection, parallel connection and deltastar transformation) considering the
positive-sequence
short-circuit impedances of electrical equipment (see Sub-clause 8.3.2).
All impedances are referred to the low-voltage side of the transformers
network feeder is treated in accordance with Sub-clause 8.3.2.1.
r; =
aI
aI
pz,
= \i3JK+T$,
where:
CU,l,3
Zk
short-circuit
impedance,
24
(15).
IS i3234 : 1992
IEC Pub 909 ( 1988 )
a)
Tl
a) System diagram.
b) Equivalent
&,, &,
FIG. 10.
9.1.3.2
with Clause 6.
For the calculation of the peak short-circuit current i, in meshed networks Equation (16) is
used and one of the following approximations A, B, or C is chosen to find a suitable value for x.
If high accuracy is not needed, the Method A is sufficient.
25
( IEC page
51)
IS 13234 : 1992
IEC Pub 909 ( 1988 )
The factor x, is determined from Figure 8, page 47, taking the smallest ratio of R/X or the
largest ratio X/R of all branches of the network.
It is only necessary to choose the branches which together carry 80% of the current at the
nominal voltage corresponding
to the short-circuit location. Any branch may be a series
combination of several elements.
In low-voltage
location:
(21)
where 1.15 is a safety factor to cover inaccuracies caused by using the ratio R/X from a meshed
network reduction with complex impedances.
The factor xh is found from Figure 8 for the ratio RlXgiven by the short-circuit impedanceg,
= Rk + jXk at the short-circuit location F, calculated with the frequencyf=
50 Hz orf= 60 Hz.
In low-voltage
2.0.
Method C - Equivalent
networks to
-=-.R
R,
fc
xc
xc
R,
fc
(224
(22b)
where:
zC
= R, + jX,
R,
location
location
The equivalent impedance zE = R, + j2 Jcf,L, is the impedance as seen from the short-circuit
location if an equivalent voltage source with the frequency fc= 20 Hz (for a nominal frequency
50 Hz) or 24 Hz (for a nominal frequency 60 Hz) is applied there as the only active voltage.
9.2
Figure 11, page 55, shows which type of short circuit leads tothe highest short-circuit
the a.c. component decays, i. e. if Zt2)/Zc1) < 1 (see Section Two).
In Section One Z&Z(l)
= 1 is valid.
26
currents if
IS 13234 : 1992
IEC Pub 909 ( 1988
1.1
1.0
0.9
0.8
0.7
I
0.6
2121
-
0.4
0.3
0.2
0.1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
2121
-Zlll
between R/X-ratios
for positive-sequence
and zero-sequence
Example:
The single phase circuit (kl) will give the highest short-circbit
current.
FIG. 11. - Chart indicating the type of short-circuit giving the highest current.
9.2.1
9.2.1.1
G2
=,,:t,,
1
withZ(l) = 32)
(23)
&J = & is the positive-sequence short-circuit impedance at the short-circuit location F (see
Figure 4a, page 27).
27
IS 13234 : 1992
IEC Pub 909 ( 1988 )
(25)
(26)
The factor x is calculated according to Sub-clause 9.1.1.2 or 9.1.3.2 depending on the system
configuration. The same value as used in the case of a three-phase short circuit may be taken.
9.2.2
9.2.2.1
ri2,
L2 =
CU,
are given:
(274
lzu,+ 2zd
(27b)
(4).
r
9.2.2.2
i-3 cu,
kE2E
= I&) +2 Z(O)I
(28)
9.2.3
wires according to
lp2E.
9.2.3.1
current
of a line-to-earth
to Figure 2d,
IS 13234 : 1992
IEC Pub 909 ( 1988 )
J3-cu,
ri, =
J'CCU,
(29)
I-z(l)
32)
Z(O) I
12 31)
30)
9.2.3.2
,2r;,
(31)
The factor x is calculated according to Sub-clauses 9.1.1.2 or 9.1.3.2 depending on the system
configuration. For simplification, the same value as used in the case of a three-phase short
circuit may be taken.
9.3.
~9.3.1
General
When calculating minimum short-circuit
conditions:
- voltage factor c for the calculation
of minimum short-circuit
the following
choose the system configuration and, in some cases, the minimum contribution from
sources and network feeders, which lead to a minimum value of short-circuit current at the
short-circuit location;
(32)
where R L20is the resistance at a temperature of 20 C and 15,in C the conductor temperature
at the end of the short circuit. The factor 0.004K is valid for copper, aluminium and
aluminium alloy.
9.3.2
according
to Sub-clause
CU
G
impedance
(33)
min =
Y
9.1, the
Zk
The value of the voltage factor c depends on many influences, for example operational
voltage of cables or overhead lines, location of short circuit. If there are no national standards,
the values of Table I may be used.
XS 13234 : 1992
IEC Pub 909 ( 1988 )
When calculating _-unbalanced short circuits according to Sub-clause 9.2, the equivalent
voltage source cU,l d 3 and impedances &, and &) under the conditions of Sub-clause 9.3.1
are chosen.
SECTION
10.
Ge;.eral
This section gives procedures for calculations in systems with short-circuit currents having
decaying a.c. components. The influence of motors is also taken into account.
Procedures for the calculation of short-circuit currents of synchronous and asynchronous
~motors are given if their contribution is higher than 5% of the initial symmetrical short-circuit
current 1; without motors (see Sub-clause 13.2.1).
11.
11.1
Short-circuit parameters
General
In the calculation of the short-circuit currents in systems supplied by generators, powerstation units and motors (near-to-generator
short circuits), it is of interest not only to know the
initial symmetrical short-circuit current ri and the peak short-circuit current i,, but also the
symmetrical short-circuit breaking current Ii, and the steady-state short-circuit current Z,.
In general the symmetrical short-circuit breaking current I,, is smaller than the initial
symmetrical short-circuit current r {. Normally the steady-state short-circuit current Ik is
smaller than the symmetrical short-circuit breaking current Ii,.
Frequently, especially when dealing with the mechanical effects of short-circuit currents, it
will be necessary to determine the asymmetrical short-circuit breaking current from the a.c.
breaking current and the superimposed
d.c. breaking current. The decaying aperiodic
component inc can be calculated according to Clause 5.
In the case of a near-to-generator
short circuit the prospective
considered as the sum of the following two components:
- the a.c. component
-
short-circuit
current can be
In a near-to-generator
short circuit, the short-circuit current behaves generally as shown in
Figure 12, page 63. In some special cases it could happen that the decaying short-circuit current
reaches zero for the first time, some periods after the short circuit took place. This is possible if
the d.c. time constant of a synchronous machine is larger than the subtransient time constant.
This phenomenon is not dealt with in detail by short-circuit currents calculated in this standard.
IS 13234-z1992
Current
t
Top envelope
Decaying
Bottom
(aperiodic)
component
envelope
current
current
short-circuit
decaying (aperiodic)
current
component
of short-circuit
FIG. 12. -
Short-circuit
iDc
current of a near-to-generator
current
iDc
Short-circuit currents may have one or more sources as shown in Figure 13, page 65. The
figure also specifies which clause of this section describes the short-circuit current calculation.
The main sub-clauses for the calculation of the three-phase short-circuit currents are:
-
12.2.3: for the cases shown in Figures 13b, 13c respectively, if the given inequality
fulfilled (three-phase short-circuit fed from non-meshed sources),
31
short-circuit,
is
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Single fed short circuit.
Calculation according
12.2.2. 12.3 and 12.4.
b)
to Sub-clauses
12.2.1,
sources.
according to Sub-clauses
(without
B-=--d
Short circuit fed from one power-station
(generator and unit transformer).
unit
to Sub-clauses
12.2.3,
according to Sub-clauses
z can be neglected if
z-co.05
un8
\ 3 fy,
FIG. 13. -
11.2
Various short-circuit
source conpections.
11.3
IS 13234 : 1992
IEC!Pub 909 ( 1988 )
Equivalent voltage source at the short-circuit location
11.4
It is possible in all cases to determine the short-circuit current at the short-circuit location F
by means of an equivalent voltage source cU,, / ,/rz if correction factors are introduced for the
impedances of generators and for the impedances of generators and transformers of~powerstation units (see Sub-clauses 11.5.3.6, 11.5.3.7, 11.5.3.8 and Clause 12). Details for the
equivalent voltage source cU, / ~7 are given in Clause 6 and Table I.
In this method the equivalent voltage source cU, lJ-3 at the short-circuit location is the only
active voltage of the system. The internal voltages of all synchronous and asynchronous
machines are set to zero. Therefore the synchronous machines are only effective with their
subtransient~impedances and the asynchronous motors are only effective with their impedances
calculated from their locked-rotor currents.
Furthermore
in this method all line capacitances and parallel admittances of non-rotating
loads except those of the zero-sequence system shall be neglected (see Figure 15, page 77, and
Figure 20, page 87).
Details for consideration
Short-circuit impedances
11.5
11.5.1
in a near-to-generator
11.5.2
The general considerations made in Sub-clause 8.3.2 are valid. Motors and generators
dealt with in Sub-clauses 11.5.3.5 to 11.5.3.8.
are
11.5.3
11.5.3.1
Network feeders
The details given in Sub-clause 8.3.2.1 are valid, except for the special case given in Subclause 12.2.3.1.
