Introduction To DCS ABB 800XA
Introduction To DCS ABB 800XA
4 X150MW CFB
Power Station
I&C Training Material
DCS
DCS
ABB Symphony 800XA DCS system
DCS
General overview
DCS
DCS
1. Layered architecture of DCS system
business management stage
4th stage
Production management stage
Procedure management stage
Final control stage
Continue process Batch process
3rd stage
2 stage
1 stage
DCS
2. Composition of DCS system
DCS
3. Network of DCS system
DCS
4. Composition of local control cabinet
DCS
4. Composition of local control cabinet
5.
6.
3.
Main control unit: also called as main controller, usually is 1:1 redundancy
configuration, communicate with each intellect I/O module with fieldbus
Power module: the power module has unit modular structure, supply power
to control unit and local I/O module, form non-interference switching mode
of redundancy configuration. Common used:DC24V 48V. (during normal
working, each power module bears half of the load power)
Terminal module: the terminal module is working together with the regular
I/O module, achieve the connection of functional module and local signal .
Easy and convenient to set the station address with code switch. Antimixing pin is equipped for modules to prevent mis-installation for different
functional modules and base modules.
DCS
5. Common I/O module:
AI: Analogue input: receive DC420mA signal , or signal from TC or RTD on
site
AO: Analogue output: DC420mA signal
DI Digital quantity input: receive contact-type switch quantity signal on site
DO Digital quantity output: output passive contact-type switch quantity
signal
DCS
6. Composition of Basic
Controller
CPU :
Memory
Communication interface
Input/output channel
Other functional
components
Data highway
CPU
Memory
Communication interface
Internal bus
Other
components
memory
Communication interface
Production process
DCS
.CPU : It is the key part of basic control, the data processing and
control center of controller. The CPU functional components can do
calculation and program of information in the re-set cycle and
procedure, as well as operate, control and failure diagnosis to the
internal functional components of controller. In order to guarantee
the reliability of system, the CPU can adopt 1:1 redundancy
configuration.
DCS
. Communication interface it mainly includes three parts: parallel
data input/output port (including the related buffering memory),
serial data receive/sent port (including receiver, sender, and
modem), and interface control circuit (including modem control
interface, receive/send controller, direct memory startup control
circuit, and synchronous inspection control)
. Input/output channel It has the interface function between the
basic controller and technical progress, which is achieved by the
high intellect I/O card.
. Other functional components In order to enlarge/expend the
function of basic controller and guarantee the safe and reliable
working of it, other functional components can be adopted, such as,
data input board, analogue display unit, diagnosis component,
switching components, and function expending components
DCS
7. Working process of DCS system
The procedure parameter from local sensor and transmitter will be
collected and processed by difference functional module, then
converted into digital signal which can be received by the computer. The
digital signal will be isolated by the optically coupled circuit and sent to
controller station via data bus
The basic controller in control station will output the control signal after
processing, based on the pre-set action laws, to control the production
process by actuating mechanism.
The procedure information will be sent to the operation station via data
highway in the control circuit. The operator can change the setting
value and control mode of each control circuit with the input device such
as keyboard and mouse, i. e. via the data highway, the control station
can receive the needed order and information sent from operation
station for optimizing the control.
For the procedure parameter not participating in the control, it will be
sent to the operation station via data highway to achieve display, alarm
and record.
DCS
8. Overview of network structure
Decentralized control system can realize the communication between
each internal unit through LAN.
Structure: bus type and ring network.
Common communication protocol: TCP/IP protocol
Profibus, CAN, ModBus, HART for local bus between basic controller
and I/O module.
Connect the different control unit with communication link, then it will
form the decentralized control system. The connection point in this
system is called as station.
The topology refers to the connection method between stations.
The topology forms: bus, ring, star, tree, and network.
DCS
9. transmission medium
. Twisted pair: refers to two twisted leading wire in together. There is
insulation medium between the two wires to control the clearance, so
the wire can meet the requirement for transmitting high frequency
signal. The twisted pair used for computer network is shielded two
conductor or four conductor type.
. Coaxial cable: used to transmitting electric signal with lower
frequency (several hundred HZ) . It has two types :75 and 50, the
former one is used to transmitting TV signal for CATV, the other one
is for baseband signal transmission in computer
. Optical fiber cable:
Principle: light can propagate in the glass.
Advantage: low transmission loss, wide transmission frequency
band, multi-way signal transmission
Application: communication field and computer network.
