U Value Calculation

This document calculates the "U" values for various building components based on tables from the ASHRAE Load Calculation Manual. It provides the U values for the main building walls (0.0865 BTU/HR°F), three different roof types (ranging from 0.0654 to 0.0778 BTU/HR°F), and the auditorium roof (0.0682 BTU/HR°F). It also states the U value for glass is 0.335 BTU/HR°F. Additional notes provide lighting and other electrical load assumptions, as well as fresh air and building operation details.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
267 views4 pages

U Value Calculation

This document calculates the "U" values for various building components based on tables from the ASHRAE Load Calculation Manual. It provides the U values for the main building walls (0.0865 BTU/HR°F), three different roof types (ranging from 0.0654 to 0.0778 BTU/HR°F), and the auditorium roof (0.0682 BTU/HR°F). It also states the U value for glass is 0.335 BTU/HR°F. Additional notes provide lighting and other electrical load assumptions, as well as fresh air and building operation details.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

"U" VALUE CALCULATION

All Calculation Based on ASHRAE Load calculation Manual

For Main Building (EW-01/03)


ASHRAE
TABLE NO.
3.3
3.1
3.11
3.1
3.11
3.1
3.1
3.11
3.3

ITEM NO.

DISCRIPTION

1
2
3
4
5
6
7
8
9

RESISTANCE

Out side air resistance


Aluminum
Air space
4 in concrete block
Air space
2 in insulation
6 in concrete block
Plaster finish
in side air resistance

0.25
0.61
0.91
0.71
0.91
6.68
0.91
0.149
0.68

R=

11.559

U = 1/R = 0.0865
For Roof (EW04) = (EW52)
3.3
3.11
3.1
3.11

1
2
3
4

Out side air resistance


Membrane
4 in insulation
3 in L.W. concrete

0.25
Neglected
11
2.49

3.11

5 in H.W. concrete

0.625

3.3

Inside air resistance

0.92

R=

15.285

U = 1/R = 0.0654
Roof (EW- 14)
3.3
3.11
3.1
3.11
3.11
3.3

1
2
3
4
5
6

Out side air resistance


Membrane
4 in insulation
3 in L.W. concrete
12 in H.W. concrete
Inside air resistance

0.25
Neglected
11
2.49
1.0
0.92

R=

U = 1/R = 0.0638

Page 1

15.66

Roof (EW-40)
3.3
3.11
3.1
3.11

1
2
3
4

Out side air resistance


Membrane
4 in insulation
8 in H.W. concrete

3.3

Inside air resistance

0.25
Neglected
11
0.667
0.92

R=

12.837

U = 1/R = 0.0778

Auditorium Roof (EW- 51)


3.3

Out side air

0.25

3.11
3.1
3.11
3.11

2
3
4
5

Membrane
4 in insulation
3 in L.W. concrete
Galvanized sheet

3.3

Inside air resistance

Neglected
11
2.49
Neglected
0.92

R=

U = 1/R = 0.0682

For glass

"U" value = 1.9/5.67 = 0.335 BTU/HR.F

Lighting load ,
2W/FT
Other elect Load ,
0.5 W/FT2
Fresh air,
20 CFM / Person
Operation of Building ,
12 HR/DAY
From,
6 A.M. TO 6 P.M

Page 2

14.66

All Calculation Based on ASHRAE Load calculation Manu

For glass "U" value =


1.9/5.67=0.335 BTU/HR.F

alculation Manual