Metering Installation Requirements: Table of Contents - Section 300
Metering Installation Requirements: Table of Contents - Section 300
PAGE
300.0
300.1
GENERAL .......................................................................................................................... 1
300.2
300.3
300.4
301.0
301.1
301.2
301.3
301.3-1
301.3-2
301.4
301.5
301.6
301.7
301.8
301.9
301.9-1
301.9-2
301.10
301.11
301.12
301.12 - 1
301.12 - 2
301.13
301.14
301.15
301.16
301.17
07/17//2012
METERING
300.0
PAGE
302.0
SPECIAL CONSIDERATIONS.21
302.1
302.1-1
302.2
302.3
302.4
302.5
302.6
302.7
302.8
302.9
302.10
302.11
302.12
302.13
302.14
303.0
303.1
303.2
303.3
303.4
303.5
303.6
303.6-1
303.6-2
303.7
303.8
CONNECTION DIAGRAM FOR SELF CONTAINED METER SOCKETS - DWG #G1 ...26
303.9
303.10
303.11
303.12
303.13
303.14
07/17/2012
METERING
302.0
PAGE
304.0
304.1
304.2
304.2-1
C.T. METER SOCKETS (See Section 300 Paragraph 303.8 for self-contained meter
sockets) ........................................................................................................................... 33
304.3
304.4
304.5
304.5-1
304.5-2
304.5-3
304.6
305.0
305.1
305.2
306.0
307.0
07/17/2012
METERING
304.0
PAGE
300.0
300.1
300.2
300.3
07/17/2012
METERING
300
PAGE
300.4
Customer Panel
Customer CT's
Meter Compartment
Sealable
120/240
Volt UG
Service
Pull Section
Sealable
Acceptable Customer
Equipment Location
3/4"
2 1/2"
1-1/4"
07/17/2012
METERING
300.4
PAGE
301.0
301.1
301.2
301.3
In a room within the building, approved by CRA-ES, for the location of electric meters, and with
access only by a door opening to the outside of the building. See Paragraph 301.9 for meter
room requirements.
In addition, the meter area must be readily accessible (See Section 100, Paragraph 102.20)
without requiring passage through restricted private areas, gates or fences. See next page for
acceptable meter locations for single family residences. The meter and main switch shall be
installed next to each other on the same wall. See Paragraph 301.13.
NOTE: See Section 500, Paragraph 506.6-1 for requirements for mobile home pedestals.
301.3-1
07/17/2012
301.0
PAGE
301.3-2
3 ft. min
6 ft. max.
Garage/Carport
Front Property Line
SES/Meter
Fence
Street
Street
Meter Location- Building Mounted
Servce Entrance Section
Alternate
Location
6ft. X 6ft. Area
07/17/2012
METER LOCATIONS
301.3-2
PAGE
301.4
301.5
301.6
REVISION
07/17/2012
METER LOCATIONS
PAGE
Nearest Corner or
Other Obstruction
10"
Min.
Obstruction
above meter
9" Min
36"
Min.
Clear
Working
Space
Figure 1
Surface or Semi-Flush
Meter Installations
36"
Min.
78" Min.
301.7
Clear
Working
Space
07/17/2012
METER LOCATIONS
MINIMUM WORKING SPACE
301.7
PAGE
10 min.
wall or obstruction
9 min.
78 min.
head room
HORIZONTAL CLEARANCE
Flush or surface mount
VERTICAL CLEARANCE
Flush or surface mount
36 working space
36 working space
4 min.
6 max.
07/17/2012
METER LOCATIONS
MINIMUM WORKING SPACE
301.7
PAGE
Minimum Required
Working Space
36"
Min.
Keep Clear
Length of Switchboard
11" Min.
Open Door
Screen Wall
Note:
Hinged door when open
may not block the exit route.
When doors are in maximum
open position exit shall be
36" minimum.
36" Min.
Open Door
Building Wall
36" Min.
