0% found this document useful (0 votes)
1K views

Intelligent Control Panel

Intelligent control panel

Uploaded by

pablo souza
Copyright
© © All Rights Reserved
Available Formats
Download as PDF or read online on Scribd
0% found this document useful (0 votes)
1K views

Intelligent Control Panel

Intelligent control panel

Uploaded by

pablo souza
Copyright
© © All Rights Reserved
Available Formats
Download as PDF or read online on Scribd
You are on page 1/ 88
ec @ NOTIFIER’ by Honeywell c Intelligent Control Panel SLC Wiring Manual c Fire Alarm & Emergency Communication System Limitations While a life safety system may lower insurance rates, it is not a substitute for life and property insurance! ‘An automatic fire alarm system—Iypically made up of smoke detectors, heat detectors, manual pul stations, audible warning devices, and a fre alarm control panel (FACP) with remote notit- ‘ation capailiy—can provide early waming of a ceveloping fre, Such a system, however, does ncl assure protecton against property damage or logs of life resulting from a fre, An emergency communication system—tysically made up of ‘an aulomatic fre alarm systern (as describes above} and a ite safety communication system that may include an autonomous contro unit (ACU), focal operating console (LOC), voice camen- nication, and otner various Interoperable communication math- ‘ods—can broadcast a mass notication message. Such a system, however, does not assure protection against property damage or logs of life resulting from a fie or Ite satety event. ‘The Manufacturer recommends that emoke ancior haat detectors be localed throughout a protected premises following ‘he recommendations of te current edition of the National Fire Protection Association Standard 72 (NFPA 72}, manufacturer's recommendations, Slate and local codes, and the reccenmendations contained in the Guide for Proper Use of ‘Syelem Smoke Detectors, which is made available at no charge ‘all instaling dealers: This decument can be found at http! ‘wa: syslomsonsor.com/appguides!. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many 39 35% of all fos. Whi fire alarm systoms are designed to provide early warning against fre, they do not ‘uarantae waming or protection again fre. A fe alarm system may not provide timely or adequate warning, or simply may not {unotion, for a variety of reasons: ‘Smoke detectors may not sense fre where smoke osnnot reach the detectars such as in ehknaays, in or behind walls, on roofs, o on the other side of clased coors, Smoke detectors also may not sense a fre on another level oF floor of a building A secondslloor detector, for example, may nat sense a firstfloor cor basement fe. Particles of combustion or “smoke" from a developing fre may nol reach the sensing chambers of sioke detectors because: ‘Barriers such 2s closed or patilly closed doors, walls, chim- ‘neys, even wet or humid areas may inhibil particle or smoke flow. + Smoke psticies may become “ool,” stratify, and not reach the celing or upper wails where detectors are tocated. + Smoke particles may be blown away fon dotoctors by air cutlets, such 2s air conditioning vents, + Smoke panicles may be drawn into air returns before raach- ing the detector. “The amount of ’smo%e" present may be insuficent to alanis omoke detectors, Smoke detaclors are designed to alarm al vi ‘ous levels of smoke density. If such density levals are not cre- ated by a developing fre at the locaton of detectors, the detectors will nol go into alarm. ‘Smoke detectors, even when working progerly, have sensing Fritations. Detectors that have photoeiectronic sensing chamm- bers tend to detacl smoldering res better than flaming fires, Uric have litle visible smoke, Detectors thal have ‘onizing-ype sensing chambers tand 1o detect fast-aming ies belle than smoldering fires. Because fres develop in diferent ways and are often unpredictable zn their growth, noithor type of dotoctor is eceseanly best and a given type of detector may not provide adequate warning ofa tre. ‘Smok detectors cannot be expacted to provide adequate wamn- ing of fies caused by arson, children playing with matches (especialy in bedrooms), smoking in bed, ane violent explosions (caused by escaping gas, improper slorage of flammable matert- als, ete) Heat detectors do not sense patticies of combustion and alarm ‘only when heat on their sensors increases at a prodolorminad rote or reaches a predetermined lavel. Rate-of-ise heat detoc- tors may be subject fo reduced sensitivity over time. For this reason, the rato-of-rse feature of each detector should be tested at east once per year by 2 qualifed fire protection spocialist. Haat delectors are designed to protect property, not ie. IMPORTANT! Smoke detectors must be installed in the same om a8 te control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, slgnaling, andar power. If detectors are nal eo located, a devel- ‘oping fra may damage she alarm system, compromising its able ity © report a fe. ‘Aulible warning devices such as bells, homs, strobes, speakers and displays may not alert people f these devices are located en the other side of closed or partly open doors oF are lacatod en anether floor of a building. Any warning devies ray fai lo alert people with a disabilty ar those who have recently consumed drugs, alcohol, or madication. Please note that + /An emergency communication system may take priority over a fia alarm system inthe event ofa Ife safety emergency. + Voice messaging systems must be designes to meet inteligi- bility raquitements as defined by NFPA, local codes, and Autherites Having Jurisaetion (AHJ), + Language and instrucionsl requirements must be cloary dis- ‘sorinated on any local displays. + Strobes can, uncer certain circumstances, cause seizures in ‘eople with conaitions such as epilepsy. + Studias have shown that certain people, even when they hear afte alarm signal, do not respond to oF comprehend the meaning ofthe signal. Audible devices, such as horns ane bells, can have different ona pattems and frequencies. [tis the property owners responsibilty © conduct fie drils and ‘other training exercises fo make people aware of fire alarm signals and instruct tem on the proper reaction to alarm sig- nels. + Inrare instances, the sounding of a waming device can cause temporary or permanent hearing loss. A iife safety system will not operate without any electrical power. If AC power falls, the system will operate from standby ‘attaries only for a specified time and only ifthe batteries have ‘been properly maintained anc replaced regularly. Equipment used in the systam may not be technically compat Tole withthe control panal. lis essential lo use only equipment lied for service with your control panel. ‘Telephone lines needed to transmit alarm signals fram & prem- ses toa central monitoring station may be out of service or tern- poral disabled. For added protection against telephone line {ilure, backup radio tranemission systems are recommendes. ‘The most common cause cf life safety aystem maifunction is. inadequate mainteriance. To keep the entielte safely system in ‘excellent working order, ongoing maintenance Is required por the ‘manufacturer's recommancations, and UL and NEPA stan- dards. Ata minimum, the requirements of NFPA 72 shall be fol- owed. Environments wih large amounts of dus, dir. oF high sir volocty require more frequent mainlonans. A raaintenenos: ‘agreement should be arrenged through the local mantacturer’s representative. Maintenance should be scheduled monthly or as required by National andor local fre codes and should be per- ormed by authorized professional ite safety system installers ‘only. Adequate writien recores of allinspections should be Kept Notifier SLC Wirtng Manua! — PIN SIDS: 2/10/2014 Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability: WARNING - Several different sources of power can be connected to the fire alarm control panel. Disconnect all ‘sources of power before servicing, Control unit and associ- fated equipment may be damaged by removing andor nsec ing cards, modules, orintorconnecting cables wile the units energized. Do nol attempt to Insal, service, or operate this Unit uct manuals are read and understood. CAUTION - System Re-acceptance Tast aftor Software Changes: To ensure propar system operation, this product ‘must be tested in accordance with NFPA 72 attar any pro- ‘gramming operation or change in sle-speciic software. Re ‘acceptance testing is required after any change, addillon or ‘deletion of system campanenis, or aller any medication, repair or adjuster to system hardware or wiring. Allcompo- ents, Groults, system operations, or software functions known to be affected by a change mus be 100% tested. In addition, to ensure that other operations are nol inadvertently affected, al least 10% of Piling dovicos that sre not directly affected by the change, up to @ maximum of 50 devices, must also be lesied and groper system oporaton verified. ‘This system meets NEPA requirements for operalion at 0-49" C182-120° F and at a relative humidlty 93% + 2% RH {none condensing) al 32°C +2°C (G0'F 3°F}, Howover, tie useful Ife ofthe system's standby batteries an¢ the elecironic com [ponents may be adversely affected by extreme temperature ranges and humicity. Therefore, Its recommended thet this system and is peripherals be installed in an environment with ‘a normal room temperature of 15-27° C/60-80"F, Verify that wire sizes are adequate for al intiting and indi- cating device loops. Most devices cannot tolerate more than a 410% LR. drop from the specified device voltage, Like all solid state electronic devices, this system may ‘operate erralically or can be damaged when subjected to ight- fing induced transients. Although no system is completely immune from figitning tansiants and intorforence, proser rounding will reduce susceptiblity, Overhead or outside aerial ‘wiring is rot recommended, due to an increasod euscoptiolity ‘tonearby lightning strikes. Consult with the Technical Ser- vies Department if any problems are anticipated or encoun tered Disconnect AC power and batteries prior to removing or inserting circult boards. Faure to do so can damage dicuils. Remove all electronic assemblies prior to any dling fing, reaming, or punching of the enclosure. When possible, make all cabie enities from the sides or rear. Before making rodif= ccafone, verity that they wll not interfere with battery, trans ormer, er printed ciruit board location Do not tighten screw terminals more than 9 inbs. Over. tightoning may éamage threads, resulting in reduoed terminal ‘contact pressure and diffouty with sorew terminal removal This system contains static-sensitive components. ‘Always ground yourself with a proper wrist strap before han- dling any circus so that static cnarges are removed from the body. Use static suppressive packaging to protect olectracic _assomblies removed from the unit Follow the instructions in the installation, oporating, and pro- ‘graraming manuals. These instructions must he followed tc ‘avoid damage te the contol panel and associated equipment. FACP operation and reliability depend upon proper instalation, FCC Warning WARNING: This equipment generates, uses, and can radiate radio frequency energy and int installed and ‘sed in accordance with the instruction manual may ‘cause intefaronce to radio communications. Ithas deen {ested anc found to comply wth the limits for class & ‘computing devices pursuant to Subpart B of Part 15 of FCC Rules, which is designed to provide reasonabie protection against such interference when devices are ‘operated in a cominercal environment. Operation of thls lequiprent in a rasidenlia area is Ikely to cause interfer- enea, in which case the user will be requlred ta oorrect the interference at his or her own expanse, ‘Canadian Requiromonts, This digital apparatus does not exceed the Class A limits {or radiation nolse emiesiane from sigtal apparatus set ‘out in the Feadio Interference Regulations of the Cana- dian Department of Communications. Le prasent apparell numerique meme! pas de Druts raci- ‘oolectriques depassant les limites appllcablas aux appa- roils numoriques oa classe A prescrites dans le Reglement sur le broullage radioelectique edicte parle ministere des Communications du Canada, HARSH™, NIS™, NOTHFIRENET™,eVance’, or SWIFT™ are leadarars; ns Acclimate® Pius, FAAST®, FlashScan®, NIONG, NOTIFIERS, ORYX® GW OUWorks®, UniNet, VeFIed, and VIEW a7 al fopsterod uaconorts of Honeywell Wetrallanel Re” Echelon 9 ogee) basen ans LonfVorks™ is adertark of Echelon Corporation. ARGNETB is rived Vstemaik of Daagont Corporat WicrosoR ana Windows® ae ‘egsieted easemarcr of tbe Mictooh Corporat, (€2014 by Honeywal Infernaional ne. AIleights reserved. Unauthorized us Notifier SLC Wiring Manual — PIN $1253:U1 2/102014 ofthis docuront i tity prohibited. Software Downloads tn order to supply the latest features and functionality in fire alarm and life-afety technology to our customers, we make fcquent upgrades to the embedded software in our products. To ensure that you are installing and programming the latest features, we strongly recommend that you download the most current version of software foreach product prior to commissioning any system. Contact Technial Support with any questions abont software and the appropriate version for a specific appfication Documentation Feedback Your feedback helps us keep our documentation up-to-date and accurate. H'you have any comments or suggestions about our onlire Help or printed manual, you ean emai us. Please include the following information: +*Product ame and version number (if applicable) +Printed manual or online Help “Topic Title (for online Help) *Page number (for printed manual) “Brief description of content you think should be improved or corrected + Your suggestion for how to correct/improve docamentation Sen! email messages to [email protected] Please note this email address is for documentation feedback only. Ifyou have any technical issues, please contact Technical Services, 4 Notifier SLO Wiring Marwal — P/N $1253:U1 2/402014 Table of Contents Cc Section 1: Introduction. 