Syabas Standard Drawing 02

The document contains technical drawings and notes for typical details of water supply infrastructure. It includes 3 sheets of drawings showing details of air valve chambers, butterfly valve chambers, scour valve chambers, sluice valve chambers, zone meter chambers, telemetry cabinets, pipe trenches, pipe crossings and bends, and air insertion points. The notes provide information on dimensions, materials, reinforcement, and revisions to the drawings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
875 views

Syabas Standard Drawing 02

The document contains technical drawings and notes for typical details of water supply infrastructure. It includes 3 sheets of drawings showing details of air valve chambers, butterfly valve chambers, scour valve chambers, sluice valve chambers, zone meter chambers, telemetry cabinets, pipe trenches, pipe crossings and bends, and air insertion points. The notes provide information on dimensions, materials, reinforcement, and revisions to the drawings.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 20

NOTE :

1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.


SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. ACTUAL LENGTH OF PE COMMUNICATION PIPES SHALL BE
DETERMINED ON SITE.

L
L

O
C

Y
P

G
I
R

T
H

E
R

R
E
S

D
E
V

REV. REVISED BY
DESCRIPTION
LPL/HS
Original drawing.
0
1

YHH

DATE
OCT. `06

PC chamber details removed.


18 APR. `11
Brickwall and RC chamber revised.
Chamber cover revised.
To remove concrete surround at the tee
for offset air valve chamber.

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF AIR VALVE CHAMBER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 001 / REV.1

NOTE :
1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.
SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. REINFORCEMENT CONCRETE 30/20.
4. LEAN CONCRETE GRADE 15/20.
5. ALL MS PLATE AND STEP IRONS TO BE HOT-DIPPED
GALVANISED TO BS 729.

L
A

O
C
L

Y
P

H
G
I
R

R
T

E
S
E

D
E
V
R

REV. REVISED BY
DESCRIPTION
Original drawing.
LPL/HS
0
1

YHH

Chamber cover revised.


Table for "Type Of Cover" removed.
Table for "Type of Chamber" removed.
Detail bypass for pipe 450 dia. and
above added.

DATE
OCT. `06
18 APR `11

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF BUTTERFLY VALVE CHAMBER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 002 / REV.1

NOTE:

1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.


2. ALL STEELWORK TO BE PAINTED WITH 2 COATS OF APPROVED
ANTI CORROSIVE PAINT/ EPOXY 325 MICRO DFT.
3. LEAN CONCRETE SHALL BE OF GRADE 15/20.
500
4. ALL VALVES SHALL BE OF DUCTILE IRON GRADE 7 PN 16 TO
SYABAS APPROVAL.
5. FOR SLUICE VALVE CHAMBER LOCATED WITHIN THE ROAD
SHALL USE RC COVER CHAMBER TO DETAILS.

L
A

C
L

Y
P
O

I
R

H
G

R
T

E
S
E

V
R

D
E

REV. REVISED BY
DESCRIPTION
0
Original drawing.
LPL/HS
1

YHH

The drawing to be seperated in two(2)


drawings.
Chamber for depth less than 1.0m
to be replace with brickwall instead of
PC chamber.
Chamber cover revised.

DATE
OCT. `06
18 APR `11

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF SCOUR VALVE CHAMBER
(FOR 500 DIA. AND BELOW)

DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 003 / 1 / REV.1

NOTE:

1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.


2. ALL STEELWORK TO BE PAINTED WITH 2 COATS OF APPROVED
ANTI CORROSIVE PAINT/ EPOXY 325 MICRO DFT.
3. LEAN CONCRETE SHALL BE OF GRADE 15/20.
500
4. ALL VALVES SHALL BE OF DUCTILE IRON GRADE 7 PN 16 TO
SYABAS APPROVAL.
5. FOR SLUICE VALVE CHAMBER LOCATED WITHIN THE ROAD
SHALL USE RC COVER CHAMBER TO DETAILS.

L
L

O
C

Y
P

G
I
R

T
H

E
R

R
E
S

D
E
V

REV. REVISED BY
DESCRIPTION
0
Original drawing.
LPL/HS
1

YHH

The drawing to be seperated in two(2)


drawings.
Chamber for depth less than 1.0m
to be replace with brickwall instead of
PC chamber.
Chamber cover revised.