07/18/2012
METER LOCATIONS
MINIMUM WORKING SPACE
301.7
PAGE
CUSTOMER
BREAKER
SECTIONS
FRONT
7 MIN.
FRONT
CUSTOMER
BREAKER
SECTIONS
METER
& CT
SECTION
CRA-ES
PULL
SECTION
NOTES
1.
Service entrance sections that face each other with staggered meter
locations shall have a minimum working space of 7 feet between service
entrance sections.
2.
CRA-ES PULL
SECTION
METER
& CT
SECTION
CUSTOMER
BREAKER
SECTIONS
FRONT
9 MIN.
FRONT
CRA-ES
PULL
SECTION
METER
& CT
SECTION
CUSTOMER
BREAKER
SECTIONS
NOTES
1.
Service entrance sections that face each other with face-to-face meter
locations shall have a minimum working space of 9 feet between service
entrance sections.
2.
07/17/2012
301.7
PAGE
301.8
BARRICADES/BARRIER POSTS
The Customer shall furnish, install and maintain permanent barricades to provide
clearances where the working space is exposed to vehicles or hazardous conditions. CRA-ES
shall specify type of barricade.
32"
34"
36"
Detail A
Final Grade
50"
Final Grade
6'-0"
2"
57"
4"
25"
21"
36"
5-1/2"
10"
Min
2" Min.
Concrete
Encasement
2" Min
Concrete
Encasement
"
1/2" Hole
9" Min.
Section A-A
Barrier Post Detail
Construction Notes:
1. Use additional barrier post as
required to prevent traffic penetrations to
SES.
2. Caution must be taken when installing posts
so that posts do not make contact
with conduit system.
Detail A
07/17/2012
BARRICADES/BARRIER POSTS
301.8
PAGE
10
301.9
S.E.S.
FRONT
S.E.S.
METER ROOM
FRONT
METER ROOM
07/17/2012
METER LOCATIONS
ELECTRIC METER ROOM REQUIREMENTS
301.9
PAGE
11
301.9
Interior of
Building
36"
Min
Interior of
Building
TELEPHONE
Access to be from
Exterior of building
Door to OPEN OUT
Lockbox
1. See requirements for locking doors. (Paragraph 301.10)
2. 36" concrete pad required in front of metering.
3. SES meter doors must open 90 (or more) with meter and test switch installed. Also, exterior doors must be
equipped with a device to hold the door in the 90 degree (or more) position.
4. Care must be exercised to design the enclosure such that neither the roof nor the door frame will interfere
with the clearances
or the installation and maintenance of the metering equipment.
301.9
5. With exterior meter doors in open 90 degree locked position, a 36 exit way is required between door edge
and closest object.
07/17/2012
METER LOCATION
ELECTRIC METER ROOM REQUIREMENTS
301.9
PAGE
12
301.9
ACCESS COVERS
WORK SPACE
ELECTRIC
EQUIPMENT
ACCESS COVERS
ELECTRIC
EQUIPMENT
ENTRANCE
WORK SPACE
ENTRANCE
At least one entrance is required to provede access to the working space around electric
equipment. The installation shown in the sketch at the right would not be acceptable if the
electric eqiupment was a switchbaord or panelboard over 6 ft. wide and rated 1200A or more.
Switchboard or
Control Panel
1200A or more.
Access
Panel
Access
Panel
WORK SPACE
For swtichboards and control panels rated 1200A or more and over 6 ft.
wide, there shall be one entrance not less than 24 in. wide and 6-1/2 ft.
high at each end.
Access
Panels
Switchboard or
Control Panel
1200A or more.
NOT
ACCEPTABLE
ENTRANCE
07/20/2012
METER LOCATION
ELECTRIC METER ROOM REQUIREMENTS
301.9
PAGE
13
301.9
Switchboard
or Control
Panel 1200A
or more.
Only one
Entrance
Required
Continuous and
unobstructed way
of exit travel.