11.5.3.2
Transformers
of power-station
units are
11.5.3.4
33
IS 13234: 1992
IEC Pub 909 ( 1988)
11.5.3.5
Motors
ZM =
ILR/lrM
\T &M
u2IM
u rM
=
lLR/lrM
%M
(34)
where:
II rM
I FM
SrM
l,RJA,
cos q,)
= as in Equation (34)
urM
= rated voltage of the static converter transformer on the network side or rated
voltage of the static converter, if no transformer is present
I TM
rated current of the static converter transformer on the network side or rated
current of the static converter, if no transformer is~present
ILRIzrM
RMlXM
11.5.3.6
= KG (RG + FG)
(35)
KG=--_.
un
urG
C max
1 +
xi sin &o
(36)
IS 13234: 1992
1EC Pub 909 ( 1988,)
where:
cnux
u,
I/ rG
~GK
corrected impedance
impedance
subtransient
ZG
I,
x*
%G
of the generator
of the generator
(Zo = RG + jXi)
(xi = Xi/Z,o)
In addition to the decay of the d.c. component, the factors 0.05, 0.07 and 0.15, also take
account of the decay of the a.c. component of the short-circuit current during the first halfperiod after the short circuit took place. The influence of various winding-tern_peratures on RG
is not considered.
Note. = The effective resistance of the stator of synchronous machines lies generally much below the~given values for
RG.
For the impedances of synchronous generators in the negative-sequence system and the
zero-sequence system the following applies:
32)~
For
X(2)(3=
salient-pole
synchronous
= ZGK
machines
(37)
= ~&$G
with
differing
values
of XA and
Xi,
+(x: +q.
&I)G = KG C&G
jx(0)G)
(38)
For the calculation of short-circuit currents for line-to-line and line-to-earth short circuits
(Sub-clause 12.3) the correction factor according to Equation (36) shall be taken into account.
35
IS 13234 : 1992
IEC Pub 909 ( 1988 )
11.5.3.7
and transformers
of power-
(39)
factor:
K G,
C max
PSU =
z
_T,PSU
of generators
1 + xi
W-8
sin Fro
(41)
factor:
K T, PSU
(42)
= cmw.
where:
corrected
impedances
of generators
(T) of power-station
Z
,Z_T.PSU
_G.PSU,
ZG
= impedance
of the generator _o
Z = RG + jXA(see Sub-clause 11 S.3.6)
Z
_TLV
= impedance
xi,
%G
(see Sub-clause
units
11.5.3.6)
If necessary the impedances z G, psu and zr, psu are converted by the fictitious transformation
ratio rf to the high-voltage side (see Sub-clause 12.2.2).
For the calculation of short-circuit currents at short circuits between generator and unit
transformer of a power-station unit the equivalent voltage source cV,~I ;3- at the short-circuit
location is to be introduced. In this case the rated voltage of the generator is chosen, because
the nominal system voltage cannot be determined.
These cases are dealt with in Subclause 12.2.3.1.
Notes
1. -
Equations (40) and (42) are valid if Uo = lJo and 0, = U,q. Special considerations are recommended if
for a power-station
unit having ~a transformer with a tap changer the operational voltage Uo,,, is
permanently higher than U,,o (Z/o,,, > U,,), and/or II, differs from U,o (Uc > .!.I,,) or for a powerstation unit having a transformer without a tap changer the voltage Uo of the generator is permanently
higher than U,, (UC > U,,).
11.5.3.8
impedances
and zero-sequence
impedances
at
Power-station units
For the calculation of short-circuit currents of power-station units for short circuits on the
high-voltage side it is not necessary to deal with the correction factors according to Sub-clause
11.5.3.7. In this case the following formula for the correction of the impedance of the whole
power-station unit (PSU) is used:
_ZPSU =
factor:
(IEC page 73 )
36
(43)
IS 13234: 1992
IEC Pub 909 ( -1988)
where:
Z
_PSU
ZG
impedance
ZTHV
impedance
u nQ
tr
rated transformation
fictitious transformation
(see Sub-clause
tf
xi,
%G
XT
Notes 1. -
corrected
impedance
of power-station
side
unit
11.5.3.6)
related to C&/&r, xT = Xrl( U~TISrT)
Equation (44) is valid if CJQ= U,,Qand UG = U&. Special considerations are recommended if for a powerstation unit having a transformer with a tap changer the operational voltage UQmin
is permanently higher
than UnQ(lJQ,i > U,o), and/or UG differs from U,G (UG > U,c) or for a power-station unit having a
transformer without a tap changer the voltage CJGof the generator is permanently higher than U, ( UG >
UrG).
2. - Values for correction factors for negative-sequence
unbalanced short circuits are under consideration.
impedances
impedances
at
11.6
12.
and zero-sequence
12.1
For the calculation of the initial symmetrical short-circuit current fi, the symmetrical shortcircuit breaking current Zt, and the steady-state short-circuit current Zk at the short-circuit
location, the system may be converted by transformations
into an equivalent short-circuit
impedance Zk. This procedure is not allowed when calculating the peak short-circuit current i,.
In this case% is necessary to distinguish between systems with and without parallel branches
(seesub-clauses9.1.1.2.9.1.2.2and9.1.3.2).
12.2
12.2.1
12.2.1.1
The initial symmetrical short-circuit current for the examples of item 1) of Figure 13a, page
65, and of Figure 15, page 77, is calculated with the equivalent source voltage cUhI ,.3 at the
short-circuit location and the short-circuit impedance gk = Rk + jX,:
(45)
For calculation of the maximum short-circuit
chosen according to Table I.
Note. = Normally it can be presumed
system voltage U,.
current,
37
IS 13234 : 1992
IEC Pub 909 ( 1988 )
k3
a)
L
1
1
bl
RG
,
F
RL
Nonrotating
load
1_
-t
F
Non-
rotatrng
load
If
KGRG KG%
c)
RL
XL
\
KG~G
a) System diagram.
b) Equivalent
circuit (positive-sequence
c) Equivalent circuit for the calculation with the equivalent voltage source (see Clause 6 and Sub-clause 11.4) and the
impedances according to Sub-clause 11.5.3 and especially to Sub-clause 11.5.3.6.
FIG. 15. - Example for the calculation of the initial symmetrical short-circuit current I;: for a
short circuit fed directly from one generator.
12.2.1.2 Peak short-circuit current i,
The calculation of the peak short-circuit current is done as shown in Sub-clause 9.1.1.2. For
the generator the corrected resistance KoRo and the corrected reactance K,X: is used.
12.2.1.3
The decay to the symmetrical short-circuit breaking current is taken account of with the
factor p.
Zb= p r;
(46)
where ,u is dependent on the minimum time delay t,in (see Sub-clause 3.23) and the ratio ZiI ZrG.
The values of ,u of the following equations apply to the case where medium voltage turbine
generators, salient-pole generators and synchronous compensators are excited by rotating
exciters or by static converter exciters (provided that for static exciters the minimum~time delay
is less than 0.25 s and the maximum excitation-voltage is less than 1.6 times the rated load
excitation-voltage). For all other cases ZAis taken to be ,u = 1 if the exact value is unknown.
p = 0.84 + 0.26 e-.26fLGrGfor
tmin = 0.02
p =
tmin= 0.05 s
0.71 + 0.51 e -0.30riG1Gfor
,U =
(47)
The values ZLo(partial short-circuit current at the terminals of the generator) and ZrGare
related to the same voltage. In the case of asynchronous motors, replace &JZ,o by Zt!MIZrM
(see
Table II).
IS 13234: 1992
IEC Pub 909 ( 1988 1
0.8
0.7
0.6
0.5
5
Three-phase
FIG. 16. -
short
ClrCUit
6
/;G
//rG
Or /(,s,, /I&,
_____t
Figure 16 can also be used for compound excited low-voltage generators with a minimum
time delay tmind 0.1 s. The calculation of low-voltage breaking currents after a time delay tmin>
0.1 s is not included in these procedures; generator manufacturers may be able to provide
information.
12.2.1.4
Steady-state short-circ¤t
Zk
XdSat(sat = saturated)
of the synchronous
for the
(48)
= AIXL.~~G
39
generator
or salient-pole
machines.
IS 13234 : 1992
IEC Pub 9il9 ( 1988 )
13max-curves of Series One are based on the highest possible excitation-voltage
according to
either 1.3 times the rated excitation at rated load and power factor for turbine generators (see
Figure 17a) or 1.6 times the rated excitation for salient-pole machines (see Figure 18a).
.I,,,,,-curves of Series Two are based on the highest possible excitation-voltage
according to
either 1.6 times the rated excitation at rated load and power factor for turbine generators (see
Figure 17b) or 2.0 times the rated excitation for salient-pole machines (see Figure Mb).
a) Series One
b) Series Two
2.8,
2.6
I
1
I
2.6
xd sat
4.4
2.4
I. max
1.8
1.8
1.6
0.8
0.6
0.4
0.2
-I
12345678
Three-phase
FIG. 17. -
012345678
short circuit
/&/&G
Three-phase
(Definitions
Amin
= &in
constant
no-load
excitation
IrG
of the
(49
or salient-pole
Note. - For bus fed static exciters without current forcing the minimum steady-state
three-phase bus short circuit is zero.
40
12~ //,~--3
short circuit
short-circuit
machines.
current for a
IS 13234 : 1992
IEC Pub 909 ( 1988 )
b)
a) Series One
Series Two
5.5
5.0
5.0
4.5
4.5
4.0
4.0
3.5
3.5
3.0
3.0
2.5
2.5
2.0
2.0
1.5
1.5
1.0
1.0
0.5
0.5
0
012345678
0
Three-phase
short-circuit
/[G//,G
Three-phase
short circuit
/i;G//&-
FIG. 18. - Factors I,, and Aminfor salient-pole machines. (Definitions of Series One and Two are
given in the text.)
