Line Protection
Line Protection
Serge Beauzile
Chair IEEE FWCS
Ch i Power
Chair
P
&E
Energy S
Society
i t
[email protected]
June, 10,
June
10 2014
8:30 -12:30
Florida Electric Cooperatives Association
Clearwater, Florida
Seminar Objective
Distribution Circuit Protection
Fuse to Fuse Coordination
Recloser to Fuse Coordination
Breaker to Recloser Coordination
June 2014
Serge Beauzile
June 2014
Serge Beauzile
C
Coordinating
di ti D
Devices
i
Basic concept: All protective devices are able to
detect a fault do so at the same instant.
If each
h device
d i that
th t sensed
d a fault
f lt operated
t d
simultaneously, large portions of the system
g
every
y time a fault needed
would be de-energized
to be cleared. This is unacceptable.
A properly designed scheme will incorporate time
delays into the protection system, allowing
certain devices to operate before others.
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
C
Coordinating
di ti D
Devices
i
Timing of device operation is verified using timetime
current characteristics or TCCs device
response curves plotted on log-log graph paper.
Devices have inverse TCCs. They operate quickly for
g magnitude
g
overcurrents,, and more slowly
y
large
for lower-magnitude overcurrents.
Operating time is plotted on the vertical axis,
axis and
current magnitude is plotted on the horizontal
scale.
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
C
Coordinating
di ti D
Devices
i
Four different TCCs
are shown
h
on the
th
left. Device D is
the fastest to
operate, and device
A is the slowest.
100
.25
25 sec
0.1
B
C
D
3 kA
100,000
1000
100
10
0.01
10,000
Time in Seconds
10
Current in Amperes
June 2014
Serge Beauzile
Coordinating
g Devices
In this example,
Device A is clearly
l
l
faster than Device B
for low ((400-700 A))
fault currents.
100
Uncertain
Coordination
0.1
A
100,000
1
10,000
1000
100
0.01
10
Time in Seconds
10
Device B is clearly
faster for high
(>1000 A) fault
currents,
t but
b t iin the
th
700-1000 A region,
g is uncertain.
timing
Current in Amperes
June 2014
Serge Beauzile
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
Minimum Melt
Average Melt + tolerance
Time in Seconds
10
Total Clear
0.1
10,000
1000
100
10
0.01
Current in Amperes
June 2014
Serge Beauzile
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
0.1
100,,000
10,,000
1000
1
100
0.01
10
Time in Seconds
10
Current in Amperes
June 2014
Serge Beauzile
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
2. Ambient
temperature.
p
3. Preloading effects.
0.1
4. Predamage effects.
100
0,000
10
0,000
1000
1
100
0.01
10
Time in Seconds
1. Tolerances.
Current in Amperes
June 2014
Serge Beauzile
10
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
Consideration of these
four factors can be
quite involved.
Practically, the 75%
Method can be used:
the maximum clearing
g
time of the protecting
link shall be no more
than 75% of the
minimum melting time
of the protected link.
0.1
Current in Amperes
100,000
10,000
1000
1
100
0.01
10
Time in Seconds
10
June 2014
Serge Beauzile
11
Coordinating Devices
Expulsion Fuse to Expulsion Fuse
100
0.1
Current in Amperes
100
0,000
10
0,000
1000
100
0.01
10
Time in Seconds
10
June 2014
Serge Beauzile
12
Utility
y Distribution Feeders
Multiple Feeder Segments
Segments are defined as sectionalizable pieces of a
feeder that can be automatically or manually
separated from the rest of the feeder.
feeder
Segments are delineated by reclosers, fuses,
sectionalizers or switches.
switches
Two primary concerns: number of customers per
segment and
d time to isolate
l
segment.
June 2014
Serge Beauzile
13
Utility
y Distribution Feeders
Number of Customers per Segment
The number of customers per segment has a major
impact on reliability indices.
As the number of segments per feeder increases,
reliability
y can also be adversely
y impacted,
p
and
construction cost will increase.
A optimum
An
ti
point
i t mustt b
be sought
ht tto d
determine
t
i th
the
best segment size.
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
14
June 2014
Serge Beauzile
15
Coordination Goal
1.
Maximum Sensitivity.
2.
Maximum Speed.
3.
Maximum Security.
4.
Maximum Selectivity.
June 2014
Serge Beauzile
16
1.
Establish a coordination
pairs.
2.
3.
4
4.
Determine
D
t
i remaining
i i
overcurrent device
characteristics starting
g to
from the load and moving
the source.
June 2014
Serge Beauzile
17
June 2014
Serge Beauzile
18
June 2014
Serge Beauzile
19
June 2014
Serge Beauzile
20
June 2014
Serge Beauzile
21
June 2014
Serge Beauzile
22
June 2014
Serge Beauzile
23
June 2014
Serge Beauzile
24
June 2014
Serge Beauzile
25
June 2014
Serge Beauzile
26
June 2014
Serge Beauzile
27
June 2014
Serge Beauzile
28
Fuse Save
Minimizes customer interruption time by attempting to
open the breaker or recloser faster than it takes to melt the
fuse.
fuse
This saves the fuse and allows a simple momentary
interruption.
