Duct Construction Chart

This document contains duct construction tables from the SMACNA HVAC Duct Construction Standards for various duct sizes, gauges, joint types, and pressures ranging from 1" to 10" WG. The tables specify the appropriate duct gauge, joint length, and connector types for rectangular ducts under different pressure classifications. The document includes 27 pages of tables from the 2005 and 1995 SMACNA standards and provides references to the SMACNA publications.

Uploaded by

Matt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
935 views

Duct Construction Chart

This document contains duct construction tables from the SMACNA HVAC Duct Construction Standards for various duct sizes, gauges, joint types, and pressures ranging from 1" to 10" WG. The tables specify the appropriate duct gauge, joint length, and connector types for rectangular ducts under different pressure classifications. The document includes 27 pages of tables from the 2005 and 1995 SMACNA standards and provides references to the SMACNA publications.

Uploaded by

Matt
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 23

Index For Rectangular Duct

Page 1 - 2005 Smacna 1 WG Submittal


Page 2 - 2005 Smacna 2 WG Submittal
Page 3 - 2005 Smacna 3 WG Submittal
Page 4 - 2005 Smacna 4 WG Submittal
Page 5 - 2005 Smacna 6 WG Submittal
Page 6 - 2005 Smacna 10 WG Submittal
Page 7 - 1995 Smacna 1 WG Submittal
Page 8 - 1995 Smacna 2 WG Submittal
Page 9 - 1995 Smacna 3 WG Submittal
Page 10 - 1995 Smacna 4 WG Submittal
Page 11 - 1995 Smacna 6 WG Submittal
Page 12 - 1995 Smacna 10 WG Submittal
Page 13 - Beaded Duct Submittal
Page 14 - Longitudinal Seam Submittal
Page 15 - T.D.C. Connector Submittal
Page 16 - Transverse Connectors Submittal
Page 17- Duct Liner Installation Submittal
Page 18 - Branch Connections Submittal
Page 19 - Single Turning Vane Submittal
Page 20 - Airfoil Turning Vane Submittal
Page 21 - Straight Duct
Page 22 - Misc. Elbows
Page 23 - Misc. Elbows
Page 24 - Misc. Transitions
Page 25 - Misc. Transitions
Page 26 - Misc. Transitions
Page 27 - Misc. Transitions
Page 28 - Misc. Tees
Page 29 - Misc. Tees
Page 30 - Misc. Fittings
Page 31 - Offsets

1" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

0 - 12"

26

59"

FLAT SLIP
T-6 24 GA

FLAT DRIVE
T-1 24 GA

13 - 18"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

19 - 30"

26

56"

T.D.C.
T-25a

T.D.C.
T-25a

31 - 42"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

43 - 54"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

55 - 60"

24

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

61 - 72"

22

56"

T.D.C. W/ C.T.R.&J.T.R
T-25a

T.D.C. W/ C.T.R.&J.T.R
T-25a

73 - 84"

22

56"

T.D.C. W/ 2C.T.R. & J.T.R.


T-25a

T.D.C. W/ 2C.T.R. & J.T.R.


T-25a

85 - 96"

20

56"

T.D.C. W/ 2C.T.R. & J.T.R.


T-25a

T.D.C. W/ 2C.T.R. & J.T.R.


T-25a

97 & UP

18

56"

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

T.D.C. W/ CENTER A.R. & J.T.R. T.D.C. W/ CENTER A.R. & J.T.R.
T-25a
T-25a

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
A.R. ANGLE REINF.
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005.

2" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

0 - 10"

26

59"

FLAT SLIP
T-6 24 GA

FLAT DRIVE
T-1 24 GA

11 - 14"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

15 - 26"

26

56"

T.D.C.
T-25a

T.D.C.
T-25a

27 - 30"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

31 - 36"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

37 - 42"

20

56"

T.D.C.
T-25a

T.D.C.
T-25a

43 -60"

22

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

61 - 72"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R. & J.T.R.


T-25a

85 - 96"

20

56"

T.D.C. W/ 2 C.T.R. & J.T.R.


T-25a

T.D.C. W/ 2 C.T.R. & J.T.R.


T-25a

97 & UP

18

56"

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

T.D.C. W/ CENTER A.R.. & J.T.R. T.D.C. W/ CENTER A.R.. & J.T.R.
T-25a
T-25a

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
A.R. ANGLE REINF.
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005.

3" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

0 - 12"

26

59"

STANDING SLIP
T-11 26 GA

13 - 26"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

27 - 30"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

31 - 36"

20

56"

T.D.C.
T-25a

T.D.C.
T-25a

37 - 42"

22

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

43 - 54"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R. & J.T.R.


T-25a

55-60"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R. & J.T.R.


T-25a

61-84

20

56"

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

85- 96

18

56

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

97- 120

18

56

T.D.C. W/ CENTERA.R.& J.T.R


T-25a

T.D.C. W/ CENTERA.R.& J.T.R


T-25a

WIDE SIDE
CONNECTOR

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005 .

NARROW SIDE
CONNECTOR
FLAT DRIVE
T-1 24 GA

4" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

0 - 10"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

11 - 12"

26

59"

T.D.C.
T-25a

T.D.C.
T-25a

13 - 22"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

23 - 28"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

29 - 42"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R. & J.T.R.


T-25a

43 - 60"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R. & J.T.R.


T-25a

61- 72

20

56"

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

73 - 96

18

56"

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

T.D.C. W/ 2 C.T.R & J.T.R


T-25a

97 120

18

56

WIDE SIDE
CONNECTOR

T.D.C. W/ CENTER A.R & J.T.R


T-25a

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
A.R. ANGLE REINF.
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005 .

NARROW SIDE
CONNECTOR

T.D.C. W/ CENTER A.R & J.T.R


T-25a

6" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

NARROW SIDE
CONNECTOR

DUCT
GAUGE

JOINT
LENGTH

0 - 8"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

9 - 12"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

13 - 24"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

25 - 26"

20

56"

T.D.C.
T-25a

T.D.C.
T-25a

27 - 30"

22

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

31 - 36"

20

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

37 - 60"

20

56"

61 - 72"

18

56"

T.D.C. W/ C.T.R & J.T.R


T-25a

T.D.C. W/ C.T.R & J.T.R


T-25a

73 84

18

56"

T.D.C. W/ 2 C.T.R.&J.T.R.
T-25a

T.D.C. W/ 2 C.T.R.&J.T.R.
T-25a

85 96

16

56

T.D.C. W/ 2 C.T.R.&J.T.R.
T-25a

T.D.C. W/ 2 C.T.R.&J.T.R.
T-25a

WIDE SIDE
CONNECTOR

T.D.C. W/ C.T.R. & J.T.R.


T-25a

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
A.R. ANGLE REINF.
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005 .

T.D.C. W/ C.T.R. & J.T.R.


T-25a

10" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

0 8

24

56

T.D.C.
T-25a

T.D.C.
T-25a

9 12

22

56

T.D.C.
T-25a

T.D.C.
T-25a

13 18

20

56

T.D.C.
T-25a

T.D.C.
T-25a

19 26

22

56

T.D.C. W/ CENTER A.R.


T-25a

T.D.C. W/ CENTER A.R.


T-25a

27 28

20

56

T.D.C. W/ CENTER A.R.


T-25a

T.D.C. W/ CENTER A.R.


T-25a

29 - 42

20

56

T.D.C. W/ CENTER A.R. & J.T.R.

T.D.C. W/ CENTER A.R. & J.T.R.

NARROW SIDE
CONNECTOR

T-25a
43 - 72

73 84

18

16

56

56

T-25a

T.D.C. W/ CENTER A.R. & J.T.R.

T.D.C. W/ CENTER A.R. & J.T.R.

T-25a

T-25a

T.D.C. W/ CENTER A.R. & J.T.R.

T.D.C. W/ CENTER A.R. & J.T.R.

T-25a

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Third Edition 2005 .

T-25a

1" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 12"

26

59"

FLAT SLIP
T-6 24 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

13 - 18"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA.

Ref. 1

19 - 30"

26

56"

T.D.C.
T-25a

31 - 42"

24

56"

T.D.C.
T-25a

43 - 54"

22

56"

T.D.C.
T-25a

55 - 60"

20

56"

T.D.C.
T-25a

61 - 72"

22

56"

T.D.C. W/ C.T.R.
T-25a

73 - 84"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

85 - 96"

20

56"

97 & UP

18

56"