12.2.2
12.2.2.1
unit
For the examples in Item 2) of Figure 13a, page 65, and in Figure 19 the initial symmetrical
short-circuit current is calculated with the equivalent voltage source cU,/d?? at the shortcircuit location and the corrected impedances of the generator and the transformer of the
power-station unit (Sub-clauses 11.5.3.7 or 11S.3.8) in series with a line impedance zL = RL +
jXL according to Sub-clause 8.3.2.3.
IS 13234 : 1992
IJX Pub 909 ( 1988 )
a)
k3
G
1
&G.
b)
PSU
43.
,,I)
111
PSU
RL
-0
XL
EPSU
a) System diagram.
b) Equivalent circuit~diagram of the positive-sequence system for the calculation with the equivalent voltage source
at the short-circuit location and the corrected impedances of the generator and the transformer of the powerstation unit.
FIG. 19. -
short-circuit
in Figure
short-circuit
current Equation
currentri
fed
(45) should be
in
go, Psu is taken from Equation (39) and ;Zr.rsu from Equation (41). Both impedances are to
be transformed to the high-voltage side wtth the fictitious transformation ratio tr = U, I UrG.
Following Sub-clause
given by:
Zk=Rk
impedance
+ jxk=<PSU
+ ZL
forthe
example in Figure 19 is
(51)
(43).
The calculation is done as shown in Sub-clause 9.1.1.2. For power-station units the corrected
resistances and the corrected reactances according to Sub-clause 11.5.3.7 and 11.5.3.8 are
used.
12.2.2.3
The calculation of the symmetrical short-circuit breaking current is done as shown in Subclause 12.2.1.3 withy according to Equation (47) or Figure 16, page 79. Insert the transformed
value YiPsUt= tJkPSU in place of &o.
(IEC page
85)
42
IS 13234: 1992
IEC Pub 909 ( 1988)
12.2.2.4 Steady-stateshort-circuit current Zk
The calculation can be done as shown in Sub-clause 12.2.1.4, if the short circuit is fed by one
power-station unit. Insert the transformed value IIi&sul= tJ&
in place of &.
12.2.3
12.2.3.1
General
In addition to short circuits fed from non-meshed sources (see Figure 13b, page 65). all short
circuits directly fed through a common impedance z, can be calculated by the procedure given
in this sub-clause, if Z < 0.05 U,,/(, 3 $a) holds (see Figure 13c, page 65).
-.
In general the equivalent voltage source cU, I, 3 is introduced (see Figure 20~) at the shortcircuit location. U, is the nominal voltage of the system in which the short circuit occurs.
Generators, feeding the short circuit directly (without transformers) are to be treated as given
inSub-clause 11.5.3.6, power-station units according to Sub-clauses 11.5.3.7 or 11.5.3.8 and
12.2.2. and asynchronous
motors as shown in Sub-clause 11.5.3.5, taking into account
Clause 13.
Gl
t:&Z.PSU
&lZGl.
PSU
t:,z,,,
RL
\-F
t:$x
PSU
PSU
L
ZPSUl
b
-
XL
1
c U
ZPSUZ
--z-
13
!F
4 System diagram.
b) Equivalent circuit diagram of the positive-sequence system with the subtransient voltages E.
cl Equivalent circuit diagram of the positive-sequence system for the calculation with the equivalent voltage source
cLl,/, 3 at the short-circuit
FIG. 20. -
location.
43
short-circuit
IS 13234 : 1992
IEC Pub 909 ( 1988 )
&AT
k3
AT
FIG. 21. - Short-circuit currents and partial_ $hort-circuit currents for three-phase short
circuits between generator and transformer of a power-station unit and at the
auxiliary busbar A (see also Sub-clause 12.2.4.1).
For calculating the partial short-circuit currents I io and Ztr at a short circuit in Fl in
Figure 21, the initial symmetrical short-circuit currents are given by:
cur,
11, =
(53)
--\ 3
ZT, PSU + 7
&nin
where:
Z
_G.
PSCI
z
_T.
PSL:
Z
_oIIUn
to SLo max
the maximum possible value expected during the life time of the power station is
to be introduced.
For the calculation of the short-circuit current I;:at the short-circuit location F2, for example
at the connection to the high-voltage side of the auxiliary transformer AT in Figure 21, it is
sufficient to take:
For %max
l;:=cL
13
ZG, PSU
1
PSU + 7
3.
=c-_ UrG
1
ZQmin
\7
(54)
I Zrsl I
The short-circuit current ItAT at the short-circuit location F3 has to be treated accordingto
Sub-clause 12.2.4.1.
IS 13234 : 1992
IEC Pub 909 ( 1988 )
12.2.3.2
The initial symmetrical short-circuit current at the short-circuit location F can be calculated
from the sum of the partial short-circuit currents as shown in Figure 22. Motors are taken into
account by the application of Clause 13.
A simpler result, to be on the safe side, is gained by using the algebraic sum of values instead
of the geometric sum.
M
3-
FIG. 22. -
12.2.3.3
Peak short-circuit current i,, symmetridal short-circuit breaking current I, and steady-state
short-circuit current I,
If the three-phase short circuit is fed from several non-meshed sources according to Figure 22
the components of the peak short-circuit current i, and the symmetrical short-circuit breaking
current I,, at the short-circuit location F are added:
ip = ippsU + iPr + ipM+ . . .
It) = zbps + Z{T +
z,, + . . .
(57) and (58) give results which are on the safe side.
- power-station
11.5.3.8,
-
(57)
(58)
I, = Z,,, + z;T + . . .
The simple formulae
(56)
units as in Sub-clause
location as in
11.5.3.7 and
45
IS 13234: 1992
IEC!Pub 909 ( 1988 )
This directive does not apply to the steady-state short-circuit current Zk. It is assumed that
generators fall out of step and produce a steady-state short-bircuit current ZkG= ZhGor ZkPsU=
ZbPsu. For network feeders IL = I,, = 1; is valid. There is no motor supplement to the threephase steady-state short-circuit current (see Table II).
Three-phase
122.4
12.2.4.1
Znitial symmetrical
short-circuit
networks
current Zt
The initial symmetrical short-circuit current is calculated with the equivalent voltage source
cll, / , 3 at the short-circuit location. Equation (45) is used. The impedances of electrical
equipment are calculated according to Sub-clause 11.5.3 (see also Sub-clause 12.2.2). For the
calculation of the partial short-circuit current ZEATin Figure 21, page 89 (short-circuit location
F3), it is permitted to take &, from Equation (54) and to transform this impedance by zAT..
The impedances in systems connected beyond transformers to the system in which the short
circuit occurs have to be transformed by the square of the rated transformation ratio. If there
are several transformers with slightly differing rated transformation
ratios t,,, t,?, . . . t,,,
between two systems, the arithmetic mean value can be used.
Figures 13d, page 6.5, and 23 show examples for meshed networks with several sources
12.2.4.2
Peak short-circuit
current i,
(TEC page 91
46
IS 13234 : 1992
IEC Pub 909 ( 1988 )
a)
T2
Gl
ZPSU
a) System diagram.
b) Equivalent
location.
* Impedance
at the short-circuit
FIG. 23. - Example of the calculation of the initial symmetrical short-circuit current 1: in a
meshed network fed from several sources.
12.2.4.3 Symmetrical short-circuit breaking current Z,
The following may be set for the short-circuit breaking current in meshed networks:
z, = r;:
(59)
Currents calculated with Equation (59) are larger than the real symmetrical short-circuit
breaking currents.
Note. - A more accurate calculation can be done with the following equations:
47
IS 13234 : 1992
IEC Pub 909 ( 1988 )
-
pjqj)
LtMj
(60)
(61)
(64
location
initial symmetrical short-circuit current, symmetrical short-circuit breaking current with influence
of all network feeders, synchronous machines and asynchronous motors
initial voltage difference at the connection points of the synchronous
ous motor j
parts of the initial symmetrical
asynchronous motor j
short-circuit
current
of the synchronous
machine
i and the
(see Sub-clause 12.2.1.3 and Figure 16, page 79) with rioi/lro, or f,!Mj/l,Mj respectively
(see Sub-clause 13.2.1 and Figure 25, page 103)
The values of Equations
12.2.4.4
12.4
12.4.1
General
The details given in Sub-clause 9.3 remain valid. In addition, consider Sub-clauses 12.4.2 to
12.4.4. Careful reflection is necessary for the impedance correction factors in the equations
(36), (40)) (42) and (44), es p ecially in the case of underexcited operation.
12.4.2
12.4.2.1
If a short circuit is fed from one generator as shown in Figure 15, page 77, apply Sub-clause
12.2.1 and introduce a voltage factor Cminaccording to Table I for the calculation of the
minimum short-circuit current.
This procedure is also applied for short circuits, which are fed by several similar generators,
operated at one point in parallel.
Short circuit in meshed networks
12.4.2.2
For the calculation use Sub-clause 12.2.4 and a voltage factor c,in according to Table I.
@ECpage
97)
48
IS 13234 : 1992
IEC Pub 909 ( 1988
Steady-stateshort-circuit current I k minfed from generators with compound excuu.ion
12.4.3
zkmin
= p
kin/
un
(64)
,jm
&, is the steady-state short-circuit current of a generator with a three-phase terminal short
circuit.
This value zkpshould be obtained from the manufacturer.
12.4.4
The initial short-circuit currents at unbalanced short circuits are calculated according to Subclauses 9.2 and 12.3. Use the voltage factor C,in according to Table I.
13. Influence of motors
13.1 Synchronous motors and synchronous compensators
When calculating the initial symmetrical short-circuit current Ii, the peak short-circuit
current i,, the symmetrical short-circuit breaking current Ii, and the steady-state short-circuit
current Ik, the synchronous motors and synchronous compensators are treated in the same way
as synchronous generators.
