Template Hose Reel Calculation

This document contains hydraulic calculations to size a pump for a hose reel system with 3 hose reels. It calculates the total head loss from friction in 200 meters of piping, 60 bends, 17 valves, a 30 meter hose, and a 60 meter vertical riser. The total head required is 95.24 meters. A pump with a performance of 100 meters head is selected, equivalent to 328 feet of head.

Uploaded by

MFaiz RHamira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (8 votes)
6K views

Template Hose Reel Calculation

This document contains hydraulic calculations to size a pump for a hose reel system with 3 hose reels. It calculates the total head loss from friction in 200 meters of piping, 60 bends, 17 valves, a 30 meter hose, and a 60 meter vertical riser. The total head required is 95.24 meters. A pump with a performance of 100 meters head is selected, equivalent to 328 feet of head.

Uploaded by

MFaiz RHamira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 3

PROJECT : ???

HOSE REEL SYSTEM (???)


HYDRAULIC CALCULATION PERTAINING TO PUMP SIZING FOR HOSE REEL SYSTEM
*Pump performance shall be based on not more than 80% efficiency factor.
Items
(i) Hose reel pump selection
(ii) Total number of hose reel
(iii) Total pipe length from HR pump to furthest HR location
(iv) Total pipe length of highest vertical riser piping
(v) Total number of 90 bends (0.05 m diameter)
(vi) Total number gate valve (0.05 m diameter)
(vii) Hose Reel (0.025 m diameter & 30 m length)
Type of tubing: Non Kink Single Braided
Friction Loss (Hazen Williams Formula)
(i) Pipe length
(ii) Volumetric flow rate
(iii) Pipe roughness coefficient, C
(iv) Pipe diameter
HEAD LOSS PER PIPE LENGTH
HEAD LOSS PER 1 METER PIPE LENGTH
Head Loss
(i) Linear length of pipe

Value
135
0.00225
88
200
60
17
3

Value
Unit
100
meter
0.00225
meter3/s
120
0.05
meter
4.161337 meter head
0.041613 meter head

Value
200
Head Loss 8.322673
(ii) Number of Bends
17
Equivalent length of smooth 90 bends (0.05 m diameter)
0.5
Total equivalent length of smooth 90 bends (0.05 m diameter)
8.5
Head Loss 0.353714
(iii) Number of valves
3
Equivalent length of gate valve (0.05 m diameter)
0.5
Total equivalent length of gate valve (0.05 m diameter)
1.5
Head Loss 0.06242
(iv) Canvas Tubing
Length
30
Diameter 0.025
Head Loss
1.5
(v) Vertical riser piping
Head Loss
60
(vi) Hose reel outlet
Head Loss
25
TOTAL HEAD REQUIRED
SELECTED PUMP PERFORMANCE (METER HEAD)
SELECTED PUMP PERFORMANCE (FEET HEAD)

Unit
Litre/min
meter3/s
Nos.
meter
meter
Nos.
Nos.

unit
meter
meter head
Nos.
meter
meter
meter head
Nos.
meter
meter
meter head
meter
meter
meter head
meter head
meter head

95.23881 meter head


100
meter head
328
feet head

Hazen Williams Friction Loss Formula (SI Unit)

L
Q
C
d
hf
S

=
=
=
=
=
=

Length of pipe in meters


Volumetric flow rate, m3/s (cubic meter per second)
Pipe roughness coefficient
Inside pipe diameter, m (meter)
Head lossin meters (water) over the length of pipe (meter head)
Hydraulic slope

pe (meter head)