Voltage Drop Calculation

This document contains a voltage drop calculation for the electrical distribution system of an infectious diseases hospital. It lists the electrical loads connected to different feeders, including details like load size, cable size, length and calculated voltage drops. The maximum allowed voltage drop is specified as 2.5%. Voltage drops are calculated for each section of cable and feeder and summed to get the total voltage drop, which is within limits for all cases.

Uploaded by

Atef Mohameden
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
129 views

Voltage Drop Calculation

This document contains a voltage drop calculation for the electrical distribution system of an infectious diseases hospital. It lists the electrical loads connected to different feeders, including details like load size, cable size, length and calculated voltage drops. The maximum allowed voltage drop is specified as 2.5%. Voltage drops are calculated for each section of cable and feeder and summed to get the total voltage drop, which is within limits for all cases.

Uploaded by

Atef Mohameden
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 6

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42

VOLTAGE DROP CALCULATION


REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.


1

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

MLTP1A
1.1

CHILLER-1

MLTP1A

1001.000

3 PHASE

3000A B.B

55

415.00

1740.80

0.00

2.24

2.24

0.54%

1.2

COOLING TOWER-1

MLTP1A

37.500

3 PHASE

50

115

415.00

65.21

0.87

0.00

6.52

6.52

1.57%

1.3

SECONDERY CHW PUMP-1

MLTP1A

94.000

3 PHASE

185

66

415.00

163.47

0.26

0.00

2.81

2.81

0.68%

1.4

PRIMARY CHW PUMP-1

MLTP1A

40.000

3 PHASE

50

60

415.00

69.56

0.87

0.00

3.63

3.63

0.87%

1.5

CONDENSING-1

MLTP1A

90.000

3 PHASE

150

68

415.00

156.52

0.3

0.00

3.19

3.19

0.77%

1.6

BOILER-1

MLTP1A

150.000

3 PHASE

240

90

415.00

260.86

0.21

0.00

4.93

4.93

1.19%

MLTP1B
2.1

TVSS

MLTP1B

2.200

3 PHASE

415.00

3.83

6.8

0.00

0.16

0.16

0.04%

2.2

CHILLER-2

MLTP1B

1001.000

3 PHASE

3000A B.B

60

415.00

1740.80

0.00

2.44

2.44

0.59%

2.3

COOLING TOWER-2

MLTP1B

37.500

3 PHASE

50

116

415.00

65.21

0.87

0.00

6.58

6.58

1.59%

2.4

SECONDERY CHW PUMP-2

MLTP1B

94.000

3 PHASE

185

68

415.00

163.47

0.26

0.00

2.89

2.89

0.70%

2.5

PRIMARY CHW PUMP-2

MLTP1B

40.000

3 PHASE

50

61

415.00

69.56

0.87

0.00

3.69

3.69

0.89%

2.6

CONDENSING-2

MLTP1B

90.000

3 PHASE

150

69

415.00

156.52

0.3

0.00

3.24

3.24

0.78%

2.7

BOILER-2

MLTP1B

150.000

3 PHASE

240

92

415.00

260.86

0.21

0.00

5.04

5.04

1.21%

MLTP 2A
3.1

CHILLER-3

MLTP 2A

1001.000

3 PHASE

3000A B.B

65

415.00

1740.80

0.00

2.65

2.65

0.64%

3.2

COOLING TOWER-3

MLTP 2A

37.500

3 PHASE

50

117

415.00

65.21

0.87

0.00

6.64

6.64

1.60%

3.3

SECONDERY CHW PUMP-3

MLTP 2A

94.000

3 PHASE

185

69

415.00

163.47

0.26

0.00

2.93

2.93

0.71%

3.4

PRIMARY CHW PUMP-3

MLTP 2A

40.000

3 PHASE

50

57

415.00

69.56

0.87

0.00

3.45

3.45

0.83%

3.5

CONDENSING-3

MLTP 2A

90.000

3 PHASE

150

69

411.55

157.83

0.3

0.00

3.27

3.27

0.79%

3.6

BOILER-3

MLTP 2A

150.000

3 PHASE

240

93

411.55

263.05

0.21

0.00

5.14

5.14

1.24%

MLTP 2B
4.1

CHILLER-4 (STAND BY)