Alternate
Entrance
Location
Excepion #1: Where the equipment location permits a
continuous and unobstructed way of exit travel.
Exception #2: Where the work space required by section 110-16(A) is doubled.
Access
Panel
Switchboard or
Control Panel
1200A or more.
Access
Panel
Only one
Entrance
Required
Exception #2: Where the work space required by section 110-16(A) is doubled.
07/20/2012
METER LOCATION
ELECTRIC METER ROOM REQUIREMENTS
301.9
PAGE
14
301.9-1
301.9-2
301.10
301.11
07/20/2012
METER LOCATIONS
METER ROOMS/LOCK BOXES/METER ENCLOSURES
301.9-1
PAGE
15
301.12
NOTES:
1. This enclosure is approved for:
A. Single family, self contained use only.
B. Communication equipment.
C. CATV
2. This enclosure is NOT approved for:
A. Gas service or piping.
B. Water service or piping.
C. Storage of any kind.
3. The structure foundation shall not extend into or
under the meter closet.
Foundation
10" min.
11" min.
15" max.
Outside wall of
residence
4. Clear and level work space shall be provided per paragraph 301.6,
notes 8,9,10 and 301.7.
5. Meter closet door shall be identified with a permanent tag showing
"Elecric Meter", manufactured per 302.1.
6. Pocket doors are acceptable.
07/20/2012
301.12
PAGE
16
301.12 - 1
24" Min.
8"
Min.
8"
Min.
75" Max.
36" Min.
07/20/2012
301.12
PAGE
17
301.12 - 2
24" Min.
4"
Min.
4"
Min.
75" Max.
36" Min.
07/20/2012
301.12
PAGE
18
301.13
301.14
301.15
Main/
Distribution
Section
Building
Wall
Pull Section
Sealable From
Front
Finish Grade
24"
See Note 1
NOTES:
1. See Section 500 for underground conduit and riser requirements.
2. See Section 1100, Drawing 301 for meter can requirements.
07/20/2012
301.13
PAGE
19
301.16
C
L
C
L
48" Min.
75" Max.
48" Min.
75" Max.
36" Min.
36" Min.
30" Min.
18" Min.
45" Min.
(See Note 5)
See Note 4
301.16
45" Min.
(See Note 5)
07/20/2012
MAIN LOCATION
ELECTRIC AND GAS METER SEPARATION
301.16
PAGE
20
301.17
ROLL-UP DOORS
Aluminum Roll-up doors used in conjunction with enclosed meter rooms are to be constructed
utilizing minimum 22-gauge slats. Dimensions of roll-up door must provide for a minimum
clearance of 12 in width and height greater than the largest piece of equipment being located
within the meter room. This is to provide for ease of installation and removal.
Door must be equipped with bottom and guide weather stripping.
A minimum clearance of 12 is required between the face of the service entrance equipment and
the door.
The door may be operated either mechanically or electronically. Manual push-up doors are not
permitted.
If the door is mechanically operated, the door must be equipped with an indoor mounted chain
hoist with a maximum allowable pull tension of ten pounds. A minimum working clearance of 36
square must be provided adjacent to the chain hoist to provide for safe operation.
Room must be equipped with light.
If the door is electrically operated it must have an emergency release device.
Chain hoist and/or electrical control switch for the door must be located so that the door may be
operated without the need to cross in front of the SES to operate.
CRA-ES lock box to be installed in close proximity to main entry door to meter room.
Owner is responsible for the on-going maintenance to insure continuous proper operation of the
door.
07/20/2012
MAIN LOCATION
ROLL-UP DOORS
301.17
PAGE
21
302.0
302.1
SPECIAL CONSIDERATIONS
METER IDENTIFICATION BY CUSTOMER
Where the installation requires more than one meter for service to the premises, then each meter
socket and corresponding disconnect shall be permanently (not painted) marked by the customer
to properly identify the portion of the premises being served.