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
29
Fuse Blow
FUSE is BLOWN
Lateral experiences
sustained interruption
30
Fuse Blow
Used primarily to minimize momentary
interruptions (reduces MAIFI)
Increases interruption duration (SAIDI)
Very successful in high short circuit areas
More suitable for industrial type
customers having very sensitive loads
June 2014
Serge Beauzile
31
Fuse Save
Entire Feeder trips
Momentary occurs
FUSE is SAVED
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
32
Fuse Save
June 2014
Serge Beauzile
33
June 2014
Serge Beauzile
34
June 2014
Serge Beauzile
35
SEL-351S
SEL
351S
Protection and Breaker Control
Relay
June 2014
Serge Beauzile
36
June 2014
Serge Beauzile
37
SEL-351S
Protection and Breaker Control Relay
Protection Features:
P f
Performs
att lleastt 18 different
diff
t protection
t ti functions.
f
ti
June 2014
Serge Beauzile
38
SEL-351S
Protection and Breaker Control Relay
Protection Features:
B U
Bus
Undervoltage
d
lt
(27)
Phase Overvoltage (59P)
G
Ground
d Overvoltage
O
lt
(59G)
Sequence Overvoltage (59Q)
O
Overfrequency
f
(81O)
Underfrequency (81U)
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
39
June 2014
Serge Beauzile
40
SEL-351S
Protection and Breaker Control Relay
Protection Features (continued):
Ti
Time
Ph
Phase Overcurrent
O
t (51P)
Time Ground Overcurrent (51G)
Ti
Time
S
Sequence Overcurrent
O
t (51Q)
Directional Neutral Overcurrent (67N)
I t t
Instantaneous
N t l Overcurrent
Neutral
O
t (50N)
Time Neutral Overcurrent (51N)
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
41
SEL-351S
Protection and Breaker Control Relay
Breaker Control Features:
S
Synchronism
h
i
Ch
Check
k (25)
Automatic Circuit Reclosing (79)
TRIP/CLOSE Pushbuttons
Enable/Disable Reclosing
Enable/Disable Supervisory Control
June 2014
Serge Beauzile
42
SEL-351S
Protection and Breaker Control Relay
Other Features:
E
Event
t Reporting
R
ti and
dR
Recording
di
Breaker Wear Monitor
St ti Battery
Station
B tt
M
Monitor
it
High-Accuracy Metering
F lt Locator
Fault
L
t
June 2014
Serge Beauzile
43
SEL-351S
Protection and Breaker Control Relay
June 2014
Serge Beauzile
44
Extremely flexible
Have many different elements (UF, UV, Directionality, etc)
One relay can protect on zone of protection
Inexpensive and require much less maintenance
Alarm if they fails and dont need calibration
Provide fault information
Provide oscillography and SER data
Can provide analog data to SCADA
June 2014
Serge Beauzile
45
Relays
Basic relay settings:
Phase overcurrent elements must be set above maximum
possible loads
Ground overcurrent elements must be set above maximum
anticipated
p
unbalanced loads
Must be coordinated with downstream protective devices
Under Frequency elements must be set according to the
predetermined set point
TAGGING
NORMAL mode 2 reclosing
g attempts
p
WORK mode HOT LINE TAG
COLD mode
June 2014
Serge Beauzile
46
Relay Curves
100
10
S
e
c
o
n
d
s
Moderately Inverse
Inverse
Very Inverse
Extremely Inverse
0.1
0.01
0.1
1
10
Multiple of Pick Up
100
June 2014
Serge Beauzile
47
100
In this example
p
Multiple of Pickup = 3.
SECONDS
10
TD=0.5
TD=2
TD=6
TD
6
TD = 0.5
05
TD = 2
TD = 6
TD = 15
Time = 0.3s
0 3s
Time = 1.1s
Time = 3.4s
Time = 7.0s
TD=15
0.1
0.01
0.1
1
10
Multiples Of Pick Up
100
June 2014
Serge Beauzile
48
In this example,
100
Pickup
Pi
k = 600 A
A.
Fault Current = 1800 A.
SECONDS
10
TD=0.5
TD=2
T = 0.5
TD
TD = 2
TD = 6
TD = 15
Time = 0.29s
0. 9s
Time = 1.16s
Time = 3.48s
Time = 8.72s
TD=6
TD
6
TD=15
0.1
0.01
0.1
1
10
Multiples Of Pick Up
100
Pickup = 900 A.
Fault Current = 1800 A.