MLTP 2B

1001.000

3 PHASE

3000A B.B

70

415.00

1740.80

0.00

2.85

2.85

0.69%

4.2

COOLING TOWER-4 (STAND BY)

MLTP 2B

37.500

3 PHASE

50

118

415.00

65.21

0.87

0.00

6.69

6.69

1.61%

4.3

SECONDERY CHW PUMP-4 (STAND BY)

MLTP 2B

94.000

3 PHASE

185

70

415.00

163.47

0.26

0.00

2.98

2.98

0.72%

4.4

PRIMARY CHW PUMP-4 (STAND BY)

MLTP 2B

40.000

3 PHASE

50

58

415.00

69.56

0.87

0.00

3.51

3.51

0.85%

Infousectious diseases Hospital

1 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

4.5

CONDENSING-4 (STAND BY)

MLTP 2B

90.000

3 PHASE

150

70

415.00

156.52

0.3

0.00

3.29

3.29

0.79%

4.6

BOILER-4 (STAND BY)

MLTP 2B

150.000

3 PHASE

240

95

415.00

260.86

0.21

0.00

5.20

5.20

1.25%

4.7

FIRE PUMP 1

MLTP 2B

120.000

3 PHASE

240

70

415.00

208.69

0.21

0.00

3.07

3.07

0.74%

4.8

FIRE PUMP 2

MLTP 2B

120.000

3 PHASE

240

72

415.00

208.69

0.21

0.00

3.16

3.16

0.76%

4.9

JOCKEY PUMP

MLTP 2B

7.500

3 PHASE

16

70

415.00

13.04

2.5

0.00

2.28

2.28

0.55%

4.1

SAND FILTER

MLTP 2B

4.500

3 PHASE

16

45

415.00

7.83

2.5

0.00

0.88

0.88

0.21%

4.11

BOOSTER PUMP

MLTP 2B

45.000

3 PHASE

70

65

415.00

78.26

0.6

0.00

3.05

3.05

0.74%

4.12

HEAT EXCHANGER-1

MLTP 2B

122.000

3 PHASE

240

65

415.00

212.17

0.21

0.00

2.90

2.90

0.70%

B.B-1

MLTP 5A

866.000

3 PHASE

2500A B.B

115

415.00

1506.02

0.00

4.47

4.47

1.08%

5.1.1

MSB-BF-1(LIGHT & POWER)

B.B-1

78.000

3 PHASE

120

410.53

137.12

0.37

4.47

0.36

4.83

1.16%

5.1.2

MSB-BF-2(LIGHT & POWER)

B.B-1

26.000

3 PHASE

35

75

410.53

45.71

1.15

4.47

3.94

8.41

2.03%

5.1.3

MSB-GF-1(LIGHT & POWER)

B.B-1

72.000

3 PHASE

120

410.53

126.58

0.37

4.47

0.33

4.80

1.16%

5.1.4

MSB-GF-2(LIGHT & POWER)

B.B-1

54.000

3 PHASE

120

100

410.53

94.93

0.37

4.47

3.51

7.98

1.92%

5.1.5

MSB-GF-4

B.B-1

234.000

3 PHASE

3 X 150

100

410.53

411.37

0.1

4.47

4.11

8.58

2.07%

5.1.6

MSB-1F-1(LIGHT & POWER)

B.B-1

60.000

3 PHASE

70

410.53

105.48

0.6

4.47

0.44

4.91

1.18%

5.1.7

MSB-1F-2(LIGHT & POWER)

B.B-1

45.000

3 PHASE

95

100

410.53

79.11

0.45

4.47

3.56

8.03

1.93%

5.1.8

MSB-1F-4

B.B-1

120.000

3 PHASE

240

100

410.53

210.96

0.21

4.47

4.43

8.90

2.14%

5.1.9

MSB-2F-1(LIGHT & POWER)

B.B-1

45.000

3 PHASE

50

410.53

79.11

0.87

4.47

0.48

4.95

1.19%

5.1.10

MSB-3F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

50

410.53

66.80

0.87

4.47

0.41

4.88

1.18%

5.1.11

MSB-4F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

50

410.53

66.80

0.87

4.47

0.41

4.88

1.18%

5.1.12

MSB-5F-1(LIGHT & POWER)