DATE
OCT. `06
18 APR `11

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF SCOUR VALVE CHAMBER
(FOR 600 DIA. AND ABOVE)
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 003 / 2 / REV.1

NOTE:
1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.
SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. NUMBER OF PRE-CAST UNIT PER CHAMBER SHOWN ARE TENTATIVE
ONLY AND ACTUAL NUMBER SHALL BE DECIDED ON SITE. ANY EXTRA
UNIT REQUIRED SHALL BE DEEMED TO BE INCLUDED IN THE
TENDER RATE.
4. STEEL BARS SHALL BE MILD STEEL( 250N/mm2 ).
5. GASKET SHALL BE INSTAL BETWEEN PART OF THE PRE-CAST
CHAMBER DURING INSTALLATION.
6. MINIMUM CONCRETE GRADE 30 N/mm2 .

L
L
A

O
C

Y
P

I
R

H
G

R
T

E
S
E

V
R

D
E

REV. REVISED BY
LPL/HS
0
1

YHH

DESCRIPTION
Original drawing.

DATE
OCT. `06

Typical details of chamber using PC and 18 APR `11


DI pipe added.

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF SLUICE VALVE CHAMBER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 004 / REV.1

NOTE :
1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.
SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. THRUST BLOCK TO BE CAST AGAINST UNDISTURBED GROUND.
4. FOR ALL STEEL PIPES, NO ALLOWANCE FOR INTERNAL LINING
CUTBACK TO BE PROVIDED.
5. ALL EXPOSED STEEL TO BE PAINTED WITH 2 PACK HIGH SOLIDS
EPOXY PAINT TO MIN. 150 um.
a. CHEQUER PLATE : LIGHT BLUE ELITE - P396 - 11463.
b. BRICK CHAMBER : UNDER COAT - PRIMIER SEALER - DPP 1035
FINISHING COAT - WEATHER COAT - DPW 9102.

L
A

C
L

Y
P
O

I
R

H
G

R
T

E
S
E

V
R

D
E

REV. REVISED BY
DESCRIPTION
1
EXCO
Replaced chequered plate cover with
composite pc slab.

DATE
25 JUNE `10

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
DETAILS OF ZONE METER CHAMBER
DRAWN BY : SHAHRUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT. 2006

DRAWING NO :

SYA / TD / 007 / REV. 1

NOTE :
1. FOR LEGEND,ABBREVIATIONS AND GENERAL NOTES, SEE DWG NO:.
SYA/STD/001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.

Y
P
O
C
L
L
A

D
E
V
R
E
S
E
R
T
H
G
I
R
REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT:

DRAWING TITLE :
DETAILS OF TELEMETRY CABINET
DRAWN BY : SHAHRUL

DESIGNED : SHAIFUL

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2006

DRAWING NO :
SYA / TD / 008

NOTE:
1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.
SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. ALL CONCRETE TO BE GRADE 25 UNLESS OTHERWISE STATED.
4. THE 300mm THK. SAND UNDER THE PIPE SHALL BE COMPACTED
IN LAYER OF 150mm.

L
L
A

O
C

Y
P

G
I
R

T
H

E
R

R
E
S

D
E
V

REV. REVISED BY
DESCRIPTION
Original drawing.
0
LPL/HS
1

DATE
APR `06

To remove the concrete surround and 01 APR `11


replaced with pipe protection.
Normal trench for MS & PE have been
combined as one detail.
For trench under road pavement and
under hard standing tiles have been
combined as one detail.

YHH

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF PIPE TRENCH
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

CHECKED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO:

SYA / TD / 009 / REV. 1

NOTE :
1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO.
SYA / STD / 001.
2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
3. S-BEND FOR PIPES 600mm DIA. AND BELOW SHALL BE OF FLANGE
ENDED MILD STEEL OR DUCTILE IRON.

L
L

O
C

Y
P

I
R

H
G

R
T

E
S
E

V
R

D
E

REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

JOB TITLE :

DRAWING TITLE :

TYPICAL DETAILS OF PIPE CROSSING AND


SPIKE GUARD
DRAWN BY : SHAHRUL

DESIGNED : SAT

CHECKED : HS

APPROVED : LPL

SCALE : NTS

DATE : OCT 2006

DRAWING NO :

SYA / TD / 010

NOTE:

1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.


