0% found this document useful (0 votes)
18 views

Examples Problem 12.3: A B C NG A B C

This document provides an example problem of analyzing a double line-to-ground (LLG) fault on a power system with two generators. The problem involves: 1) Drawing the positive, negative, and zero sequence networks and determining the Thevenin impedances and voltages seen from the fault point in each network. 2) Combining the three Thevenin equivalent networks into a single faulted circuit to calculate the phase and sequence currents flowing into the fault. 3) Converting the sequence currents into abc currents flowing at the fault location. 4) Demonstrating how the sequence voltages at the fault can be used to determine currents elsewhere in the system by accounting for phase shifts in the networks.

Uploaded by

Fengxing Zhu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
18 views

Examples Problem 12.3: A B C NG A B C

This document provides an example problem of analyzing a double line-to-ground (LLG) fault on a power system with two generators. The problem involves: 1) Drawing the positive, negative, and zero sequence networks and determining the Thevenin impedances and voltages seen from the fault point in each network. 2) Combining the three Thevenin equivalent networks into a single faulted circuit to calculate the phase and sequence currents flowing into the fault. 3) Converting the sequence currents into abc currents flowing at the fault location. 4) Demonstrating how the sequence voltages at the fault can be used to determine currents elsewhere in the system by accounting for phase shifts in the networks.

Uploaded by

Fengxing Zhu
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 13

Examples

I will do 2 of your assigned problems


Problem 12.3
The problem requires us to find the three
currents Ia, Ib, and Ic, and also Vng, given that
Ea=1, Eb=-1, and Ec=j1.
Ia
j1
Ec=j

Eb=-1

j1

Ea

Ea=1

j1

Eb

Ec

j1

j1
Ib
j1
Ic

The network is symmetric. Therefore, the


sequence circuits will be decoupled and we
can analyze them one at a time.
The zero sequence current must be zero
since the source is ungrounded and therefore
Ia+Ib+Ic=0.

But the given voltages are unbalanced. So


lets hit them with an A-1 to get the sequence
voltages as follows:
E 0
1 1
1
E 3 1
2
E

1 1 0.333390
2 1 0.9107 30
j1 0.244030

Recall that for loads and transmission lines,


Z+=Z-. So we find the positive and negative
sequence currents using the below circuits.
I+

j1

0.9107/_-30

j1

Vng

I-

j1

0.2440/_30

j1

Vng

We obtain:

0.9107 30
0.4554 120
j2
0.244030
I
0.1220 60
j2

We can then obtain the abc currents as


2

1
0
I a 1 1
0.5271 108.44
I 1 2 0.4554 120 0.9107108.44
b

2
I c 1 0.1220 60 0.33340

Now what about Vng?


Notice from the positive and negative
sequence circuits that Vng 0 and Vng 0 .
But consider
is

Vng0 .

The zero sequence circuit

I0

Z0

0.3333/_90

j1

0
ng

From the zero-sequence circuit, a KVL


equation results in
0.333390 Vng0 0
Vng0 0.333390 0.3333 90

Now we have all of the symmetrical


components of Vng, and we can therefore
obtain Vng as their sum:
Vng Vng Vng Vng0 0 0 0.3333 90 0.3333 90

Clarification: When getting abc quantities


from 0+- quantities, we hit the 0+- quantities
with A (which contains terms in for the band c-phase quantities). But that is to obtain
ALL abc quantities from the a-phase 0+quantities, as indicated below.

1 Va0
Va 1 1
V 1 2 V
b
a
Vc 1 2 Va
Notice that Va=Va0+Va++Va-.
If we were to have the b-phase 0+quantities, then the b-phase quantity would
just be the sum of those b-phase 0+quantities, i.e., it would be Vb=Vb0+Vb++Vb-.
And if we were to have the c-phase 0+quantities, then the c-phase quantity would
just be the sum of those c-phase 0+quantities, i.e., it would be Vc=Vc0+Vc++Vc-.
And so a phase quantity is just the sum of
the sequence quantities in that phase.
4

Problem 12.17
From book: Repeat Ex 12.5 if there is a
DLG fault (between phases b and c) at the
terminals of G1. Assume that the prefault
(phase a) voltage at the fault point is 1/_0.
Find the fault currents Ibf and Icf.
Ex12.5 is a good one (review it carefully),
below. In P.12.17, the fault location is left of
T1, not right of T1 as below for Ex12.5.

Recall that a LLG fault requires a parallel


combination of all three sequence networks.
So we must find all 3 sequence networks.
Below are some comments about doing this.