Exceptions are: no modification for internal voltage; motors may have constant field voltage
and no regulators. Motors and compensators with terminal-fed static exciters do not contribute
to Ik.
13.2 Asynchronous motors
13~.2.1 General
High-voltage motors and low-voltage motors contribute to the initial symmetrical shortcircuit current Zi,to the peak short-circuit i,, to the symmetrical short-circuit breaking current
I,,, and for unbalanced short circuits also to the steady-state short-circuit current Ik.
High-voltage motors have to be considered in the calculation of short circuit. Low-voltage
motors are to be taken into account in auxiliaries of power-stations and in industrial and similar
installations, for example in networks of chemical~and steel industries and pump-stations.
Motors in low-voltage public power supply systems may be neglected.
In the calculation of short-circuit currents those high-voltage and low-voltage motors may be
neglected, which, according to the circuit diagram (interlocking) or to the process (reversible
drives), are not switched inat the same time.
( IEC
49
page 99)
IS 13234: 1992
IEC Pab 909 ( 1988 )
High-voltage and low-voltage motors -which are connected through two-winding transformers to the network in which the short circuit occurs, ~maybe neglected in the calculation of
currents for a short circuit at the feeder connection point Q (see Figure 24), if:
PrM
&T
0.8
c 100 i? &T
-
0.3
SiQ
where:
=*kl
= sum of the rated active powers of the high-voltage and the low-voltage motors which should be considered
=,r
SLJ = initial symmetrical short-circuit power at the feeder connection point Q without supplement of the motors
The estimation according to Equation (66) is not allowed in the case of three-winding
transformers.
k3
20 kV
Ml
M2
M3
M4
z
p,M
FIG. 24. - Example for the estimation of the contribution from the asynchronous motors in
relation to the total short-circuit current.
50
IS13234:1992
IEC Pub 909 ( 1988 )
Minimum time de
0.8
0.6
0.5
0.3
,
/
0.1
T/
0.01
A@
0.02
0.04
1
0.4
0.2
0.1
10 (MW)
FIG.
25.- Factor 9 for the calculation of the symmetrical
asynchronous
short-circuit
breaking current of
motors.
The factor 4 for the calculation of the symmetrical short-circuit breaking current for
asynchronous motors may be determined as a function of the minimum time delay tmin:
with m:
(67)
If the calculation in Equation (67) provides larger values than 1 for q, assume that q = 1. The
factor q may also be obtained from Figure 25.
Low-voltage motors are usually connected to the busbar by cables with different lengths and
cross-sections. For simplification of the calculation, groups of motors including their connection cables may be combined to an equivalent motor, see motor M4 in Figure 24.
For these equivalent
may be used:
asynchronous
51
(IEC
page 103)
IS 13234: 1992
= (according
I FM
to Equation
(34))
ILRI&M
= 5
RM/XM
motor)
xM = 1.3
For a short circuit at the busbar 3 in Figure 24, page 101, the partial short-circuit current of
the low-voltage motor group M4 may be neglected, if the following condition holds:
Zr~4is the rated current of the equivalent motor M4.Z&+, is the initial symmetrical short-circuit
current at the short-circuit location B without supplement of the equivalent motor M4.
In the case of a short circuit on the high-voltage side (e. g. short-circuit locations Q or A in
Figure 24) it is possible to simplify the calculation of ZM according to Equation (34) with the
rated current of the transformer T3 (ZrT3,Lv) in Figure 24 instead of the rated current frMj of the
equivalent motor M4.
Terminal short circuit of asynchronous
13.2.2
motors
In the case of balanced and line-to-line short circuits at the terminals of asynchronous motors
the currents 16, i,, I,, and Zkare evaluated as shown in Table II. For solid grounded systems the
influence of motors on the line-to-earth short-circuit current cannot be neglected.
13.2.3
IS 13234 : 1992
IEC Pub 909 ( 1988 )
TABLE II
Initial symmetrical
circuit current
Line-to-line
Short circuit
short-
Peak short-circuit
current
I,,
C&I
k3M= m
Ip3M = XM JTI;,,
High-voltage motors:
xM = 1.65 (corresponding
c1MW
X~ = 1.75 (corresponding
21MW
(69)
ltzM = $-
&
(73)
(70)
ipZM= $-
ipsM
(74)
to
RMIXM = 0.15)
for motor powers per pair of poles
to
RMIXM = 0.10)
for motor powers per pair of poles
lb,,
(71)
= p 4 1;3M
short circuit
I,,,
,y
2
Iz3M
to
(75)
13.3
I k3M
-0
-
(72)
Ik2M
Ik3M
(76)
Static converter fed drives (e. g. as in rolling mill drives) are considered for three-phase short
circuits only, if the rotational masses of the motors and the static equipment provide reverse
transfer of energy for deceleration (a transient inverter operation) at the time of short circuit.
Then they contribute only to the initial symmetrical short-circuit current Ziand to the peak
short-circuit current i,. They do not contribute to the symmetrical short-circuit breaking
current Zb.
Apply Sub-clause 11.5.3.5 for the equivalent motor of the static converter fed drive.
14. Consideration of non-rotating loads and capacitors
Calculation methods are given in Sub-clauses 12.2 and 12.3 which allow, as stated in
Clause 6, line capacitances and parallel admittances of non-rotating loads to be neglected.
of the capacitors
53
IS 13234 : 1992
IEC Pub 909 ( 1988 )
APPENDIX
CALCULATION
Al.
OF SHORT-CIRCUIT
CURRENTS
A.l.l
A low-voltage system with U,, = 380 V and f = 50 Hz is given in Figure Al. The short-circuit
currents Ziand i, shall be determined at the short-circuit locations Fl to F3 according to Section
One (Systems with short-circuit currents having no a,c. component decay). The equipment
data for the positive-sequence, negative-sequence and zero-sequence systems are given in
Table Al.
T2
= 400 kVA
Network feeder
SI:a = 2 50 MWA
(ca=l.l)
&a=15
kV
*
s,Tl = 630 kVA
FIG. Al. - Low-voltage system with short-circuit locations Fl, F2 and F3.
Example 1.
Network feeder
ZQt
-C&Q .
KQ
1
-
tT
1.1 . (15kV)*
=
250MVA
(EC
page 109)
54
IS 13234 : 1992
IEC Pub 909 ( 1988 )
A1.2.2
Transformers
100%
RTl
PkrTl
4%
(400 v)2
100%
630 kVA
u2
UkrTl
ZTl_.
= 10.16 m&I
Pkirl U2rT1
3 tT1
s2 rT1
XT1 = Jz,,_=
9.82 mQ
10 m = (0.385 + j 0.395) m0
$-
(0.208 + j 0.068)
~4
Line L3 (cable):
52
zL3 = (0.271 + j 0.087) -km - 20 m = (5.420 + j 1.740) m&
55
- 50
= 4.55 mm
m = (18.52 + j 14.85) mQ
IS 13234 : 1992
IEC Pub 909 ( 1988 )
TABLE AI
Network feeder
Q
Data of equipment
Data and
equations for
the calculation of
Z(l) and Z(O)
(5b)
Z(l) = Z(Z)
Z(O)
(ma)
(mn)
ZQt =
0.070 + j 0.700
ZQ
Transformers
Tl
T2
Lines
Ll
U,,,
= 15 kV;
(6) to (8)
6.5 kW; Dy 5
r/,,v = 15 kV;
(6) to (8)
g(O)T,=
zr2=
4.60 + j 15.32
Z(O)Tz=
4.60 + j 14.55
ZLI =
Z(O!L,=
2.62 + j-9.33
4.6 kW; Dy 5
0.385 + J 0.395
1.425 + j 0.715
L2
ZTl =
2.62 + j 9.82
XL
given by the
manufacturer
_zu=
0.416 + j 0.136
Z(O)LZ=
ZL3 =
&)L3
1.760 + j 0.165
sz
z; = (0.208 + j 0.068) G
L3
Four-core cable
I=20m:4X70mm2Cu
5.420 + j 1.740
16.26 + j 7.76
R
Z;. = (0.271 + j 0.087) T;;;
L4
Overhead line
I=50m;q,=50mm2Cu;d=0.4m
n
z; = (0.3704 + j 0.297) G
(ll), (12a)
ZLL4=
18.52 + j 14.85
*&=+
j 44.55
Transformers
For the transformers Tl and T2 with the vector group Dy5 the following relations are given
by the manufacturer:
Transformer Tl:
z(O)Tl = R(o)~l + jX(0)T1 = (2.62 + j 9.33) ma
Transformer T2:
+ jXco)n = (4.60 + j 14.55) mQ
Z(o)n= R(op-2
56
IS 13234 : 1992
IEC Pub 909 ( 1988)
A1.3.2
The zero-sequence impedances are to be calculated with the relations R,,J~IZ?, and X&XL
obtained from the manufacturer.
- Line L1: R(o),_= 3.7 RL; X(O)L = 1.81 XL with return circuit by the fourth conductor and
surrounding conductor:
~~oI~l= (3.7 RLI + j 1.81 XL1) = (1.425 + j 0.715) mQ
- Line L2: RtOJL= 4.23 R,; XtoIL= 1.21 XL with return circuit by sheath:
_Zco)r2
= (4.23 RL2 + j 1.21 XL2) = (1.76 + j 0.165)mQ
- Line L3:
3 RL;
and earth:
R(o)L =
X(O)L =
Calculation of the short-circuit currents I: and i, for balanced short circuits at the short-circuit
ZocationsFl, I?? and F3
A1.4.1
Short-circuit location Fl
+ ZLl + zL2)
=
Zk = 6Qt +
zTl+&
(1.857 + j 6.771) mQ
+zLl+zL2
FIG. A2. - Positive-sequence system (according to Figure Al, page 109) for the calculation of
I; and i, at the short-circuit location Fl.