B.B-1

38.000

3 PHASE

25

410.53

66.80

0.87

2.28

0.41

2.69

0.65%

5.1.13

MSB-RF-1(LIGHT & POWER)

B.B-1

18.000

3 PHASE

16

410.53

31.64

2.5

2.28

0.55

2.84

0.68%

MLTP 3A
5.1

MLTP 3B
6.1

B.B-2

MLTP 5B

455.740

3 PHASE

1350A B.B

110

415.00

792.56

0.00

4.63

4.63

1.12%

6.2

B.B-10

MLTP 5B

535.000

3 PHASE

1600A B.B

55

415.00

930.40

0.00

2.20

2.20

0.53%

MCC-BF-1 (FOR A/C's)

B.B-2

27.260

3 PHASE

35

410.37

47.94

1.15

4.63

0.39

5.02

1.21%

6.1.1

Infousectious diseases Hospital

2 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

6.1.2

MCC-BF-2 (FOR A/C's)

B.B-2

27.260

3 PHASE

50

75

410.37

47.94

0.87

4.63

3.13

7.76

1.87%

6.1.3

MCC-GF-1 (FOR A/C's)

B.B-2

18.250

3 PHASE

25

410.37

32.10

1.65

4.63

0.37

5.00

1.20%

6.1.4

MCC-GF-2 (FOR A/C's)

B.B-2

18.250

3 PHASE

35

100

410.37

32.10

1.15

4.63

3.69

8.32

2.01%

6.1.5

MCC-1F-1 (FOR A/C's)

B.B-2

19.460

3 PHASE

25

410.37

34.22

1.65

4.63

0.40

5.03

1.21%

6.1.6

MCC-1F-2 (FOR A/C's)

B.B-2

19.460

3 PHASE

35

100

410.37

34.22

1.15

4.63

3.94

8.57

2.06%

6.1.7

MCC-2F-1 (FOR A/C's)

B.B-2

4.300

3 PHASE

16

410.37

7.56

2.5

4.63

0.13

4.76

1.15%

6.1.8

MCC-3F-1 (FOR A/C's)

B.B-2

4.300

3 PHASE

16

410.37

7.56

2.5

4.63

0.13

4.76

1.15%

6.1.9

MCC-4F-1 (FOR A/C's)

B.B-2

3.700

3 PHASE

16

410.37

6.51

2.5

4.63

0.11

4.74

1.14%

6.1.10

MCC-5F-1 (FOR A/C's)

B.B-2

5.000

3 PHASE

16

410.37

8.79

2.5

4.63

0.15

4.78

1.15%

6.1.11

MCC-RF-1 (FOR A/C's)

B.B-2

308.500

3 PHASE

3 X 240

410.37

542.55

0.07

4.63

0.27

4.90

1.18%

6.2.1

MSB-KIT-1

B.B-10

179.000

3 PHASE

2 X 150

10

412.80

312.95

0.15

2.20

0.47

2.67

0.64%

6.2.2

MSB-KIT-2

B.B-10

179.000

3 PHASE

2 X 150

11

412.80

312.95

0.15

2.20

0.52

2.72

0.65%

6.2.3

MSB-KIT-3

B.B-10

179.000

3 PHASE

2 X 150

12

412.80

312.95

0.15

2.20

0.56

2.76

0.67%

1042.000

3 PHASE

3000A B.B

110

415.00

1812.10

0.00

4.66

4.66

1.12%

MLTP 4A
7.1

B.B-3

MLTP 4A

7.1.1

MSB-BF-3

B.B-3

27.000

3 PHASE

25

410.34

47.49

1.65

4.66

0.55

5.21

1.26%

7.1.2

MSB-BF-4

B.B-3

18.000

3 PHASE

25

75

410.34

31.66

1.65

4.66

3.92

8.58

2.07%

7.1.3

MSB-GF-3

B.B-3

312.000

3 PHASE

4 X 120

410.34

548.75

0.0925

4.66

0.36

5.02

1.21%

7.1.4

MSB-1F-3

B.B-3

80.000

3 PHASE

120

410.34

140.70

0.37

4.66

0.36

5.02

1.21%

7.1.5

MSB-1F-11(LAB)