T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/ C.T.R.& J.T.R.
T-25a

T.D.C.
T-25a

Ref. 1

T.D.C.
T25a

Ref. 1

T.D.C.
T25a
T.D.C.
T-25a

Ref. 1

Ref. 1

T.D.C. W/ C.T.R.
T-25a

Ref. 1

T.D.C.
W/C.T.R. &J.T.R.
T-25a

Ref. 1

T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/ C.T.R. & J.T.R.
T-25a

Ref. 1

Ref. 1

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1995. Page 1-20, Table 1-4
2. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1997. Addendum 1, Page 1-41-6,
Table 1-45

2" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 10"

26

59"

FLAT SLIP
T-6 24 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

11 - 14"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

15 - 26"

26

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 1,2

27 - 30"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 1,2

31 - 36"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 2

37 - 42"

20

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 2

43 - 54"

22

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

Ref. 2

55 - 84"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

85 - 96"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

97 & UP

18

56"

T.D.C. W/ C.T.R & J.T.R


T-25a

T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/C.T.R. & J.T.R.
T-25A
T.D.C.
W/ C.T.R. & J.T.R.
T-25A

Ref. 2

Ref. 2

Ref. 2

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT AND ROD SPACING CANNOT EXCEED 48".
If MPT (Mid-point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'.
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible. Second Edition, 1995, Page 1-22, Table 1-5.
2. SMACNA-HVAC Duct Construction Standards-Metal and Flexible. Second Edition 1997, Addendum 1, page 1-41-6
Table 1-55

3" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 12"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

13 - 26"

24

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 1

27 - 30"

22

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 1

31 - 36"

20

56"

T.D.C.
T-25a

T.D.C.
T-25a

Ref. 1

37 - 42"

22

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C W/ C.T.R
T-25a

Ref. 1

43 - 72"

22

56"

T.D.C. W/ C.T.R. & J.T.R


T-25a

63 - 84"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

85- UP

18

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.
W/ C.T.R & J.T.R
T-25a
T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/ C.T.R. & J.T.R.
T-25a

Ref. 1

Ref. 1

Ref. 1

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1995, Page 1-24, Table 1-6
2. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1997, Addendum 1, Page 1-41-7
Table 1-65

4" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 10"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

11 - 12"

26

56"

T.D.C
T-25a

FLAT DRIVE
T-1 24 GA.

Ref. 1

13 - 22"

24

56"

T.D.C
T-25a

T.D.C.

Ref. 1

23 - 28"

22

56"

T.D.C.
T-25a

T.D.C.

Ref. 1

29 - 60"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.

Ref. 2

61 - 72"

20

56"

T.D.C. W/ C.T.R. & J.T.R


T25a

T.D.C. W/ C.T.R.

Ref. 2

73- UP"

18

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C. W/ C.T.R.

Ref. 1 & 2

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA - HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1995, page 1-26, Table 1-7
2. SMACNA - HVAC Duct Construction Standards-Metal and Flexible, Second Edition 1997, Addendum 1, page 1-41-7
Table 1-75

6" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 8"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

9 - 12"

24

56"

T.D.C
T-25a

T.D.C
T-25a

Ref. 1

56"

T.D.C.
T-25a

56"

T.D.C.
T-25a

13 - 24"

25 - 26"

22

20

T.D.C.
T-25a

Ref. 1

T.D.C.
T-25a

Ref. 1

27 - 48"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

49 - 54"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.
W/ C.T.R & J.T.R
T-25a
T.D.C.
W/ C.T.R. & J.T.R.
T-25a

55 - 60"

18

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

61 - 72"

18

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

73 - UP

16

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/C.T.R. & J.T.R.
T-25a

Ref. 2

Ref. 2

Ref. 2

Ref. 2

Ref. 1

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible. Second Edition, 1995, Page 1-28, Table 1-8
2. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition, 1997, Addendum 1, Page 1-41-7
Table 1-85

10" W.G.
STATIC
POS.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 30"

26

60"

DUCTMATE 35
"E", I.R

DUCTMATE 35
"E", I.R.

Ref. 1

31 - 36"

24

60"

DUCTMATE35
"E" I.R.

DUCTMATE35
"E" I.R.

Ref. 1

37 - 42"

22

60"

DUCTMATE35
"F" I.R.

DUCTAMATE35
"F" I.R.

Ref. 1

43 - 48"

22

60"

DUCTMATE35
"G" I.R.

DUCTMATE35
"G" I.R.

Ref. 1

49 - 54"

22

60"

DUCTMATE35
"H" I.R.

DUCTMATE35
"H" I.R.

