Buildings Structural Open Issues With TBC Remarks 25apr2013
Buildings Structural Open Issues With TBC Remarks 25apr2013
- Change reinforcement of beams B105 , B139 , B142 , B145 , RC design of most critical beams of building is done as
Use 2 layers of 6 25 , first layer consist of 4 25 while
B149 , B154 , B157 , B160 , B165 , B169 , B170 , from 4 25 T&B to per maximum bending moment of sways (to prevent to the second layer consist of 2 25
6 25 T&B
use any additional bar) and chosen bar areas for top and
bottom sections are almost 1,50 2,00 times greater
than required. Chosen number of reinforcement bars,
minimum 6,67 cm clear space is provided between
longitudinal bars to allow reliable concrete pouring
during site work If number of longitudinal bars are
increased to 6 instead of 4 clear space between bars will
be only 3 cm and there will be no gap at overlapping
sections.So it will be a must to put bars at 2 layers to be
able to pour concrete. Finally we would like to inform you
that there is no technical reason to increase number of
bars from 4 to 6 which will cause concrete pouring
problems during site work.
open
- Change reinforcement of link beams from 3 16 T&B to 416 Average capacity ratio of link beams for chosen RC bars Use 416 T&B
T&B
is almost 60%. So chosen RC areas are quite enough to
meet forces. Clear space between bars is almost 9 cm
and enough for reliable pouring concrete. By increasing
number of bars, capacity ratio will decrease to almost
40%. Decreasing the clear space between bars from 9
cm to 5,5 cm causes difficulty during the concrete
pouring.
open
HAYDARIA 4xGE Fr.9E GPP / ELECTRICAL CONTROL BUILDING STRUCTURAL COMMENTS REVIEW
MOE review transmital no. 313
ENKA response (transmital 332)
MOE response
ENKA
MOE review transmital no. 281,282,283
response
no
no
no
no
no
done
done
no
status
open
open
status
closed
CLOSED
closed
closed
CLOSED
closed
closed
CLOSED
closed
closed
CLOSED
closed
closed
CLOSED
3.
Use 4-16mm bar diameter for link beams to
ensure minimum reinforcement area requirements.
For most critical Link Beam; Asrequired = 4,17 cm2 Asminimum O.K. we will wait your revised drawings
= 5,54 cm2
(As per ACI 10.5.3) Asused =
6,03 cm2
as soon as possible
(3 no 16 mm steel bar) As seen above used 3 no 16 mm steel
bar is quite enough to meet both Asrequired and Asminimum.
Although we will like to inform you that we will increase number of
bars as 4 instead of 3 as you inquired in your letter for extra safety.
closed
closed
CLOSED
open
2.
4.
open
open
4.c
Attached please find calculation sheets of regarding beams O.K. we will wait your revised drawings
to be sure of design.
as soon as possible
closed
closed
CLOSED
d. it is suggesred to support the cantiliver slab by adding 4.a,b,d We will add steel frame members to the landings to limit
inclined ( hypotenuse )RC beam
deflection and provide extra safety.
open
5.
Width for foundation of interior stair should be
increased to be 1.0 m and to be at the same level of
strip foundation (DWG. C-18025).
closed
closed
CLOSED
6.
Give a suitable detail for all expansion joints in
slab at roof with 2 parapets and cap to prevent leakage
of rain water.
closed
closed
CLOSED
7.
Add detail for expansion joint between part 3 and 4 OK. We will add dedicated detail for this part.
to prevent leakage of rain water (DWG.C-18032)
closed
closed
CLOSED
8.
O.K. we will wait your revised drawings Add tread reinforcement of bar lOmm
as soon as possible
each 30 em for both exterior and interior
stair. (drawing no.C-18063 and C-18064).
Add tread reinforcement of bar 10 mm each 30 cm. Please clarify to which type of structural members you want to add
thread reinforcement bars?
open
ENKA response
status
open
ENKA response
HAYDARIA 4xGE Fr.9E GPP / SINGLE ROOMS BUILDING STRUCTURAL COMMENTS REVIEW
MOE response
MOE review transmital no.
314-316
status
closed
closed
CLOSED
0,0034 x bw x d
But this value need not be applied if as provided it is at
least one-third greater than required area by analysis
(see 10.5.3).
closed
closed
closed
closed
CLOSED
CLOSED
closed
closed
CLOSED
closed
closed
CLOSED
closed
closed
CLOSED
o.k
Check cantilever slab thickness requirements Confirmed. Please see note below.
at stair panel
o.k
closed
closed
CLOSED
o.k
closed
closed
CLOSED
Add penthouse to the building and stair at first Architectural design of building is prepared by
floor
considering the area requirements specified in
Contract documentation. A penthouse is not required
in the related Contract specification. Therefore, we
kindly request you to remove this comment
open
open
open