Maximum initial symmetrical short-circuit current according to Equation (20) with c = 1.05
(see Table I):
r; =
;;,
1.05 * 380 v
J3 7.021 m&2 = 3281 hA
57
(IEC
page 115)
IS 13234: 1992
sIECPab909(1988)
Peak short-circuit current i, according to Sub-clause 9.1.3.2. Because the calculation of & is
carried out with complex values, it is sufficient to choose the conservative Method B or for
higher accuracy Method C of Sub-clause 9.1.3.2.
Method B (impedance ratio at the short-circuit location, Equation (21)):
= 1.15 ; 1.45 JT
- 32.81
kA = 77.37 kA
The impedance z, = R, + j X, is calculated according to the comments of Method C of Subclause 9.1.3.2 with an equivalent source voltage of the frequencyf, = 20 Hz (f, = 50 Hz). The
calculation procedure is similar to the calculation of &, but taking the following values:
ZQ,
= (0.070 + i 0.280) mQ
z
_Ll,c
= (0.385 + j 0.158) mQ; &c
gc
ZQt,c
Tl,c
&2,c
gTl,c
zLl,c
= (0.416 + j 0.0544) mQ
zL2.c)
+
$2.~
zLl,c
zL2,c
20 Hz
_ - Rc . -_fc =
-R =
x
xc
2.718 mQ
50Hz
= 0.272
&
In order to interpret this result, the ratios R/X of the parallel branches zrl and zr2 + i& +
are to be considered. These can be calculated as:
RTI
= 0.27
XT,
RTZ
XT2 +
RLI
RL~
XL,
XL,
0.34
Additionally, two-thirds of the short-circuit current are taken by the transformer Tl.
The breaking current &,and the steady state short-circuit current Z, at all three short-circuit
locations need not be calculated since they are equal to the corresponding initial symmetrical
short-circuit current Zi(see Equation (15)).
58
IS 13234 : 1992
IIECPub 909 ( 1988 )
A1.4.2
Short-circuit location E?
Zk
ZQt
@Tl
+ ZLl)
zT1
&2
zL2)
zL2
ZLl
(1.953 + j 6.852) mQ
1.05 . 380 V
-= 32.33 kA
= 4 3 - 7.125 mQ
c&
jT.&
r,: =
@T2
xcv 2 li = 1.44 ,I 2
* 32.33
kA = 65.84 kA
The decisive ratio R/X is mostly determined by those of the branches zrr + zL1 and & +
zL2 with (RTI + RLI)I(XTI + XL,) = 0.29 and (RR + RL2)l(Xm + XL2) = 0.32. Moreover, these
two r&tiOnS
are similar to Rk/Xk = 1.953 S2/6.852 9 = 0.29 + xb = 1.43.
A1.4.3
z,
Short-circuit location F3
ZQt
@Tl
ZLl)
ZTl
ZT?
(zT2
zL2)
r;
ZLl
dT
~r,~= x, E
zL4
1.05 - 380 V
cun
sL3
Zk
(25;893 + j 23.442) mQ
zL2
JrF
34.93 mS2
& = 1.05 j2
= 6.6 kA
6.6 kA = 9.89 kA
with:
+ &c
= (1.951 + j 2.742) mQ +
& = R + j Xc = ZF~,~ + &
(23.94 + j 6.636) mQ = (25.89 + j 9.38) mQ
-=R
x
R,
Y/fn=
fc
25.89 mQ
9.38 mS2
20 Hz
*
50 Hz
= 1.104
25.893 mQ
23.442 mQ
= 1.1043
therefore:
xc= 1.05=x,,
59
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Al .5
Calculation of the short-cirmit currents I;, and iplfor line-to-earth short circuits at the shortcircuit locations Fl, IQ and F3
Al .5.1
Short-circuit location Fl
Fl
~11)=~(21
Positive-sequence
=j(o]
Negative-sequence
= -Kl
system
3-
system
Zero-sequence
system
Short-circuit impedances:
&) = &) = z, = (1.857 +j 6.771) mQ
Z(O)=
= (2 099 + j 5 872) ma
*
Es 13234 : 1992
JEC Pub 909 ( Z988 )
Initial short-circuit current for a line-to-earth short circuit according to Equation (29) (see
Sub-clause 9.2.3.1):
pl.0538OV
JTCU,
r;, =
I %l)
+ 30) I
20.266 mQ
Peak short-circuit current ipl according to Equation (31) of Sub-clause 9.2.3.2, calculated
with the same value for x, as in the case of a balanced three-phase short circuit (see Sub-clause
9.1.3.2 for x,):
i,, = x, fl
ri, = 1.453 - F
+ 34.10
kA = 70.07 ~kA
Shortycircuit location lQ
A1.5.2
(IT Z(O)L)
(Z(O)rr
Z(O)L)
=
30) =
$O)Tl
Z(O)R
D-c&
ri, =
z(O)Ll
,2zt,) + zoo),
iPI = x, fl
A1.5.3
475
30)L2
. 1.05 - 380
20.684 mS2
$I = 1.44 fl
(2
970)
~SZ
V
=
33.41 kA = 68.04 kA
Short-circuit location F3
&) = g(2) = Zk = (25.893 + j 23.442) mQ
Z(0)
@(O)Tl
g(O)Ll)
Z(O)Tl
g(O)T2
g(O)Ll
DCU
r;, =
I %I,
+
+
X, \j2
z(O)Ld
z(oIL3
g(o)L4
3O)L2
pl.O5*38OV
150.43 mQ
-I- 30, I
i,l =
Al .6
@(O)T2
FL, =
1.05 p
4.59 kA = 6.82 kA
Collection of results
TABLE
AI1
z(l) =
zk
zw
r;
$l.c
41
lP1.C
&,/I;
(mQ)
(mQ)
04
04
GA)
OW
7.021
7.125
34.93
6.24
6.46
80.67
32.81
32.33
6.60
67.42
65.84
9.89
34.10
33.41
4.59
70.07
68.04
6.82
1.04
1.03
0.70
61
Is 13234 : 1992
IEC Pub 909 ( 1988 )
A2.
A2.1
system,
Problem
A medium-voltage
system 33 kV16 kV (50 Hz) is given in Figure A4, page 127. The
calculations are to be carried out without asynchronous motors according to Sub-clause 9.1 of
Section One and with the influence of asynchronous motors according to Sub-clause 13.2 of
Section Two.
The 33-kV-/6-kV-sub-station
with two transformers each of SrT = 15 MVA is fed through
two three-core solid type 33-kV-cables from a network feeder with S,io = 750 MVA and LI,o =
33 ~kV.
As the short-circuit resistance is small in comparison with the short-circuit reactance (RI, <
0.3 Xk, see Sub-clause 9.1.1.1) it is sufficiently accurate to calculate only the short-circuit
reactances of the electrical equipment and the short-circuit reactance X, at the short-circuit
location F in Figure A4.
To demonstrate the difference, when calculating the short-circuit current ri with absolute
quantities or with quantities of a per unit system, both calculations are carried out (see Subclause A2.3 for the calculation with per unit quantities). To show the difference between a real
and a complex calculation and to demonstrate the decaying of the aperiodic component of the
short-circuit current an additional calculation is given in Sub-clause A2.4.
A2.2
C(J
&
,3x,
\ 3 . 0.2655 Q
= 14.35 kA
IS 13234 : 1992
IEC Pub 909 ( 1988 )
.?$a=750
Network
MVA
feeder
U~Q = 33 kV
1
I?
Cable L2
Xip =O.l SUkm
1=4.85 km
Cable Ll
XL1 ~0.1 Nkm
l=4.85
km
Transformer
Tl
k3
Nonrotating
load
Asynchronous motor Ml
PrM= 5 MW; lJr, = 6 kV
cos qF = 0.86; Q = 0.97
I,,lI,,
= 4
pair of poles: 2
FIG. A4. -
motors.
(IEC
63
page 127)
IS 13234: 1992
IEC Pub 909 ( 1988 )
TABLE AI11
Network feeder
Equation (Sb):
Xo, = - cu,,
. f
Cable Ll
Transformer
XL,,
Tl
. 1 .+
XL1
. 4.85 km .
0.1;
0.0582
0.0177
ukrTl
XTl_.
_=-.rTlLV
&i
100%
15%
(6.3 kV)*
100%
15 MVA
Ll + Tl
Short-circuit
reactance Xk
xk
1
. (33 kVl6.3 kV)*
150 MVA
so
Reactance
(Q)
Equipment
0.
xLl,
xTl
XL,,
0.3969
0.4146
XI-2
(XL,, + XT,)
0.2073
1
=
x,
(XL,,
0.2655
XT,)
The initial symmetrical short-circuit current, without the influence of motors, at the shortcircuit location (see Figure A4) is:
GUI
L (withoutMl, M2) =
j3
=-.
*x,
1.1
6kV
J3
0.2655 Q
m=14.35 kA
According to Sub-clause 12.2.3 (three-phase short circuit fed from non-meshed sources and
Equation (55) it is possible to add the partial symmetrical short-circuit current at the shortcircuit location (see Figure A4, page 127):
r;:
{LMl
&M2
1
zMl
ILRlbM
where:
u2IM
(6 kV)
SrM
6 MVA
-=-.
=
*
s,, =
IM =
cos v,rlr
5MW
0.86 . 0.97
1.5Q
=6MVA
2M2 =where:
1
3
ILRizrM
s,, =
u2rM
SrM
-=-.
PrM =
cos 9vlr
1MW
0.83 . 0.94
(6 kV)2
5.5
1.28 MVA
-.