2. GRADE 316 SS PIPE SHALL BE USED AT LOCATION WITH
CORROSION SOIL CONDITION AND ALONG COASTAL AREA.
3. GRADE 304 SS PIPE SHALL BE USED AT LOCATION WITH
NORMAL SOIL CONDITION.

L
L

O
C

Y
P

I
R

H
G

R
T

E
S
E

V
R

D
E

REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :
AIR INSERTION POINT

DRAWING TITLE :
DETAILS OF AIR INSERTION POINT AND PRECAST CHAMBER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 011

NOTE:
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.

C
L
L
A

Y
P
O

I
R

H
G

R
T

R
E
S
E

D
E
V

REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
DETAILS OF MULTIPLE SHAPED CHAMBER COVER TYPE A
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : HS

APPROVED : SS

SCALE : AS SHOWN

DATE : JULY 2010

DRAWING NO :

SYA / TD / 012

NOTE:
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.

L
L
A

Y
P
O
C

H
G
I
R

E
R
T

D
E
V
R
SE

REV.

DATE

DESCRIPTION

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
DETAILS OF MULTIPLE SHAPED CHAMBER COVER TYPE B
DRAWN BY : SHAHRUL

DESIGNED :

CHECKED : HS

APPROVED : SS

SCALE : AS SHOWN

DATE : JULY 2010

DRAWING NO :

SYA / TD / 013

YHH

NOTE :
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
2. THE MINIMUM SPACING BETWEEN THE OUTER BRIM OF FLANGES
AND THE RC WALL AND FLOOR SHOULD BE 600mm.
3. ALL METALS SHALL BE PAINTED WITH ANTI-RUST AND 2 LAYERS OF
PAINT APPROVED BY SYABAS.
4. BRICK CHAMBER SHALL BE PAINTED WITH UNDER COAT,
PRIMIER SEALER, FINISHING COAT - WEATHER COAT.

L
L
A

Y
P
O
C

I
R

H
G

R
E
S
E
R
T

D
E
V

REV. REVISED BY

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
DETAILS OF COMPOSITE CHAMBER COVER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : HS

APPROVED : SS

SCALE : NTS

DATE : JULY 2010

DRAWING NO :

SYA / TD / 014

NOTE:

1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.


2. CONNECTION BETWEEN HDPE PIPE AND HDPE FITTING (ELBOW,
BEND, TEE, etc) SHALL BE BY ELECTROFUSION COUPLER.
3. CONNECTION BETWEEN HDPE PIPE WITH METALLIC FITTING
AND PIPE SHALL BE BY STUB END JOINT.
4. MS PIPE BELOW 700mm SHALL BE FLANGED JOINT.
5. JOINTING BETWEEN HDPE PIPES SHALL BE BUTT FUSION.

L
L

O
C

Y
P

G
I
R

T
H

E
R

R
E
S

D
E
V

REV.

DATE

DESCRIPTION

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
JOINTING DETAILS OF HDPE / MS PIPE

DRAWN BY : SHAHRUL

DESIGNED :

KA

CHECKED : YHH

APPROVED : SS

SCALE : NTS

DATE :

DRAWING NO :

SYA / TD / 015

OCT. 2010

NOTE:
SHORT PIECE
LENGTH TO SUIT

SLUICE VALVE

600 x 600 x 300 SUMP

200

WIDTH

200

200

200

200

200

200

PIPE SIZE
(D)

WIDTH
TO SUIT

600

TO SUIT
25 DIA. STEP IRON
STAGGERED AT 300 CRS

C
d

150

150

SV1

TS AV

600

SV2

FLOW

FLANGE
ADAPTOR

FLANGE JOINT

250

SV3

600

SEE DETAIL `A'

150

SEE DETAIL `A'

A
600

ALTITUDE VALVE

150

PLAN

DETAIL `X'

TYPICAL DETAIL OF ALTITUDE VALVE WITH STRAINER

`C` CHANNEL MS
75 x 37.5 x 4.1mm THK.

150

100

ALTITUDE VALVE

TO BE DECIDED
ON SITE

GL
25 DIA. STEP IRON
STAGGERED AT 300 CRS
TEE

160

CONCRETE GRADE 25 C/W


BRC NO 10 PLUS WATER
PROOFING CEMENT
(1 LAYER)

110 x 80 x 12mm
MS HOLDER

`L' CHANNEL MS
CONCRETE SLAB
GRADE 25
BRC A6

600

FALL

SECTION C-C
600 x 600 x 300 SUMP

50 THK. BLINDING
CONCRETE

FLANGE
ADAPTOR

CONCRETE
SUPPORT

50 THK. BLINDING CONCRETE

T10-200 BOTHWAY

6mm CHEQUER PLATE

0
16

`C` CHANNEL MS
75 x 37.5 x 4.1mm THK.

