Multicore Armoured Control: Product Sheet No. Cables 060-01 B

This section discusses low voltage cables including multiconductor armored control cables with circular construction. It provides current ratings and voltage drops for different conductor sizes of these cables. It also notes that the current ratings are for single circuit operation and provides a table for reducing the ratings if multiple circuits are operated on the same cable.

Uploaded by

Lucian2001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views

Multicore Armoured Control: Product Sheet No. Cables 060-01 B

This section discusses low voltage cables including multiconductor armored control cables with circular construction. It provides current ratings and voltage drops for different conductor sizes of these cables. It also notes that the current ratings are for single circuit operation and provides a table for reducing the ratings if multiple circuits are operated on the same cable.

Uploaded by

Lucian2001
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Section Three

Low Voltage Cables

MULTICORE ARMOURED CONTROL


Circular construction
Copper conductor
PVC insulation
Extruded bedding
Galvanised steel wire armour
PVC sheath
Current ratings (A) and voltage drops (mV/A.m)

Product Sheet No. Cables 060-01 B


Conductor
Size
(mm2)

(A)

(mV/A.m)

(A)

(mV/A.m)

1.5

21

33.0

17

28.6

2.5

30

18.0

25

15.6

Issue: January 2012


0.6/1 kV. Made to BS 6346
Note:
Content from AS/NZS 3008.1.2:2010 has been reproduced with the permission from Standards New Zealand under
Copyright Licence 000926. Please see the Standard for full details.
The values in this table are for typical New Zealand installation conditions of:Ambient Air Temperature
30C

Multi Circuit Operation


The current ratings given above are single circuit ratings, i.e they relate to a single set of 2 or 3 loaded conductors.
Whilst these cables are not intended for use as power cables, if they are to be operated with more than one set of
conductors loaded for significant periods, the ratings given above should be reduced by application of an appropriate
rating factor from the following table:

Rating Factors for No. of Circuits


No. of circuits

10

12

14

16

18

20 or more

Rating factor

0.80

0.70

0.65

0.60

0.57

0.52

0.48

0.45

0.43

0.41

0.39

0.38

A cable consisting of n loaded conductors should be considered as n/2 circuits of two loaded conductors or n/3 circuits
of three loaded conductors as applicable.

Section 3, Page 72