1.1; About This Manual. 1.2: UL 864 Compliance... 1.2.1: Products Subject to ALJ Approval. 1.3: Reference Documentation 7 1.4: SLC Overview. LS: Polling Protocols. 1.5.1: Available Protocols FlashScan... 16: Devices sso 1.6.1; Monitor/Zone Interface Module. 1.6.2: Control Modules 1.6.3 Isolator Modules... 1.6.4: Relay Modules... 1.6.5: Multiple Input/Output Module 1.6.6: Transponder nn 1.6.7: Plug-in Detector Bases. 1.6.8: Intelligent Detector. 1.5.9: Addressable Manual Pull Stations. 1.6.10: Wireless Interfere 1.6.11: ACPS-GL0 Addressable Charger/Power Supply. 1.6.12: ACPS-2406 Addressable Charger/Power Supple 1613, AMPS.24 Asa Powe Supp i 1.7: SLC Capacity. : 1.8: SLC Performance. 1.9: LED Operation : Section 2: Wiring Requirements. 2.1: Recommended SLC Wiring 2.2: Two-Wire SLC - Style 4 (Class B) 2.2.1: Measuring Loop Resistance... 2.2.2: Measuring Total Wiee Length . 2.3: Four-Wire SLC Style 6 & 7 (Class A). 2.3.1: Measuring Loop Resistance... 2.3.2: Measuring Total Wire Length 24: Control Panel Terminal Blocks... 2.4.1: NFS2-3030 and NFS-3030 with LOM-320, LEM-320...... 2.4.2: NFS2-640 with Loop Expander Modules, NFS-320 and NFS-3208S saosin 2.4.5: AFP-200 2.4.6: AFP-300/4] 2.4.7: AM2020/AFP L010 with LIB-200A or LIB-100 2.4.8: System $000 with AIM-200 Section 3: Shielded Wire Termination 3.1: Overview. 3.2: No Conduit 3.3: Full Conduit, 3.4: Partial Conduit Cc 3.5: Floating Shield.. Section 4: SLC Circuits without Isolators 4.1: Overview. Notifier SLC Waring Manuol — PIN 51253:U1 202014 5 ‘Table of Contents 4.2: NFPA Style 4 SLC wu 4.3: NFPA Style 6 SLC Section 5: SLC Circuits with Isolators. SAL: OVERVIEW rc 5.2: Fant Isolator Modules 5.4: Isolatar Detector Bases 5.3.1: How an Isolator Base Works... 3.4: NFPA Style 4 SLC Using Isolator Modules 5.5: NFPA Style 6 SLC Using Isolator Modates 5.6: NFPA Style 7 SLC Using an Isolating Devi Section 6: Monitor Modules... 6.1: Deseription...... se 6.1.1: Addressabie Monitor Module 6.12: Zone Interface Module .. 6.1.3; Miniature Monitor Module... 6.1.4: FMM-4-20 4-20mA Monitor Module 6.2: Setting au SLC Address for a Module. 6.3: NFPA Style B IDC Using Monitor Moduies 6.4: NEPA Sryle D IDC Using Monitor Modules 6.5: NFPA Style B IDC Using Zone Interface Modus... 6.6: NFPA Style D IDC Using Zone Interface Modules... Section 7: Control Modules 7.1; Deserta oven . 7.1.4: Setting an SLC Address 7.2: Wiring. a NAC with Addressable Control Modules 7.2.4: Wiring a Solenoid with the FOM-L-REL sass 7.3: Wiring a Style ¥ NAC (Two-Wite) with Addressable Control Modules ‘7.4: Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules 7.5: Connecting « Releasing Device te the Addressable Contzol Module. Section 8: Relay Module B.l: Description. 8.11: Setting an SLC Adres ss 8.2; Wiring the Aderessabie Relay Module (Farm-C Relay). Section 9: Multiple 'nputOutput Modules. 9.1: Description. 9.14: EDM 9.1.2: PDRM-1 se 9.2: Setting the SLC Address... 9.2.1: FDM-i 9.2.2: FDRM-1 9.3: Wiring the Dual Monitor Moshe... 9.4: Wiing the Addressable Duat Monitor/Dual Relay Module 9.5: NEPA Style B IDC Wiring Using Dual Monitor Modules Section 10: Intelligent Detectors, Intelligent Detector Bases, and Wireless Gateway. 10.1: Description, 10.1.1: Intelligent Detector Bases 10.1.2: Intelligent Detectors. 10.1.3: Wireless Gateway..... 10.2: Wiring a Detector Base. 10.3: Wiring an [solator Base... 10.4: Wiring a Relay Base, 10.5: Wiring a Sounder Bas ‘Table of Contents Programming Options Setting an SLC Address, Cc 10.7; Wiring the FWSG 10.7.1: SLC Connections. 10.8: Power Connections: Powered by the SLC. 10.8.1; Power Connections: External, Regulate ‘Section 11: Addressable Manual Pull Station 11.1: Description, ILL: Setting an SLC address. 11.2: Wiring a Manual Pull Station, Appendix A: Power Considerations... ‘A.L: Supplying Power to 24 VDC Detectors and NACS.. ‘42: Supervising 24 VDC Power. ee A.2.1; Using Type Codes with Built-In Power Supervision on the NFS2 3030, NFS.3030, NFS2-640, NES- 320 and NFS-320SYS “ 64 /A.2.2: Power Supervision Relay. A.2.3: Using the Addressable Control. ‘Module ‘Without ‘Relay... Style Y NAC Power Wiring Style Z NAC Power Wiring (Alternate). Appendix B: SLC Surge Suppression. Bl: Introdoction B.2: Installation.. B21: AFP-100 & AFP-200 DTK-2LVLP-F Connections sexsensn PLP-42N Connections. SLCP-30 Connection Cc B22: APP-300, AFP-400 DTK-2LVLP-F Connections. PLP-42N Connection: SLCP-30 Connections B.2.3: AM2020 & AFP1(10(LIB-200A or LIB-400) DTK-2LVLP-F Connections. . PLP-42N Connections... SLCP-30 Connections... : NFS2-3030, NFS-3030, NFS2-640, NFS-640, NFS-320, and NPS-3208YS DTK-2LVLP-F Connections. PLP-42N Conneettons B2. SLCP-30 Connections oe Appendix C: Terminal Conversion Charts for V- ype a and H-type Devices. CU PRMEL €2: FOM-1 and FZM-L . 3: FMMel C4: FIM-1 CS) FDM-} Appendix D: Intelligent Detector Base Layouts for Legacy Devices... D.l: Wiring a Detevtor Base. D2: Wiring an Isolatr Base. D3: Wiring a Relay Base Da: Wiring a Sounder Base Appendix E: Canadian Versions of SLC Devices C Index., Notfier SLC Wiring Maruol — PIN $i2834N 202014. 7 —— Section 1: Introduction 1.1 About This Manual ‘This document covers the installation and wiring of various Signaling Line Circuit (SLC) devices, ‘when used with the following Fire Alarm Control Panels' (FACPs): + ABP-100 + AFP-200 + APP-300/AFP-400 + AM2020/AFP1010 + NFS-3030FS2-3030 + NFS-640MNFS2-640 + NFS-320/NFS-3208YS + System 5000 with AIM-200 : + NCA and NCA2 This document also provides basic information that applics to Notifier SLC loops in general, such as the branch resistance measurements. NOTE: This manual does not call out Canadian and Export versions of panels. The information presented applies to all versions of the base panel. See Section 2.4, “Control Panel Terminal Blocks”, on page 23 for basic panel-end SLC connec fions. Additional information sbout each control pane! and the modules and detectors referenced in this document, and the part numbers for their manuals, can be found in the respective installation ‘manual as listed in Section 1.3, “Reference Documentation”. FlashScan modules are changing to a new format. Several models are now available in this new format and bave replaced the old format illustrations in this manual. While the old format is 110 longer manufactured for these models, Appendix C has been provided for those who need that wiring information: it contains terminal conversion charts between the old and new formats. In this appendix, the modules are referred to 2s “h-type” (the new format, which has horizoutal rotary 1, The AFC-600 has heen discontinued. Ta service existing insta!lations of this panel, refer co the original manuals shipped with the panel, Notifer SLC Wire Manwal — PIN 51253:01 2/1072014 UL 864 Compliance Induction dials) and “v-type” (he old formst, which has vertical rotary dials). This naming convention is a convenient way ta avoid confusion when referring to a particular model, as the name of the snadel does not indicate the format, Refer to Figure 1.1. CSS aN is : 3 Qs OP) dain nowernn "eyo" FoMt Logacy Vorsion Module OMA Newer Version Module : Figure 1.1 Example of Old and New Module Formats 1.2 UL 864 Compliance 1.2.1 Products Subject to AHJ Approval ‘This SLC Wiring Manual accompanies installation, operation, and programming manuals for various fire alarm control pancls (FACPs). The NFS2-3030, NF'S2-640, NFS-320, and NFS- 3208YS have been certified to comply with the requirements in the Standard for Control Units and ‘Accessories for Fire Alarm Systems, UL 864 9th Edition. ‘The following products have not received UL 864 9th Edition certification and may only be used in retrofit applications. Operation with products not tested for UL B64 9th Edition has not been evaluated and may not comply with NFPA 72 and/or the latest edition of UL 864. These applications will require the approval of the local Authority Having Jurisdiction (AHJ), AFP-100 AFP-200 AFP-300/AEP-400 ‘AIM-200 AM2020/AFPLO10 MX CMX-2 LIB-400 MMX-1 MMX-101 MMX-2 MPS-24AE MPS.24B/E MPS-400 NCA NES-3030 with CPU-3030 NFS-640 System 5000 XP Series (XPP-1, XPC-8, XPM-8 & XPR-8) + xPSC Noten SLC Wiring Mameal —PIN 512530 2/1022014 + XPS-M + ACPS-2406 + FCPS24E Continued on next page... Introduction Reference Documentation 1.3 Reference Documentation ‘The table below provides alist of documents eferenced in this manual, as well as documents for selected other compatible devices. The document series chart (DOC-NOT) provides the current document revision. A copy of this document is included in every shipment. See Appendix E, “Cnadian Versions of SLC Devices” for Canadian purt numbers. Compatibte Conventional Devioss (Non-eddressable) Document Number Device Compatbiity Document 15578 Fire Alarm Control Panel (FACP) and Mala Power Supply Intallation Document Nambor ‘AFP-100 Insituction Manual 1010 ‘AFP-200 jnsiructon Mantel 16511 ‘AFP-S0OIAFP-40 Installs, Operations, end Programming Manas ‘50258, 50250, 50250 ‘System 8000 with AINt-Z00" Refer to the AIN-200 Manual 548 ‘System 5000 Inatelation, Operations, and Programming Manuale 15585, 15581, 15864 ‘AN2G20/AFPTO(0 iretalaion Manual 715068 [NFS-640 Instafalion, Operations, and Programming Manuals 31982, 51994, 81998 NF5-300 FACE instastion, Operations, and Programming Manuals 61350, 51945, 51048 NES-320 Inialation, Operations, and Programming Wanuale 80745, 62747, 82746 NFS.2200 Canacian Applications Adgendem BETASCON NES-S2087S Inselston Manual 53717 'NFS2-640 notation, Operations, and Programming Wer uals ‘2741, BOTA, 62722 'NF52.2090 FACP Installation, Operations, and Programming Manuals 52544, S246, SDA \oiee Alarm System Mandal 5282 FreVoloe-25150 & FreVoloe 26/5028 Manual 52280 ‘OVC DiglalVoioe Commend Manual Ea DAAZIDAX manast 35705 ‘Ad-serias Audio Amplifier Manual 32526 Power Supplies, Auxiliary Power Supplies & Batiory Chargers Document Number ‘AGPS-2406 instalation Manual 51804 "AMPS: 247E Power Supply Manual 51907 FCPS-24 Field Chargov/Powor Supoty Manual 50059 ACPS-6103E instalation Maral 3018 FCRS-2438/FOPS 2488 Field ChargeriPowar Supply Bte77 System Components Decurment Number XP Tvanspondor Manual “5888 XPS Series Manual 50786 XP6-C InstaFation Document T5805 XP6.AIA Installation Document 155-1806 XPE-R lnetalation Document ‘66-1004 XP104M instalation Document 1561808 RATO02 Remete LED Annuncicior Feallation Document 156-0508 ‘SLC Loop Devicos Document Number SWIFT Smart Wiolass tegrated Technology instruction Manual 1$10086.000NF= Table 1.1 Reference Documentation (1 of 3) 10 Nouifer SEC Wiring Manual — P/N 51253: 2/10/2014 Reference Documentation Introduction ———— ee C pe = Sea ano = cree a mon = ET ee = puncte ee as wean ee a vr tae ene = oe = See a = Te = PAPT-851: See document for FSP-851, FSP-851T and FAPT-851 156-3524 ~ ana ee aw EE eas Te Pe a — nites = Cc FDRM-1 Dual Monior?Dual Relay Module 156-3669, ee = Soa oe = Sa ei nig = oe as ea = oe = —— a ae ee = a = a = ¢ HPX-T51 FARSA™ Installation Docament 156-1250 Table 1.1 Reference Documentation (2 of 3) ‘Noiifier SLC Wiring Manual — PIN 51253:U1 2/10/2014 ul Introduction SiC Overview (SO-X Isolator Module Installation Document “ 156-1380, TPKE Laser Desir rstnation Docurnent 7a (PATTI Taser Door raion Document i678 'NOG-12L% Pa Seton istalion Docuront 31088 'NBG-T2LXGP Spanien Engi Labeled Acdressable Manual Pll tation TET Engin 188-2787 (Soarsh) NBG-12LXP Potagsese abeed Adrseabie Nani Pal Saton isaTe SCM Ung Document TSioReS NF FSA S000) Iieliger] FAAST lstalaion and Walnenance nsttans 155 3007 Nate Reler othe Dave Gompatblty Document for coma convenfona davies Table 1.1 Reference Documentation (3 of 3) 1.4 SLC Overview Communication between the contol panel and intent addressable monitor and Zontrol devices takes place through a Signaling Line Circuit (SLC), which can be wired to meet the requirements of NFPA Style 4, Style 6, or Style 7. Atleast one socondary surge protector must be used with each SLC wiring pair whenever SLC witing runs outside the building, For detailed information refer to Appendix B, “SLC Surge Suppression”, on page 68. 1.5 Polling Protocols 1.5.1 Available Protocols FlashScan FlashScan® is a patented system (US Patent Number 5,539,389) that greatly enhances the speed of communication between analog intelligent devices. Communication isin a grouped fashion. [fone of the devices within the group has new information, the panel CPU stops the group poll aud con- centrates on single points. Not all panels are FlashScan® capable: see “Protocol Use” below. cLIP CLIP (Classic Loop Interface Protocol) polls devices in sequential order. Many bat not all Flash- Scan-eapabie devices can be set to rm in CLIP mode; see installation sheet shipped with the device. 