Heat Exchanger
Heat Exchanger
Diinginkan untuk memanaskan 9820 lb/hr Benzena dingin dari 80 ke 130oF menggunakan Toluena
Specific gravity pada 80oF masing-masing 0.88 dan 0.87
Fouling factornya 0.002, sedangkan pressure drop yang diperkenankan adalah 10.0 psi
Sejumlah pipa hairpin: 20-ft, IPS 2 x 1 in tersedia
Berapa diperlukan pipa hairpin?
1.Heat Balance
Dengan menggunakan asa black, Q terima = Q lepas, kita dapat mengetahui massa
Benzene
Toluene
tave
c
=
=
m c dt
9820 x 0.42 x 40
Tave
105 F
=
=
m c dt
mt x 0.44 x 60
(dth - dtc)/ln(2)
Lihat gambar 2
Benzena 10
164976 Btu/hr
166940 Btu/hr
6323.48 lb/hr
28.8539 F
Caloric Temperature
Caloric Temperature: check of both streams will show that neither is viscous at the cold terminal (t
Mendata
panjang
diameter dalam
dan luar
dari Tabel
11
centipoise) and the temperature
ranges
and temperature
difference
are pipa
moderate.
The coefficients
evaluated from properties at the arithmatic and the value of (u/uw)0.14 may be assumed equal to
Ukuran
ID
OD
Panjang
=
=
=
=
Pipa dalam
1.25 in
1.38 in
1.66 in
Pipa luar
2 in
2.067 in
2.38 in
2.067/12 =
1.66/12
=
0.17225 ft
0.1383333333 ft
Luas penampang
a =
(D22 - D12)/4 =
0.0082766761
Diameter Equivalen
Da =
(D2^2-D1^2)/D1 =
0.0761490462 ft
Diameter luar untuk toluena
Bilangan Reynolds
Viscosity at 130 oF
=
W/aa
764012.60346 lb/hr.ft2
0.44 cp =
Re a
Jh
1.0648 lb/ft.hr
De Ga
Re =
DaxGa/
54638.271062
Jh =
Re^0.795/36.5 =
160.18037512
Ta =
c =
k =
Lihat Gambar 2
130 oF
0.44 Btu/(lb)(oF)
0.082 Btu/(hr)(ft2)(oF/ft)
ka
ho j H
De
(c/k)^1/3 =
ho =
Jh k/Da (c/k)^1/3 a
Perhitungan ko
1/ 3
1.7877304463
ho/a =
tw =
308.36191028 Btu/(hr.ft2.oF)
tc + (ho/a)/((ho/a)+(hio/p))*Tc-tc)
117.70020578
UC
hio ho
hio ho
Rd =
U D
UC
1 U C Rd
0.001 + 0.001 =
0.002 (hr.ft^2.oF)/Btu
1/UD = 1/Uc + Rd =
Ud =
116.3946905 Btu/(hr.ft^2.oF)
Q
U D LMTD
A =
49.122794507 ft^2
0.435 ft
A
External Surface p er foot length (Table 11)
L=
The surface supplied actually be:
L=
Corrected UD will be:
UD
UD =
112.92596438 ft
120 ft
52.2 ft^2
Q
AAKTUAL LMTD
109.53318895 Btu/(hr.ft^2.oF)
Rd CALC
UC U D
U CU D
(D2 - D1)
Bilangan Reynolds
0.0339166667 ft
Re
'
a
D 'e Ga
Rea =
f 0.0035
Menghitung f
24335.800902
0.264
Re'
0.42
f =
0.007185
s=
0.772
Menghitung = s x 62.5
=
Menghitung Fa
62.5 x 0.772
Fa
4 fG a2 L
2 g 2 De'
Fa =
Menghitung Velocity
V=
Menghitung Ft
Pressure Drop
Pa
30.35162663 ft
Ga
3600
Ga/3600 x
Fl
48.25 lb/ft^3
4.3984605841 fps
V2
nd phe
2 g'
Ft =
F a F l
144
Pa =
10.773853552
1.8025
0.115 ft
ap = x D^2/4
0.0103910714 ft2
yang W nya lebih besar
dialirkan pada pipa yang flow
areanya lebih besar
Diameter dalam untuk benzena
Mass Velocity
Gp =
Lihat Gambar 2
W/ap
945042.1 lb/hr.ft2
Viscosity at 100 oF
=
0.42 cp =
Re p
1.0164 lb/ft.hr
DG p
Repada
= Gambar
DxGp/
h dapat dihitung atau dapat dilihat
24
Jh
Jh =
106926.3
Re^0.795/36.5 =
Tp =
c =
k =
Perhitungan koefisien film
273.1966
100 oF
0.42 Btu/(lb)(oF)
0.09 Btu/(hr)(ft2)(oF/ft)
k c
D k
1/ 3
hi j H
(c/k)^1/3 =
hi/p =
1.680184
359.2335
hi/p =
Btu/(hr.ft2.oF)
298.6399
Re
106926.3
0.005693
0.72
45 lb/ft^3
Fp =
12.47621 ft
5.833593 fps
Pp
3.898815
ft
Pp
F p
144
besar
ang flow
sar
tuk benzena
yng dibutuhkan
dibagi dengan
haipin (20 ft ) =
uah hairpin
tuk benzena
C Benzena 100 F
adalah 0,42
C Toluena 130
F adalah 0,44
Soal Latihan
Diinginkan untuk memanaskan 9820 lb/hr Benzena dingin dari 85 ke 130oF menggunakan Toluena
Specific gravity pada 80oF masing-masing 0.88 dan 0.87
Fouling factornya 0.002, sedangkan pressure drop yang diperkenankan adalah 10.0 psi
Sejumlah pipa hairpin: 20-ft, IPS 2,5 x 1 in tersedia
Berapa diperlukan pipa hairpin?
