Marine Electrical Engineering: Transformers
Marine Electrical Engineering: Transformers
Engineering
TRANSFORMERS
EDITED BY : D E DHANSINGH
EDITED BY : D E DHANSINGH
Theory of operation
CORE
FLUX
Es
Vp
Vs
LOAD
Ep
PRIMARY WINDING
SECONDARY WINDING
EDITED BY : D E DHANSINGH
Types of transformers
Based on type of cores
CORE
SECY .WDG.
PRY .WDG
PRY .WDG
SECY .WDG.
CORE TY PE
SHELL TY PE
EDITED BY : D E DHANSINGH
Types of transformers
EDITED BY : D E DHANSINGH
CY CLE
d
dt
max
=4 f
max
1/4 T
d
dt
max VOLT
max VOLT
1
T =-f
Ep =4.44 f N1
max VOLTS =- Vp
Es =4.44f N2
Es
Vp
Ep
T
4
O
Im
max VOLTS =- Vp
PRY .WDG
SECY .WDG
Vp =PRY.APPLIED VOLTAGE
Ep =PRY .INDUCED VOLTAGE
Es =SECY .INDUCED VOLTAGE
Vs =SECY .TERMINAL VOLTAGE
Im=MAGNETISING CURRENT
O =CORE FLUX
TRANSFORMATION RATIO
Es
Ep
N2
= K
N1
EDITED BY : D E DHANSINGH
An Ideal Transformer
O
Im
Es
Vp
Ep
SECONDARY WINDING
EDITED BY : D E DHANSINGH
Phasor Diagram of
An Ideal Transformer
Vp
FLUX
Io
Vp
Es
Ep
Vs
Io =
Es ,Vs
Ep
EDITED BY : D E DHANSINGH
Magnetic Leakage
ALL THE FLUX IN THE CORE DOES NOT LINK WITH BOTH
THE WINDINGS.
A SMALL PERCENTAGE OF FLUX LINKS ONLY WITH ONE OF
THE WINDINGS.
Xp
FLUX
Rp
Vp
Ep
Rs
Es
Xs
Vs
EDITED BY : D E DHANSINGH
Io
Vp
Rp
FLUX
Xp
Rs
Es
Ep
Xs
Vp
Im=Io Sin Oo
A MAGNETISING COMPONENT
OF NO LOAD PRIMARY CURRENT
A WATTLESS COMPONENT WHICH
PRODUCES THE MAG.FLUX
Vs
o
Io
Iw
O
Im
Iw =Io Cos Oo
A WATTFUL COMPONENT OF
NO LOAD PRIMARY CURRENT
PRODUCES THE REAL POWER
TO SUPPLY THE IRON LOSSES.
Es
Ep
Vs =Es
EDITED BY : D E DHANSINGH
Transformer on load
and its effect on Iron Losses
WHEN A SECY . CURRENT FLOWS, THE SECY AMPERE-TURNS NsIs WILL TEND TO PRODUCE A
SECONDARY M.M.F.. IF IT EXISTS, IT WOULD DISTURB THE FLUX CONDITIONS EXISTING AT NO
LOAD. THIS WOULD ALTER THE PRIMARY INDUCED EMF "Ep" AND THE BALANCE BETWEEN
BETWEEN "Vp" AND "Ep" WOULD NO LONGER EXIST.
THE PRESENCE OF THE SECONDARY M.M.F. NECESSITATES PRODUCTION OF A PRIMARY M.M.F
EQUAL IN MAGNITUDE BUT OPPOSITE IN DIRECTION. THIS IS PROVIDED BY A LOAD CURRENT
"Ip'" WHICH FLOWS FROM THE SUPPLY THROUGH THE PRIMARY . THIS "Ip'" IS CALLED THE
PRIMARY INDUCED CURRENT WHICH PRODUCES AN M.M.F. EQUAL AND OPPOSITE TO THE SECY .M.M.F.
SINCE THE INDUCED PRIMARY AND THE SECONDARY M.M.F. NEUTRALISE ONE ANOTHER, THE FLUX
ON LOAD IS THE SAME AS THE FLUX ON NO LOAD. HENCE, THE IRON LOSSES ARE CONSTANT
AND ARE INDEPENDENT OF THE LOAD
EDITED BY : D E DHANSINGH
Current Transformation
Primary induced m.m.f = secondary m.m.f.
Np x Ip = Ns x Is
Ip = (Ns/Np) x Is
The total primary current theIp is therefore the vector sum of Ip and
Io and for all but light loads can be taken as equal to Ip. We thus
have
Ip = (Ns/Np) X Is
Ip/Is = Ns/Np
The current transformation ratio is thus the inverse of the voltage
transformation ratio
Transformer on load
Phasor Diagrams
EDITED BY : D E DHANSINGH
Vp
Vp
Ip
Ip
Ip'
Io
Ip'
Io
0p
0s
Es
Es
Is
A RESISTIVE LOAD
A PRACTICAL LOAD
EDITED BY : D E DHANSINGH
Equivalent circuit of a
Transformer on load
SECONDARY WINDING
PRIMARY WINDING
Ip
Xp
Rp
Rs
Np
Vp
Xs
Is
Ns
Ep
Vs
Es
Ep =VOLTAGE AVAILABLE FOR TRANSFORMATION ='Vp' - DROP OF VOLTAGE IN THE PRIMARY WINDING
Vs =TERMINAL VOLTAGE ACROSS LOAD ='Es' (K x Ep) - DROP OF VOLTAGE IN THE SECONDARY WINDING
"K" - TRANSFORMATION RATIO =Ns/Np
EDITED BY : D E DHANSINGH
Characteristics of a
Good Transformer
EDITED BY : D E DHANSINGH
Regulation of a Transformer
Voltage Drops in
Primary & Secondary
Transformer on load
Derivation Of Secy.Term. voltage-1
PRY INDUCED EMF (Ep) =Vp - OD approx.
