PSV Scenario and Calculation
PSV Scenario and Calculation
Unfired Boilers
(ASME Sect I)
Piping
(ASME B16.5 and 31.3)
106
103
Kerosene Pumparound
LP Steam Generator
106
106
PSV SCENARIOS
(Refer API 521)
FOCUS ON COMMON CASES :
- Closed Outlets on Vessels
- External Fire
- Failure of Automatic Controls
- Hydraulic Expansion
- Heat Exchanger Tube Rupture
- Total Power Failure
- Partial
P i lP
Power Failure
F il
- Cooling Water Failure
- Reflux Loss
- Failure of Air-Cooled Heat X
DOUBLE JEOPARDY NOT
CONSIDERED
(Simultaneous occurrence of two or
more unrelated causes of
6
overpressure)
Effects
Pressure built-up in vessel
Calculation
No
Yes
Relief
R
li f case not
considered
Relief rate =
maximum inlet flow
Case 2 :
C
If adequate drainage and firefighting equipment do not exist.
Q = 70,900 x F x A0.82
Q = Heat absorbed by liquid from external fire(W)
F = Environment Factor
A = Wetted Surface Area (m2)
10
External Fire
Liq. Vessel (4/4)
Latent Heat of Vaporization of liquid ()
for multi-component mixture
5 wt% flashed
Relief Pressure
Bubble point T
Effects
- Control valve fail open : maximum fluid flow
through
g valve
- Control valve fail close : no fluid flow
- Effect of control valve fail open or close to be
considered on case-by-case basis
Calculation
Calculation of maximum fluid flow in control valve
p
case,, refer next slide
fail open
12
SPLIT-RANGE
N2
Header
FC
PIC
FO
Flare
13
SPLIT-RANGE
N2
Header
PV01
PV02
Flare
PIC
2. LPG VAPORIZER
14
Relief rate =
LPG Generated by max. steam flow
normal LPG outlet flow
15
If applicable (e.g. in
cooling circuit)
circuit), consider
administrative control in
place of relief valve.
16
18
19
FEED
HF
HD
DISTILLATE
QR
HB
B
BOTTOMS
22
2. Fired Heater
No flow to fired heater, but consider the
possibility
p
y that remaining
g fluid inside tube is
heated up by heat from refractory surfaces
(QR = 30% of normal duty)
Steam
2. Fired Heater
Heat from refractory surfaces
(QR = 30% of normal duty)
FUEL
23
24
FEED
HF
HD
DISTILLATE
QR
HB
B
BOTTOMS
Reflux
27
= 0
mRCp,R(TH-TR)
H
28
FEED
HD
HF
DISTILLATE
QR
HB
B
BOTTOMS
30
Reflux
Reflux Loss(1/2)
Cause
Failure of reflux pumps
Effects
- Loss of reflux to column
- Liquid level in overhead receiver rises, ultimately flooding the condenser,
causing loss of condensing duty
Calculation
For Fractionating Column : Enthalpy Balance Method
Alternative : Internal Reflux Method
31
FEED
HF
HD
QR
DISTILLATE
HB
B
BOTTOMS
Failure of air
air-cooled
cooled heat exchanger (1/2)
Cause
Failure
l
off individual
d d l air-cooled
l d heat
h
exchanger
h
Effects
- Loss of condensing duty in fractionating column
Calculation
For Fractionating Column : Enthalpy Balance Method
Internal Reflux Method (Alternative)
33
Failure of air
air-cooled
cooled heat exchanger (2/2)
QC
FEED
HF
HD
DISTILLATE
QR
HB
B
BOTTOMS
THANK YOU
February 3, 2014
35