= 1.28 MVA
= 1.705 &
IS 13234 : 1992
IEC Pub 909 ( 1988 )
1.1.6kV
=
;;Ml
IkM2=;;w
1.1 - 6 kV
. 1.705 & = 2*23 kA
Short-circuit current at the short-circuit location F in Figure A4, page 127, including the
influence of the motors Ml and M2:
ZG;
= Z;(tithoutM1
M2J+ &,, + Zi, = (14.35 + 2.54 + 2.23) kA
Zi = 19.12 kA
The influence of the asynchronous motors raises the short-circuit current to 1.3 of the value
without motors.
Si = n
UJL = n
When calculating the partial short-circuit current fed from the network, Sub-clause 12.2.3.3
is used:
k (without Ml, M2) =
b(without Ml,
M2) =
rl (withoutMl,
M.2)
Ib ctithout
Ml q
zb3M1
zb3M2
zk =
A2.3
r; (witboutMl
M2)
14.35 kA
65
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Per-unit
follows:
*u=__,
IUR
ZSR
SR
u=R
* *I = _-;*~=_;
UR
therefore
*SE
are defined as
S
SR
If the system is not coherent as indicated in Sub-clause 8.4, that means UrTHV/I!.!,,,, # UnNV/
UnLV, then the rated transformation ratio related to p. u. voltages becomes:
UrTHV
*t, =
UR,6kV
u rTLV
33 kV
=-.
6kV
~
6.3 k-V
uR.33kV
33 kV
= 0.9524
The procedure for the calculation of the initial symmetrical short-circuit current without the
influence of the motors is given in Table AIV in a similar manner as in Table AIII.
The initial symmetrical
Figure A4, page 127, is:
current *ZL(without
M1 M2)at the short-circuit
short-circuit
c*u,
*L (without
1.1 * 1 p. u.
=
Ml, M2) =
JT * 0.7375 p. u.
current in kiloamperes
SR
L (without
Ml, M2) =
100 MVA
= 14.35 kA
6kV
R,6 kV
TABLE
0.8611 p. u.
is calculated:
0.8611 p. u.
location in
AIV
Network feeder
Equation (Sb):
*xo, = -
Cable Ll
Transformer
Tl
0.1 E.
1.1 . (1 p. u.y
. *r, =
7.5 p. u.
c* LIZ,0
*&o
*x,,, = *xt
Reactance
(P.M.)
~Equipment
SR
.1
4.85 km
1
0.9524
0.1617
.-
lJ2R.33kV
.-
*I,
100 MVA
(33 kV)
.-
0.9524
0.0491
lJ2rTLV
Srr*
15%
(6.3 kV)
100%
15 MVA
&
u2R.hkV
. 100 MVA
(6 kV)2
1.1025
1.1516
Ll + Tl
0.5758
Short-circuit
reactance *Xk
0.7375
IS 13234: 1992
IEC Pub 909 ( 1988)
The short-circuit
impedances
in p. u. of the asynchronous
motors are:
Motor Ml:
1
*.&I =
u2
-. IM
IL,/&,
*.&
%M
= -
SR
&6k
100 MVA
6 MVA
SR
srM
zLRJIrM
= 4.167 p. u.
Motor M2:
1
*.&=-
SR
1
ILRIlrM
*&? = -.
Partial short-circuit
1.1
100 MVA
5.5
1.28 MVA
1.:1
*I II
k = 3% U,
*&,z =
u2rM
-.
*u,
,T_ *.z&
1.1 1
SR
.
&M
= 4.735 p. u.
(69):
p.u.
= 0.1524 p. u. \3- . 4.167 p. u.
&,,,, = 2.54 kA
1.1 * 1 p. u.
_~~
= 0.1341 p. u. + FL,, = 2.23 kA
; 3 4.735 p. u.
quantities
for the
The complex impedances of electrical equipment are calculated from the data given in
Figure A5. This figure indicates the partial short-circuit currents of the branches and their
addition at the short-circuit location.
67
IS 13234: 1992
IJW Iab 909 ( 1988 )
Network feeder
Ril =O.l
Wkm
X;l =O.l bllkm
I=435 km
T2
s,T2 = 15 MVA
URrT2 =0.6%
152,
s,Tl = 15 MVA
U,=GkV
FIG. A5. -
68
IS 13234 : 1992
IEC Pub 909 ( 1988 )
TABLE AV
Equations
Equipment
Network
feeder
zol = -
cI/2o
. G
0.995
X0
XQ,
ZQ,
0.0579 &
Cable Ll
RQt
Impedance
(Q)
et calculations
See Sub-clause
8.3.2.1
0.0058 +
j 0.0579
jxQt
RLl, = R;, 1 $
4.85 km .
= 0.1;.
:3i
RL,, = 0.0177 R
1
Transformer
Tl
XL,,
x;,
I,
ZLI,
RI I, +
SL,,
ZT,
UkiTL
0.0177 +
j 0.0177
ll2 rTlLV
.
100%
S,r,
Equation (7):
u2
rTlLV
PC_.
Rr,=~.
s 1Tl
100%
(6.3 kV)
0.6%
___
100%
15 MVA
RT, = 0.015 88 Q
Equation (8):
Ll + Tl
XT,
r2----v ZT,
1
- RT,
= 0.3966 Q
gT1
RT1
jxTl
ZLlt
ZT,
0.01588 +
j 0.3966
ZL,,
0.03358 +
j 0.4143
&!
0.01679 +
j 0.2072
Short-circuit
impedance
1
zk
(Tl.T2)
ZQr
69
@Lit
ZTd
0.02259 +
j 0.2651
IS 13234 : 1992
IEC Pob 909 ( 1988 )
1
ZMl
G&I
=
zLRlhM
1.5 51
SrM
therefore:
X, = 0.995 ZM et RM = 0.1 X,
z,,
zM2
-.
IL,/&,
cJ2
rM
= 1.705 &
(see
Sub-clause A2.2)
SrM
Short-circuit current L;: at the short-circuit location F in Figure A5, page 137, according to
Equation (55) in Sub-clause 12.2.3.2:
&,
+ $,
1.1.6kV
&:i.T)
JT (0.02259 + j 0.2651) Q
1.1 .6kV
&Ml
/2M2
J$
= (1.216 - j 14.27) kA
= (0.253 - j 2.527) kA
1.1.6kV
D
(IEC
(ipT1
$Td
page 141)
70
&Ml
$M2
IS 13234: -1992
IEC Pub 909 ( 1988)
0.02259 R
= ,0.0852
0.2651 Q
Ml:
ipT2 =
v 2
lpT1 +
lpT2 =
\i
R
x
_~~
R
x
%l2)
ipMl =
M2:
x c&T,
xMl
(lDC.TI
lDC,T2)
iDC,TI + iDC,n = jT
IDC,Tl
IDC,T;! =
IDC.Ml
_+ 2
iDC,M2
,,-2- FL,,
&Ml
J2
iDC. Ml +
iDC, M2
. 14.32
-2nftRlX
e-2r
ft R/X =
kA
vE,
e-2n 50 sc 0.0852 t
2.54
kA
e-2n50sm1.0.1.
2.24 kA e-*n50s-.O.r t
&Tl
ZbTZ) +
ZbMl +
IbM2
lb,,
+ zbn = &T,
+ &,
= 14.32 kA
(according to Sub-clause 12.2.3.3, far-from-generator short circuit)
Z bM1
With a minimum time delay tmin= 0.1 s and the already calculated values for ,u and q:
I,,, = 0.80 - 0.68 - 2.54 kA = 1.38 kA
71
IS 13234 : 1992
UC Pub 909 ( 1988 )
and corresponding
short-circuit
s (f=
50 HZ):
inc = ;T
zbasym
short-circuit
---
IkT,
1,
IkMl
1.192 kA
VT
I b asym =
Steady-state
$2.
(16.62 kA)* +
IkM2
(I,,,
IkT-2 =
IkT2)
?;T,
fin
IkMl
(58):
IkM2
14.32 kA
according to Equation
(72)
Zk = 14.32 kA
A3.
A3.1
locations
Fl to F4 in Figure A6,
A power-station unit (PSU) is connected to a 220 kV system with the actual, initial shortcircuit power Yio = 8000 MVA of the network feeder. The auxiliary transformer AT is of the
three-winding type feeding two auxiliary busbars B and C with U, = 10 kV.
The influence of asynchronous motors on the short-circuit currents is to be taken into account
when calculating short-circuit currents at the short-circuit locations F2, F3 and F4. Low-voltage
asynchronous motors shall be handled as motor groups. The terminal short-circuit currents of the
high-voltage or low-voltage motors are calculated within the Tables AVI or AVII.
72
IS 13234 : 1992
EC Pub 909 ( 1988 )
A3.2
A3.2.1
Network feeder
According to Sub-clause 8.3.2.1 it follows, with c = 1.1 from the actual symmetrical shortcircuit power at the feeder connection point, that:
ZQC
-=
CU2,
%Q
XQ = 0.995 ZQ
(0.6622 + j 6.622) Sz
For the calculation of the maximum short-circuit current at the short-circuit locations F2 and
F3, ZQ min (corresponding to 3iQ ma ) is found according to Sub-clause 12.2.3.1. $Q max is to be
estimated from the future planning~of the power-system.