1.5.2 Protocol Use LCM-320/LEM-320 loops on NFS2-640, NFS2-3030, NFS-3030 and NFS-640, and SLC loops on ‘NFS-320 can run in FlashScan mode or CLIP mode. AEP-100, AFP1OL0, AFP-200, AFP- 300/AFP-400, AM2020, and System 5000 with AIM-200 run in CLIP mode only. ‘Many FlashScan devices can be programmed to run in either CLIP or FlashScan mode, Use one of the following three options with SLC loaps: 1, Program all modules and detectors on an SLC as FlashScan, 2, Program all modules and detectors on an SLC as CLIP, ‘CAUTION: Do nat program more than 99 addresses on a CLIP-mode SLC loop, because this will slow the system down and compromise the response time of the panel to display of-normal events. Notifier SLC Wiring Manual —PIN $1253] 2/102014 “ Devices 3, Program all detectors as CLIP and all modules az FlashScan on an SLC. CAUTION: Do not program modules as CLIP and detectors as FlashScan on the same SLC. This combination. does not work, 1.6 Devices 1.6.1 1.6.2 NOTE: In this manual, UL-listed model numbers are used; the ULC-isted versions are specified in Section F, “Canadian Versions of SLC Devices’, on page 81. Monitor/Zone interface Module ‘These addressable modules allow the control panel (o monitor entire cireuits of conventional alarm initiating devices, such as manoal pull stations, smoke detectors, heat detectors, waterflow and supervisory devices. + FMM¢1 Monitor Module; FlashScan or CLIP mode, (An earlier module named MMX-1 was CLIP mode only.) FMM-101 Addressable Mini-Monitor Module; FlashScan or CLIP mode. (An earlier module named MMX-101 was CLIP mode only.) FMM-4-20 Four-to-Twenty Milli-Amp Monitor Module; FlashScan mode only. CLIP mode ‘operation will gencrate& trouble message atthe panel. This module is only compatible with the NFS2.3030, FZML-1 Zone Interface Module; FlashScan or CLIP mode. (As earlier module named MMX-2 ‘was CLIP mode only). XPS-M Supervises five Class-B addressable Initiating Device Circuits (IDC) which monitor normally open contact initiating devices. Supports FlashScan or CLIP inode. This module is capable of participating in degraded mode where supported by the FACP. (See the XPS Series Manual.) + XP6-MA Allows an intelligent alarm system to monitor six zones of conventional two-wire detectors; FlashSean or CLIP mode, + XP10-M Supervises ten Class-B addressable Initiating Device Circuits (IDC) which monitor ‘normally open contact initiating devices; FlashScan or CLIP mode. This module is capable of patticipating in degraded mode where supported by the FACP. + SLC-IM SLC Integration Module communicates between the VHS-1420-HES and a Fire Alarm Control Panel (FACP). It translates Modbus protocol to SILC protacol enabling events, ‘on the VESDAnet to be annunciated by an FACP, Control Modules ‘Through these addressable modules, the control panel ean selectively activate Notification Appliance Circuits (NAC). + FCM-1 Control Module; FlashScan or CLIP mode. (Earlier monitor modules named CMX-1 and CMX.2 were CLIP mode only.) + FCM-1-REL Control Module for releasing applications; FlashScan mode only. CLIP mode ‘operation will generate a trouble message at the panel, - + XPS-C Acts as a NAC or a speaker/telephone circuit (Class B only) or a Form-C relay. FlashScan capable, (See the XPS Series Manual.) + XP6-C Controls six NAC or speaker/telephone circuits; FlashScan or CLIP mode. Notifier SLC Wiring Manual — P/N 51253:U1 2/1072014 3 Ineroduetion, + RTIM-1 Firepbone Control Module; FlashSean-only device for use with Fire Fighters Telephone on NFS-320, NFS2-640, NFS-640, NF'S-3030, and NF'S2-3030. (See the Voice Alarm System Manual, tae DVC Manual, or the D4A2/DAX Manual.) 1.6.3 Isolator Modules Isolator Modules permit a short-circuited section of the SLC to be fault isolated from the remainder ‘of the SLC loop, allowing critical components to function in the event ofa circuit fault, Isolator ‘modules are required to meet the requirements of an NEPA Style 7 cirouit + ISO-X Loop Fault Isolator Module; FlashScan or CLIP mode. 1.6.4 Relay Modules ‘These addressable modules provides the control panel with a dry-contact output for activating & variety of auxiliary devices. + PRIA Relay Module with two Form-C relays; FlashScan or CLIP mode. + XP6-R Controls six independent Form-C relays; FlashScan or CLIP mode. 1.6.5 Multiple Input/Output Modules ‘These addressable modules offer dual input and/or dual ouput in a single device. + FDML-1 Dual Class B Monitor Module; FlashScan or CLIP mode. + FDRM-1 Dual Monitor/Dual Relay Module; finetions as two Class B monitor modules and ‘wo individual relay modules. FlashSean or CLIP mode. 1.6.6 Transponders + XPSeries (XPP-1, XPC-8, XPM-8 & XPR-8) Provides the FACP with en efficient mutiplex ‘subsystem capability. It communicates with the FACP and functions as a data-gethering panel for alarm Initiating Device Circuits and as 2 remote switching center for Notification Appliance Circuits (NAC), telephone circuits or relays. Not FlashSean capable. For information on connecting these transponders to the SLC, refer ta the XP Transponder Manual. 1.6.7 Plug-in Detector Bases Plug-in detector bases provide a connection between the SEC and a variety of intelligent detectors ‘which are snapped into place, Standard and isotator bases are used depending upon which NFPA SLC style is requited, Sounder and relay bases ace similar to standard bases, but have sound or relay capabilites, + Standard Base - Models B501 (4 inch standard small diameter base, commonly used in European installations) and B210LP (6 inch standard large diameter base, commonly used in US installations, replacement model for B710LP).. + HARSH™ Base - Model B710HD + Isolator Base - Model B224BI isolator base. + Sounder Base - Models B501BH (standard sounder hase), BSOIBH-2 (UL. 864 9th edition compliant standard sounder base), B501BHT(base with temporal sounder), BSO1BHT-2 (UL ‘864 9th edition compliant temporal sounder base), B200S (intelligent sounder base) B200SR (ntelligent sounder base, designed to be compatible with existing installations of the BS0|- Series sounder beses). + Relay Base - Model B224RB relay base Notifier SLC Wiring Mariwal PIN $1283:U1 2/10/2014 Devices Introduction 1.6.8 Intelligent Detectors FCO-851 IntelliQuad PLUS Intelligent Photoolectric Multi-Criteria Smoke/CO (Carbon Monoxide) detector, Plug-in type smoke sensor that is a photoelectric sensing chamber combined ‘with Carbon Monoxide (CO), thermal, and intta-red (IR) sensors 1o help reduce false alarms. For CO, the detectors electromechanical sensing cell creates a separate indication of for life safety CO detection. The FCO-851 adds thermal sensors that witl alarm at a fixed temperature of 135° F (57.2° C) and alarm sensitivity options with built-in alarm and pre-alarm time delay. FlashSean mode only. FSB-2008 Addressable, intelligent, single ended beam smoke detector with built-in sensitivity testing. The FSB-200 is the same except that it does not provide sensitivity testing, Both models support FlashScan and CLIP mode. FAPES51 (Acclimate® Phus™) Addressable, intelligent detector that combines a photoelectric sensing chamber and foed temperature heat detection (135°F / 57,2°C), FlashSean-and CLIP- ‘mode capable. (An earlier version named FAPT:751 was also FlashScan capable. The model named IPX-751 was discontinued as of December 1, 2001.) FSC-851 IntelliQuad Imelligent Photoelectric Multi-Criteria Smoke Sensor. Plug-in ype smoke sensor that is a photoelectric sensing chamber combined with Carbon Monoxide (CO), thermal, and infra-red (IR) sensors to help reduce false alarms. The F8C-851 adds thermal sensors that will alarm ata fixed temperature of 135° F (57.2° C) and alarm sensitivity options with built-in alarm ‘and pro-alarm time delay. Notifier panels offer different feature sets across different models, Certain features of the FSC-851 may not be available on some panels. The FSC-851 supports both FlashScan and CLIP modes. Read Status limitations may apply in CLIP mode, FSLESI Addressable, intelligent smoke detector that incorporates an ionization sensing chamber. Designed to provide open area protection. FlashScan- and CLIP-mode capable, (An earlier model named FSI-75I (discontinued) was also FlashScan- and CLIP-mode capable. Eatlier models named CPX-751 and CPX-551 were CLIP mode only’) FSP-851 Analog, addressable intelligent smoke detector that uses a photoelectric sensing chamber. Listed for use in ducts. Designed to provide open area protection, The FSP-851T adds thermal sensors that will alarm at a fixed temperature of 135° F (57.2°C). The FSP-8S1R is a low profile, intelligent photoelectric sensor that is remotc test capable. It's for use with DNR(W). Both madeis support FlashScan or CLIP mode. (Farlier versions named FSP-751 and FSP-751T [both discontinued] also supported FlashScan or CLIP mode, but were not listed for use in ducts. Earlier models named SDX-551, SDX-751, and SDX-551TH were CLIP mode only. FST-851 Intelligent thermistor sensing circuit for fast response. Designed to provide open area protection with 50 foot spacing capability, A ised temperature sensor with 135°F (57.2°C) fixed temperature alarm. The FST-8512 incorporates a thermal rate of rise of L5°F (8.3°C). The FST- 851H is a high temperature sensor with 190°F (87.8°C) fixed temperature alarm, Both models support FlashSean or CLIP mode. (Earlier yersions named FST-751 and FST-751R [both discontinued] also supported FlashScan or CLIP mode. Earlier models named FDX-551, and FDX- 551R were CLIP mode only.) FSD~751P Photoelectric Duct Detector. The FSD-751RP includes an alarm relay. All models support FlashSean or CLIP mode, FSD-751PL Low-flow Photocleciric Duct Detector, with extended speed range of 100-4000 FPM (0.5 mis to 20.3 mis). FSD-751RPL adds a relay. Both models support FlashScan or CLAP mode. DNR/W Innovairflex intelligent, non-relay, low-flow photoelectric duct detector housing. Low Flow refers tothe air velocity rating of 100 to 4,000 feet per minute (0.5 to 20.32 m/sec). Use with PSP-851R photoelectric smoke detector. Accommodaics the installation of the FRM-] addressable relay module, The DNRW is the same as the DNR with a watertight housing. FSH-751 (HARSH™) A special smoke detector that provides early warning smoke detection in hostile environments where traditional smoke detectors are not practical. Supports FlashScan ot CLIP mode. (Am carlier model named HPX-751 was CLIP mode only.) Notifier SLO Wiring Manual — PIN $1253:U1 21072014, Is Introduction SLC Capacity FSL-751 VIEW® An advanced intelligent photoelecteic detector that uses 2 laser diode, special optics, ad signal processing to obtain extremely high sensitivity. Supports FlashSean and CLIP rode; compatible with AFP-300/AFP-400, NFS-640, NFS2-640, NFS-320 and NFS-3030/NFS2- 3030 only. LPX-7S1L is compatible with AFP-200 and AM2020/AFP1010; CLIP mode only. (An earlier version named LPX-751 was CLIP mode only and compatible with AFP-300/AFP-400.) FSA-8000 Intelligent FAST aspiration smoke detector. Supports FlashScan and CLIP mode. (At earlier model was CLAP mode only). Compatible with NES-320, NFS-320SYS, NFS2-640, and ‘NFS2-3030 only. Addressed using PipelQW software. 1.6.9 Addressable Manual Pull Stations ‘The NBG-12LX is a dual-action pull station that, when activated, provides an addressable identifi «cation and its location to the control panel. An addressable monitor module is mounted inside the pull station to facilitate servicing and replacement. Supports FlashScan or CLIP mode. An earlier model named BGX-101L was CLIP mode only. “The NBG-I2LXSP is a Spanish/English labeled version; NBG-12LXP is 2 Portuguese-labeled version, Both support FlashScan or CLIP mode. . 1.6.10 Wireless Interface 1.6.11 FWSG: The Wireless Gateway acts esa bridge between a group of wireless fire devices, anda FlashScan SLC loop on NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030 (operating with fir \ware version 22.x or higher), The Gateway can be powered by the SLC loop or by an external 2AVDC UL listed power supply. Available wireless devices include a photo detector, an Aeclimatt detector, a fixed-temperature heat detector, a ratc-of-rise heat detector, and a monitor module. For details about wireless devices, system setup, and operation, see the SWIFT™ Smart Wireless Inte- ‘grated Techaology Insiruetion Manual a NOTE: Wireless option is not suitable for ULC applications. ACPS-610 Addressable Charger/Power Supply ‘The ACPS-610 is an addressable power supply and battery charger with 24 VDC outputs, It oper ates in FlashScan or CLIP mode and has built-in strobe synchronization. ts four outputs may be independently configured to drive Notification Appliance Circuits (NACs) or to provide auxiliary power. 1.6.12 ACPS-2406 Addressable Charger/Power Supply ‘The ACPS-2406 is an auxiliary power supply and battery charger. Each ofits four Notification Appliance Cirouits (NAC) i individually addressable, eliminating the need for control modules. 1 addition, cach cireuit can provide notification appliance synchronization. FlashScan and CLIP capable. This product has been discontinued. 1.6.13 AMPS-24 Addressable Power Supply “The AMPS.24 is a primary power supply and battery charger. Depending on its configuration, it ‘can occupy either one or four addresses on an SLC. FlashScan capable. 