The document discusses operating a gas turbine in base load with droop speed control versus exhaust temperature control. It clarifies that a gas turbine cannot be operated in both droop speed control and exhaust temperature control at the same time. When operating in droop speed control, the load will change based on grid frequency fluctuations. When operating in exhaust temperature control, the load will change to maintain a target exhaust temperature setting. The document also cautions against using isochronous speed control when connected to a grid with variable frequency.

Uploaded by

Äbdur Ráhmán
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (2 votes)
344 views

Gas Turbine in Base Load With Droop Speed Control

The document discusses operating a gas turbine in base load with droop speed control versus exhaust temperature control. It clarifies that a gas turbine cannot be operated in both droop speed control and exhaust temperature control at the same time. When operating in droop speed control, the load will change based on grid frequency fluctuations. When operating in exhaust temperature control, the load will change to maintain a target exhaust temperature setting. The document also cautions against using isochronous speed control when connected to a grid with variable frequency.

Uploaded by

Äbdur Ráhmán
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

12/8/2015

GasTurbineinBaseLoadwithDroopSpeedcontrol

GasTurbineinBaseLoadwithDroopSpeedcontrol
ClarificationaboutGasturbineoperationinbaseloadwithdifferentloadcontrols
Bysriramsandeepon19June,20132:54pm
Dearall,
ourmachineGE9fawithMKviecontroller.GenerallyGasturbineinbaseloadoperationmeansitis
undercpr/cpdexhausttemperaturecontrol(whenwegivethecommandLoadselectasbaseload)
Butrecentlybyseeingsomepostsincontrol.comIhavegotonedoubthowcanweoperatethe
machineinbaseloadwithdroopspeedcontrol.aswhenwearesayingbaseloadallthetimeiusedto
consideritisundercpr/cpdexhausttemperaturecontrol.
Isitinthisway.amiright?
Loadselectionwillbeinpreselectloadonly,butwewillgivetheMWsetpointneartothebaseload
ratingsothatitwillstayindroopspeedcontrolwithouttransferringtoexhausttemperaturecontrolor
istheresomeotherway?kindlyclarify...
andincaseofisochronouscontroliunderstandthatthecontrollertriestomaintainthegridfrequency
whichisviceversatoothercontrolsofGasturbinelikeexhausttempcontrolanddroopspeed
control.butmyconcernisincaseofotherthanisochronouscontrolgridfrequencyeffectsthe
machineoperationaloutputfrequencyandhencetheoutputproducedbygasturbine.so,in
isochronouscontrolasthoughtherecentpostsiunderstandthemachinewilladjustthefuelflowto
maintainthegridfrequencywhichisveryoddtohear(veryhardtoimaginegasturbinethermal
stresseseventhoughgridissomewhatreasonablystable).isthereanygridfrequencysetpointwhen
operatinginisochronouscontrol???
Anotherdoubt...
fewweeksbackourmachineoperatedonbaseloadthattimeTTXMis629degc..butwhereasduring
preselectloadoperationtheTTXMismaintainingaround648degc.Duringbaseloadoperationitis
followingTTRXasTTRXB(speedbiased)whichisminimumvalue.butincaseofpreselectload
operationTTRXisnotTTRXB(morevalue)butlessvaluethanTTRXB.why?
Asinbaseloadandunderexhausttemperaturecontrolspeedtronictriestoputmorefueltomaintain
thehigherexhausttemperatures.butwhyitsnothappeninghere?

ByCSA

on19June,201311:30pm

Hi,
Idon'tknowwheretostart.
WhentheunitisatPartLoadtheIGVsarenotfullyopen,sotheexhausttemperaturecanbehigher
thanwhentheunitisatBaseLoadpartofthedefinitionofBaseLoadistheIGVsmustbefull
open,whichmeanstheexhausttemperaturemaybe(usuallyis)lowerbecausethemassflowofair
http://my.control.com/thread/1371668081

