Design variants
The fire detection control panel is a modular extendable 19" unit assembly system.
Even in its smallest basic design (GAB 32),
it is capable of accomodating 2 x 32 fire
alarm groups and 32 primary control
groups, besides the central equipment
such as the power supply unit, battery and
main alarm tripping.
In the larger model (GAB 128), the system
can be extended to 3 x 128 groups by
means of additional plug-in zone modules.
In this case, a common central plug-in unit
(master system) takes over the overriding
control procedure for the otherwise autarkic plug-in zone modules (master-slave
process).
A total combination of 3072 groups can be
obtained by joining together up to 8 standing cabinets of the above type.
Wall
mounted
cabinet 15U
Extinguishing control
for the fire extinguishing system
The system component extinguishing
control is used to control single and multi-
zone fire extinguishing systems. It functions independently from the other systems of the fire detection control panel
and therefore has its own display and
operating panel.
Each extinguishing zone is controlled and
monitored by an autarkical functioning extinguishing control card. All the important
components which are necessary for the
trouble-free functioning of an extinguishing
system (e.g. detectors, release and alarm)
devices are connected to the extinguishing
control system. In the case of alarm, the
extinguishing control system registers and
analyses the detector signal, sounds
the fire alarm and activates the pre-programmed control function as well as the fire
extinguishing system.
Programming
The fire detection control panel FMZ 4100
can be programmed for different applications. For this purpose a special configuration programme has been developed
which transforms the physical values of
entered characteristics (e.g. alarm threshold, short circuit threshold, etc.) into a
language understandable for the microcontroller. In this way, the user has the
maximum amount of flexibility which, for
instance, is required when extending
already existing systems.
Programming is greatly simplified by the
use of modern pull-down-menu-techniques and easy-to-understand input instructions.
Secondary groups
The fire detection control panel FMZ 4100
can be equipped with free programmable
relays in order to enable further alarm organization, for example: the disconnection
of the air conditioning, the interruption of
the manufacturing process, the opening of
smoke vent flaps, etc. 2 break contacts
(b-contacts) and 2 make contacts (a-contacts) with a maximum contact load of 2
amperes are available for each relay. The
operating and logical combination of the
relays is determined for each specific system by means of the Minimax configuration programme. The standard functions
are as follows: operating tripped by alarm,
pre-alarm and interferences as well as the
disconnection of fire detector groups.
ZID-V detector
Serial interfaces
The fire detection control panel FMZ 4100
has standard serial interfaces for connection to external equipment, e.g. alarm and
graphics reporting system or printer, as
well as enabling communication with a
superordinate administration system. An
additional microcontroller circuit which has
been especially developed for the operating of repeater panels as well as externally situated control devices can exchange
information with the fire detection control
panel via a serial interface. There are 768
programmable outputs available for the
operating of the LEDs in a repeater panel.
Additionally, the microcontroller has a serial interface for data transmission, e.g. for a
desk-top printer. The fire detection control
panel FMZ 4100 offers further interfaces
for fire brigade control panels as well as for
the so-called public main alarm. An alarm
signal can be automatically transmitted further to an external service, e.g. fire brigade,
by means of the main alarm function. Additional VdS standard interfaces are available for the connection of fire detection
equipment from other manufacturers to the
FMZ 4100 extinguishing control system.
Special applications
Spark extinguishing systems
The possibility of realizing special applications of fire detection and extinguishing
technology were taken into consideration
during the development of the fire detection control panel FMZ 4100. These special applications are, for example, spark
extinguishing systems for the wood industry, fire suppression systems for paint
spraying plants as well as for the protection of equipment in computing centres. If
one takes the spark extinguishing system
as an example, it can be seen that this system can be connected to the control panel
without any special or additional analyzing
electronics. All the requirements necessary for operating a spark extinguishing
system such as adjustable extinguishing
times for each extinguishing area, monitoring of the extinguishing agent supply,
electrical monitoring of heat tapes and
leak detectors are to be found in the standard programme of the control panel. It is,
therefore, guaranteed that the evaluation
of spark alarms as well as the operating of
the automatic extinguishing system will be
carried out with virtually no delay.
