Panel No. Designation: 1. General Data and Information

This document summarizes the testing and inspection of a METASOL MR-4 2a2b protective relay with a 57.7V AC rating and 2NO + 2NC contacts. Section 1 provides general information on the relay. Section 2 describes performing a visual inspection and checks of mechanical components. Section 3 outlines electrical tests of contact continuity, resistance, flag operation, reset operation, and coil resistance. Section A-C details pickup/drop off testing, operating/reset time testing, and relay burden testing along with limits and results. Section 4 lists the test equipment used.

Uploaded by

Anonymous VXpghP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
13 views

Panel No. Designation: 1. General Data and Information

This document summarizes the testing and inspection of a METASOL MR-4 2a2b protective relay with a 57.7V AC rating and 2NO + 2NC contacts. Section 1 provides general information on the relay. Section 2 describes performing a visual inspection and checks of mechanical components. Section 3 outlines electrical tests of contact continuity, resistance, flag operation, reset operation, and coil resistance. Section A-C details pickup/drop off testing, operating/reset time testing, and relay burden testing along with limits and results. Section 4 lists the test equipment used.

Uploaded by

Anonymous VXpghP
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

1.

General Data and Information:


Panel No.
Make
Serial No.
Model No.

LS
METASOL

Designation
Type
Aux. Voltage
No. of Contacts

MR-4 2a2b
57.7V AC
2NO + 2NC

2. Mechanical Checks and Visual Inspection: (Ref: 4.1 of TCS-P-105-R1)


Item
1
2
3
4
5
6
7
3.

Description
Inspect for any physical damage or defects.
Verify connections as per approved drawings.
Check tightness of all connections.
Check that serial no. of relay matching with serial no. of case.
Check condition of any connectors, contacts alignment and travel.
(if applicable)
Check armature gap. (if applicable)
Check Reset mechanism.

Remarks

N/A

Electrical Test: (Ref: 4.2 of TCS-P-105-R1)

Item
1
2
3
4
5
7

Description
Check the continuity of the contacts.
All output contacts resistance measured (0.2 Max).
Check Flag Operation (if applicable).
Check Reset Operation.
Check operating Coil resistance.
Voltage operated relays to have a pickup voltage less than 80% of
the rated substation voltage to allow for proper operation of the relay
even during substation DC under-voltage condition.

Remarks
N/A

A) Pickup & Drop Off Test:


Pick Up
Voltage (V)
Current (mA)
Tested by
Name:
Signature:
Date:

Drop off
Voltage (V)
Current (mA)

Contact terminals

Witnessed by

Limit:

(According to relay catalogue page NO.

B) Operating and Drop Off Time Test:


Operating Time (mSec)

Contact Terminals

Limit:

Reset time (mSec)

Contact Terminals

(According to Relay, catalogue page NO.

C) RELAY Burden Test:


Voltage Applied (Volts)

Measure Current (mA)

Limit:

Relay Burden
Actual Value (W)

Relay Burden
Measured Value(W)

(According to relay catalogue page NO.

4. Test Equipment Used


Item

Test Equipment

Serial Number

Calibration
Date

SVERKER 780

1301404

05-10-13

Tested by
Name:
Signature:
Date:

Witnessed by

Calibration
Due Date
05-10-14