1.7 SLC Capacity “The protocol selected for an SLC loop determines the maximum number of devices that can beh dled by the loop (see Section 1.5, “Polling Proxocols”, on page 12), Within those limits, the indivi ‘al cootrol panel may have additional restrictions. See the specific installation manual for this information. Notifier SLC Wiring Manual — PIN SI2S3Ui 210720 SLC Performance Invvodnction | 1.8 SLC Performance SLC performance (Style 4, Style 6, or Style 7) depends on the configuration of the circuit and the components on the circuit (see Table 1.2). SLC operation mecting Style 7 requirements isolates, ceach addressable device on the SLC from faults that may occur on the SLC. Wiring style requirements are determined by national and local codes. Consult with the Authority Having Jurisdiction before wiring the SILC. The table below (derived from NFPA 72-2002) ists the trouble conditions that result when a fault exists on an SLC. Additional information is broken out in Section 2, “Wiring Requirements”, on page 18, end Section 3, “Shielded Wire Termination”, on page 26. ‘Type of Fault Siylod syle Sye7 ‘Single Open Trouble ‘Alarm, Wouble ‘Alarm, Trouble Single Ground ‘Alarm, Troublo (around) —_| Alarm, Trouble (ground) | Alarm, Trouble (ground) Short Trouble Trouble ‘Alam, Trouble ‘Short ahd Oper Trouble Trouble Trouble hort and ground Trouble ‘Trouble ‘Alarm, Touble Open and ground Trouble ‘Alarm, Trouble ‘Alarm, Trouble Communications 1688 | Trouble Trouble “Trouble * Trouble - The control panel wil incicale a Wouble conditon or this fypa of aul + Alarm The eantrl nanel must able fe proves an alarm input signal nthe presence ofthis type of au Table 1.2 SLC Circuit Configuration and Performance: Style 4, Style 6, Style 7 1.9 LED Operation ‘The table below list the LED operation on the various devices of an SLC in CLIP (Classi Loop Interface Protocol) Mode and FlashScan® Made. When switching ftom FlashScan® to CLIP. ‘mode, the loop circuit must be powered down for at least 30 seconds to reset devices to CLIP mode LED operation. CLIP Mode FlashScan® Mode ‘Control Panel Device Standby ‘Activated ‘Standby ‘Activated /asi2020 Monitor Module | Blinks RED | RED continuous NA Nim AFPIOTO ‘Control Module | Blinks GREEN [2 sec. GREEN, then OFF | NYA BIA Deteclor Blinks RED | RED continuous NA NA ‘AP-200/AFP-400 |Montor Module | Blinks RED [RED continuous NA NA Control Meduie | Blinks GREEN | GREEN continous NA NA Detector Binks RED | RED continvaus NA Na /AEP-109, Monitor Module [Stinks RED | RED continuous WA WA /AlM-200 ‘Control Mocule | eirke GREEN | Blaks GREEN NA NA Detector Birks RES [RED continuous NA NA /AFP-200 Monitor Madule [inks RED | RED continuous NA WA Control Module | Blinke GREEN. | OFF WA NA Detector Blinks RED | RED continuous WA NA 'NES-320,NFS2-640, | Monitor Nodule [Blinks RED | RED continuous ‘Birks GREEN [RED continuous NFB.840, Control Module |Blinks GREEN | GREEN continuous” | Binks GREEN | GREEN continuous NF52-3000, Detector Blinks RED | RED oontinucus Blinka GREEN | RED continuous NFS-3030, Table 1.3 LED Operations NOTE: In GLIP mode, the LPX751 and HPX-751 blink GREEN in slandby and stay RED when activated Notifier SLC Wiring Manual — PIN 51253101 2/10/2014 ” Section 2: Wii ing Requirements 2.1 Recommended SLC Wiring Depending on the panel, there are two recommended options for SLC wiring: + ‘Twisted, unshielded pair: NFS-320, NFS2-640, NFS-640, NFS2-3030, NFS-3030, LCM-32( LEM.320, LIB-200A, LIB 400, Maximum resistance $0 ohms per branch. See Table 2.1. Maximum capacitance: 0.5 pFarads per branch. + Twisted-shiclded pair: AFP-100, AFP-200, AFP-300/400, LIB-200, AIM-200. ‘Maximum resistance 40 ohms per branch. See Table 2.2. ‘Tomaximize distance on the SLC loop, use the recommended type of wire, Using other wiring types makes the SLC circuit more susceptible to electrical interference aad thas reduces its ‘maximums loop length FACH Recommended o ife Type and Limitations Max. Distance re Gaus [LIB-200A or LIS-400 on AMZOZ0/AFPTO10 (Seo Table 2.2 for LIB-200.) RECOMMENDED: Twisted unshielded pair, 121018 [12,500 F. (3,810 m) {2AWGIS.S1 mm ANG (3:31 mm? to 0.82 mm), 50 ohm max per |9500%.2.805.6m) | 14 AINGI2.08 mn? length of Siye 8 and 7 loops, SO ohme per branch | 6,000 t (1,828.8 mr) SBAWGI34 mm? ‘max or Sie 4 loops 3.700 (1,127.76 m) 118 AWGIO.82 mn (NOTE: Teicehinged pair or nwo’ unaided we ene recommended or use wi LIB-220R or LIB 40, NF5-640 and LEN-320 on NFS-G40 RECOMMENDED: Twictod-anshicldod pai, 12 to 18 [12,800 . (3,810 m) T2ANG (2.354 mm) AWG (3.31 ain Wo 6.82 mm} 50 ohms maximum |9,500 (2.858) | 14 AWG (208 mm) per lon of Sle 6 & 7 loons. 60 cbs perbranch |6.000% (1.8288m) | 18 AWG (1.31 mma) ‘avdmums fer Ste 4 loop. 3.7000. (1127-76 m}) | 1BAWG (0.82 men") Untwistod, unshielded wir, im conduit or outside of | 4,000 8 (804.8 m) 1210 78 AWG (3.31 mr 100.82 mm") conduit. Tote: Teatsa ldo pa ot rosamended for ue wh is pane. Noe: Maximum ea cepactance of SL. wing (bas betnaan sarducor anatem any concuct to gtr) sha nal exceed 0 ora NFS-20, NFS-920SYS, NFS2-640, LEW-320 on NFS2-640, LCM-320/LEM-320 on NFS-3030/MFS23030 RECOMMENDED! Twisted-unshelae parr, 12t018 | 12,500 8. (2,810 m) TZANG 8.31 mi) AWG (3.31 mn 100.82 mm), 50 ohms, maximum | 9.500 2. (2,696.6 m) 14 AWG 2.08 mre) per length of Sile 6 & 7 Joos. 80 ohms por branch | 6.000 . (1,828.8 m) AGAWG (1.31 ma) ‘maximum for Syle 4 lop. 3.700 R, (1,127.76) | 1B AWG (0.82 me) UUntwisted, unchieldet wire, in conduit or ouside of | 5,000 ft (1,524 m) 12 16 ANG (931 mn to 131 mmr) conduit 3.700 (1,127.76m) | 1B AWG (0.82 mmr) Twisted, shielded pair 5,000 (3,624 m) 12 fo 16 ANG Gt mnFto 1.31 mir) oe: B7OOHL (1,12778m) | ABAWG (0.82 mm) Shield mut bo fabio om ground . 1 Stolle enol bak teach dese Note: Maximum lata! capacitance ofall SLC wiing (both between conductors and from any conductor to ground) should not exc000 0.5 microfarads. ‘Table 2.1 Wiring Recommendations: NFS-320, NFS2-640, NFS-640, NFS2-3030, NFS-3030, LCM-32 LEM-320, LIB-200A, and LIB-400 8 Notifier SLC Wiring Manual — PIN 512531 2/10720 Recommended SLC Wiring ‘Wiring Requirements FAGP: [Rocommended ‘Wice Type anc Limitations Max, Distance Wire Gauge aFP=00 ¢ Twisted, shieiied pai, 40 ohrs | 10,0008. @.000m) ‘| 12.AWNG (3.31 mA) ‘maximum per tong of tye 6 ane 7 18.0008. (2400) +4 ANG (2.08 er?) Jcops. 40 chine gor branen maximum |4.875 (1450 16 AWG (1.31 ma?) for Sie 4 loops. 32258 (680 m) 18 AWG (0.2 mm) ‘Uiwisted, Uneheided 7,000 8 (00 m) 12:10 120 18 ANG G31 mio OBZ) ‘ote: Taisen ed par wie nl meinen rw wi spel | AFP 200 Twsled-shielded pat. 40 ohms 100008. 6.010) | RANG (1 mmm maximum perlengih cf Sio 6 ané 7 |e,0008. (2438.4 my | 14.A1UG (208 mn) teops. 40 ohms pertranen maximum [4a7oft (48s 9m) | 46AWNG (1.94 mm) ‘or Sve 4 seops 32287 (082.98m) | 18.AWvG (082 mF) ‘Uninisted,unshielced wire, in conduit ],000 804 8 mp io ANG (3 mm 19 082 mmr) . or ourige of conduit ‘Note: Tristed-unshietded pair wie Is not recommended for use with this panel Note: Maximum total capacitance of all SLC wing (both betwesn conductors and from any conductor to earth) should not exceed 0.5 mlorofarads. [AFP-300/AFP-400 “Twistec-ahielded pai, 1216 Bawa —]10,000 8 (3,048 m) AZ AWG (2.31 mr) 40 ohms, maximum por length of Siyo |8.000% (2438.4 m | 74 ANG (2.08 ma) and 7 loops. 40 ohms per branch [4875 R (1 485.9 m) 16 AWG (1.31 me) maximum for Siva 4 loops. 3.226 f (982.88 mm) 1B AWG (0.82 mer?) Untwistod, unshisided wire, in conduit. |,000 f (304.8 m) 1210 18 AWG (3.31 rm 10 0.82 mur) ‘er outside of concuit Note: Twisted: unsiieidad pair wire Ie ot recarnmended for use wit this panel. LIB-200 on AMZ020/AFP1010 (See Table 2.1 for LIB-200A or LIB-400,) ‘TWwisted-shiekded pair. Maximum loop] 10,000 f. (2,048 m) TRANG (3.31 mt) rosietance is 40 ohms. Maximum 8,000 (2.438.4m) | 4 AWG.(2.08 mr) length is 10,000 f. por channol (NEPA |4.875. (1,485.9) | 16 AVIG(1.31 mer ‘Sie 4 oF 10,000 f, total twisted pair | 3.226 t. (882.98 m) 1B AWG (0.82 ma) length (NEPA Style 6 and 7), Maximum Toop current is 200 mA {short creui or | te wiing connectad to tho LIB-200 leaves the building it must be in conduit. can not 400 mA (norma, Jexoeed 1000 m (109% yards), must not eos ay power lin, and must not be Inte vicinity of any high vollage. These outdoor wiring restrictions do not apply tothe LIB 200A or the 118-400. ‘Systor 6000 with AIM-200 “Twisted-shiekded pale Maximum loop | 10,000-% (3,048 m IZAWG (3.31 mre) i resistance: 40 ohms. 8.0008. (2,438.4m) | 14 AWG (2.08 mn) ‘Maximum loop volage: 27.6 v0C. |4.876A (1,485.9) | 1BAWG (1 34 mee) ‘Maximum loop current: 200 mA (short |3.225 f, (082.88 m} BAW (0.82 mae) trout) oF 100 mA (norma operation) Table 2.2 Wiring: AFP-100, AFP-200, AFP-300/400, LIB-200, AIM-200 Notifier SLC Wiring Manual — PIN $12S3:01 2/10/2014 19 rg Regsbene Tote SLC Sy (Coe 2.2 Two-Wire SLC - Style 4 (Class B) 2.2.1 Measuring Loop Resistance ‘THtapping of the SLC wiring is permitted for two-wire Style 4 configurations. The total DC resistance from the control panel to each branch end cannot exceed + 50. chms for NFS-320, NFS2-640, NFS-640, LCM-320, LEM-320, LIB-200A, and LIB-400. + 40 ohms for AFP-100, AFP-200, AFP-300/400, LIB-200, and AIM-200. Measure DC resistance as detailed and showm below: 1. With power removed, short the termination point of one branch at a time and measure the Dt resistance from the beginning of the SLC to the end of that particular branch, 2. Repeat this procedure forall remaining branches in the SLC. In Figure 2.1, Branches A, B, and C all begin at the SLC terminal, even though Branch B is ‘Trapped, Branch A Branch 8 Branet C on Shor Point sictenn| @ QO) Se Figure 2.1 Measuring DC Resistance of a Two-Wire SLC 2.2.2 Measuring Total Wire Length The total wire leugth of all combined branches of one SLC cannot exceed the limits set forth in each system’s instruction manual, Determine the total length in each SLC by summing all wire segments. In Figure 2.1 above, the picture on the right shows an SLC with 3 branches. Figure 2.2 below shows the seme SLC divided into segments. The total length ofthe SLC is determined by adding the lengths of Segment | + Segment 2+ Segment 3 + Segment 4 + Segment 5. No segme: should be summed twice, Faw Wire SLC Sole 6 & 7 (Class 4) Wiring Requirements tC a coment Five Four seonent ot Searent tie. - i OOOO] ac remeisen : Figure 2.2 Measuring the Total Wire Length of a Two-wire SLC 2.3 Four-Wire SLC Style 6 & 7 (Class A) 2.3.1 Measuring Loop Resistance The total DC resistance of the SLC pair exceed: + 50 ohms for NFS-320, NFS2-640, NFS.640, LCM-20, LEM-320, LIB.200A and LIB-400 + 40 obins for AFP-100, AFP-200, AFP-300/400, LIB-200, AIM-200. ‘Measure DC resistance as detailed and shown below: 1. Disconnect the SLC channel B (Out) and SLC channel A (Return) a the contol panel. 2. Short the SLC at the last device and measure the resistance al SLC Out. Record resistance and remove the short. Refer to Figure 2.3 Shore he SLC atthe first device and measure the resistance at SLC return, Record resistance and remove the short. Refer to Figure 23. a ‘The maximum DC resistance of the SLC is the higher of 2 and 3. Notifier SLC Wiring Manual — PIN 51253:U1 2102014 2 Wiring Requirements Four-Wire SLC Sigle 6 & 7 (Class + sTeP2 Last Device son Point sic out af STEPS Figure 2.3 Measuring DC Resistance of a Four-Wire SLC 2.3.2 Measuring Total Wire Length the control panel: ‘The total wire length in a four-wire SLC cannot exceed the limits set forth in each system's instruction manual. The figure belo identifies the output and return loops from SLC terminal on ‘so channel 6 [| SSL channel A {ourput loop) (return oop) SLC Tominal Bok BGO] DATE Figure 2.4 Measuring the Wire Length of a Four-Wire SLC 2 Notifier SLC Wiring Manual — PIN 5125311 2/10/20 Control Panel Terminal Blocks Wiring Requirements 2.4 Control Panel Terminal Blocks r 2.4.1 NFS2-3030 and NFS-3030 with LCM-320, LEM-320 ‘The NES-3030/NFS2-3030 supports up to five pairs of loop control and expander modules, provid- ing from one to ten SLC loops. Loops can be either CLIP mode or FlashScan mode. SLC loops connect to TB! on the LCM-320 or LEM-320, BAT EA 161 BPAY EA roy } SLC Loop Connections ‘SLC Loop Connections i ‘on Loop Control Modules, ‘on Loop Expancler Module Figure 2.5 NFS2-3030, NFS-3030 SLC Loop Connections and Wiring - 2.4.2 NFS2-640 with Loop Expander Modules, NFS-320 and NFS-320SYS ‘The NFS2-640 provide one SLC loop and supports a second using optional expander module LEM-320. The NFS-320 provides one SLC loop on the FACP’s main eireuit board, Terminal block designations are the sane on the eirouit board for both FACPs. Loops can be either CLIP mode or FlashSca mode. The SLC loop #1 connects to B13 on the control panel. SLC loop #2 connects to c ‘TBI on the LEM-320. ag BeAe A Tat ik arte cat : iigescacaim, atbeeeerntes i Figure 2.6 SLC Loop Connections and Wiring for NFS2-640, LEM-320, and NFS- 2.4.3 NFS-640 with Loop Expander Modules ‘The NFS-640 provides one SLC loop and supports a second using optional expander module LEM-320. Loops can be either CLIP mode or PlashScan mnode, SLC loop #1 connects 10 TB16 on the control panel; SLC loop #2 connects to TBH on the LEM-320. ser Bek ago a 4 = i ‘TE16 3 Suctaw ft comactons sk uaepGomactens a t oSeaseaneecte, —— SAidatbesSomitene Figure 2.7 SLC Loop Connections and Wiring for NFS-640 and LEM-320 Notifier SLC Wiring Manual — PIN S1253:111 2/1072014 2 Wiring Requitements Control Pane! Terminal Boe 2.4.4 AFP-100 ‘The AFP-100 supports one SLC loop; the loop is CLIP mode only. The SLC loop connects to TBE AB Be ke Bk se ew ‘SLC Loop Connections ‘on FACP's main elreult Board Figure 2.8 SLC Connections for AFP-100 2.4.5 AFP-200 ‘The AFP-200 supports one SLC loop; the loop is CLIP mode only. The SLC ioop connects to TBS eRERCEERE : SEER eth sia sc ae ‘SLC Loop Connections ‘on FACP%s main circuit board Figure 2.9 SLC Connections for AFP-200 2.4.6 AFP-300/AFP-400 ‘The AFP-300 supports one SLC oop; the AFP-400 supports two SLC loops. The loops are CLIP ‘mode only. SLC loops connect to TG on the AFP-300; SLC loops connect to TBS and TB6 on th AEP-400, T?aai SSEYET 4 al a q ql i Be ke Bh Rat Eth Ba AL ke at Gath Be Re Beh Eat t fh ah dh dn th an saan } {516 Loop Connections on