When adding a new meter to an existing service location, all meters and corresponding
disconnects shall be labeled to properly identify the portion of the premises being served by each
meter and corresponding disconnect.
The identification shall be the same as the apartment, townhouse, office, suite, trailer, R.V. space,
etc., actually served through the socket and the corresponding disconnect. The identifying marking
placed on each meter panel shall be impressed into or raised from a tag of aluminum, brass or
other approved non-ferrous metal with minimum 1/4" high letters. The tag shall be riveted to the
meter socket panel and corresponding disconnect.
If meters are located in a meter room or cabinet, micarda tags are acceptable. Tags will be black
with white letters Minimum 1/4 high letters. Micarda tags shall be riveted to the meter panel. These
requirements are intended to prevent the identification(s) from being obscured by painting of the
building and attached service equipment.
The Companys meter department may require the assistance of the Customer prior to the setting
of the meters in a multi-metered development in order to verify that each meter socket identification
coincides with the apartment, townhouse, office, suite, trailer, R.V. space, etc. actually served
through the socket.
302.1-1
SERVICE IDENTIFICATION
All equipment shall be permanently labeled for the specific voltage and current being served.
302.2
METER HEIGHT
The requirements for meter height, which is the vertical distance between the center line of the
meter and the standing surface, shall be as follows:
1. When meters are located in a meter room or enclosed cabinet.
36" min. 75" max.
2. When meters are wall, semi-flush, pedestal, or surface mounted
outdoors, but not located in a meter room or enclosed cabinet.
48" min. 75" max.
302.3
MAIN SWITCH
For each meter installed on a service, the contractor/customer, in compliance with applicable
codes, shall furnish and install a fusible switch, a circuit breaker, or other approved disconnecting
means which shall control all of and only the energy registered by that meter. The disconnecting
means, where permitted by the governing code or ordinance, may consist of a group of fusible
switches or circuit breakers. These fuses or circuit breakers must be lockable and designed to
interrupt and withstand the available fault current. (See Paragraph 301.13 Main Switch Locations)
In cases where residential all-in-one meter panels are installed with multiple positions for main
disconnects, CRA-ES requires all positions to be filled with disconnects that are designed to interrupt
and withstand the available fault current.
302.4
07/202012
SPECIAL CONSIDERATIONS
302.5
PAGE
22
302.5
302.6
302.7
302.8
302.9
302.10
302.11
07/20/2012
SPECIAL CONSIDERATIONS
302.5
PAGE
23
302.12
302.13
302.14
DESCRIPTION
1S
2S
3S
4S
5S
6S
8S
9S
12S
14S
15S
16S
07/20/2012
SPECIAL CONSIDERATIONS
302.12
PAGE
24
303.0
303.1
303.2
303.3
SIZE OF
SERVICE ENTRANCE
SOCKET RATINGS
All sockets shall have a maximum ampere rating not less than the
ampacity of the main service switch. (Maximum ampere rating of socket
being 125% of continuous duty rating.)
Non-residential
& Industrial
Up to 100 amp
Non-residential
& Industrial
101-200 amp
Irrigation
(277/480)
Up to 100 amp
(Up to & including 75 HP)
Irrigation
(277/480)
101-200 amp
(Up to & including 125 HP)
303.4
SOCKET ENCLOSURES
All sockets enclosures shall be of the ring-type.
303.5
07/20/2012
303.0
PAGE
25
303.6
303.6-1
303.6-2
303.7
07/20/2012
303.6
PAGE
26
Load
120V - 1 - 2 WIRE
Load
120/240V - 1 - 3 WIRE
Load
120/208V - 1 - 3 WIRE WYE
FIG 3
FIG 2
FIG 1
POWER
LEG
Load
240V - 3 - 3 WIRE
Load
480V - 3 - 3 WIRE
FIG 4
FIG 5
Load
120/240V - 3 - 4 WIRE
FIG 6
Load
120/208V - 3 4 WIRE WYE
277/480V - 3 4 WIRE WYE
FIG 7
07/20/2012
303.8
PAGE
27
TBF
TBF
TBF
TBF
Fig. 1
Commercial
Fig. 2
Residential
Fig. 3
Residential
OVERHEAD INSTALLATIONS
TBF
TBF
TBF
Fig. 4
Residential
TBF
Fig. 6
Commercial
Fig. 5
Residential
TBF=TEST BLOCK FACILITIES
UNDERGROUND INSTALLATIONS
Fig. 7
Residential
07/20/2012
303.9
PAGE
28
Main
Cable Pulling
Section. See
Dwg. 343.