DCS
10.DCS system grounding/earthing
Evolution
through
Enhancement
1996
1992
1987
1980
800XA DCS
Main function in the power plant
It can achieve the control function of following systems:
MCS: modulation control system
DAS: Data acquisition system
FSSS: Furnace safeguard supervisory system
SCS: sequence control system
DEH: digital electrohydraulic system
ECS: electric control system
BPS: bypass control system
Operator can monitor the production process through MMI
Display operation
real-time and historical trend
Alarm
Operation log
Periodical log
Event log
SOE log
Alarm log
800XA DCS
Two different hardware configuration:
BRC400 as main controllers : DEH,ETS
AC800M as main controller:
MCS,DAS,FSSS,SCS,ECS,BPS
800XA DCS:BCR-400
Operation Network Onet
Control Network Cnet
Control way C.W
I/O Expansion Bus X.B
O net
C net
BRC400
NIS
C. W
NPM
I/O X.B
800XA DCS:BCR-400
2. Main component of local control cabinet
800XA DCS:BCR-400
800XA DCS:BCR-400
3. Introduction of main modules
.main controller BRC400
800XA DCS:BCR-400
(2). Communication network module
INNIS01 INNPM11/12 module
network interface module INNIS01
network processing module (INNPM11/12)
800XA DCS:BCR-400
.I/O module
AI: Analogue input
AO: Analogue output
DI Digital quantity input
DO Digital quantity output
800XA DCS:BCR-400
(4). Power supply system
800XA DCS:BCR-400
. Feature of power supply system
800XA DCS:BCR-400
Main common used module
type
name
control
BRC400
General
module
SOE
module
description
CPU. 160MHz. 32bit
IMASI
IMFEC
IMASO
IMDSI
IMDSO
IMDSM
IMRIO
IMSOE
IMSED
IMSET
800XA DCS:BCR-400
type
name
IMFCS
DEH
module
IMHSS
description
Frequency computer
Frequency response range:1Hz----12.5kHz
Hydraulic servo module: redundancy LVDT input
Control output: control redundancy double-coil servo valve
Control current range:8--64mA
Status monitoring module: monitor the shaft vibration,
eccentricity, axial displacement
IMCMM
Electric
module
IMTAS
800XA DCS:AC800
800XA DCS:AC800
800XA DCS:AC800
800XA DCS:AC800
HARDWARE
Status indication
Push button
RCU connector
Optical cable interface
Status indication
Communication interface
Baseplate
SN
Ethernet address
800XA DCS:AC800
HARDWARE
Inner battery
CPU module
baseplate
slot
slot
Slot for power supply and signal
monitoring (connection:SS822)
800XA DCS:AC800
AC 800M
F(ault)
Red
Normal off
R(un)
Green
Normal (on)
P(ower)
Green
When Normal(on)
B(attery)
Green
Normal (on)
Tx
Yellow
Data transmission
(flash)
Rx
Yellow
Data transmission
(flash)
PRIM
Yellow
Dual
Yellow
When synchronization
(on)
800XA DCS:AC800
Redundancy CPU status indication
PRIM: yellow , DUAL:
flash
Primary is in service
Backup is in synchronization
800XA DCS:AC800
TB840
S(tatus Green
)
Red
Green, in service
Red, fault
P(owo
k)
Green
Green, in service
Rx1
Yellow
Rx2
Yellow
ERx1
Yellow
Data communication
with I/O (A ) is normal
(flash)
ERx2
Yellow
Data communication
with I/O (B) is normal
(flash, ONLY FOR IO
REDUNDANCY
CONTION)
800XA DCS:AC800
800XA DCS:AC800
800XA DCS:AC800
I/O module
F(ault)
Red
Default (off)
R(un)
Green
Default (on)
W(arning)
1. Environment requirement
(1) Temperature and moisture
The control room and electronic room should have air conditioner,
humidifying/de-humidifying device, and thermometer for detection and
maintenance use.
(2) Dust and vibration (in control room and electronic room )
Air particle density 0.3g/ , vibration magnitude0 5mm
The material used for control and electronic room should be anti-static
fire-retardant material. It is forbidden to use the equipment which can
generate interference (such as Mobil phone and walkie-talkie,) in the
electronic room during the operation of DCS
DCS has two ways of power supply, the normal power supply is
UPS power supply, and the other one is emergency power supply.
DCS is equipped with corresponding power module, making the
two ways of AC power supply is in redundancy and back up for
each other. The power module has auto, non-interference
switching mode, the switching speed 5ms
(2) Power supply index
. Voltage: AC 220V10
. Frequency: 50HZlHz ]
. waveform distortion<5
(3) Requirement on UPS
THE Max. actual load of UPS should not exceed the 40% of rated
load.
c.
d.
e.
f.
equipment inspection:
Clean periodically
Check the operation conditions and make record periodically
Check system time and make correction periodically
Check the working condition and printing quality of printer
periodically
Check whether the color and size of graphics in monitor is normal
Check the printer once a week, make sure the printing is good
and clean, spare paper is enough.
Check and make sure the keys on keyboard are flexible, no dead
key and key loss, the keyboard is clean, no dirt
Clean the mouse once a week, make sure it is flexible
Clean the computer desk once per day to make sure the whole
computer system is tidy without dust.