B.B-3

80.000

3 PHASE

120

410.34

140.70

0.37

4.66

0.36

5.02

1.21%

7.1.6

MSB-2F-2

B.B-3

125.000

3 PHASE

240

410.34

219.85

0.21

4.66

0.32

4.98

1.20%

7.1.7

MSB-3F-2

B.B-3

125.000

3 PHASE

240

410.34

219.85

0.21

4.66

0.32

4.98

1.20%

7.1.8

MSB-4F-2

B.B-3

125.000

3 PHASE

240

28

410.34

219.85

0.21

4.66

1.29

5.95

1.43%

7.1.9

MSB-5F-2

B.B-3

170.000

3 PHASE

2 X 150

31

410.34

299.00

0.15

4.66

1.39

6.05

1.46%

1054.000

3 PHASE

3200A B.B

65

415.00

1832.97

0.00

2.17

2.17

0.52%

58.500

3 PHASE

95

412.83

102.27

0.45

2.17

0.32

2.49

0.60%

MLTP 4B
8.1
8.1.1

Infousectious diseases Hospital

B.B-4

MLTP 4B

MSB-BF-5(LIGHT & POWER)

B.B-4

3 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

8.1.2

MSB-BF-6(LIGHT & POWER)

B.B-4

58.500

3 PHASE

95

80

412.83

102.27

0.45

2.17

3.68

5.85

1.41%

8.1.3

MSB-GF-5(LIGHT & POWER)

B.B-4

36.000

3 PHASE

50

412.83

62.94

0.87

2.17

0.38

2.55

0.62%

8.1.4

MSB-GF-6(LIGHT & POWER)

B.B-4

36.000

3 PHASE

50

100

412.83

62.94

0.87

2.17

5.48

7.65

1.84%

8.1.5

MSB-GF-8

B.B-4

156.000

3 PHASE

2 X 120

412.83

272.72

0.185

2.17

0.35

2.52

0.61%

8.1.6

MSB-1F-5(LIGHT & POWER)

B.B-4

30.000

3 PHASE

50

412.83

52.45

0.87

2.17

0.32

2.49

0.60%

8.1.7

MSB-1F-6(LIGHT & POWER)

B.B-4

30.000

3 PHASE

50

100

412.83

52.45

0.87

2.17

4.56

6.73

1.62%

8.1.8

MSB-2F-3(LIGHT & POWER)

B.B-4

45.000

3 PHASE

50

412.83

78.67

0.87

2.17

0.48

2.65

0.64%

8.1.9

MSB-3F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.10

MSB-4F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.11

MSB-4F-6 (ICU)

B.B-4

100.000

3 PHASE

185

412.83

174.82

0.26

2.17

0.32

2.49

0.60%

8.1.12

MSB-4F-7 (ICU)

B.B-4

100.000

3 PHASE

185

412.83

174.82

0.26

2.17

0.32

2.49

0.60%

8.1.13

MSB-5F-3(LIGHT & POWER)

B.B-4

38.000

3 PHASE

50

412.83

66.43

0.87

2.17

0.40

2.57

0.62%

8.1.14

MSB-5F-6 (ICU)

B.B-4

136.000

3 PHASE

300

412.83

237.76

0.19

2.17

0.32

2.49

0.60%

8.1.15

MSB-5F-7 (ICU)

B.B-4

136.000

3 PHASE

300

412.83

237.76

0.19

2.17

0.32

2.49

0.60%

8.1.16

MSB-RF-2(LIGHT & POWER)

B.B-4

18.000

3 PHASE

25

412.83

31.47

1.65

2.17

0.36

2.53

0.61%

555.800

3 PHASE

2000A B.B

65

415.00

966.57

0.00

2.26

2.26

0.54%

MLTP 5A
9.1

B.B-5

MLTP 5A

9.1.1

MCC-BF-3(FOR A/C's)

B.B-5

27.260

3 PHASE

35

412.74

47.67

1.15

2.26

0.38

2.64

0.64%

9.1.2

MCC-BF-4(FOR A/C's)

B.B-5

27.260

3 PHASE

35

80

412.74

47.67

1.15

2.26

4.39

6.65

1.60%

9.1.3

MCC-GF-3(FOR A/C's)