AFP- Se Loop ComuctnsonnrPaeomin SSeS an Sicatboad Figure 2.10 SLC Connections for AFP-200/AFP-400 mM Notifier SLC Wiring Manual — P/N S125%U8 2/10/20) Control Panel Terasigal Blocks Wiring Requirements 2.4.7 AM2020/AFP1010 with LIB-200A or LIB-400 AM2020/AFP1010 supports up to ten SLC loops using LIB-200A (one SLC loop per board) and/or LIB-400 (one or ewe SLC loops per board). The loops are CLIP mode only. SLC leops connect to ‘TBI and TB2 on LIB-400, and TBI on LIB-200A. ao Pin SLC Loop Pot At Pin 3 SLC Loop Port A- Pin 5 SLC Loop Fon B+ Pin 7 SLC Loop Port B- Fin 8 Garth Ground Plat SLC Loop Port + Pint SLCLoop Fortar | Fin 3 SLC Loog Port A Pin SSLC Loos Pon & Pin SLCLoop Pon B+ 5 Pin 5SLC Loop Pon B+ Pin 7 SLC Loop Port B- Pin TSLG Loop Pot B- & Pin 8 Earth Ground =| Pin 8Earh Ground =| C uosaa vse Figure 2.11 SLC Connections for LIB-200A & LIB~400 se 20n erfato-0 004. NOTE: LIB-200 has been replaced by L 2.4.8 System 5000 with AIM-200 ‘System 5000 with AIM.200 supports one SLC loop; the loop is CLIP mode only. The SLC toop connects to PS on AIM-200. Bee ae a Figure 2.42 SLC Connections for AIM-200 NOTE: The AFC-600 has been discontinued; fo service existing Installations ofthis panel, reler to the original manuals shipped with the pane! Notifier SUC Wiring Mamual — PAN S1283:U11 2/10/2014 2s Section 3: Shielded Wire Termination 3.1 Overview This section shows the proper termination of the shield, if used. Shielding of the SLC is recommended for use with the AFP-100, AFP-200, AFP-300/400, LIB- 200, and AIM-200, Proper termination of the shield depends on the type of conduit used + Section 3.2, “No Conduit” + Section 3.3, “Full Conduit” (Canadian requirement) + Section 3.4, “Partial Conduit” Shielding of the SLC is not recommended for use with the NFS-320, NFS-3208YS, NFS2-640, ‘NFS-640, NFS2-3030, NFS-3030, LCM-320, LEM-320, LIB-200A or LIB-400. If wvisted~ shielded wire is used in one of these installations, use a floating shield to termivate she wire as ‘shown in Section 3.5, “Floating Shield”, on page 28. - ‘Use of good wiring practice consistent with loval electrical codes is expected, 3.2 No Conduit For use with the AFP-100, AFP-200, AFP-300/400, LIB-200, and AIM-200 only Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Fold the foi and drain wire back over the cable jacket. Slide the cable into the connector clamp and secure. Th dain wire should be connected to the connector screw. Do not allow the sbield drain wire or foil t enter the system cabinet. ‘Shiele Drain We Figure 3.1 Shield Termination - No Gonduit 26 Nodifier SLC Wiring Manual —PIN S12S%U01 2/10/26 ct Full Conduit Shielded Wice Termination 3.3 Full Conduit For use with the AFP-100, AFP-200, AFP-300/400, LIB-200, and AIM-200 only ‘Connect the metal conduit to the cabinet by using the proper connector. Feed the shielded wire ‘through the conduit, into the control box. The shield drain wire must be connected to the “refer cence” or “shield” terminal on the SLC terminal block, or connected to the negative side of the loop if there is no “reference” or “shield” terminal on the SLC terminal block. Do not let the shield drain ‘wire or the shield foil touch the system cabinet or be connected to earth ground at any point, Shiol¢ Drain Wee 2] cabinet Example a ight esate NY Shield an we comocton ‘an SLC ternal block with ‘eference* connection. Gongag “ype over } Cabinet Foil 7 : \ ‘Shield Drain Wee i Example alright uses = SN - g Shield ran wre conection : lean SLC terminal block Conduit 2 z without a “reference” or a + g “St Soom 2+ g Figure 3.2 Shield Termination ~ Full Conduit NOTE: For Styie 6 o Style 7 SLC wiring, connect one end of the shield to the reference/negative side of the respective channel, 3.4 Partial Conduit For use with the AFP-100, AFP.200, AFP-300/400, LIB-200, and AIM-200 only If the length of conduit from the control panel cabinet is less than 20 ft. (6.1 m), terminate the shield as shown. If using a metal box, you must use a metal conduit. ‘Connect the shielded wire to the junction box by using a proper connector. Scrape the paint on the cabinet to bare metal to provide a good electrical connection. Connect the metal conduit between the junction box and the cabinet by using the proper connectors. Feed the twisted-pair wire into the junction box, through the conduit, into the cabinet box. Within the junction box, connect the appropriate wires together using wire muts. Connect the shield drain ‘wire to the junction box, at the end of the conduit run, as shown below. Do not allow the shield drain wire to enter the system cabinet or the conduit, Fol (Shield Drain Wire f Cabinet cot | Figure 3.3 Shield Termination — Partial Conduit Notifier SLC Wiring Manual — PIN $1253:U1 2/10/2014 0 Shielded Wire Termination Floating Sh 3.5 Floating Shield ted-unshielded wire is recommended for the NFS-320, NFS-320SYS, NFS2-640, NFS-64( NFS2-3030, NFS-3030, LCM-320, LEM-320, LIB-200A and LIB-400,, If tisted-shielded pair wire is used in these installations, use a fo wire, The following precautions must be met: + Ifthe SLC is more than 3.000 ft. (914.4 m), divide the shield into floating segments of less ‘than 1,000 i. (304.8 m). The shield should be broken at each device + Todivide the shield wire into floating segments, cut shield even with jacket and tape as shows 1g shield to terminate the Figure 3.4 Floating the Shield NOTE: Using shielded wire in applications where it isnot recommended wil reduce the maxima SLC lengh. If siaided wie must be Used where not recommended, fag to Neat the ends wl reduce the maximum SLC length even further. 28 Notifir SLC Wiring Manual — PIN $1253:01 210/20 Section 4: SLC Circuits without Isolators o 4.1 Overview ‘This chapter concems itself with the wo styles of cteuts that do net require isolation devices NFPA 72.8tyle4 NFPA 72 Style 6 4.2 NFPA Style 4 SLC NFPA Style 4 requirements can be met by using the diagram below, ‘Tapping of the SLC wiring is allowed for Style 4 configuration. Two-wire Addressable Detector -Addresseble Module Hopped Circus Control Panel sic state amt Figure 4.1 Basic NFPA Style 4 SLC Notifier SLC Wiring Mana! — P/N $1253:U1 2/102014 29 ‘SLC Cirguits without Isolators NEPA Style 65; 4.3 NFPA Style 6 SLC [NEPA Style 6 requirements can be met by using the diagram below. Se myessent Figure 4.2 Basic NFPA Style 6 SLC NOTE: Tapping of tho SLC wiring is NOT allowed for Siyle 6 configuration. 30 Notifier SLC Wiring Manual — PIN 51253101 2/1020 Section 5: SLC Circuits with Isolators io ad 5.1 Overview ‘There are Wo isolator devices used to protec eval clement of the FlashScan-mode or CLIP- mocle SLC loop from faults on other SLC branches or segments. + Fault solator Module ISO-X + — Isolator Detector Base B224B1 A Fault Isolator Module on both sides of a device, or the combination of an Isolator and Isolator Module arc required to comply with NFPA Style 7 requirements, A CAUTION: ISOLATOR LIMITS If relay or sounder bases are not used, a maximum of 25 addressable devices can be connected between Isolator Modules and/or Bases. When relay or sounder bases are used, the maximum number of addressable devices that can be connected between Isolators is reduced to seven Isolator modutes will not function property when these limits are exceeded ‘When more than 100 tsolator Modules and/or Isolaor Bases are connected from the AFP-300 or AFP-400 to an SLC loop, the address capacty of the loop is roducod by two (2) addresses for every ‘isolator device in excess of 100. The address capacity ofthe loop is roduced by two (2) addresses for every isolator device in excess of 200 when the lsolaior Modules and/or Isolator bases are connected to the SLC loop from the NFS-320, NFS-320SYS, NFS2-640, NFS2-3030, NFS-3030, NFS-640, AFP-100, or AFP-200. 5.2 Fault Isolator Modules ¢ The 150-X module continuously monitors the circuit connected to terminals 3(~) and 4(+). Upon powerup, an integral relay is latched on. The module periodically pulses the coil of this relay. A short circuit on the SLC resets the relay. The module detects the short and disconnects the faulted SLC branch or segment by opening the positive side of the SLC (terminal 4). This isolates the faulted branch from the remainder ofthe loop preventing a communication problem with all other addressable devices on the remaining branches (labeled “Continuation of the SLC” in the figure below). During a fault condition, the control panel registers a trouble condition for each addressable device which is isolated on the SLC segment or branch. Once the fault is removed, the module automatically reapplies power to the SLC branch ot segment. Figure 5.1 shows a Style 4 example for wiring of an isolator Module. Continuation ofthe SLC SLC Isolated branch or i the SLC Figure 5.1 Wiring the 1SO-X Isolator Module Norifer SLC Wiring Manual — PAN $1283%01 2/102014 aL SLC Qireuits with (solatons solator Detector E 5.3 Isolator Detector Bases Isolator detector bases prevent an entire communications loop from being disabled when a sho circuit oceurs. This is accomplished by isolating that part of the loop containing the short from remainder of the circuit, These bases also automatically restore the entire loop when the cause ‘the short circuit is corrected, 'B224B1 is an intelligent isolator base used with FlashSean® detectors and most CLIP mode de tors, 5.3.1 How an Isolator Base Works Ifa short cieuit fault occurs at point “X”, devices A, B, C & detector 2 will ease to function: display a rouble wacning atthe contol panel. Devices D, F, F & detectors 1, 3, 4, and 5 wit remain normal as they are served by ‘SLC Return’, Ifa short circuit fault occurs at point “Y”, all devices will continue to function. Ifa short circuit fault occurs at point “2”, only detector 4 will cease to funetion. F Detectors NG voir Base } Nomtsolating Device |onow ath Figure 5.2 Isolator Base Circuit: Sample Style 6 Wiring NOTE: Forinforration on wring an isoiator base, referto Figure 10.3, Wing @ B224B! soll avo Mounting Plate’ on page 56. 2 Notifter SLC Wiring Manual — P/N 53283101 2/1 NFPA Style 4 SEC Uing iotator Modules SLC Circuits with Isolators 5.4 NFPA Style 4 SLC Using Isolator Modules - {A vation ofa Style 4 operation using isolator modules to protet each branch ofthe SLC. Refer es to Figure 5.1 on page 31 for [SO-X wiring and to Section 5, “SLC Circuits with Isolators” for Tmiatons. Isolates feolated Branch ‘Tworvre Addressable Detector Isolates Md Isolated Branch -Addressatle Pul Staton Isolator Modile Ivolated Branch le fox Convo! Pane! sic, Siesta Figure 5.3 NFPA Style 4 SLC Using ISO-X Modules Noiifier SLC Wiring Mermeal — PIN 51253:U1 2/10/2014 3 SLC Cigguits with Isolators NFPA Style 6 SLC Using lolatar Moch 5.5 NFPA Style 6 SLC Using Isolator Modules A variation of Style 6 operation using isolator modules to protect a section ofthe SLC. By flanki ‘each group of devices with ISO-X fault isolator modules each group is protected from faults tha may oceur in the other groups, For example, a fault in Seetion B will not aifect Sections A&C. The isolator modules on either side of Section B will open the loop. Section A will still operate {from power on the SLC Out side and Section C will operate from the SLC Retum side, + Acombination of isolator modules and isolator bases may be used. + Tapping is NOT allowed within the Style 6 configuration, + Isolator modules shall be within 20 fi (6.1 m) of device and the wire must be enclosed in me conduit ‘Aldona isolator made required whon fst device in the ——_ ys at —— 1 section Is more than 20 fest fom the contol pane, sic (*) Solano A (+) Solenoid B/A (#) Solonaié BIA () i FOM1-REL FOM-LREL, (Wiring Connections Rear View - Jumper Locaton Figure 7.3 FCM-1-REL Wiring Locations and Rear View - Jumper Location SSS NOTE! ‘The FCNM1-REL will not function on an SLC loop thats programmed for CLIP mad, a Notifier SLC Wiring Manval —PAN 51285101 2/1 Wiring a Sie Y NAC Two-Wire) with Addressable Control Modiles Control Modules 7.3 Wiring a Styie Y NAC (Two-Wire) with Addressable Control Modules tT Figure 7.4 depicts a supervised and power-limited NFPA Style Y (Class B) Notification Appliance Circuit (NAC) using the FCM-1 module. Inthe sample wiring drawing below, polarized alarm ‘otification appliances are shown connected to the module in a two-wire configuration, 1, See “Power Considerations” on page 63 for information oa monitoring 24 VDC power. 2, Each module can contro! 2 amps of resistive load (on electronic devices) ot 1 amp of inductive oad (on mechanical bells and horns). 3. A power supervision relay is required only on the last module of the power run unless: * using the uo-relay alternative wire method; see Figure A.2, “Alternate: 2-Address Method of Supervising a 24 VDC Circuit”. + using a panel with FlashScan type [Ds that provide builtin power supervision. Refer to the Panel installation manual fora list of type codes.) 4, Do not'Ftap or branch » Style ¥ circuit, 5. ‘Temiinate the cironit across the last device using a UL-listed End-of-Line Resistor 47K, ‘Wa-watt, SSD P/N A2143-00 (ELR-47K in Canada). 6. Donotloop wiring under the sere terminals of any notification appliance. To maintain supervision, break the wire run at each device. 