1/3

12/8/2015

GasTurbineinBaseLoadwithDroopSpeedcontrol

throughthemachineishigherwhentheIGVsarefullyopen.
HavealookattheexampleoftheexhausttemperaturecontrolcurveinSect.03oftheControl
Specification.Ithasanegativeslopewhichiscounterintuitive.Yestheexhausttemperature
generallyincreasesasloadincreases,butastheunitnearsBaseLoadtheexhausttemperaturewill
decreaseasloadincreases.And,whentheunitisatBaseLoadonexhausttemperaturecontrolthe
exhausttemperaturewilldecreaseasloadincreasesanditwilldecreaseasloaddecreases.Again,
it'scounterintuitivebutthat'sthewaycombustionturbineswork.Youmightdoubtthat,butthat's
thewayitis.
Ifyouputaloadsetpointinthatishigherthantheunitcanachieve(becauseitgoesonexhaust
temperaturecontrol)thenit'snotonDroopSpeedControlanditisonexhausttemperaturecontrol.
That'sbecausetheFSRMinimumSelectfunctionchoosesFSRTbecauseitwillbelessthanFSRN
becausetheloadsetpointwilldriveFSRNtobehigherthanFSRT.
IfyouwanttoruntheunitonDroopSpeedControl,itdoesNOThavetobeinPreSelectedLoad
Control.YoucanjustclickonLOWERSPD/LDuntilFSRNislessthanFSRT(whichiswhenload
willstarttodecrease)andwhenyoureachtheloadyouwanttomaintainjuststopclickingon
LOWERSPD/LD.Ifthefrequencyislowerthanitshouldbetheunitshouldbeincreasingload
notmaintainingloadwhichisactuallyexacerbatingthefrequencyexcursion.Idon'tunderstand
whatyou'retryingtoaccomplishbykeepingtheunitinDroopSpeedControlnearBaseLoad
unlessit'sbecauseyouwanttohavetheunitincreaseloadwhenfrequencyislessthanrated.
Iftheunitissynchronizedtoagridwithotherturbinegeneratorsitshouldnotbeoperatedin
isochronousspeedcontrolespeciallyifthegridfrequencyislessthannominal.And,theunit
shouldnotbeatornearBaseLoadwhenitisbeingoperatedinisochronousspeedcontrol.Because
whenthegridfrequencydecreasesandtheunittriestorespondbyincreasingloaditwillhitBase
Loadveryquicklywhichmeansitwon'tbeabletodoanymore.Worse,whenagasturbineisat
BaseLoadandthefrequencydecreasesthepoweroutputwillnotstayatrateditwilldecrease
whichmakesthefrequencyproblemworse.
So,it'snotpossibletobeonbothDroopSpeedControlandexhausttemperaturecontrolatthesame
time.
Doesthishelpatall?

ByCSA

on20June,20133:47pm

>>CORRECTION<<
WhenaGEdesignheavydutygasturbineisoperatingonexhausttemperaturecontrolasload
increasesexhausttemperaturewilldecrease.
WhenaGEdesignheavydutygasturbineisoperatingonexhausttemperaturecontrolasload
decreasesexhausttemperaturewillincrease.

Byrikoon21June,20132:59am
CSAsir,itisagreatanswer.
http://my.control.com/thread/1371668081

2/3

12/8/2015

GasTurbineinBaseLoadwithDroopSpeedcontrol

Justwanttoputsomeadditionalinformation.
Ioperatefr6GEwithmk6controlsystem.Becausemanagementpolicy,wesettheload34MW
whichis1MWlowerthanthebaseloadpower(baseload=35).Atthisconditiontheloadis
changingaccordingtothefrequencyexactlyasMrCSAexplained.Icanseeitclearlyon
SIGNALTRENDapplication.Itrequiresyoutopauseandzoomthegraphicsbeforeyoufindit,
prettysmallfluctuationhappensthere.MrCSAmaycalleditnegativegradient,butIcallit
negativelycorrelated.Asfrequencyincrease,theload(andFSR,andtempexhaust)will
decrease.Viseversa.
Butaround5monthsfromnow,theexhausttemperaturewillincreaseduetocompressorfouling
(commonproblemongt).atthissituationtheloadwillchangeaccordingtothetemperature
exhaust.Atthesameload,butduetocompressorfouling,thetempexhaustincreaseandturbine
controlnolongercontrollingthefrequency.Asthetempincreasetheloaddecrease.The
negativecorrelationisnowbetweentemperatureandload(nolongerbetweenthefrequencyand
load).
Itsallbecauseoftheminimumvalueselectorappliedthere.Whichoneisminimum,FSRNor
FSRT,willbechosenasthefinalFSR.Strictlysaidthatallthegasturbinecontrolmanufacturer
ihavedealtwithappliedthesamephilosophy(Siemens,Trisen,etc).Becauseitensuressafety
operationofgasturbine.
IcansaythatFSRNisdroopmodeandFSRTintemperaturecontrolmode.Theycannotbeat
thesametimeasMrCSAsaid.
Hopeithelps
YouruseofthissiteissubjecttothetermsandconditionssetforthunderLegalNoticesandthe
PrivacyPolicy.Pleasereadthosetermsandconditionscarefully.Subjecttotherightsexpressly
reservedtoothersunderLegalNotices,thecontentofthissiteandthecompilationthereofis1999
2015NerdsinControl,LLC.Allrightsreserved.

http://my.control.com/thread/1371668081

3/3

You might also like