Connection Manual Drive VVVF5
Versin / Version: 0.1
Pg. 1 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
Pg. 2 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
DESCRIPTION OF SWITCHES
The unit may be programmed using the DIL switches on the front of the unit. If
any change is made to any of the above switch selections, the Mains Supply to the
VVVF-5 unit MUST be switched OFF and ON again to read the new programming.
The switches functions are:
1.- 1 & 2 Inputs.
ON: 1 Input.
The door control unit will be controlled by a single input. Any voltage between 12 to 250
volts AC or DC applied between terminals 8 & 10 will close the doors. Without input active
the door opens. Open input is not used.
OFF: 2 Inputs.
The door control module will be controlled by two independent inputs. Any voltage between
12 to 250 volts AC or DC applied between terminals 8 & 10 will cause the doors to close.
And between terminals 12 & 10 will cause the doors to open. In the absence of a signal, the
doors will remain static. If both inputs are applied then the open signal has priority.
Skate fixed on the top side of the belt and the motor on the right side.
Skate fixed on the bottom side of the belt and the motor on the left side.
Pg. 3 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
4.-
Pg. 4 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
SERIAL PORT (13, 14, 15, 16)
The serial port is used to connect with external
devices like the diagnostic console, interfaces and
future expansion devices. Operating speed 1.200
Baud, current loop.
Pg. 5 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
OUTPUT RELAYS AND LED INDICATORS (from 30 to 41)
Output relays have been provided to give continuous information to the main lift controller
concerning the status of the doors. One 2 Amp 150 Volts volt free change over contact is provided
on each relay that may be used by the main lift controller to pilot such information as doors fully
opened, doors fully closed, Photoelectric detection, obstruction in the doorway and door
control O.K..
Opened.
Led indicator and relay activated when the doors
are fully open.
Closed.
Led indicator and relay activated when the doors
are fully closed and locked.
Photocell.
Led indicator and relay activated when the
photocell or the reopening input is operated.
Obstruction.
Led indicator and relay activated when an
obstacle is detected that stops the doors from
closing. The signal will reset when the doors reach
the opened or closed position.
Status.
Blinking led indicating proper working conditions
Disconnect the inputs (Pins 8,9,10,11 & 12) and the priority inputs (Pins 26,21,25 & 23).
Switch OFF the VVVF5 and place the doors in closed position.
Switch ON the VVVF5 and Push auto-adjustment button (51)
1st Movement: The door will open 200mm (If the door instead of opening makes small
rebounds, means that it's trying to close and that the direction is the opposite. The pin 3 of
the DIP switch has to be changed.).
2nd Movement: The door will close 150mm.
Pg. 6 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
Next 3 movements are to detect the clear opening of the door, the 3rd movement is starting 2 or 3
seconds after finishing the second one.
3rd Movement: The door will close completely in slow velocity until the end to detect the 0
position.
4th Movement: The door will open slowly counting the pulses from the encoder built into
drive motor until it reach the open mechanical stop. Will detect the final position.
5th Movement: The door will close after a short delay. From the information gained the
microprocessor will calculate the acceleration and deceleration ramps and the bracking
torque required to give the optimum control of the doors.
SAFETY (54)
This potentiometer is used to set the closing pressure onto an obstacle in the doorway. The closing
pressure can be set between 40 and 150 Nw.
ENCODER (55)
An integral quadrature pulse encoder is connected to this input. The purpose of the encoder, which
is situated inside the motor, is to inform the control of the exact position and speed of doors.
Pg. 7 / 8
Instructions
DOC-TC.AS.IN.V00001.EN
Connection Manual Drive VVVF5
Versin / Version: 0.1
MOTOR (56)
Output to the 3 phase motor varying the voltage and frequency to control speed and torque.
ON / OFF SWITCH (57)
Disconnects the unit from the 230 Volts AC mains supply.
Caution: When the supply is switched off, capacitors in the control system will remain
charged for a short time. Allow 60 seconds before handling the Control Card or Motor.