100% found this document useful (1 vote)
288 views2 pages

Pe3608 & Pe4710

This document provides maximum recommended working pressures for PE 3608 and PE 4710 HDPE pipes at different DR ratings and operating temperatures for water, brine and dry natural gas gathering services. It also lists some notes on how the pressures are calculated and specifications for the pipes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
288 views2 pages

Pe3608 & Pe4710

This document provides maximum recommended working pressures for PE 3608 and PE 4710 HDPE pipes at different DR ratings and operating temperatures for water, brine and dry natural gas gathering services. It also lists some notes on how the pressures are calculated and specifications for the pipes.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

www.performancepipe.

com

DRISCOPLEX 6400

PE3608 HDPE PIPE

Pressure Rating Vs Temperature


The following chart provides maximum recommended working pressures for PE 3608/3408 pipes &
fittings for Water, Brine, and Dry Natural Gas Gathering service at the indicated operating temperatures.
Design (Working) Pressures for Water, Brine and Dry Natural Gas Gathering service
(Class 1, Class 2 and non-Federally Regulated Areas)

Pipe DR

Operating Temperature ( p sig )


73F

100F

120F

140F

320

250

202

160

267

208

168

134

200

156

126

100

11

160

125

101

80

17

100

78

63

50

21

80

62

50

40

1.

Design (Working) Pressures are calculated in accordance with API 15LE specification. A check should be
made to determine if these pressures meet state and/or
local codes

2.

PE 3608 pipes with different outside diameter, but the


same DR have the same Design (Working) Pressure
Ratings.

BulletinPP6813608

3.

Minimum pipe wall thickness is determined by dividing


the pipe average outside diameter (O.D.) by the DR
number.

4.

Meets or exceeds requirements of API 15LE, ASTM


D2513 and PPI TR-4 Material Designation Code
PE3608.

5.

ASTM D3350, Cell Classification PE345464C

September2009
ChevronPhillipsChemicalCompanyLP

PerformancePipe,adivisionofChevronPhillipsChemicalCompanyLP5085W.ParkBlvdSuite500Plano,TX75093Phone:8005270662Fax:9725997348

www.performancepipe.com

DRISCOPLEX 6400

PE4710 HDPE PIPE

Pressure Rating Vs Temperature


The following chart provides maximum recommended working pressures for PE 4710/3408 pipes &
fittings for Water, Brine, and Dry Natural Gas Gathering service at the indicated operating temperatures.
Design (Working) Pressures for Water, Brine and Dry Natural Gas Gathering service
(Class 1, Class 2 and non-Federally Regulated Areas)

Pipe DR

Operating Temperature ( p sig )


73F

100F

120F

140F

403

314

254

202

336

262

212

168

252

197

159

126

11

202

158

127

101

17

126

98

79

63

21

101

79

64

51

1.

Design (Working) Pressures are calculated in accordance with API 15LE specification. A check should be
made to determine if these pressures meet state and/or
local codes

2.

PE 4710 pipes with different outside diameter, but the


same DR have the same Design (Working) Pressure
Ratings.

BulletinPP6814710

3.

Minimum pipe wall thickness is determined by dividing


the pipe average outside diameter (O.D.) by the DR
number.

4.

Meets or exceeds requirements of API 15LE, ASTM


D2513 and PPI TR-4 Material Designation Code
PE4710.

5.

ASTM D3350, Cell Classification PE445474C

September2009