Cable Pulling
Section. See
Dwg. 343.
Disconnect
Switch
House
Meter
TBF
Barrier
Barrier
Main
Disconnect
Compartment
Barrier
Sealable Gutter
Cable Pulling
Section See
Dwg. 343.
Test
Bypass
Facilities
TBF
TBF
TBF
Barrier
Customer's
Distribution
Section
Test Bypass
Facilities
Incoming Underground
Service Cable
Fig-2 Typical Service Termination Enclosure
Combination Meter Socket Panel
for Commercial use.
07/23/2012
303.10
PAGE
29
Closed
Closed
Removed
Location optional
top or bottom.
Note #5
8-1/2" min.
Note #14
Note #4
10" min.
Note #6
Main
Main
Optional
11" min.
Note 3
Front View
Side View
This device may be used for multiple non-residential and industrial meter installations mounted in a ganged array.
2.
Test-bypass blocks with rigid insulating barriers shall be installed and wired or bussed to a line raceway and also wired or
bussed to the meter socket then to the main switch by the manufacturer. Blocks and barriers shall conform to EUSERC
drawing 312 requirements with physical arrangement conforming to drawings 304 and 305. Connections sequence is line-load,
line load, line load from left to right.
3.
4.
5.
All section covers shall be independently removable. Upper cover shall be non-removable when meter is in place. Meter
socket shall be mounted on support and attached to panel. Test by-pass cover shall be sealable and permanently labeled:
DO NOT BREAK SEAL. NO FUSES INSIDE.
6.
When a neutral is required for metering or testing, an insulated neutral terminal, mounted on either side, shall be provided
behind each test-bypass cover panel. The terminal shall be readily accessible when the cover panel is removed and shall be
individually connected to the neutral bus with a minimum of No. 8 copper wire.
7.
For 3, 4 wire. Connect 7 jaw to body of neutral lug with No. 12 minimum copper wire.
8.
9.
For 3, 3 wire, install bus to connect line and load poles together at top of center test-bypass block and connect 5 jaw to this
bus using No. 12 minimum copper wire.
th
th
11. For 1, 3 wire, 120/208 volts, omit center test-bypass block. Connect 5 jaw to body of neutral lug with No. 12 minimum
copper wire.
12. Permanent line-load labels on inside back of enclosure in (min.) high block letters.
13. Minimum depth shall be 4 inches for 0 100 amps and 6 inches for 101 200 amps
14. See EUSERC drawing 343 for pull box details when used on underground service
07/23/2012
303.11
PAGE
30
Ground/Bond Compartment
Gutter
(Sized per NEC)
10" min.
10" min.
10" min.
TBF
TBF
TBF
Main
Main
Main
See Note 1
NOTES:
1. This area of pull box for CRA-ES service conductors. Pull box and gutter covers to be sealable.
2. A minimum of one (1) meter must be installed at the time service is energized.
3. Pull box to be according to EUSERC Dwg. 343.
4. Customer shall install each set of service conductors from pull box through gutter to each meter.
Size to be per NEC requirements.
5. See Section 700 for Grounding and Bonding requirements
6. See EUSERC Dwgs. 304, 305 and G4 for meter can requirements.
7. Main disconnect required to be adjacent to the meter (See Paragraph 301.13). Optional factory
installed main is shown.