B.B-5

18.280

3 PHASE

25

412.74

31.96

1.65

2.26

0.37

2.63

0.63%

9.1.4

MCC-GF-4(FOR A/C's)

B.B-5

18.280

3 PHASE

25

100

412.74

31.96

1.65

2.26

5.27

7.53

1.82%

9.1.5

MCC-1F-3(FOR A/C's)

B.B-5

19.460

3 PHASE

25

412.74

34.03

1.65

2.26

0.39

2.65

0.64%

9.1.6

MCC-1F-4(FOR A/C's)

B.B-5

19.460

3 PHASE

25

100

412.74

34.03

1.65

2.26

5.61

7.87

1.90%

9.1.7

MCC-2F-2(FOR A/C's)

B.B-5

4.300

3 PHASE

16

412.74

7.52

2.5

2.26

0.13

2.39

0.58%

9.1.8

MCC-3F-2(FOR A/C's)

B.B-5

4.300

3 PHASE

16

412.74

7.52

2.5

2.26

0.13

2.39

0.58%

9.1.9

MSB-3F-5 (ICU)

B.B-5

100.000

3 PHASE

185

412.74

174.86

0.26

2.26

0.32

2.58

0.62%

9.1.10

MCC-4F-2(FOR A/C's)

B.B-5

3.700

3 PHASE

16

412.74

6.47

2.5

2.26

0.11

2.37

0.57%

Infousectious diseases Hospital

4 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

9.1.11

MCC-5F-2(FOR A/C's)

B.B-5

5.000

3 PHASE

16

412.74

8.74

2.5

2.26

0.15

2.41

0.58%

9.1.12

MCC-RF-2(FOR A/C's)

B.B-5

308.500

3 PHASE

3 X 240

412.74

539.44

0.07

2.26

0.26

2.52

0.61%

1088.000

3 PHASE

3200A B.B

60

415.00

1892.09

0.00

2.09

2.09

0.50%

10

MLTP 5B
10.1

B.B-6

MLTP 5B

10.1.1

MSB-BF-7

B.B-6

18.000

3 PHASE

25

412.91

31.46

1.65

2.09

0.36

2.45

0.59%

10.1.2

MSB-BF-8

B.B-6

18.000

3 PHASE

25

412.91

31.46

1.65

2.09

0.36

2.45

0.59%

10.1.3

MSB-GF-7

B.B-6

156.000

3 PHASE

2 X 120

412.91

272.67

0.185

2.09

0.35

2.44

0.59%

10.1.4

MSB-1F-7

B.B-6

80.000

3 PHASE

120

412.91

139.83

0.37

2.09

0.36

2.45

0.59%

10.1.5

MSB-1F-8

B.B-6

80.000

3 PHASE

120

412.91

139.83

0.37

2.09

0.36

2.45

0.59%

10.1.6

MSB-2F-5 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.7

MSB-2F-6 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.8

MSB-2F-7 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.9

MSB-3F-6 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.10

MSB-3F-7 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.11

MSB-4F-5 (ICU)

B.B-6

100.000

3 PHASE

185

412.91

174.79

0.26

2.09

0.32

2.41

0.58%

10.1.12

MSB-5F-5 (ICU)

B.B-6

136.000

3 PHASE

300

412.91

237.71

0.19

2.09

0.32

2.41

0.58%

11

MLTB 6A
11.1

B.B-7

MLTB 6A

390.800

3 PHASE

1250A B.B

120

415.00

679.62

0.00

4.74

4.74

1.14%

11.2

B.B-8

MLTB 6A

607.500

3 PHASE

2000A B.B

120

415.00

1056.48

0.00

4.56

4.56

1.10%

11.2.1

MSB-BF-9(LIGHT & POWER)

B.B-8

58.500

3 PHASE

95

410.44

102.87

0.45

4.56

0.32

4.88

1.18%

11.2.2

MSB-GF-9(LIGHT & POWER)

B.B-8

72.000

3 PHASE

120

410.44

126.60

0.37

4.56

0.33

4.89

1.18%

11.2.3

MSB-LAUNDRY

B.B-8

240.000

3 PHASE

2 X 240

20

410.44

422.01

0.105

4.56

0.89

5.45

1.31%

11.2.4

MSB-1F-9(LIGHT & POWER)