Benzene
Toluene
tave
c
=
=
m c dt
9820 x 0.42 x 45
Tave
=
=
m c dt
mt x 0.44 x 65
LMTD
Hot Fluid
160 Higher Temp
95 Lower Temp
LMTD
Caloric Temperature
Cold Fluid
t
130
85
30
10
t 2 t1
t 2 t1
t 2
t 2
ln
2.3 log
t1
t1
(dth - dtc)/ln(2)
Caloric Temperature: check of both streams will show that neither is viscous at the cold terminal (t
the temperature ranges and temperature difference are moderate. The coefficients may according
arithmatic and the value of (u/uw)0.14 may be assumed equal to 1.0
=
=
=
=
1.25 in
1.38 in
1.66 in
2.47/12 =
1.66/12
=
0.2058333333
0.1383333333
Luas penampang
a =
0.018253125
De=
0.167936747
Diameter Equivalen
W/aa
355524.90653
Lihat Gambar 2
Bilangan Reynolds
Viscosity at 127,5oF
=
0.44 cp =
Re a
1.0648
De Ga
Re =
56072.216637
Jh dapat dihitung atau
Jh
Jh =
Re^0.795/36.5 =
Ta =
c =
k =
163.51430588
127.5 oF
0.44 Btu/(lb)(oF)
0.082 Btu/(hr)(ft2)(oF/ft)
Perhitungan
k c
ho jH a
De k
1/ 3
(c/k)^1/3 =
ho =
Jh k/Da (c/k)^1/3 a
ho/a =
tw =
1.7877304463
142.73349746
tc + (ho/a)/((ho/a)+(hio/p))*Tc-tc)
113.96769841
Perhitungan U, A dan Rd
UC
hio ho
hio ho
Rd =
U D
0.001 + 0.001 =
UC
1 U C Rd
0.002
1/UD = 1/Uc + Rd =
Ud =
Q
U D LMTD
80.941653324
A =
125.95507701
0.435
A
External Surface p er foot length (Table
L=
289.55190117
1. Pipa hairpin
pipa hairpin =
7.2387975292
L=
9 x 20 x 0.435 =
UD
UD =
78.3
Q
AAKTUAL LMTD
130.2044978
Rd CALC
Rd =
Pressure Drop
-0.0026744
Bilangan Reynolds
(D2 - D1)
Re
'
a
0.0675
D 'e Ga
Rea =
Menghitung f
UC U D
U CU D
f 0.0035
22537.501118
0.264
Re'
0.4 2
f =
0.007185
s=
0.772
Menghitung = s x 62.5
=
Menghitung Fa
62.5 x 0.772
Fa
4 fG a2 L
2 g 2 De'
Fa =
Menghitung Velocity
V=
Menghitung Ft
Pressure Drop
48.25
Ga
3600
Ga/3600 x
2.0467755125
V2
Fl
nd p he
2 g'
Pa
F a F l
144
Pa =
0.1307797894
ke 130oF menggunakan Toluena panas yang menjadi dingin dari 160 ke 95oF
tav, c, Q, W
107.5 F
Lihat gambar 2 untuk Benzena
107,5 F
185598 Btu/hr
127.5 F
Lihat gambar 2 untuk Toluena
127,5 F
185598 Btu/hr
6489.440559 lb/hr
t2
t1
18.20478453 F
s viscous at the cold terminal (the viscousities is less than 1 centipoise) and
The coefficients may accordingly be evaluated from properties at the
.0
D = 1.38/12
0.115
ap = x D^2/4
0.0103910714
ft
Mass Velocity
Gp =
W/ap
Gambar 2
Viscosity at 107,5 oF
=
0.42 cp =
lb/ft.hr
Re p
DG p
Re =
Jh dapat dihitung atau dapat dilihat pada Gambar 24
Jh
Jh =
Re^0.795/36.5 =
Tp =
c =
k =
107.5 oF
0.42 Btu/(lb)(oF)
0.09 Btu/(hr)(ft2)(oF/ft)
k c
hi jH
D k
1/ 3
(c/k)^1/3 =
hi/p =
Btu/(hr.ft2.oF)
hi/p =
A dan Rd
hio ho
hio ho
(hr.ft^2.oF)/Btu
Btu/(hr.ft^2.oF)
ft^2
ft
A
urface p er foot length (Table 11)
ft
Panjang yng
dibutuhkan dibulatkan
keatas, sehingga pipa
haripin yang
dibutuhkan adalah 8
Btu/(hr.ft^2.oF)
UC U D
U CU D
(hr.ft^2.oF)/Btu
Diameter dalam untuk benzena
ft
D =
0.115
Re =
f=
lb/ft^3
ft
Fp =
fps
Ft =
0.3903 ft
Pp
F p
144
psia
Pp
ft
ft2
Diameter dalam untuk benzena
lebih besar
pipa yang flow
bih besar
benzena
945042.1 lb/hr.ft2
1.0164 lb/ft.hr
106926.3
273.1966
)(ft2)(oF/ft)
1.680184
359.2335
Btu/(hr.ft2.oF)
298.6399
106926.3
0.005693
0.72
45 lb/ft^3
0 ft
5.833593 fps
0 psia
C Benzena 107,5
F adalah 0,42
C Toluena 127,5 F
adalah 0,44
k pada 127,5 F =
0,082