TD = 0.5
TD = 2
TD = 6
TD = 15
June 2014
Time = 0.69s
Time = 2.78s
Time = 8.33s
Time = 20.8s
20 8s
Serge Beauzile
49
Pickup
p Current of Delayed
y Ground OC Devices
Source Side
Backup
Load Side
Primary
Single
g Phase to Ground Fault
June 2014
Serge Beauzile
50
Pickup
p Current of Delayed
y Phase OC Devices
Source Side
IML<IPU<Imin Fault
Load Side
June 2014
Serge Beauzile
51
TB > TR + CTI
June 2014
Serge Beauzile
52
June 2014
Serge Beauzile
53
Trip Logic
TR
= OC + PB9 + 51P1T + 51G1T * (LT6 + LT7) + (50P3 + 50G3) * LT7 + (50P2 + 50G2) * SH1
June 2014
Serge Beauzile
54
June 2014
Serge Beauzile
55
June 2014
Serge Beauzile
56
June 2014
Serge Beauzile
57
SEL-351S
History Summary (HIS Command)
Sample output:
June 2014
Serge Beauzile
58
SEL-351S
Sequence of Events Recording (SER)
June 2014
Serge Beauzile
59
SEL-351S
Metering Data (MET Command)
Sample output - Metering Data (MET):
June 2014
Serge Beauzile
60
SEL-351S
Metering Data (MET Command)
Sample output - Metering Demand (MET D):
June 2014
Serge Beauzile
61
SEL-351S
Metering Data (MET Command)
Sample output - Metering Energy (MET E):
June 2014
Serge Beauzile
62
SEL-351S
Metering Data (MET Command)
Sample output - Metering Max/Min (MET M):
June 2014
Serge Beauzile
63
DifferentialRelays
ProtectionofaDeltaWyeTransformer
IaIIb
A
B
C
IbIc
IcIa
IaIIb
IaIb
IbIc
IbIc
52
IcIa
Ia
Ib
Ic
IcIa
Ia
Ia
Ia I
b
52
Ib
Ib I
c
Ic
a
b
c
Ic
IaIb
IaIb
IbIc
IcIa
OP
R
IaIb
OP
R
IbIc IbIIc
OP
R
IcIa
-64-
IcIa
DistanceRelays
y
ProtectionFeatures
Fourzonesof distanceprotection
Pilotschemes
Phase/Neutral/GroundTOCs
Phase/Neutral/GroundIOCs
Phase/Neutral/Ground IOCs
Power System Protection
-65-
DistanceRelays
y
ProtectionFeatures continued
NegativesequenceTOC
NegativesequenceIOC
PhasedirectionalOCs
NeutraldirectionalOC
NegativesequencedirectionalOC
Phaseunder andovervoltage
Powerswingblocking
Outofsteptripping
Power System Protection
-66-
DistanceRelays
Control Features
ControlFeatures
BreakerFailure(phase/neutralamps)
B k F il
( h /
t l
)
Synchrocheck
Autoreclosing
-67-
DistanceRelays
Metering Features
MeteringFeatures
FaultLocator
F lt L t
Oscillography
EventRecorder
DataLogger
Phasors/trueRMS/active,reactive
and apparent power, power factor
andapparentpower,powerfactor
-68-
DistanceRelays
ZonesofProtection
Zone 2
Zone2
X
3
Zone1
2
1
A1
Z
Zone3
3
Bus1
Zone3
Bus2
NormalLoad
Normal
Load
R
DistanceRelay
atBus1
toprotectLineA
A2
3
Zone1
2
LineA
Zone1 fastest(80%ofline)
Zone2 slower(120%ofline)
Zone3(backwardsUseinPilot
Protectionforcurrent
Reversallogic)
-69-
Zone of Protection
Zone 2
Zone 1
1
t
2
Zone 2
Zone 1
4
Zone 1
Zone 2
Zone 3
Zone 1
Zone 2
Zone 3
Zone 1: Under reaches the remote line end Typically 0.7 Z1L to 0.9 Z1L
With no intentional time delay.
Zone 2:
Z
2 Over
O
reaches
h the
th remote
t line
li end
d Typically
T i ll 1.2
1 2 Z1L
with definite time delay.
Zone 3: Over reaches the longest adjacent line
with
i h definite
d fi i time
i
d
delay
l greater than
h Z
Zone2.
2
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
70
Zone 2
Zone 1
Long Line
Short Line
June 2014
Serge Beauzile
71
PTR = 600:1
June 2014
Serge Beauzile
72
June 2014
Serge Beauzile
73
Check Zone 2 reach does not overreach = Circuit 2 Impedance + (Zone 1 of Circuit 3) or (Zone 1of Circuit 6).
General rule = p
protected Circuit Impedance
p
+ Zone 1 of the Shortest Circuit p
past the p
protected circuit.
June 2014
Serge Beauzile
74
75
Relay Input
June 2014
Serge Beauzile
76
June 2014
Serge Beauzile
77
Current Infeed
IL =0.5 A
ZL =2
IR =1 A
ZR =1
IT =0.5 A
ZT =1
Apparent Impedance = EL
IL
Apparent Impedance = ( IL x ZL) + (IR x ZR)
IL
Apparent Impedance = 4
June 2014
Serge Beauzile
78
Thank You
IEEE/ FECA Protection Coordination
June 2014
Serge Beauzile
79