20
0

250

300

350

300

350

400

350

400

450

400

450

500

450

500

600

550

600

700

650

700

800

750

900

850

100

Y
P
O
C
L
L
A
B

LIFTING HANDLE

900

1500

900

1000

600

900

600

800

600

700

600

600

600

500

400

450

400

400

400

300

400

200

350

150

300

100

250

90

200

80

200

75

200

60

150

50

150

DETAIL OF CENTER PIECE

DETAIL `X'

150

40

150

30

100

20

100

10

65

65

65

50

50

50

EITHER HALF PORT


OR FULL PORT
ALTITUDE VALVE
TO BE APPROVED
BY SYABAS

FULL PORT
ALTITUDE VALVE

REV.

20
0

100

S
RIE

VA

60

VARIES

PLAN
TYPICAL DETAIL OF RC SLAB COVER

20
0

DATE

RIE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD

0
16

100

DESCRIPTION

1. TO AVOID ANY CAVITATION, THE VELOCITY MUST


NOT LESS THAN 2m/s AND NOT MORE THAN 6m/s.

100

VA

45

TYPE OF
ALTITUDE VALVE

NOTE :

VARIES

RECOMMENDED
MINIMUM SIZE OF
ALTITUDE VALVE
(mm)

2000

110 x 80 x 12mm
MS HOLDER

50 x 50 x 4.1mm THK.
`L` CHANNEL

25
0

600 x 600 OPENING


FOR PUMP

900 x 900 ACCESS


OPENING

SECTION D-D

250

SECTION A-A

75 THK. PC
SLAB COVER

250

300

0
16

R10 MS RING

PETI SURAT 5001,


JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

CONCRETE SLAB
GRADE 25

60

FLOW

200

200

D
E
V
R
E
S
E
R
T
H
G
I
R

T10 MS RING
T-POT STRAINER
SLUICE VALVE

150

250

RECOMMENDED SIZE OF ALTITUDE VALVE

PLAN VIEW

Q
(l/s)

100

200

250

150

SLUICE VALVE

T-POT
STRAINER

T-POT
STRAINER SIZE
(TS)

SENSING LINE

500 LONG
SHORT PIECE

500 LONG
SHORT PIECE

BYPASS
PIPE SIZE
(d)

1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED.


2. ALL BEND AND TEE SHALL HAVE CONCRETE SUPPORT.
3. ALL JOINT FOR PIPE 700 DIA. AND ABOVE SHALL BE OF FLANGE JOINT.

60 x 60 x 4.1mm THK.

60 x 60 x 4.1mm THK.
`L' CHANNEL
COLLAR/FLANGE
JOINT

(FOR VALVE SIZE 600 DIA. AND ABOVE)

BRICKWALL

PROJECT :

DETAILS OF PC SLAB COVER


(FOR VALVE SIZE 400 DIA. AND BELOW)

VARIES

CONCENTRIC TAPER
IF REQUIRED
LIFTING RING

CONCRETE GRADE 25

SHORT PIECE
LENGTH TO SUIT

DETAIL `A'

TYPICAL DETAIL OF ALTITUDE VALVE WITH STRAINER


DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

75

(USING TAPER/REDUCER WHERE PIPE SIZE


GRATER THAN THE SELECTED VALVE)

DRAWING TITLE :

BRC A8

SECTION B-B

DRAWING NO :

SYA / TD / 016

NOTE :
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
2. FLANGED JOINT TYPE SHALL BE USE FOR PIPE BELOW 600 DIA.

L
L
A

O
C

Y
P

G
I
R

T
H

E
R

E
S

V
R

D
E

REV. REVISED BY

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
LAYOUT PLAN OF PRESSURE REDUCING VALVE
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO :

SYA / TD / 017

NOTE:
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
2. ALL CONCRETE TO BE GRADE 25 UNLESS OTHERWISE STATED.