7. Refer to Device Compatibility Document for compatible notification appliances and relays. ‘A power supervision sic felayis required only on tho. 24VDC_ + — last mecule of tho power run Nonresettsbo| unless a iypo ID wan buitin power superisionarihe alomative We method Is used, + ALR ami van AVC Notitaton ‘Appliances semeratint ‘Modu polarities ste show in alarm condition Figure 7.4 NFPA Style Y Notification Appliance Circuit with FCM-41 Notfler SLC Wiring Manual — PIN 51253:U1 2/10/2014 45 Contrat Modules Wiring a Style Z NAC (Fourie) with Addressable Control Mi 7.4 Wiring a Style Z NAC (Four-Wire) with Addressable Control Modules Figure 7.5 depicts a supervised and power-limited NFPA Style Z (Class A) Notification Appl Circuit (NAC) using the FCM-1 module. In the sample wiring drawing below, polarized alare ofification appliances are shown connected to the module in « four-wire configuration. 1, See “Power Considerations” on page 63 for information on supervising 24 VDC power. 2. Each module can control 2 amps of resistive Toad (on electronic devices) or Lamp of indy load (on mechanical bells and horns). A power supervision relay is required only on the last module of the power run unless: + using the no-relay altemative wire method; sce Figure A.2, “Alternate: 2-Address Met of Supervising a 24 VDC Circuit". + using a panel with FlashScan type IDs that provide built-in power supervision. Refer t panel installation mamual for a list of type codes.) |. Do not T-Tap or branch a Style Z cirewt. 5. Do not loop wiring uncle the serew terminals of any notification appliaice, To maintain supervision, break the wire run at each device. 6. Referto the Device Compatibility Document for compatible notification appliances and r. 24 VOC Nonresettabie power + — sic +1 NOTE: A power super’ relay required onfy or Inet module of the pone uniess a pe ID with Dt supervision arte aterm ‘to math fs usod, Module polaies are shown in Alarm Figure 7.5 NFPA Style Z Notification Appliance Circuit with FCM-1 46 Notifier SLC Wiring Manual — P/N $1253:U1 2/1 Cormecting a Refeasing Device tothe Addressable Control Module Control Modules 7.5 Connecting a Releasing Device to ‘the Addressable t Control Module ‘The FCM-1-REL module can contol | A of current. Make sure to keep total system current within the limits of the power supply, Power forthe module must come from the FACP’s main power sup- ply or any UL 864-listed 24 VDC reguleted, power limited power supply for Fire Protective Sig- naling. For more information, refer to the Device Compatibility Document. Figure 7.6 shows Class B wiring of the FCM-1-REL. FoMA-REL : Non-tesettae 24.VDC power A z sie() Module potatos ere shown in am : condlion”Allwing show's sL0(*) | supervised ane powered | When using the Gompatbie UL-sted FCM REL for 24 VDC releasing device Chess 8 ‘One (7 doves maximum. applications, fomeve jumper Jt. Figure 7.6 NFPA Class B Wiring of the FCM-1-REL, Notifier SLC Wiring Maral — PON 51253:1!1 20/2014 fy ‘Control Modules Connecting a Releasing Device tothe Adivessable Contrat Moc, ‘Figure 77 shows Class A wiring of the FOM-1-REL- FOMA-REL, [Non-resetable 24-VDC power igolated,rogulaisd, power Iimed per NEPA, listed for fro ‘protection with battery backup. ‘Module polars are showm in aor Condon. Abwaring shown I Supervead and powered, ‘Compatible UListes 24'VDC releasing devi. ‘Ope (1) davies maximum, Figure 7.7 NFPA Class A Wiring of the FOM-1-REL Critical Requirements {When connecting 2 releasing device to the FCM-1-REL module, note the following: LL See “Power Considerations” on page 63 for information on monitoring 24 VDC power 2. Do not Tap or branch a Style ¥ oF Style Z circuit. 3. Only one (1)24V solenoid or two (2) 12¥ solenoids in series ena be connected Ne FC REL. 44, Donot loop wiring undor the sew terminals, Break the wire run to provide supervision ‘connections. ‘5. All applications using the FCM-1-REL are power-limited «Program the releasing crit for Type Code REL CK ULC of RELEASE KT. + Circuits are supervised against opens and shorts, 6. Refer to your FACP's programming manual fr instructions on seting the Soak Time, B ‘The FCM 1-RET. module must be programmed with the correct releasing type code ISK your FACP's programming manual. Nouifier SLC Wirtng Manual — PIN S1253:U1 T Section 8: Relay Module 8.1 Description ‘The FRMC-1 isan addressable module that provides two isolated sets of Form-C relay contacts. Ratings forthe dry relay contacts on a Form-C module are: + Resistive 2 amps @ 30 VDC (e.g. Blectronic devices and strobes.) + Inductive ~ 1 amp @ 30 VDC (0.6pF) (e-g. Mechanical bells and hors.) + Pilot Duty ~0.5 amp @ 125 VAC (0.35pF) (e.g. Using a smaller relay to trip another relay.) For more information on the module specifications refer 1o the installation instructions provided with this device. For information on transponders, refer to the specific transponder manval 8.1.1 Setting an SLC Address Each relay module is factory preset with an address of “00.” To set on SLC address refer to~ Section 6.2, “Setting an SLC Address for a Module”, on page 37. 8.2 Wiring the Addressable Relay Module (Form-C Relay) ‘The figure below shows the FRM-1 module wired to the Control Panel. suc ho s.oenetlinnt Figure 8.1 FRM-1 Relay Module Wiring Connections. Notifier SLC Wiring Mannal — PIN S1253-U1 2/10/2014 “9 Section 9: Multiple Input/Output Modules 9.1 Description 9.1.1 FDM-1 ‘The FDM-1 is similar to the FMM-1, except intended for use in intelligent two-wire syste viding two independent Style B (Class B) IDCs at two separate, consecutive addresses. Adc can start using either an even or odd number. 9.1.2 FDRM-1 ‘The FDRM-I is an addressable module that functions as two individual relay control modul isolated sets of Form-C relay contacts) and two Class B monitor modules. Ratings for the dry relay contacts on a Form-C module are: Lendbescnotion | Appicaion | Mauimum 7 Curt Tricia Pea) | Wowcaand | aww [Zn Fos NenGoaed [save | 38h Tein Sade wovea | 20a Trcbe (UR= n=) | Worcated | s0vbe | —Ba8a Tico PF =035) | Worceced | YO7VAG | 7A Rei nen Coded | ~W5vOs™ | @8A inico @F=O7H) | Worcasos | YaB VAC | OBA ince (PF=036) | Norceced | ~vasvmo | 03 For more information on the module specifications refer to the installation instructions prov with this device. 9.2 Setting the SLC Address Each multiple inputfourput module is factory preset with an address of “00”. To set an SLC a use a screwdriver to adjust the rotary switches on the module to the desired address. 9.2.1 FDM-1 Each FDM-1 module can use up to two (2) addresses, The base address selected via the rot address switches will be assigned to the first monitored input. The next consecutive address assigned to the second monitored input 9.2.2 FDRM-1 Bach FDRM-] module can use up to four (4) addresses, ‘The base address selected via the n ‘address switches will be assigned to relay output #1 from 00 to 156. The module will autor, assign the next three addresses as appropriate to monitored input #1, relay output #2, and mo input #2. o Notifier SLC Wiring Manual — BIN 51253101 2 i Hiring the Dual Monijor Module ‘Multiple Input/Output Modules 9.3 Wiring the Dual Monitor Module Tt ‘The figure below shows the FDM-1 wired to the control panel. ‘Argos used fo record the devi i ‘address and SLC number. ! Figure 9.1. FDM-1 Dual Monitor Module Fagot | 9.4 Wiring the Addressable Dual Monitor/Dual Relay Module ‘The figure below shows the FDRM-1 module wired to the control panel | sic Nesmaly Closed fos ‘Commen Figure 9.2 FDRM-1 Multiple Input/Output Module Wiring Connections Notifier SLC Wiring Manual — PIN $125%:01 2102014 31 ‘Muthiple Ingu/Output Modules [NEPA Style B IDC Wiring Using Dual Monitor Me 9.5 NFPA Style B IDC Wiring Using Dual Monitor Modules ‘Connect the FlashScan or CLIP SLC wiring to the FDM-1 module terminals | (-) and 2 (+), Use the rotary switches on the module to setit tothe required SLC address. Each dual module two addresses on the SLC. Circuit ‘L’ corresponds tothe address set on rotary switches, Cireui ‘will automatically respond at the next higher adess. The Circuit L “base address” is always even number; the lowest possible address is 02. The Circuit H “base + 1” address is always oc Use caution to avoid duplicate addressing of modules on the system. Each IDC (H & L) is power limited to 230 microamps @ 24 VDC. Figure 9.3 shows typical wiring for a supervised and power-limited NFPA Style B (Class B) I ing Device Citeuit using the FDM-1 dual monitor. “Module installation notes: L. The Initiating Device Circuit (IDC) is supervised and current-limited to 210 microamps 24 VDC (nominal) 2. ‘The IDC provides the following services (do not mix): + Fire alarm service + Automatic and manual waterflow elarm service with normally open contact devices + Sprinkler supervisory service with normally opea contact devices + Security service Refer to the Device Compatibility Document for compatible smoke detectors. (OC Circuit H) ase Address DC Crovit Ly Figure 9.3 Typical Style B IDC Wiring with FDM-1 2 ‘Nouifler SLC Wiring Manual — PIN 51253401 211 reerer pent Section 10: Intelligent Detectors, Intelligent Detector t Bases, and Wireless Gateway 10.1 Description 10.1.1 Intelligent Detector Bases ‘The B501 and B210LP Detector Bases, the B224BI Isolator Base, the B224RB plug-in Relay Detector Base, and the BS01BH/BS01BH-2, B501BH1/B501BHT-2, B200S and B200SR Sounder Base provide the connection between the SLC and a variety of intelligent detectors. Use the B7IDHD Detector Base with all HARSH™ detectors, See Sections 10,2 ~ 10.5 For more information refer to the Installation Instructions documents provided with these devices. 10.1.2 Intelligent Detectors . ‘The FSA-8000 Inteltigent FAAST aspiration smoke detector may be used to provide early warning fire pretection using aspiration sensing technology. Ths detector i ised with UL for usc withthe [NFS-320, NFS-320SYS, NFS2-640, and NF'S2-3030, CLIP and FlashScan mode are supported. (An earlier version supported CLIP only) See Section 10.6 10.1.3 Wireless Gateway ey ‘The FWSG Wireless Gateway acts as a bridge between a group of wireless fire devices, and a FlashScau SLC loop on NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030 (version 22 and above). The gateway can be powered by the SLC loop or by an external 24 VDC, ULslisted power supply. See Seetion 10.7 NOTE: When using a Wireless Gatoway on the SLC loop, the panel cannot have ANY modules {wired or wireless) inthe address range from 140 to 189. FFor details about the wireless network itself, see the SWIFT™'Smart Wireless Imegrated Technol- ogy Instruction Manual. Notifier SLC Wiring Manual — PIN 512531 21072014 3 Intelligent Detectors, intelligent Detector Bases, and Wireless Gateway Wirkng a Deeect 10.2 Wiring a Detector Base © Figure 10.1 shows typical wiring of a standard detector base (BS01 is shown) connected to at An optionsl RA1OOZ Remote LED Annunciator is shown connected to the base. Fram Control Panel SLC Figure 10.1 Wiring a B210LP or 8501 Detector Base NOTE: The BZIOLP base wring a denteal to the BEOT. 860 I the Nangeless model 4 Notifier SLC Wiring Manual — PIN S1253:UL Wiring a Detector Base, Invlligent Detectors, Intelligent Detector Bases, and Wireless Gateway base, : | Figure 10.2 shows typical wiring of the B710HD detector base (for use with a HARSH™ detector) i ‘connected to an SLC. An optional KA1O0Z Remote LED Annunciator is shown connected to the Tonaxt * sevios on suc For connaction of cable shill Figure 10.2 Wiring of the B710HD Detector Base NOTE: Use a spade lug to wire the Remote LED Annunciator (-) to Terminal 2 -). Ielligent Detectors, Intelligent Detector Bases, and Wireless Gateway Wiring on lsok 10.3 Wiring an Isolator Base ‘The Isolator base will isolate its detector from short circuits that occur on the SLC connect! sninals 3 and 2 It will not isolate its installed detector from shor ciruits that oecur on the connected at terminals | and 2. In Style 7 applications, the loss ofa single detector daring sireuit s not acceptable, and an isolator madule must be installed as shown in the igure bx sicout Note: To “ipa on a hee Bozse ‘ouring tha eee S ‘avowed fr turtaton furposes ony 8, oO ° eG s Sh . sich conduit i so Xtras — ‘ © ols S : Figure 10.3 Wiring a B224B! Isolator Base Mounting Plate 10.4 Wiring a Relay Base Figure 10.4 shows typical wiring of the B224RB plug-in relay detector base connected to Noto: The "grt" pattern on the redesigned 82248 rountra plate has been removed for justralion purposes only. Normally Closed Common Nerrally Open Figure 10.4 Wiring of a B224RB Relay Base Mounting Plate Notifier SLC Waring Manual — PIN $1253:U1 Woring a Sounder Base Intelligent Detectors, Intelligent Detector Bases, and Wireless Gateway 10.5 Wiring a Sounder Base Figure 10.5 shows typical wiring of the B2008 Sounder Base. Note: The "arid" pata on the 8200S has bocn removed for Iuetraton purposes onl. f Optionar amete LED Arnunciator RAtoozi4002 I i | 4 se Figure 10.5 Wiring of the B200S Sounder Base Figure 10.6 shows typical wiring of the B200SR Sounder Base. toe: Teg! tenon te Pitta becom theranon poses __. Optional Sounder heed i : eae i Figure 19.6 Wiring of the B200SR Sounder Base For more detailed wiring on sounder bases, refer to the device's installation instructions. [oiler SLC Wiring Monuat — PAN $128%:U1 2102014 31 Intelligent Detectors, Intelligent Detector Bases, and Wireloss Gateway Wiring and Programming the F ing and Programming the FSA-8000 ‘The FSA-8000 Intelligent FAST aspiration smoke detector may be used to provide early ¥ fire protection using aspiration sensing technology. This detector is listed with UL for use NES-320, NFS-320SYS, NFS2-640, and NFS2-3030. Figure 10.7 shows how to wire the FSA-8000 detector on an SLC Joop. For additional ins information for the FSA-8000, refer the Installation and Maintenance Instruction documer™ smumber 156-3903, — To Newt SLC Dovioa - sic rom FAGP or Previous Device - Connection -| “ToNext SLC Device = From ACP ex