Ep =Vp - (RpIp COS O1+XpIp SIN O1)
Vp
D
1
Ep
Ip
B
O
Is
Vs =KVp - K (RpIp COS O1 +XpIp SIN O1) - (RsIs COS O2+XsIs SIN O2)
SINCE O1AND O2 ARE APPROXIMATELY EQUAL, REPLACING THEM BY O
Vs =KVp - K (RpIp COS O +XpIp SIN O) - (RsIs COS O + XsIs SIN O)
Transformer on load
Derivation Of Secy.Term. voltage-2
D
1
Ep
2
Vs =KVp - (K Rp +Rs) COS O +(K2Xp +Xs) SIN O
Is
THE EXPRESSION
Is
EDITED BY : D E DHANSINGH
Vp
Ip
Rs
Rp
Iw
Im
Ep
Es
Xs
Is'
Rp
Rs
K2Rp
Ep
=Es/K
Is
Rs =SECY .WDG.RESISTANCE
Xs =SECY .WDG.REACTANCE
Is =SECY .CURRENT
Xs/K
Xp
Ip
Vp
Xp
Rs/K 2
Rp
LOAD
Xp
Vs
Xs
2
K Xp
Rs
Xs
Is
Es
Small Things
EDITED BY : D E DHANSINGH
Losses in a Transformer
Hysteresis loss
EDITED BY : D E DHANSINGH
H.V.
L.V.
0.C. TEST IS CONDUCTED ON "NO LOAD" FOR FINDING OUT IRON LOSSES.
WATTMETER READS APPROXIMATELY THE "IRON LOSSES" =VoIo COS Oo =Wo
Wo
NO LOAD PF (COS Oo) = -----VoIo
FROM COSOo, CALCULATE SIN Oo
Vo
RESISTANCE REPRESENTING CORE LOSS (Rp) = -----Iw
EDITED BY : D E DHANSINGH
Io
Iw
Xs'
Im
Vp
150WATTS
COS Oo =-----------------
200V X 1.25A
=0.6
o
o
AND SIN 53 13' =0.8
200V
Rw =-------------------------------------------- =------ =
266.67OHMS
Xm=------------------------------------------------
200V
=------
=200OHMS
EDITED BY : D E DHANSINGH
PRY
SECY
Isc
Vsc
S.C. TEST IS CONDUCTED ON SIMULATED FULL LOAD FOR FINDING OUT COPPER LOSSES.
2
WATTMETER READS APPROXIMATELY THE COPPER LOSSES =Isc X Rp
SECY IS SHORTED AND A REDUCED VOLTAGE APPLIED TO PRY
TO CAUSE A F,L CURRENT TO FLOW IN THE PRIMARY .
Wsc
RESISTANCE REFERRED TO PRY (Rp) =-----Isc 2
Vsc
IMPEDANCE REFERRED TO PRY (Zp) =-----Isc
REACTANCE REFERRED TO PRY (Xp) = V
2
2
Zp - Rp
Rs
RESISTANCE REFERRED TO PRY (Rp) =Rp +-------2
K
Xs
2
EDITED BY : D E DHANSINGH
Io
Vp
Xp+Xs'
NEGLECTED
RESISTANCE OF TRANSFORMER REFERRED TO PRY . (Rp')
175W
WATTMETER READING
Rp' =---------------------------------------------- =---=1.12OHMS
2 12.5A 2
SHORT CIRCUIT CURRENT (Ip')
IMPEDANCE OF TRANSFORMER REFERRED TO PRY (Zp')
20V
PRY APPLIED VOLTAGE
Zp' =--------------------------- ----------------- =---- =1.6 OHMS
SHORT CIRCUIT CURRENT (Ip') 12.5A
Xp' =V
2 - Rp'
2
Zp'
= V
1.62- 1.122
=1.14 OHMS
EDITED BY : D E DHANSINGH
OUTPUT IN KW
------------------------------------------------------OUTPUT IN KW +IRON LOSSES IN KW +COPPER LOSSES IN KW
2
2
2
TOTAL COPPER LOSS =Is Rs +Ip Rp =Is Rs (ALL RESISTANCES REFERRED TO SECY .)
Vs Is COS Os
IN A SINGLE PH. TRANSFORMER, EFFICIENCY OF TRANSFORMER =------------------------------------------------------Vs Is COS Os +Rs Is2+Pi
DIVIDING BY "Is"
Vs COS Os
=------------------------------------------------------Vs COS Os +Rs Is +Pi/Is
EDITED BY : D E DHANSINGH
Discipline
EDITED BY : D E DHANSINGH
Auto Transformer
EDITED BY : D E DHANSINGH
Parts of an
Oil-filled Transformer
9
4
10
5
6
CONSERVATOR
BUCHHOLZ RELAY
BREATHER
RADIATOR
DRAIN COCK
WDG,TEMP,INDICATOR
10
EDITED BY : D E DHANSINGH
Requirement of a good
Transformer oil.
EDITED BY : D E DHANSINGH
Instrument Transformers
EDITED BY : D E DHANSINGH
EDITED BY : D E DHANSINGH