07/23/2012
303.12
PAGE
31
MOBILE HOME
AND
TEMPORARY METER PEDESTAL
1 3w 120/240 VOLT
This is a list of material for a normal meter pedestal installation. It is
not intended to be all inclusive but gives the more common
requirements. All equipment shall comply with EUSERC
requirements (See Section 1100, Dwg. 307) and Section 500,
Neutral Bus
Paragraph 506.6-1, 2.
1.) Meter socket, breaker compartment and pull section
must be rain tight equipment. Meter socket jaws or clips shall
be free of foreign material (mud, paint, plaster, etc.).
RINGLESS METER SOCKETS ARE NOT ACCEPTABLE.
2.) Breaker compartment.
3.) Pedestal bond lug. May be a bond screw in some models.
4.) Customers neutral landing block.
48" Min.
5.) Service termination lugs shall be twin #2 to #350 MCM
aluminum bodied pressure type for in and out connection of the
service conductors.
6.) The ground wire (#4 bare copper) shall be continuous
from the neutral landing block in the breaker
compartment to a grounding electrode system in
compliance with NEC (Check with AHJ). The ground wire must
be properly supported and attached to the outside of the
pedestal at 24" intervals. When attaching the ground
wire to the pedestal, the method of attachment shall not
result in sharp projections, such as metal screws into the
wireway below the neutral landing block. See illustration
at left for preferred method of installing the ground
electrode conductor.
7.) Access to utility pull section shall not be blocked in any
manner. Pull section shall be sealable. No customer
Approved
wiring or equipment is allowed in this area.
Grounding
8.) Poured concrete slab shall be 24" x 24" minimum size and have
Electrode
a 3 1/2" minimum thickness.
9.) Provide and install 2 1/2" conduit(s) with 24" sweep(s). Conduit to extend a minimum of 1" and a maximum of 2" above the
concrete slab. Conduit system shall be customer installed per CRA-ES specifications to a location determined by an CRA-ES
Representative.
10) Approved ground electrode clamp shall be buried, flush or somehow protected from physical damage. Clamp shall be designed for
underground use. Ground rod shall not be installed in or beneath the concrete slab.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
07/23/2012
303.13
PAGE
32
METER PEDESTAL
2
3
Load
Wires
4
5
48"
Min.
6
7
8
9
10
Grade
To Customer
Load
Grade
18" Min.
24" Min.
Approved
Grounding
Electrode
9.) Provide and install 2 1/2" conduit(s) with 24" sweep(s). Consult an CRA-ES Representative to determine if service will be radial or
cascaded. Conduit to extend a minimum of 1" and a maximum of 2" above the concrete slab. Conduit system shall be customer
installed per CRA-ES specifications to a location determined by an CRA-ES Representative.
10) Approved ground electrode clamp shall be buried, flush or somehow protected from physical damage. Clamp shall be designed for
underground use. Ground rod shall not be installed in or beneath the concrete slab.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
07/23/2012
303.14
PAGE
33
304.0
304.1
C.T. METERING
EQUIPMENT FURNISHED AND INSTALLED BY CRA-ES STANDARD OFFER
CUSTOMERS ONLY
1.
2.
3.
4.
5.
6.
304.2
304.2-1
Transformer rated meter sockets. (See paragraph 304.2-1 for socket configuration.)
Pre-fabricated panels.
Meter enclosures.
Service entrance sections.
Perches for test switches.
Metering transformer cabinets.
Proper grounding and bonding.
C.T. METER SOCKETS (See Section 300 Paragraph 303.8 for self-contained meter
sockets)
Front views shown
Figure 1
8 Jaw Socket
120/240V 1 3 Wire
Figure 2
13 Jaw Socket
120/208V 3 4 Wire
277/480V 3 4 Wire
120/240V 3 4 Wire
(See Section 1100, EUSERC Dwg. 332 for meter panel drilling & tapping specifications)
304.3
304.4
07/23/2012
C.T. METERING
304.0
PAGE
34
304.5
NOTES:
1. Pad shall be 4" thick. Walking surface of Pad should be flush with finished grade.
2. Pad material shall be rated 3000 lb. PSI at 28 day minimum.
3. Pad shall be constructed so drainage is away from service entrance section at a maximum ratio of 1
inch in 3 feet drop.