Previous Doves * — To Next Device ¢ 24V extemal From Power Supoly or Previous Devieo + Power ‘To Next Device - From Power Supply or Previous Device - Figure 10.7 FSA-8000(A) Connection to the FACP Installation Considerations “The following installation fuctors should be taken into consideration when installing the F detector: + CLIP Loop limitations: = Detectors per CLIP loop: Up to 75 total = Modules per loop: Up to 45 total. + Power supply: FACP AUX or use a power supply ULC listed for fire protective sign with regulated outputs, Programming Options ‘The following programming options should be set when programming the NFS-320, NES [NES2.640, ancl NFS2-3030. with the FSA-8000. ‘+ FlashiSean oop Protocol = Type ID: Acclimmate ~ Flashcan Type ID: FAAST + CLIP Loop Protocol. ~ Type ID: Aspiration — FlashSean Type ID: Nove Setting an SLC Address "The SLC loop address for this product is set using PipelQ®; for information on this pros to the FAAST Comprehensive Instruction Manuai on hitp: ISO Notifier SLC Wiring Manual — PN 512530 Wirtng the FSG Intelligent Detectors, Intelligent Detector Bases, and Wireless Gateway 10.7 Wiring the FWSG id NOTE! The FWSG os par fo wise newark hes ben aid fr sonmlange wi the Federal Conrunetion Conmisoon £60] royerent ate Unies Stee Sovomnart This produto at ben vous fr tos out he USA Use of es sytomoute he USAe bjt ecto on tus fo wich hs pred my net confor tine sl osponly Gitte wore dtomin ths prt may bogey used ute BUS 10.7.1 SLC Connections ‘The Wireless Gateway acts as a bridge between a group of wireless fire devices and a FlashScan ‘SLC loop on NFS-320, NFS-320SYS, NFS2-640, and NFS2-3030. It is powered by the SLC loop or by an extemal 24 VDC UL-listed power supply, Available wireless devices include a photo detector, a photo/heat detector, a fixed temperature heat detector, a rate-of rise heat detector, and @ ‘monitor module, For details about witeless devices, system sctup, and operation, see the SWIFT™ ‘Smart Wireless Integrated Technology Instruction Manual. AT SLC OUTWiIne AB SLC INMOUT+ ‘AS SLC- (Common) £ Aé SLC Powar Select 2 ‘83 Powior #24VDC ‘82 Power Ground At SLC Power. Select 4 Figure 10.8 FWSG Mounting Plats Terminal Layout Notifter SLC Wiring Manual PIN S1253:U1 2/1072014 89 Inelligent Docostors, Intelligent Detector Bases, and Wireless Garewsy Power Connections: Powered 10.8 Power Connections: Powered by the SLC ‘The FWSG provides isolation of short circuits on the SLC in Class A (Style 6) installation connections are power-limited by the panel. An interruption in the SLC that causes a less ¢ at the FWSG for more than 100ms may result in a trouble condition and loss of fire protec vided by the wireless devices for approximately 15 minutes. Use of aa external +24V powe (not SLC power) is recommended for installations that require fire protoction in the preset short circuits, including Class A applications and applications that use isolator modules Figure 10.9 shows typical wiring of a Wireless Network Gateway connected to an SLC wi power is supplied by the SLC loop. scout teen on 8) + ws “or SLC back to FACP (Class A) - ——# a8 i] } ‘s sc fom FAcPinie + fg 5 sage S S Figure 10.9 FWSG Wiring Diagram, Powered by SLC Loop 60 Notifier SLC Wiring Manual — PIN 51253:01 Power Connections: Powered by she SLC Intelligent Detector, intelligent Detector Bases, and Wireless Gateway 10.8.1 Power Connections: External, Regulated +24 VDC Power € Source ‘The FWSG provides isolation of short circuits of the SLC in Class A (Style 6) installations. SLC connections are power-limited by the panel. +24VDC must be power-limited by the source, Figure 10.10 shows typical wiring of a Wireless Network Gateway connected to an SLC when power i supplied by an exeraah, regulated 26 VDC power mpply, UL-listed fet Fe proactive serve, ° { 2 2, sxcgute roan yo ‘or SLC back fo FACP (Class A} ~ 2} AS “s : SLC tom FaCPHoven + ee Era o24VD0 Power rs op Figure 0.10 FWSG Wiring Diagram, Powered by External 24 VDC Powor Source NOTE: Terminal AS is referenced more than once inthe above connections. tis recommended {0 uso wire of he same gauge forall connections fo. AB and usa the samo wire gauge there are multiple connections tothe sam terminal Notifier SLC Wiring Manual —PIN 51253:U1 2/10/2014 Section 11: Addressable Manual Pull Station 41.1 Description ‘The NBG-12LXis an addressable manual pull station with a key-lock reset feature, The ? “led version; NBG-12LXP is a Portuguese-labeled vers 12LXSP is a Spanish/English label support FleshSean or CLIP mode. Wiring is the same as forthe NBG-12LX Mansal Pull provided with the @ ‘For more information refer to the Installation Instructions document 41.1.1 Setting an SLC address ‘Each unit is factory preset with an address of “00,” To set an SLC address refer to “Seitit ‘Address for ¢ Module” on page 37, 41.2 Wiring a Manual Pull Station + “Typical witng forthe NBG-12LX Manual Pull tation to an SLC is shown below, Figure 11.1. Wiring the NBG-12LX Pull Station to an SLC Notifier SLC Wiring Manus! —PIN S12 t Appendix A: Power Considerations A.1 Supplying Power to 24 VDC Detectors and NACs Resistance and Size ‘To determine the maximum allowable resistance that can be tolerated in supplying power to 24 VDC four-wire devices and NACs, use the calculations below. These simplified equations assume that the devices are atthe end of a long wire run. With the computed resistance and using the manufacturers specifications for the desired wire, select the proper enuge wire for the power nin, For Fout-Wire Detectors: (me= Von) NG) + WE) + ED For NACs: ‘as ~ Vou R, Oo » Ox) ‘Where: Ryyax = maximum resistance of the 24 VDC wires ‘Yias ~ minimum supply voltage (see Table A.1 below) ‘Vou = mninimuzn operating voltage of the detector or end-of-line relay, whichever is greeter, in volts {otal number of detectors on the 24 VDC supply circuit I, = detector current in standby N, = number of detectors om the 24 VDC power circuit which must function at the same time in alarm detector current in alarm. cend-of line relay current number of Notification Appliance Devices Notification Appliance current when activated NOTE: This simplified equation assumos thal the devices are at the end of a lang wire run. The minimum supply voltages produced by Notifier power supplies are listed below: FACP Vins [Power Supply Wa ‘AEP100 781 __|)MPS248 BT ‘AFP2O0 Tea || FOPS 24 7a ‘NFS-640 15.15 || MPS 24K 7; CPS-D4 oNFSTEM, 10.48 || FOPS 24S8FCPS 2488737 NFS.320, or NFS-2208¥S AP S-400 7025 ACPS- 206 738 ANPS24 20.74 ACPSBIO O57 APSZOR OD Table A.1 Minimum Supply Voltage Notifier SLC Wiring Manual —PIN 12531 2/10/2014 8 ~ Power Considerstions Supervising 2+ A.2 Supervising 24 VDC Power A2A A.2.2 ‘There are options for supervising 24 VDC power, as discussed betow. + Using FlashScan Type Codes with Built-In Power Supervision + Power Supervision Relay + Using the FCM-I module without relay Using Type Codes with Built-In Power Supervision ot NFS2-3030, NFS-3030, NFS2-640, NFS-320 and NFS-3 Certain FlashScan type codes have extemal power supervision built into the software. F refer to “Devices Requiring Extemal Power Supervision” in the appropriate installation Power Supervision Relay Power used to supply 24 VDC detectors, notification appliances (using the FOM-1) and detectors (using the FZM-1) can be supervised with a power supervision relay. This rel: ‘energized by the 24 VDC power itself, is installed at the end of cach respective power f ‘wired in tine with the supervised circuit of any intelligent module. When power is removed from the relay, the normally closed contacts open the supervise ‘generating a trouble condition. Therefore, the relay needs to be installed at the end of th, supervised cireuit, 80 it does not disrupt the operating capability ofall the devices on ts ‘The relay can be installed in line with any leg (+ or ~) ofthe supervised NAC or IDC cir a two ora fourwire style. Figure A.{ shows the supervision of a24VDC circuit using the FCM-1 or FZM-1. Refe Device Compatibility Document for compatible notification appliances and relays 24VDC Power fom ‘Coniol Pana or + Power Supply Last device on the SLC loop (FON or FPN) EUR (Use 47K wth OMA ‘or 3.9K with FZ) Figure A.1 Supervised 24 VDC Circuit Noufler SLC Wiring Manual — PIN 51253101 Supervising 24 VDC Power Power Considerations Figure A2 shows an altemate mothod of supervising a 24VDC ciel 28VDC Power from Control Pane! or Power Supply roma Power Supervision Rolay (EOLR-1y elR4rK Figure A.2 Alternate: 2-Address Method of Supervising a 24 VDC Circuit Noiifer SLC Wiring Momual — BAN SY2S3:U1 2/10/2014 Sle pee antasetent 6 Power Considerations Supervising 24 VD: A.2.3 Using the Addressable Control Module Without Relay ‘An alternate method of supervising 24 VDC power fed to the Notification Appliance Cireui FCM-1 module eliminstes the need for a power supervision relay, This ruethiod uses a Notit ‘Appliance Circuit from the control pane] or power supply to supply power to the FCM-1 \ ‘Tae control panel supervises this circuit, which cam be either a Style ¥ or Style Z. h Style Y NAC Power Wiring Program the NAC from the control panel for general alarm. (Refer 1o the programming mat : programming section ofthe FACP documentation for instructions.) Note that ifthe NAC is ‘output, the FCM-L output will be coded as well. Refer to the Device Compatibility Document for compatible notification appliances. +The cireuitis supervised and power-limited. + In this circuit, an extemal ELR is required at end of the NAC circuit, + Refer to the respective control pane! installation manual for NAC terminal block coune i information and FLR value . + Remove intemal resistor on each FCM-1 (see instructions in Figure 7.2 on page 44). Connect the NAC power as follo NAC Terminal Block (24 VOC} Note: Drawing shows & ‘wing only: SLC Wing shown, Circuit supervised by coniral pane! Figure A.3. NFPA Style Y NAC Power (Alternate) 6 Notifier SLC Wirtng Manual — P/N S1253:U1 7 Supervising 24 VDC Paver Power Considerations Style Z NAC Power Wiring (Alternate) Program the NAC from the control panel for general alan. (Refer to the programming manual or ge ‘programming section of the FACP documentation for instructions.) Note that ifthe NAC is a coded ‘output, the FCM-1 output will be coded as well. Refer to the Device Compatibility Document for compatible notification appliances. + The cireuit is supervised and power-limited. + Inthis circuit, an extemal ELR is not required at end of the NAC circuit. + Refer to the respective control panel installation manual for NAC terminal block connection information, + Remove internal jumper on each FCM-1 (see instructions in Figure 7.2 on page 44). ‘Connect the NAC power as follows: FM NAG Terral etock avec) UJ Circutt supervised by contr pane Note: Drawing shows power witing ‘only; SLC Wiring not shown, sic omen Figure A.4 NFPA Style Z NAC Power (Alternate) Notifier SLC Wiring Manual — PIN 51253:U1 211072014 er 68 Appendix B: SLC Surge Suppression B.1 Introduction ‘There are one primary and three socondary UL-listed surge protectors approved for use \ FACDs listed in this appendix. Primary Surge Protector: + 326-2M TH Station Protector Secondary Surge Protectors: + DTK-2LVLP-F: Diversified Technology Group, Inc. (DITEK) 1720 Starkey Rd. Le 33971 (800) 753-2345 + SLCP-30; EDCO 1805 N.E. 19th Ave. Ovals, FL 34470 (352) 732-3029 + PLP-42N: Norther Technologies, Inc. 23123 E, Madison Ave, Liberty Lake, WA 9 (800) 727-9119 - ——— NOTE: For detailed information refer to the installation documentation supplied with the eee ——————eee—oooererOr— ‘One primary surge protector must be used with each SLC wiring pair whenever SLC wit outside the building, + Install primary protection only a shown in this document. + Refer to NEC Article 800 and local building code requirements, Additional primary surge suppressors may be added as required by the NEC. Add these suppressors in series with the SLC wiring at the building entrylexit, ‘Wiring connected to the surge suppressor output must remain within the building while connected to the surge suppressor input may be routed outside the building as shown be Building #2 ulding #4 Nontfier SLC Wiring Marmual -- PIN 5125331 t Insillasion ~ SLC Surge Suppression B.2 Installation ‘Mounting of the secondary surge suppressor mmust be inside the FACP enclosure or in a separate enclosure listed for fire protective signaling use. + Locate on an available stud and secure with not, + Unit is connected in series with the SLC Loop to protect the Control Panel. + Provide a common ground to liminate the possibility of« differential in ground potentials. B.2.1 AFP-100 & AFP-200 DTK-2LVLP-F Connections Optional Four-wire Return Loop Siyie 6 (Class A) HL] @ [ashi SLC Loop. © |B Shield sot! PLP-42N Connections. = => Optional Four-nire Return Loop = =|! Style 6 Class A) 4 ' 4 "1 s.e emia aos ' i NOTE: Use 12 AWG (3.31 mm) 0 18 AING (0.82 mm?) wire with erimp-on connectors to connect the units ground terminal io equipment ground. Wie length must be minimized to provi boat protection. Notifier SLC Wiring Marual — P/N $1253101 27102014 o ‘SLC Surge Suppression SLCP-30 Connections B.2.2 AFP-300, AFP-400 DTK-2LVLP-F Connections (Optional Fourie Rotur L000 ‘Sie 6 (Class A) SLC Terminal Block acesa Sle uf S ole 3) = (2\| ok ——J 2 | 5 2 —_ 12 | a sto Blo © | pew [are YB] [OH== H+ cmos eournie Rumor Q@)l|Op-n7 ie 8S 8118 1 Style 6 (Class A) fe\{ell on [wepour| |! 7 ete eck wor] Se 3\ seas 8) [BS Ieee © Earth 4 4 Ee * Optional Fourwire Return 11 She 6 (Ciess A) GT] a NOTE: Use 12 AWG (2.1 mF) to 18 AWG (0.82 ra) wire with crimp-on connecto ‘Snnedt the units ground terminal © equipment ground. Wie Yongth must be miniize provide best protection. 