We get positive sequence phase shift of 30


going from low to high; negative sequence
of -30 going from low to high.
5

The problem requires pre-fault, phase a


voltage at the fault point be 1.0/_0.
- This 1.0/_0 is a positive sequence voltage
and therefore lies in the positive sequence
network.
- Pre-fault implies no fault current, and
since we are ignoring load currents, there
is no current flow in the pre-fault network.
- In the text, Fig. E 12.5(b), because the
fault was on the line (in the middle of the
diagram), and therefore on the opposite
side, from G1 and G2, of the transformer
phase shifts, the source voltages had to be
1/_-30 in order to impose the fault point
to have a voltage of 1/_0.
- Here, because the fault is at the generator
terminals, and therefore on the same side
of the transformer phase shift as G1, G1
must be 1/_0 in order to impose the fault
point to have a voltage of 1/_0. Because
there are equal and opposite phase shifts
between the fault point and G2, G2 must
also be 1/_0.
6

The zero sequence network is


- to ground at each gen since both gens are
solidly grounded.
- open between each gen and the network
because of low side delta connection in the
xfmrs.

j0.1

1 : 30

j0.1

j0.2

1 : 30

j0.1

j0.2
10

10

Positive sequence network

1 : 30

j0.1

j0.1

j0.2

1 : 30

j0.1

j0.2

Negative sequence network

j0.1

j0.3

j0.1

j0.06

j0.06

Zero sequence network

The fault point, at the terminals of G1 (on


the left), is indicated in the sequence
networks using the bold, short vertical lines.

We must compute the Thevenin impedances


and voltages for each sequence network, as
seen from the fault point.
The Thevenin voltage for each network is
easy it will be zero for zero and negative
sequence, and it will be the pre-fault voltage
at the fault point, 1/_0, for the positive
sequence network.
Obtaining the zero-sequence Thevenin
network is also easy because of the open
circuit to the right of the fault point; it is
shown below.
j0.06

Zero sequence Thevenin network

Obtaining positive, negative sequence Thev.


impedances requires analyzing networks
with phase shifts. However, because the
phase shifts occur to voltages and currents,
Thevenin impedances may be computed
without consideration of phase shifts.
8

This is true for what your text calls normal


systems (see pp 151-157), which are systems
for which the product of the voltage
transformations around any closed loop is
1.0/_0. Below are examples.
1 : 30

1 : 25

1 : 30

1 : 30

Normal System

Not normal System

So the positive and negative sequence


networks to use in obtaining the Thevenin
impedances are below. Note that the positive
sequence sources were idled.
j0.1

j0.1

j0.1

j0.2

j0.2

Positive sequence network

j0.1

j0.1

j0.1

j0.2

j0.2

Negative sequence network

These are identical networks. Therefore the


positive and negative sequence Thevenin
reactances are the same:
X X

(0.2)(0.1 0.1 0.1 0.2)


0.1429
(0.2) (0.1 0.1 0.1 0.2)

Now we may draw the three Thevenin


equivalent networks.
j0.1429
10

Positive sequence Thevenin network

j0.1429

Positive sequence Thevenin network

j0.06

Zero sequence Thevenin network

As mentioned at the beginning of this


problem, a LLG fault requires a parallel
combination of all three sequence networks.
The connected circuits for analysis of a LLG
at the G1 terminals is shown below.
10

I af
j0.1429
1 : 0

I af

j0.1429

I af0

j0.06

From this network, we may compute the


three currents shown, as
I af

1
1

j5.4
j (0.1429 0.1429 // 0.06) 0.1852

Then using current division, we obtain


0.06
0.06
j5.4
j1.597
0.1429 0.06
0.2029
0.1429
0.1429
I af0 ( j5.4)
j5.4
j3.8032
0.1429 0.06
0.2029

I af ( j5.4)

Now we can compute the abc currents:


1 j 3.8032
0
I a 1 1

I 1 2 j5.4 - 6.0596 + j5.7047


b

2
I c 1 j1.597 6.0596 + j5.7047
0

8.3224136.73
8.322442.27

11

What if we wanted to obtain abc currents in


other parts of the system?
The first thing to do is to compute the faulton sequence voltages at the fault point. This
is easily done from the Thevenin circuits
and knowledge of the fault currents, as seen
below.
I af

j0.1429

Vaf

10

Vaf 10 ( j5.4)( j 0.1429) 0.2282

Positive sequence Thevenin network

I af

Vaf ( j1.597)( j 0.1429) 0.2282

j0.1429

Vaf
Positive sequence Thevenin network

I af0
j0.06

0
af

Vaf0 ( j3.8032)( j.06) 0.2282

Zero sequence Thevenin network

As a check on this work, lets take a look at


the abc voltages at the fault point.
12

1 0.2282 0.6846
Va 1 1
V 1 2 0.2282 0
b

2
Vc 1 0.2282 0

Then we would use the sequence voltages at


the fault point, in each sequence network, to
compute the currents in the various
elements. To do this, we would need to go
back to circuits with the phase shifts (see
page 6 above). Your book, pg. 481, shows
an example of this. Key point here is that in
these calculations, the phase shifts matter!!!!

13

You might also like