Reinforcement Design For Metal Building Systems
Reinforcement Design For Metal Building Systems
Figure 1
Figure 2
Figure 3
Figure 4
LENGTH MODIFICATION
Extending the length of a
metal building is very easy if the
site permits it. Additional units
of frames and secondary members identical to the original can
be added to the building. The
end frames of the original building must be checked. If expansion were contemplated in the
original design, the end frame
would be the same design as the
interior frame, with no modifications necessary. In the case of a
non-expandable endwall, it can
be replaced with an intermediate
rigid frame and the existing endwall parts can be dismantled and
moved to the end of the new
addition.
Non-expandable endwalls are
commonly beam and post construction. If the endwall footings
were designed for this condition,
they will not be suitable for an
intermediate rigid frame, which
can have a significant horizontal
reaction. If this is the case, the
footings will have to be replaced.
The other option would be to
reinforce the existing endwall.
The footing must be checked for
the increased reactions.
WIDTH MODIFICATION
Expanding a metal building
laterally is relatively simple with
use of a width extension (figure
5). Width extensions (a lean-to
type structure) are available
from virtually all manufacturers.
Figure 5
Figure 6
Figure 8
Figure 7
PURLIN REINFORCEMENT
Concentrated loads are a common addition to any building.
The list of items that could be
hung from the roof is endless;
most concentrated loads are supported from a single point and
this can be a problem. Point
loads on cold-formed purlins
should be avoided unless they
are quite small in magnitude.
Before adding load to a purlin it
is necessary to know its capacity. Most roofs will have been
supplied with some amount of
collateral load included. A simple rule of thumb to determine
what the allowable concentrated
load might be is to take the
excess uniform load capacity, if
there is any, and find the equivalent concentrated load. A 25
purlin with a 3 psf excess capacity on 5 centers has a total load
capacity of 5 x 25 x 3 = 375
pounds or a concentrated load of
half of 375 or 187 pounds. An
additional problem is the method
of hanging the load. Many
installers make the mistake of
Figure 9
Figure 10
Table 1
Member
Z purlin
C Reinf.
Angle Reinf.
Depth (Inches)
9.0
7.0
2.0
Width (Inches)
3.0
2.5
2.0
Table 2
Member
Unreinf. Z
Z Purlin plus C
Z Purlin plus 2-Angles
Area
1.285 sq. in.
2.45 sq. in.
2.41 sq. in.
Allowable Moment
89.4 in. kips
135.3 in. kips
182.87 in. kips
Figure 11
Figure 12
Figure 13
Figure AA