4. The pad shall extend a minimum of 3 feet beyond the leading edge of the service entrance section.
(See above drawing)
5. On a NEMA 3R (outdoor) S.E.S., the Customer shall install a locking device that will allow one lock
for the Customer and one lock for CRA-ES on the door.
07/23/2012
304.5
PAGE
35
304.5-1
Side View
SES
Expansion
Joint
3'
7'
No more than
8" slope
36"
4"
36"
Possible
Final Grades
9" min
Concrete Fill
Detail 1
Notes:
1. An acceptable personnel escape route shall be provided in front of the SES per Detail 2.
2. There shall not be more than 8 of drop in 4 feet in front of the SES pad along the route of escape
(see Detail 1 above), unless an alternative acceptable escape route is provided. (See Detail 3).
3. Absolutely no obstructions shall be allowed in the provided safety escape route, including but not
limited to: shrubs, trees, rocks, or gravel in excess of 1.5 diameter. Additional, no fencing shall be
allowed in front of the SES within the escape route unless an operable gate is provided which
opens to the full width of the SES, or unless an alternative escape route has been provided. (See
additional details provided in Detail 2, & Detail 3
4. If barrier posts are to be installed to protect the SES from vehicular damage, they shall be installed
no closer than 7 feet in front of the closed SES doors.
5. See 301.8 for additional Barrier information.
07/23/2012
304.5-1
PAGE
36
304.5-2
Hinges
on Right
Required 90o
Locking
Mechanism
3'
4'
Ground in front of SES pad
should be flush with top edge of pad.
Detail 2
07/23/20
304.5-2
PAGE
37
304.5-3
Hinges
on Right
6" Min
Required 90o
from fence
Locking
Mechanism
Notes:
1) Opening to steps to be
minimum 3' 0" wide
2) If steps are placed directly
Detail 3
07/23/2012
304.5-3
PAGE
38
75"
MAX
ON
OFF
ON
ON
OFF
OFF
ON
OFF
House-keeping pad
2-1/2" Maximum
(See Note)
Notes:
1. Housekeeping pad shall be 2-1/2 inches thick, and shall not extend more than 1 inch beyond the
front edge of the service entrance section. Do not use 2" x 4" as form for concrete pad.
2. Pad material to be rated 3000 lb. at 28 day minimum.
3. See Section 300, paragraph 301.9 for meter room requirements.
07/23/2012
304.5-4
PAGE
39
305.0
305.1
specifications. Customer shall provide and install totalizing cabinet. See Section 300,
Paragraph 305.2 for requirements.
3. Customer shall provide and install all totalized metering conduit. Conduits shall be installed in
accordance with the current National Electric Code requirements. All conduit installations shall
be 1 inch conduit.
4. Totalized metering conduits shall originate in the individual service entrance sections CT
compartments and shall terminate in the totalized metering compartment. Exact location of
conduit entries shall be specified by the Electric Meter Shop.
5. Conduit shall be rigid steel when installed outdoor, underground, or in locations exposing it to
6. Steel conduit, bends, and accessory parts installed underground shall be factory coated or
wrapped with an approved PVC tape (overlapped a minimum of 1/2 the tape width thereby
providing a minimum thickness of 40 mils) suitable for direct burial. See Section 500,
Paragraph 501.4 for Coating requirements.
7. A pull box with a sealable cover shall be installed for each 270 of conduit bends. In no case
shall pull boxes be more than 500 feet apart. Pull boxes shall normally be 6" x 18" x 18". If
installed outdoors or below grade, pull boxes shall be watertight and approved for the purpose.