Gas detectors
A gas detector is an autonomous subsystem that can be easily integrated in the
FMZ 4100 fire detection control panel.
Owing to the increasingly complex chemical processes used in industry, gas detection at an early stage is often the main
element of a safety scheme and is accordingly very suitable for combination with
fire detection and fire systems. A display
continuously indicates the gas concentrations in the gas detectors. If the gas concentration measured exceeds a preset limit, external equipment can be activated
via secondary control lines. All measured
data is passed on to the FMZ 4100 where
it is recorded. This assures the traceability
of events even after a lengthy period.
Report
printer
Building
management
system
Serial
interface
Alarm and
graphics reporting system
Repeater
panel
Slave control
panels
Network
interface
Operator panel
extinguishing
control
Manual
release
Second
release
Extinguishing
delay
System
monitoring
Multi-zone
extinguishing control system
Field termination
card for primary
control zones
EMI protection
Automatic
release
CO 2 / Argon high
pressure system
Fire brigade
key box
Mimic panel
Fire brigade
main alarm
Operator panel
Group LEDs
Line
card
Master CPU
peripheral evaluation
and control
Automatic
detectors
Optical / acoustic
alarm
Contact giving
detectors
Trigger solenoid
valve
Air condition
off
Relay
control
card
Slave CPU 1
evaluation and control
Relay
card
Detector
identification
system
System
Gas detection
Gas line card
Concentration
display and
operating panel
Machinery
off
Smoke vent
unlock
Field
termination
card
detector
identification
Detector
identification
for automatic and
contact giving detectors
EMI protection
Gas detector
Termination
and
control
card
Optical / acoustic
alarm
Machinery
off
Repeater panel
Processor card
Field termination
card detector
identification
Interface to master module
Relay card
Field
termination
card for
detector
groups
Field termination
card for primary
control groups
Field termination
card for detector
groups
Technical Data
Fire Detection Control Panel FMZ 4100 GAB 32, GAB 96, GAB 128
Specific System Data
Power supply
Operating voltages
Control voltage of external devices
Emergency power supply
Control relay rating
Control signal of main alarm
Permissible ambient temperature
Permissible ambient air humidity
Place of installation
VdS approval
FM approval
230 V /110 V, 50/60 Hz, (+10 %, -15 %) switchable by jumper at power supply
15 V, 12 V, 5 V
24 V DC
24 V DC (2 x 12 V maintenance free and sealed batteries, independent of
position, deep-discharge resitant, capacity range application specific)
30 W/60 VA /1.5 A / 250 V
24 V DC, constant or pulses, adjustable from 1 to 10 seconds
-5 - +40 C
12 g /m3
dry operating areas with restricted access
G 29013
OY4AO.AY
Specific Data
Colour
Weight of complete unit (without batteries)
IP rating
Dimensions in mm (W x H x D) 2
Line cards 3
Automatic detector groups
Detection Group voltage
Detection Group quiescent current
Detection Group alarm current
Detection Group terminating resistance
Alarm resistance (detector)
Permissible max. line resistance
Permissible max. number of detectors per group
9V
approx. 5 mA
9 mA (spark extinguishing system: 15 mA) 4
1800
470 - 1000
50
10 manual call points or 60 sprinkler monitoring modules 5
approx. 2.2 mA
3.9 - 4.1 V
2.7 V 4
ZPD 4V3 (spark extinguishing system BZX 4V3)
ZPD 2V7 (spark extinguishing system BZX 2V4)6
50
10 5
approx. 2.6 mA
24 V DC
approx. 2.6 V
2 A ( limited by fuse)
1000 /1 Watt
3
4
5
6
7
For 32, 96 or 128 automatic and contact giving groups and primary control groups
Other cabinet sizes available
A reduced version can be supplied when only automatic fire alarm groups are required
Other current/voltage threshold values programmable
VdS standard value
For evaluation of different interferences in sparc extinguishing systems, e.g. continuous extinguishing, water supply fault, 3 additional thershold voltage values are monitored
Technical data for groups of the extinguishing control system are similar to the line card
The right is reserved to modify any specification without prior notice.