SmallSheds,CanopiesandTemporaryStructures
Canopiesorshedsover12sq.metersrequiresinglezonesmokedetectorsanda2A10BC
extinguisherincloseproximity.
Smallshedsorcanopieswithasourceofignition(heaters,fansorlightsetc.)thatare
energizedatanytimealsorequireasinglestagesmokedetectorandextinguisher.
Groupsofadjacentcanopiesorshedswithanaggregatesizeofmaximum30sq.meterswill
needtobeflameretardantandseparatedfromothergroupsby3meters.
Maximumsizeofsheds,canopiesortemporaryroofedstructuresis30sq.metersunless
approvedbyaFireInspectorinwriting.
Canopiesorshedsupto12sq.meterswithnosourceofignitiondonotrequireanything.
Allandanytentsoffabricsandcanopiesmustbeapprovedforindooruseandfire
retardant.AtaghastobeaccessibleandreadCAN/ULCS109.