All pull boxes shall be accessible after job completion. Pull box locations shall be approved by
Electric Meter Shop. The conduit system shall be a clean, usable system at the time CRA-ES
installs conductors.
Because each installation is different, the above general rules may not be all inclusive. Each
installation must be designed and approved on an individual basis; therefore, additional
requirements may be necessary.
07/23/2012
305.0
PAGE
40
C of Cabinet
L
36"
15"
30"
Height
48" Min
75" Max
Floor
NOTES:
1. Cabinet to be made with a minimum of 12 gauge steel.
2. Cabinet dimensions shown are minimums.
3. Cabinet to be painted to same specs and color as service entrance section.
4. Cover/door to be demountable and reversible.
5. Cover/door to be sealable.
6. 3/4" minimum plywood to be installed on back inside wall of cabinet. Size to be 24" x 24".
(See above)
7. Cabinet to be bonded to service entrance section with minimum of #8 copper wire.
8. Cabinet to be solidly anchored to the wall.
9. CRA-ES Meter Shop to determine size of conduit and point of entry into service sections.
10. Door to be hinged.
07/23/2012
305.2
PAGE
41
36"
Height
48" Min.
75" Max
15"
30"
CL
Plywood
Backing
Hasp
11"
11"
Floor
30"
15"
26"
15"
Type 3R
Overhang
Hinge
36"
12 Position
Ground Bar
30"
Side View
Note:
30"X36"X26" Outdoor Type 3R removable, reversible and
sealable Dead Front Cover. Steel required to be repainted
ANSI 61Gray Enamel.
Front View
NOTES:
07/23/2012
305.2
PAGE
42
306.0
Note 1
Note 11
2 X 12 boards, Unistrut
or 12 gauge steel plate
(Plywood Not Acceptable)
Unistrut
Main
Disconnect
Customer
Equipment
36" Max
Main
Disconnect
7' Max.
8' Max.
Note 2
Note 5
Grade
Grade
Note 5
Note 5
NOTES:
1. For minimum service heights see Section 400, paragraphs 401.0 and 401.0-3.
2. All wood posts and poles used for service equipment shall be full length pressure treated as per CRA-ES
specification MS-1900. See Section 400, paragraph 402.0 for wood pole requirements.
3. See Section 400, paragraph 402.3 for customer pole sizes and minimum setting depth.
4. See Section 700 - grounding and bonding.
5. Minimum dimensions of posts shall be:
A. Wood posts = 6" x 6" or 8" in diameter. (Maximum length - 10')
B. Pipe posts = 3" in diameter. (Maximum length - 10') Pipe posts to be of rigid galvanized steel, halflapped with 20 mil tape below grade, extending 6 above grade.
6. The post shall be placed in the center of a 12 inch minimum diameter concrete footing. The footing
shall be a minimum of 36 inches in the ground and extend a minimum of 4 inches above the ground
level, and have a 1/2 inch slope away from the post to allow for drainage. Except: concrete not required
for 6 x 6 or 8 dia. post buried 48.
7. For underground applications delete overhead pole, use post and attach underground riser to post per
paragraph 501.3 of the 500 Section of this book.
8. All boards, steel and unistrut shall be attached to pole or post securely with a minimum 1/2" galvanized
through bolt with a 1-1/2" galvanized backing and a lock nut. Nails or lag screws will not be acceptable.
Pole shall be notched to the depth of the unistrut. (1" unistrut maximum)
9. All service equipment shall be securely fastened to boards or steel with minimum 1/4" through bolts.
Nails or lag screws will not be acceptable.
10. The meter can shall be as required by this book for each installation.
11. Conduit support. Not over 6 feet apart.
REVISION
07/23/2012
306.0
PAGE
43
307.0
Top View
Stem Wall
Side VIew
Front View
Finished Grade
Only rigid metal riser
shall be permitted, if
semi-flush or recessed,
no bends or offsets above
grade.
Stem Wall
Stem Wall
07/23/2012
307.0
PAGE
44