Ref. 1

55 - 60"

22

60"

DUCTMATE35
"H" I.R., J.T.R.

DUCTMATE 35
"H" I.R., J.T.R.

Ref. 1

61 - 84"

20

60"

DUCTMATE35
"H" I.R., J.T.R.

DUCTMATE35
"H" I.R., J.T.R.

Ref. 1

85 & UP

18

60"

DUCTMATE 35
"H" I.R., J.T.R.

DUCTMATE 35
"H" I.R., J.T.R.

Ref. 1

NOTES:
J.T.R.-JOINTTIEROD
C.T.R.-CENTERTIEROD
I.R.-INTERMEDIATEREINFORCEMENT
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. Ductmate Industries, Inc., Rectangular Duct Construction Standards, 1995 Edition, page 10, table 7.

6" W.G.
STATIC
POS. OR NEG.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 8"

26

59"

STANDING SLIP
T-11 26 GA

FLAT DRIVE
T-1 24 GA

Ref. 1

9 - 12"

24

56"

T.D.C
T-25a

T.D.C
T-25a

Ref. 1

56"

T.D.C.
T-25a

56"

T.D.C.
T-25a

13 - 24"

25 - 26"

22

20

T.D.C.
T-25a

Ref. 1

T.D.C.
T-25a

Ref. 1

27 - 48"

22

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

49 - 54"

20

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.
W/ C.T.R & J.T.R
T-25a
T.D.C.
W/ C.T.R. & J.T.R.
T-25a

55 - 60"

18

56"

T.D.C. W/ C.T.R.
T-25a

T.D.C. W/ C.T.R.
T-25a

61 - 72"

18

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

73 - UP

16

56"

T.D.C. W/ C.T.R. & J.T.R.


T-25a

T.D.C.
W/ C.T.R. & J.T.R.
T-25a
T.D.C.
W/C.T.R. & J.T.R.
T-25a

Ref. 2

Ref. 2

Ref. 2

Ref. 2

Ref. 1

NOTES:
J.T.R. - JOINT TIE ROD
C.T.R. - CENTER TIE ROD
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. SMACNA-HVAC Duct Construction Standards-Metal and Flexible. Second Edition, 1995, Page 1-28, Table 1-8
2. SMACNA-HVAC Duct Construction Standards-Metal and Flexible, Second Edition, 1997, Addendum 1, Page 1-41-7
Table 1-85

10" W.G.
STATIC
POS.

SHOP STANDARDS
DUCT CONSTRUCTION TABLE
(FOR GALVANIZED & 304 S.S. & 316 S.S. DUCTWORK)
(NOT FOR ALUMINUM)

DUCT
SIZE

DUCT
GAUGE

JOINT
LENGTH

WIDE SIDE
CONNECTOR

NARROW SIDE
CONNECTOR

SPECIAL
NOTES

0 - 30"

26

60"

DUCTMATE 35
"E", I.R

DUCTMATE 35
"E", I.R.

Ref. 1

31 - 36"

24

60"

DUCTMATE35
"E" I.R.

DUCTMATE35
"E" I.R.

Ref. 1

37 - 42"

22

60"

DUCTMATE35
"F" I.R.

DUCTAMATE35
"F" I.R.

Ref. 1

43 - 48"

22

60"

DUCTMATE35
"G" I.R.

DUCTMATE35
"G" I.R.

Ref. 1

49 - 54"

22

60"

DUCTMATE35
"H" I.R.

DUCTMATE35
"H" I.R.

Ref. 1

55 - 60"

22

60"

DUCTMATE35
"H" I.R., J.T.R.

DUCTMATE 35
"H" I.R., J.T.R.

Ref. 1

61 - 84"

20

60"

DUCTMATE35
"H" I.R., J.T.R.

DUCTMATE35
"H" I.R., J.T.R.

Ref. 1

85 & UP

18

60"

DUCTMATE 35
"H" I.R., J.T.R.

DUCTMATE 35
"H" I.R., J.T.R.

Ref. 1

NOTES:
J.T.R.-JOINTTIEROD
C.T.R.-CENTERTIEROD
I.R.-INTERMEDIATEREINFORCEMENT
TIE RODS ARE 1/2" EMT
If MPT (Mid-Point Tie Rods) are used, the reinforcement spacing is based on 2-1/2'
References:
1. Ductmate Industries, Inc., Rectangular Duct Construction Standards, 1995 Edition, page 10, table 7.