B.B-8

60.000

3 PHASE

95

410.44

105.50

0.45

4.56

0.33

4.89

1.18%

11.2.5

MSB-2F-5(LIGHT & POWER)

B.B-8

45.000

3 PHASE

70

410.44

79.13

0.6

4.56

0.33

4.89

1.18%

11.2.6

MSB-3F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

11.2.7

MSB-4F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

11.2.8

MSB-5F-5(LIGHT & POWER)

B.B-8

38.000

3 PHASE

50

410.44

66.82

0.87

4.56

0.41

4.97

1.20%

Infousectious diseases Hospital

5 OF 6

REM.

INFECTIOUS DISEASES HOSPITAL-10-2012/2011/42


VOLTAGE DROP CALCULATION
REFERENCE -GULF CABLE CATALOGUE AND SCHNEIDER ELECTRIC B.B CATALOGUE

TREE CODE NO.

NAME

FED FROM

LOAD
(KW)

LOAD
TYPE

B.B/CABLE
section(mm2)

LENGTH
(m)

VOLTAGE
(V)

I
(A)

V.D./A*KM

FIRST
STAGE (V)

FINAL
TOTAL VOLTAGE
STAGE (V)
DROP (V)

VD/V%
<2.5%

11.2.9

MSB-RF-5(LIGHT & POWER)

B.B-8

18.000

3 PHASE

25

410.44

31.65

1.65

4.56

0.37

4.93

1.19%

11.1.1

MCC-BF-5(FOR A/C's)

B.B-7

27.260

3 PHASE

35

410.26

47.95

1.15

4.74

0.39

5.13

1.24%

11.1.2

MCC-GF-5(FOR A/C's)

B.B-7

18.280

3 PHASE

35

100

410.26

32.16

1.15

4.74

3.70

8.44

2.03%

11.1.3

MCC-1F-5(FOR A/C's)

B.B-7

19.460

3 PHASE

25

410.26

34.23

1.65

4.74

0.40

5.14

1.24%

11.1.4

MCC-2F-3(FOR A/C's)

B.B-7

4.300

3 PHASE

16

410.26

7.56

2.5

4.74

0.13

4.87

1.17%

11.1.5

MCC-3F-3(FOR A/C's)

B.B-7

4.300

3 PHASE

16

410.26

7.56

2.5

4.74

0.13

4.87

1.17%

11.1.6

MCC-4F-3(FOR A/C's)

B.B-7

3.700

3 PHASE

16

410.26

6.51

2.5

4.74

0.11

4.85

1.17%

11.1.7

MCC-5F-3(FOR A/C's)

B.B-7

5.000

3 PHASE

16

410.26

8.80

2.5

4.74

0.15

4.89

1.18%

11.1.8

MCC-RF-2(FOR A/C's)

B.B-7

308.500

3 PHASE

3 X 240

410.26

542.70

0.07

4.74

0.27

5.01

1.21%

1035.000

3 PHASE

3200A B.B

115

415.00

1799.92

0.00

3.81

3.81

0.92%

12

MLTP 6B
12.1

B.B-9

MLTP 6B

12.1.1

MSB-BF-10

B.B-9

18.000

3 PHASE

25

411.19

31.59

1.65

3.81

0.36

4.17

1.01%

12.1.2

MSB-GF-10

B.B-9

312.000

3 PHASE

3 X 185

411.19

547.61

0.0867

3.81

0.33

4.14

1.00%

12.1.3

MSB-1F-10

B.B-9

160.000

3 PHASE

2 X 120

411.19

280.83

0.185

3.81

0.36

4.17

1.01%

12.1.4

MSB-2F-6 (MEDICAL EQUIPMENTS)

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.5

MSB-3F-6

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.6

MSB-4F-6

B.B-9

125.000

3 PHASE

240

411.19

219.40

0.21

3.81

0.32

4.13

1.00%

12.1.7

MSB-5F-6

B.B-9

170.000

3 PHASE

2 X 120

411.19

298.38

0.185

3.81

0.39

4.20

1.01%

Infousectious diseases Hospital

6 OF 6

REM.