Unit transformer
From the data given in Figure A6, page 149, Equations (6) to (8) according to Subclause 8.3.2.2 yield:
u2 rTHV
-. Ukr
THV= 100%
=-.
s,,
PkrT
X,v
u*
rTHV
S2rT
15%
(240 kV)2
100%
250 MVA
0.52 MW
= 34.56 Q
(240 kV)*
(250 MVA)2 = o479 a
= (0.479 + j 34.56) Q
Converted to the low-voltage side of the unit transformer with t, = 240 kV/21 kV:
X TLv=XrHv.---
1
t,
= 34*56
Generator
With the data given in Figure A6, the calculation according to Sub-clause 11.5.3.7 with
c = 1.1 (see Table I) and RG = 0.05 Xi (see Sub-clause 11.5.3.6) can be performed as:
,73
( IEC
page1 147)
Network
feeder
S;h=BOOO
&a=220
Unit transformer
MVA
(S;a,,,,,,=
20000
MVA)
kV
(+12%)121
Generator
kV
G:
s,~=250MVA
U&=21
kV
x8=17%
COS
9rG =0.70
Auxiliary
transformer
AT
P,M=
M7
M6
1.71
2x
lx
busbar
; UkrBC=
13%
kW ; PkrTaC =I14
B, lJ, = 10 kV
AuxiliarJ
M5
M4
M3
M2
Ml
2x
lx
2x
lx
2x
kW
busbar
MB
M9
Ml0
lx
lx
2x
C, U, =lO kV
Ml1
lx
Ml2
2x
Ml3
2x
(AT),
Ml4
IS 13234 : 1992
IEC Pub 909 ( 1988 )
u2
_go = RG + ,j X: = 2; (0.05 + j) = x; +
(0.05 + j)
rG
Zo = (0.0150 + j 0.2999) R
The correction
K G.PSU
1.1
C
mm
1 + xb sin cprG
1 + 0.17 . 0.6258
= 0.9942
therefore:
z
_G.PSU
--
In order to calculate the short-circuit current on the high-voltage side of the transformer
(~Fl in Figure A6, page 149) the equations in Sub-clause 11.5.3.8 are used with c,,, = 1.1, tf =
LI,lUrG = 220 kV/21 kV and t, = 240 kV/21 kV, and therefore:
1.1
220 kV
K
1 +
(x;
-Cm,XT)
sin q,o =
21 kV
Kpsu = 0.9129
Auxiliary transformer
The positive-sequence
short-circuit impedances &, zn and zc according to Figure 7,
page 41, can be determined with the equations of Sub-clause 8.3.2.2. Substituting the data
presented in Figure A6 in Equation (9), the positive-sequence short-circuit impedances of the
transformer are calculated as follows (related to the 21 kV side A):
u2rTA
UkrAB
ZAB
100%
z-e
Srr~n
ZAC
u2 rTA
UkrBC
ZBC
100%
=-.
L$TBC
u2rTA
S2rTAB
7%
(21 kV)2
100%
25 MVA
ZAB
13%
(21 kV)2
100%
25 MVA
= 0.059 MW
75
= 1.2348 52
2.2932 Q
(21 kV)2
(25 MVA)2
= 0.04163 52
IS 13234: 1992
IEC Pub 909 ( 1988 )
u2rTA
RBC
(21 kV)
0.114 MW
PkrTBC
(25 MVA)
SZ,TBC
x,,
= x,,
\ Z& - R&
Xa, =
Using Equation
(ZAB
Z AC -
(ZBC
ZAB
(&
+ &c
1
ZB
zc = +
= 2.2918 52
1
ZA
= 0.08044 Q
to UrrA = 21 kV:
&C)
&-)
- ZAn) = +
+ j 0.0882) B
Converted to the 10.5 kV (side B or C) with t, = 21 kV/ 10.5 kV, the impedances of the threewinding transformer AT are:
Z
_ALV
ZBLV
--Z _A
*$
ZCLV
(0.000353 + j 0.02205) Q
I
(0.0101 + j 0.2865) Q
* 1 t2
ZB
A3.2.5
Low-voltage
According to Figure A6, page 149, and Figure A8, page 165, there are five transformers with
Srr = 2.5 MVA and Urrnv/ u,rLv = 10 kV/0.693 kV connected to each of the two auxiliary
busbars 10 kV and in addition one transformer with &r = 1.6 MVA, UrTHv/UirLV = 10 kV/
0.4 kV. Each of these transformers feeds a group of low-voltage asynchronous motors.
With the equations
Z T15HV
UkrT15
-.--=-.
loo%
U2,T15HV
6%
s, T15
R risuv =
P krT1S
3 ITTi5
U2rT15HV
=
(10
PkrT15
0.0235 MW
s!TT15
,-
RTISHV
ZTMIV
100%
. . . ZT19HVy
U2rT20HV
UkrT20
r20HV=
i- j XT,,,V
srno
76
2 4 Q
(10 kV)2
(2.5 MVA)
= 0.376-Q
= 2.3704 Q
(0.376 + j 2.3704) Q
ZTZlHV
. . * $25HV
(10 kV)2
6%
=- 100%
2.5 MVA
100%
1.6MVA
3.75 52
IS 13234 : 1992
IEC Pub 909 ( 1988 )
(10 kV)
RnoHV = 0.0165 MW (I.6 MVA)2 = o6445
_.____~_
X TZOHV
Z
_T20HV
Converted
to the low-voltage
Asynchronous
R:20HV = 3.694 Q
-ZT'OLV
A3.2.6
= \&2OHv
(1.031 + j 5.910) mQ
motors
Data and calculations of the short-circuit impedances of the high-voltage motors Ml to Ml4
according to Sub-clauses 11.5.3.5 and 13.2 are given in Table AVI.
Using Equations (69) and (34) and bearing in mind that lJrMis equal to U, in this special case,
the following expression can be found for Z&:
IrM
ILR
c -
u,Mi,-3
. lrM
I&,
Data and calculation of the short-circuit impedances of the low-voltage motor groups
including their supply cables according to Sub-clauses 11.5.3.5 and 13.2 are given in Figure A8,
page 165, and Table AVII.
77
IS 13234: 1992
IEC Pub 909 ( 1988)
TABLE AVI
123
PrM
Quantity of motors
u rM
cos &r
LM
MW
kV
-
Pair of poles
p
6.8
2
3.1
1
1.5
2
-2
I:
(1...7)
0.7 0.53 2
1.71
1212
10
0.85 0.75 0.85 0.95
0.952
4
0.948 0.96 0.96
5.1
-112
3.1
3533
-321
456
0.87
10
I1
1.5
1.85 0.7
2
32.0
12
13
z
14 (R... 14) Remarks
0.53 2
2
1
3353
6.02 3.80 3.54
2.27
:
-
21.3
,
Calculatedwith &, = P,,/cos qjq,)
1 0.05 0.086 0.141 0.242 1.85 0.348 0.219 0.204 1 0.131 0.10 0.086 0.141 1.23 Calculatedwith!,,, = S+,/(, 3 U,,)
1.55 1.5
0.1 0.1
4.4
0.23 0.11 0.67 0.57
0.15 0.15 0.15 0.15
1.7
0.1
1.55 1.5
0.1 0.1
4.4
0.62 0.23 0.11 0.67
0.15 0.15 0.15 0.15
See Sub-clauseA3.2.6
m = P,,lp
according to Sub-clause11.5.3.5
xu
u (L, =O.ls)
1.65 1.65
0.796
1.65 1.65
1.75 1.75
1.75
)
p = 0.62 + 0,72e-0 32IliNI,M!)
4 (Ll,= 0.1 s)
q = 0.57 t 0.12 In m3
ipsM
1blM
kA
kA
kA
8.14
19.8
4.04
5.41
13.12
2.41
r;,, = (&,&,)I,,
i,,, = xv, 2 !;j,,,. Equation(70)
lbiU = q&,,
Equation (71)
&4
XM
RM
Q
R
R
0.78
0.777
0.08
1.17
1.165
0.138
rkJM
1, The values
28.74 16.78
-0.989
-0.15x,-
10.2
5.97
ZM----
13.2.2.
A3.3
A3.3. I
The calculation is done according to Sub-clause 12.2.3. It is not necessary to take the
asynchronous motors into account (see Sub-clause 13.2.1, contribution of motors smaller than
5%).
The initial symmetrical
short-circuit
1.1 . u,
~k,J
1.1 . 220 kV
(~3 zPsU =
[Lo =
1.1 . u,
_-.
~ 3 ZQ
,-%
s%Q
,--.
\3 u,
8000 MVA
_
< 3 * 220 kV
= 20.99 kA
1.1 - 220 kV
___
= (2.088 - j 20.89) kA;
(0.6622 + j 6.622) Q
(55):
ILLQ
1 =
20.99 kA
IS 13234 : 1992
IEC Pub 909 ( 1988 )
L;: = /zps.
Equation (56):
i, = ipps + i,Q
Power-station unit:
RIX =
RpsuIXPSU
= 2.226 52167.31 Q = 0.033 -+ xpsu = 1.91
&PSU = XPSU J2
r ipSU
Network feeder:
RQIXQ = 0.1; XQ= 1.75
i,Q
XQ
&Q
S:
/$;,,
=
p
(0.0149 + j 0.2982) Q
I=
44.67 kA
1.1 . 21 kV
1.1(0.00367+jO.2646)52+
2(0.2649+j2.649)Q
79
IS 13234: 1992
IJZCPub 909 ( 1988 )
$r
1.1 - 21 kV
n
(0.00645 + j 0.3152) Q
L;: = &
Z
_T,PSU
z =
_rsl
and
* ZQmin
1
1
(0.02135 + j 0.6134) 52
(_Zrs,I= 0.1534 Q
c&G
ri+
IZrslI =
1.1 - 21 kV
J3.0.153452
=86.94kA
&G
&$;psu
1.1 . 21 kV
. 0.2986 Q = 44.66 kA
(T,PSU
+ ;
ZQmin)
f
1.1 . 21 kV
=
n
1.1 - 0.2646 Q +
( 22:g;
)2 .2.66252
= 42,30kA
r; = $, + &r = 86.96 kA
= ipo + ipr
lP
ipG
PT
OECpage 161)
80
IS 13234 : 1992
IEC Pub 909 ( 1988 )
Zb =
= 44.67 kAl6.873
(57))
c UrG
V3
Auxiliary transformer
Busbar B
\
EMEH
FIG. A7. -
AT
Busbar C
U,=lO
kV
I
ZMCr
Positive-sequence
system for the calculation of the partial short-circuit current
Zk,_,r from high-voltage and low-voltage motors at the short-circuit location F2.