7” Notifter SLC Wiring Manual — PIN 5125? Installation B.2.3 ‘SLCP.30 Connections 5 g i y 9 SSOSe, S888 2 5 8 & SLC Surge Suppression ptonal Fourie Reluen Loop Style 6 (Class A) AM2020 & AFP1010(LIB-200A DTK-2LVLP-F Connections ‘tev [SJE sve renal tock 8 I can se tional Four-wire sone Seturntoop la £ Style 6 (Class A) Q |Nocom 3 a NOTE: bo not connect shal (if present Yo surge protector or fe panel PLP-42N Connections = Ze sxc Tomina tock - Qe: emia scum (Th 3 lteom Te Optional Faure rag, geen } Reto Loop & \Nocom i Style 6 (Ciass A) Glee £ NOTE: Uso 12 AWG (3.31 mm) fo 18 AWG (0.82 mm?) wire ‘connect the unit’s ground terminal to equipment ground. Wire k vith crimp-on connectors to length must be minimized 10 provide best protection. Do not connect shield (if present) to surge protector or fire pane. Notifier SLC Waring Manuel — PAN 51283:01 2102014 SLC Surge Suppression dnste SLCP-30 Connections L030 oie Qo ste termina! Boa SLC Loop | & [Ne conn 1 3 )a Optional Fourwira, “TT No conn Retum Loop i. 8 nN i Style 6 (Class A) 8 lNocenn i Ol STE Dowco (oT Sane TT ae a B.2.4 NFS2-3030, NFS-3030, NFS2-640, NFS-640, NFS-320, an / NFS-320SYS eq DTK-2LVLP-F Connections _ [BRIS serosa | Ino com He tC Loop ois & [Nocona i; nal Fourie Hs Stamntan Be Spe ose A) 2 ocom ys : NOTED Do not connect shield (present to surge protector ore pane i PLP-42N Connections i psa / i A a ‘SLO Te i Bloe Hl -1 75h Sec tama | pre tS | no core suc Loop BOP gle ie comstorvie 04 sige" Retum Loop TT 7S [conn Siylo 6 (Ciass A) Logie ToTes oe 12 AWG (3.31 mm) to 10 AWG (0.82 me) wire wth cdmp-on connectors : aoe patie ground termina equipment round, Wir length must be misiized & ar ex protection, not sect shelf resent) o surge protector or repel ii SLCP-30 Connections ij acess com | Ble src remiosm stoLooe 2 Noon ctor Faure $ oom Careless gix ee ee 8 Wo com Dae NOTE: Do nat connect shield (f prosent o suege protector ar fre pane Nottfier SLC Wiring Manual —PIN 31253 Appendix C: Terminal Conversion Charts for V-type ® and H-type Devices C1 FRM-1 Common om sc. Glosed Common 2} 740 : ‘Open Closed 215 ta. 720 [8 commen Open 21 48 a common |S tr 4S Cured 15 OE 780 [0F%"* Tye V-type Terminal Number | Terminal Function H-type Terminal Number SLC 1 sic+ Unused ‘Normally Open (1) Normally Closed (1) Relay Common (1} Normally Open (2) Normally Ciosed (2) Relay Common (2) 10 NA Unused 4 NIA Unused 1" e Table C.1. FRM-1 Terminal Conversions Notifier SLC Wiring Manual — PIN S253401 2/1012014 n i | “Terminal Cofiversion Charts for V-type and H-type Devices Type v FCM and FEAL C.2 FCM-1 and FZM-1 ‘caass A Supervision A-}O. voor ° Sa A Superson sic BERT” polge, chess A Superiion «| Stes Cless ASuperision OT? 720 |SLC+ ‘Gaus Na Supentsion= vos. Gime ASureriemnAt| OTe = BO voc + Gigs Ave Supervision ‘Vaype Terminal Number _| Terminal Function ‘type Terminal Nomber 1 slo 1 2 sic+ 2 3 voc- 1 a voc + 70 5 Unused 5 6 ‘Solenoid BIA 6 7 Solenoid BIA + 7 8 Solenoid A + 3 ° Solencid A~ 9 NA Unused 3 NA Unused 4 m Table C.2 FCM-1 and FZM-1 Terminal Conversions Notifier SLC Wiring Manual — PIN 5125311 2/10/20 Fuel . ‘Terminal Conversion Chars for V-type and H-type Devices C.3 FMM-1 , Class A Supervision |) Class A Supervision 1c. 119 sic (Class A/B Supenision + LC + CessASupenisin|O te TO ISLC Class A/B Supervision - Giass A Supersion| © 43 Cinss AB Superson OT | TH lass AB Supervision O16 QO) 130 Twey Type V-type Terminal Number | Torminal Function Hetype Terminal Number 1 sic 1 2 sic+ 2 3 Unused 3 4 Unused 4 5 Unused 5 6 Class WB Supervision- | 6 7 Class AB Supervision + | 7 € 8 Class A Supervision + 8 9 Class A Supersision - 9 NA Unused 10 NA Unused) 1 Table C.3 FMM-1 Terminal Conversions: Notifier SLC Wiring Manual — P/N 31253201 27202014 5 ‘Terminal Conversion Charts for V-type and H-type Devices FIM C.4 FTM-1 ma somsintig we! (Class A Supervision =| LC Resor + m9 |sic- SEER 6 Ss eeanemam leg? gS RE: lass AIB Suponision *)C) Riser cuss Ae Somnsen® Sty AO. r+ Class AB Supervision -| 48 CYC) 150 Typev Typ \Vaype Terminal Number | Terminal Function Hetype Terminal Number 1 ‘SLC - 1 2 sic+ 2 3 Riser- 11 4 Riser + 10 5 Unused 5 7 Class AB Supervision- | 6 6 Class A/S Supervision+ | 7 9 lass A Supervision + 8 8 Class A Supervision - 9 NA Unused 3 NA Unused 4 Table C.4 FTM-1 Terminal Conversions 18 Notifier SLC Wiring Manual — PIN 51253:U1 2/10/2014 FDMI C.5 FDM-1 @ crerspeninling Sass Serio |O su lass AB Supervision + lass AB Supersion =| ‘Teeminal Conversion Chats for Veype and Hetype Devices niQlsuc- lass & Supanvision sO 19 20 |sic+ Crass A Supers ‘Class MB Supervision >| O77 ud ‘lass AB Superson] © 18 EYE 50 Tye H Vype Terminal Number | Terminal Function ype Terminal Number 7 Ste. 7 2 aie+ 2 3 Unused a 4 Unused 4 5 Unused 5 5 Class AB Supenition- | 6 7 tess AB Supervision | 7 a Glass ASupenvaion® | 8 ® 3 Gis ASuensen- NA Unused 10 WA Unused "4 Table C.5 FDM-1 Terminal Conversions Notifier SLC Wiring Manual — PAN 51253:U1 27102014 n Appendix D: Intelligent Detector Base Layouts for Legacy Devices D.1 Wiring a Detector Base Figure D.1 shows typical wiring of the B7IOLP or B50] detector base connected to an SLC. An optional RA100Z, Remote LED Annunciator is shown connected to the base, sic # Use 2 female daconnect fo wire the RAIOO2 (5) Tetminal 1 (-) able sols Figure D.1 Wiring of the B710LP or B501 Detector Base NOTE: The B70LP base wiring is identical to the 8501, except there ie no shield terminal n Notifier SLC Wiring Manual — PIN $2253:U1 2/1030 Wiring an isolator Base, Intelligent Detector Base Layouts for Legacy Devices D.2 Wiring an lsoiator Base @ Figure D.2 shows typical wiring of B224BI Isolator Base. Condut am 1s0.x ee s 2 Iselator Medule Figure D.2 Wiring an Isolator Base ° D.3 Wiring a Relay Base Figure D.3 shows typical wiring of the B224RB plug-in relay detector base connected to an SLC. To next deviee on SLC Foe connection of ‘be shield Relay Common Normally Open 1 Nermaly Closed i i Figure D.3 Wiring of the B224RB Plug-in Relay Detector Base Novifler SEC Woring Mama! — PIN S1253:001 2710/2014 Intelligent Detegtor Base Layouts for Legacy Devices Wiring 2 Sounder Base D.4 Wiring a Sounder Base Figure D.4 shows typical wiring of the B501BH(-2) and B50] BHT(-2) Sounder Bases. UL-Lsted 249 Power Supply + ‘Optional Sounder Interconrect i e = |O i i © sce sic- Figure D.4 Wiring the B501BH(-2) and B501BHT(-2) Sounder Bases. 80 Notifier SLC Wirins Maral — PIN S1253:U1 2102014 Lule We Lee Appendix E: Canadian Versions of SLC Devices Uidisted SLC Device ___ULGAIsted SLO Device Description [Detectors FAPT-85t (Accimate™) —-PAPT-851A Tnfeligent detector thal Gombines a photoctociric sonsing chamber lection (138°F/57.2°C), FlashScan [FS8-200, FSE-2008 FSB-200A, FS8-2008A ‘AdGrosbable,ineligank Sngle-snded beam smoko detector with builtin senstivity testing, FleshScan and CLIP mode, Fsvest FOVESTA “Acdressabe,ineligenl smoke detector that Incorporation an Tonization sensing chamber. Designed to provice open ares protection. FlashSean capablo, FsP-a55 FSPOSIA “Analog, adressable interigont smoke dotecor Wet uses 3 photosiedte sensing chamber. Listed for use in ducts. Designed to Provide opon area protection. Flashcan capanie, FSP asiT FSP-ESITA “Rade thon eansors Wal wil alan ata fixed temperature of 135° (7°). FOPASIR FSP-ASTRA “Analog, addressable intelligent photoelectric sensor thats remote test eapabie, For use with DNR(W) FaTe5t FSTESTA Tnieligent theamistor sensing cout for fast respanse, Designed to provide open area pratation with 80 foot spacing capably Ahad Temaorature sensor with 135°F fixed tempersture alarm, FlasnScan capable. [FsT-asiR FST-RSIRA Incorporates a thermal rie of se of 15° (8.4°O). FlashiScan capable, lesrasie FST-B6THA High temperature senor with 190°F (87-8°C) fed temperature alarm. [FSD-751PL FSO-TS1PLA Photoelecne Duct Detector, Lowow [FSO-75tRPL FOD-TSIRPLA Photoelectric Duct Detector, Low-fow. FSHTEI FSH TSA “Srroke deledir provides early waring smoke detection in hostile lervironmants where traditional smoke detectors ere not practical FSLT5t FOL-TSTA ‘an advanced inleligent photoelecte detector that uses alaser ‘dode, special optics, and signal processing Ic obtain extremaly| high sensitivity. FS0-854 FECBETA Intoligort mali-ortena Gelecor thal combines eholoeiecic ‘sonsing, heal detection, carbon monoxide and far, FCO-851 FOO-85A ‘Adérossablo,inleligant delecior tral combines a photoelectic ‘sonsing chamber combined wth Carbon Monoxide (CO) sensors. FlaghScan rnede only. FSA-B000 FSA-B000A Inteligent FAAST aspiration smoke detector. Supports FlashSaan ‘and CLIP made, (An eater model was CLIP mode only) Bases lear B2s0LPA ‘Standard US. LowProfile ase (6°, 1524 om). [eso7 BOTA, ‘Standard European flangeless base (# 10.16 om), [arrow B7AOLPA ‘Siandard US. Low-Profis base (6, 15.24 cr). Discontinved faso1BH, BsorRAT BEOIBHA, BEOTBHA ‘Sounder base, includes BSO‘VA Sounder base with temporal sounder (UL 8th Fon) Discantinved [SS016H2, BEOIEHT2 NA ‘Sounder base, includes BSOT/A Sounder base with temporal sounder (Ui. Sth Eston) Discontinued Ee BE2aRGA Low Profle intligent relay bese, feazeel BR2IBIA ‘Tow Profle neligent isolator base. [a7 10HD B7IOHDA Base for hostle environment detector. Notifier SLC Wiring Marvel —PIN 51283:U1 202014 81 (Canadian Versiois of SLC Devices Ubilsted SLC Device __ULCullsted SLE Davies Description 'Ba008 'B200SA, B2OOSCOR ‘Addressable sounder base B2008COA provides CO detector markings in EnglishiFrench, for Canacian appiicatians ony. B200sR Ba00sRA ‘Sounder base, ‘Monitor and Zone interface Modules Fun Faina-1a (Used for normally o3en contact alarm intiating davies, Such as :menval pal staons, feur-nire stpoks deleciore, nest detectors, ‘ralerfow, and supervisory devices. Fame FAIA Used fo interface with wo.uire smoke dotectons in addon fo normaly open contac, FON FDMLIA Provides two independent -wire Iiating Device Circuits (IDS) at ‘wo separate, consecutive addresses. Wire supervised IDCs 28 NEPA Ste B (Clase B) or Slyle D (Class A) crcl, The modules come with a thermoplastic cover for mounting to 2 inch (10 16 ‘6m square mounting box, Fxie-r0r FAN TOTA Functionally sinilar tothe FMLA Monitor Module, but fered in a ‘smaller package for mounting decty inthe electrical Box ofthe ‘evico being monitored, (Class 8 input crit only) Pull Stitions NeciaLx NeG-H2Ex ‘An addressable marival pul tation with keylock resol feature Tho addressable module fs housed within the pul station. ry MPS Secies ‘Addressable manual pul stations with bax Key reso feature The addressable module's nousad within the pl station. [Control Modules roe FOMTA ‘Control Modil, NAC: Addressable Control Module used as ‘Notification Appliance Circuits (NAC) te power and supervise compatible, ULsslee cotncation apptances. Wired suparvises INACs as NFPA Style ¥ (Class B)er SiyleZ (Glass A) The modules ‘ome witha thermoplastic covor for mounting toa 4-nch (10.16 {on} square mounting box. FON RELA ‘Conirol Modu for releasing applications, Flash Scan only. FRI FRUMIA RRolay Control Module is similar to the FONT except used asa Form-C contro einy module Awe Ita Fraightors Telephone Made; FastSoan-only device foruse with Fire Fighters Tetephone. Fault isolator Module iso 180-4 ‘The Fault lslaior Module proiscs the eystom against wieo-wire short creuts on the S.C. ft should be placed between groups of sonsors in a Siyle 6 or Silo 7 SLC ta Isolate short- and open-crcuil problems and protect the rest of tho loop 80 can continu to ‘porate normaly. tis not adressabl, but lstod hare due to its use in an suc, |Muit-inputioutput madules [EDR FORMA Dual Class 8 monitor /Fom-G relay modula [roc XPECA Contrls six NAC or speakeritelephone cial. (Not Isied for ure in releasing applications) PER XPERA Contos six Form relays, peerowr XPIOMA ‘Supervises ten Class-A addressable inilaling Devioe Crauts (10) Jwhien menitor normaly open contact initating devices. Pema XPBMAA Monitors sik zanes of conventional wo wire detector 2 Notifier SLC Wering Manual ~ PIN 1253: 2/10/2014 Index Numerics 24 VDC power 63-66 alternate method of supervising 66 monitoring and switching NAC power 43 A ATTAGB Replaced by BOLR-1 See power supervision relay Acefimate 18, 16 ACPS-2406 16, 63 ACPS-6LOE 16, 63 address capacity 31 addressable devices 31 addressable modules 13, 36 Addressable Modiles (Overview) 82 AFC-600 Discontinued AFP-100 19, 24 ‘AFP.200 19, 24 AFP-300/AFP-400 19, 24 AIM-200 19, 25 AM2020/AF P1010 18, 19, 25, AMPS-248 16, 63 analog intelligent devices 12 APS2-6R 63 aspiration detector 12, 16, 53, 58 auniliary devices 14 B B210LP 53, B224BI, see isolator bases BSOL 53, 78 BTIOHD 14, 53 bases #4 building entry/exit 68 c cabinet 26 cirenit fault 14 cirenit, speakevtelephone 13 CLIP (Cassie Loop Interface Protocol) 12, 17 cored output 66, 67 common ground 69 communications loop 32 conduit, types of 26-28 connector serew 26 eonnectors, erimp-on 70, 71, 72 control modules 13 Control Modules (Overview) 82 CPX-551 15 CPX-151 15 Notifier SLC Wiring Monwal — PIN 5125301 2102014 D DC resistance 20 degraded mode 13, 36 detector bases | list of 14 ‘see also isolator bases detectors 24 VDC 64 detector bases 81 duct 15 heat 15 hheat-wireless 16, 53, 59, 60, 61 listing 15, 81 photoelectric 15 wireless 16, $3, 59, 60, 61 devices addressable 31 auxiliary 14 isolator 31 ‘maxirmam number between isolators 31 SLC capacity 16 supervised 64 wireless 16, $3, 59, 60, 61 dey contact ratings 49, 50 sdey-contact 14 DTK-2LVLP-F 68 ‘dual monitor module 14, 51, 52

You might also like