Y
P
O
C
L
L
A

D
E
V
R
E
S
E
R
T
H
G
I
R
REV. REVISED BY

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF THERMOSPLACTIC, DI AND MS PIPE
TRENCH FOR CONCRETED ROAD SHOULDER
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO:

SYA / TD / 018

NOTE:
1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED.
2. THIS CONCEPTUAL DRAWING IS FOR ILLUSTRATION PURPOSE
ONLY. THE DETAILED STRUCTURAL DESIGN SHALL BE CARRIED
OUT AND ENDORSED BY A PROFESSIONAL ENGINEER.
3. OTHER OPTIONS MAY BE CONSIDERED BUT MUST BE RC
STAIRCASE.

L
L
A

Y
P
O
C

I
R

H
G

R
T

R
E
S
E

D
E
V

REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF INTERNAL STAIRCASE
FOR RC RESERVOIR
DRAWN BY : SHAHRUL

DESIGNED :

YHH

CHECKED : KTT

APPROVED : SS

SCALE : AS SHOWN

DATE : JUNE 2011

DRAWING NO:

SYA / TD / 019

NOTE:
1. ALL DIMENSION ARE IN mm UNLESS OTHERWISE STATED.
2. THIS CONCEPTUAL DRAWING IS FOR ILLUSTRATION PURPOSE
ONLY. THE DETAILED STRUCTURAL DESIGN SHALL BE CARRIED
OUT AND ENDORSED BY A PROFESSIONAL ENGINEER.
3. OTHER OPTIONS MAY BE CONSIDERED BUT MUST BE RC
STAIRCASE.

L
L
A

O
C

Y
P

I
R

H
G

R
T

E
S
E

V
R

D
E

REV.

DATE

DESCRIPTION

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD

PETI SURAT 5001,


JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

X
PROJECT :

DRAWING TITLE :
TYPICAL DETAILS OF EXTERNAL STAIRCASE
FOR RC RESERVOIR
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED :

APPROVED :

KTT

SCALE : NTS

SS

DATE : JUNE 2011

DRAWING NO:

SYA / TD / 020

NOTE:
1. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED.
2. FOR DIMENSIONS X & Y ( X+Y = 90m ).

WATER PIPE
TO BE DOWNSIZED

SUBJECTED TO MIN. PIPE SIZE


AT 150mm
WATER PIPE TO BE DOWNSIZED

SCOUR VALVE

90m

90m

SCOUR VALVE

90m

SUBJECTED TO MIN. PIPE SIZE


AT 150mm

E
R

FOR BRANCH < 90m


(DOWNSIZE)

90m

WATER PIPE
TO BE DOWNSIZED

90m

O
C

SCOUR VALVE

Y
P

SUBJECTED TO MIN. PIPE SIZE


AT 150mm
WATER PIPE
TO BE DOWNSIZED

WATER PIPE
TO BE DOWNSIZED

L
L

(DOWNSIZE)

G
I
R

FOR BRANCH > 90m

SCOUR VALVE

90m

SUBJECTED TO MIN. PIPE SIZE


AT 150mm

T
H

R
E
S

D
E
V

90m

FOR BRANCH BOTH SIDE OF LANE (1)

FOR BRANCH BOTH SIDE OF LANE (2)

(DOWNSIZE)

(DOWNSIZE)

REV.

DESCRIPTION

DATE

SYABAS

SYARIKAT BEKALAN AIR SELANGOR SDN BHD


PETI SURAT 5001,
JALAN PANTAI BAHRU,
59990, KUALA LUMPUR.
TEL NO : 03 - 2282 6244 / 03 - 2283 1111
FAX NO : 03 - 2282 5498
LAMAN WEB : www.syabas.com.my
EMAIL : [email protected]

TABLE FOR PIPE SIZING


PEAK FLOW
Q ( /s)

PE PIPE SIZE
OD (mm)

DI PIPE SIZE
ND (mm)

UP TO 0.55

63

NA

UP TO 1.40

90

NA

UP TO 2.96

125

100

UP TO 8.60

180

150

PROJECT :

DRAWING TITLE :
DOWNSIZING OF PIPE SIZE AND REPOSITIONING
OF FIRE HYDRANT
DRAWN BY : SHAHRUL

DESIGNED : YHH

CHECKED : KTT

APPROVED : SS

SCALE : NTS

DATE : JUNE 2011

DRAWING NO:

SYA / TD / 021