Impedances are transferred to the high-voltage side of the auxiliary transformer
AT with t, = 21 kV/lOS kV = 2.
Sl
IS 13234 : 1992
Auxiliary
busbar B, U, =lO kV
Motors
Ml...M7
-=~
T20
&TLV
0.693
kV
Sq =1.6 MVA
UrTHV
-=-
UrTLV
1OkV
kV
0.4
@QB@B
U,=38OV
Ml9
Ml8
Ml7
Ml6
Ml5
M20
FIG. A8. -
Detail of Figure A6, page 149. Transformers and groups of low-voltage asynchronous motors connected to the auxiliary busbar B. Transformers and low-voltage
motor groups connected to the busbar C are identical.
(0.086 + j 0.777) Q
z
-M.8...14
(0.138 + j 1.165) Q
z
-MB
z
-M,
I...7
-M
+ T, 15.. .19
z
-M
+ T. 20
-MC
@B
&-AT
ZA
ZMBJ
@C
2,,,,2s
26
&Kt>
ZB +ZC
= (0.00141 + j 0.0882) Q +
+ZMB~
+ZMC~
(1.110 + j 7.986) Q
ZM_Ar = (0.00141 + j 0.0882) Q + (0.2688 + j 1.9744) 52 = (0.270 + j 2.063) Q
WG
~&-AT
1.1 . 21 kV
=
J3/_ZM_ATI
0-m
2.08 Q = (je41kA
IS 13234 : 1992
IEC Pub 909 ( 1988 )
TABLE
AVII
Data of low-voltage asynchronous motors and data of transformers 10 kVlO.693 kV and 10 kV10.4 kV
respectively connected to the auxiliary busbar B. Partial short-circuit currents of the low-voltage
motors at the short-circuit location F3.
Transformer No.
Motor group No.
S
G-w
u
rTLV
Ukr
Pkil
PrM (motor
group)
u rM
cos w/r
LJlrM
RJXhl
1.s 16 17 18 19
tiVA
kV
kV
%
kW
MW
kV
_
srM
Z TH
R TH
X THV
I.6
10
0.4
6
16.5
___. __~
12.5
0.9
0.66
0.8. 0.9 = 0.72
5
0.42
1.0
0.38
0.72
5
0.42
4.5
1.3
1.25
n
&
R
2.40
0.376
2.3704
3.75
0.6445
3.694
::
e
kA
0.0697
0.0270
0.0643
5.74
0.0208
0.0081
0.0192
11.8
XM
G,M
R TH
X WV
&r
xMT
Data
given by
the manufacturer
7.67
14.51
5.62
13.39
Q
S-2
6.00
15.76
1.20
3.152
16.862
0.377
3.372
1.883
Sub-clause 13.2. I
Suh-clause 11.5.3.5
and Table II
Table 11
&M = P,rvl/(cos (un,)
Equations (6) to (8)
Equation (34)
RM = 0.42 X,
XM = 0.922 2,
lJ, = 0.66 kV; 0.3X kV; c = 1.OS
Converted to the
high-voltage side
of the transformer
5.64
15.69
._II
16.693
0.381
Data
given by
the manufacturer
13.00
5.w
12.00
Q
R
Q
R
kA
14.1
5.5
1.3
1.39
____
6.25
44
RM
Remarks
20
(115.. 19)
2.5
10
0.693
6
23.5
_
MVA
XM
l-
0.991
2.625
2.806
2.264
This partial short-circuit current has to be considered because its magnitude reaches
approximately 7% of the current fi, + fi, = fi = 86.96 kA as calculated before. The sum of the
short-circuit current .Di reaches:
zfi
Additionally,
partial peak short-circuit currents and breaking currents fed from the
asynchronous motors are to be added to the above calculated currents i, and I,,. These are
ipM_A.I.= x ,-? I)LMpA-,= 1.7 ~2. 6.41 kA = 15.41 kA with x = 1.7 as a first approach (highvoltage motors have zt = 1.75 or x = 1.65, see Table AVI, low-voltage motor groups are to be
considered with x = 1.3) and I hM AT = J!,_,,. as a conservative approach. Account has been
taken of the fact that Ib(; + IhMpAr is smaller than I ,,, = /i7, so that the breaking capacity for a
circuit breaker between the unit transformer and the generator may be Ihl. = 42.30 kA. When
calculating &-AT with Method C of Sub-clause 9.1.3.2 taking the impedances of the motors
from Tables AVI and AVII, the factor x, = 1.701 is found and therefore ipM_A.,.= IS.42 kA;
that is equal to the value given above.
x3
IS 13234 : 1992
IEC Pub 909 ( 1988 )
A3.3.3
F3
FIG. A9. -
Busbar
Positive-sequence
Calculation
Busbar
location F3.
of Ik~r:
(ZAL + Zrsl. ,) @CL,
&AT=ZBLV
Z
_ALV
+ ZCLV
&r
+ ZMC,
+ &sl.t
+ ZMC
where:
zBLv = (0.0101 + j 0.2865) Q = ZCLV
Z
_ALv
= (0.000353 + j 0.02205) Q
Z
_rsl.l
= (0.00546 + j 0.1533) Q
Z
_MC
=
&(M8.
M14)
--~
k3
ZkAT
:i5ktt
IIZ
_Z(M+T.2,.
= (0.00137 + j 0.0383) 52
)
.26)
(0.157 + j 0.817) Q
1.1 . 10 kV
CUtI
$AT
J3-
(0.0121 + j 0.3438) S2
I$ATI
18.46 kA
= (0.649 - j 18.45) kA
IS13234:1992
IEC Pub909(
1988)
Together with 1 ZzCMl..,M7)
= (0.894 - j 8.075) kA; ( I~~r(M1...7)1= 8.124 kA) and
~&l+T,15...20) = (0.799 - j 2.118) kA; ( (I;rCM+T,15...20J1= 2.264 kA)
the current $ can be calculated:
$ = (0.649 - j 18.45) kA + (0.894 - j 8.075) kA + (0.799 - j 2.118) kA
= (2.342 - j 28.64) kA
lLil=28.74 kA
It follows for the short-circuit power (see Sub-clause 3.6):
s;: = p
U, ZL= F
The peak short-circuit current i, can be derived with the following x-factors:
XAr = 1.02 + 0.98 e- 3 (0.0121R/0.3438Q) = 1.90
(see Sub-clause 9.1.3.2, Method B: 1.15 - 1.9 > 2.0)
19.8 kA
iP3M
xZ(M1...M7)
=
fl
fi3M
8.124 kA
n-
xrCM+T,15,,,20)
= 1.02 + 0.98 e-3(0.991R2.625R)
= 1.34
$ = l.15 %A* n
i, =
2. F.
riA-T+ %(Ml...M7) J2
rh(M~...M7)
i- xx (M + T,15...20)
J2
b(M
+ T. 15...20)
2.264 kA = 76.30 kA
with 1.15 - xAT = 2 (see Sub-clause 9.1.3.2, Method B) and the ratio RIXof the low-voltage
motors including the transformers 15 to 20 according to Table AVII.
As a medium effective value x is found:
76.30 kA
lP
;=
$2 ri
y/2 - 28.74 kA
= 1.88
If the short-circuit current Z,&r is transformed to the side A of the auxiliary transformer AT it
becomes obvious, that &!Ar,is already smaller than twice Zro, SO that IbAr = ZL,ris valid (-see
Equation (18)) far-from generator short circuit).
1bP(Ml...M7)
Z bX(M+T,15...20
lb =
zbAT
i
i=l
zbL(M1...M7)
& qi riMi
= ,@&(M+T,l5...20)
4.04
b~((M+T,15,,,2@
0.77.0.342-2.264kA = 0.60 kA
$5
S)
(IEC
page 171)
IS 13234 : 1992
IJZC Pub 909 ( 1988 )
A3.3.4
~UM+T,15...19jt
=(0.134
+ j1.243)mQ
=(1.92
+ j5.043)mQ
%Ol94
+ j0.55)mQ
$(0.028
+ j0.3~57)mn
4-
~TZO,.V=(1.031
zhnno=(8.1
FIG. AlO. -
L);r20 =
Positive-sequence
+ j5.910)mR
+ j19.2)mR
cull
~\ 3 @I +
$M?[, =
/6 =
1.05 * 380 v
<M20
{iTZO
zT?OLV)
CU,
~~
\ 3
location F4.
ziMzo
1.05 . 380 V
~
\ 3 (8.1 +_j 19.2) mQ
=
= (4.30 - j 10.19) kA
current is calculated
ip =
= (6.04 - j 35.74) kA
from:
ipT20 +
ipM2O
mD/6261mn) = 1.61
with X b = 1.02 + 0.98 e-3 (1.052
According to Method B of Sub-clause 9.1.3.2, it is necessary to take 1.15 . x,, = 1.15 . 1.61 =
1.85. In this case for a low-voltage short circuit the maximum for 1.15 xh is limited to 1.8.
rpMzO= xM y 2 &a
i, = 1.8 * v3..
86
IS 13234: 1992
IEC Pub 909 ( 1988)
87