Engineering College Building Design
Engineering College Building Design
Table of Contents
Page 1 of 4
Table of Contents
Page 2 of 4
Table of Contents
Division 27 Communications
27 00 00
Emory University Library & Information Technology Services Standards
Division 28 Electronic Safety and Security
28 10 00
Electronic Security Systems
28 31 00
Fire Detection and Alarm
SITE AND INFRASTRUCTURE
Division 31 Earthwork
31 00 00
Earthwork
31 10 00
Tree Protection and Selective Clearing
31 25 00
Construction Storm Water and Erosion Control
Division 32 Exterior Improvements
32 00 00
Exterior Improvements
32 12 00
Flexible Paving
32 12 16
Asphalt Paving
32 12 43
Porous Flexible Paving
32 13 13
Concrete Paving
32 16 13
Concrete Curbs and Gutters
32 17 13
Car Stops
32 17 23
Pavement Markings
32 80 00
Irrigation
32 90 00
Planting
32 92 00
Turf and Grasses
Page 3 of 4
Table of Contents
Division 33 Utilities
33 10 00
Water Utilities
33 30 00
Sanitary Sewerage Utilities
33 40 00
Storm Drainage Utilities
33 60 00
Steam and Chilled Water Distribution Systems
Page 4 of 4
Division / Section
Comment/Issue/Section
Document Delivery
Standards
Updated throughout
Table of Contents
Other
00 01 31
01 43 39
Mock-Ups
01 78 23
01 81 13
07 50 00
Division 08 Openings
08 00 00
Division 09 Finishes
09 20 00
09 90 00
Division 10 Specialties
10 44 00
Fume Hoods
Elevators
21 30 00
Fire Pumps
Division 22 Plumbing
22 00 00
Plumbing
23 05 00
23 07 00
HVAC Insulation
23 09 00
23 21 23
Hydronic Pumps
Emory University Design & Construction Standards - 2015 Comments & Revisions revised 5/8/15
Page 1 of 2
Division / Section
Comment/Issue/Section
23 30 00
23 50 00
23 57 00
23 60 00
23 64 16
23 65 13
Cooling Towers
23 65 23
23 70 00
HVAC Equipment
Division 26 Electrical
Division
26 00 00 00
26 00 00
26 10 00
26 05 00
26 30 00
26 50 00
Lighting
Division 27 Communications
27 00 00
28 31 00
Division 31 Earthwork
32 12 16
Asphalt Paving
32 12 43
32 90 00
Planting
32 92 00
Division 33 Utilities
33 10 00
Water Utilities
33 30 00
33 40 00
Format changes.
33 60 00
Emory University Design & Construction Standards - 2015 Comments & Revisions revised 5/8/15
Page 2 of 2
WARRANTY LOG
SECTION
015000
StandardTitle
TempFacilitiesandContractorMobilization
017700
CloseOutProcedures
ReferencedSubsections
Warranties
Detail
permanentequipmentusedinabuilding'stemporaryfacilitiesmusthavewarrantyextendedto
coincidewithwarrantiesandcompletionofentireproject
SubstantialCompletiondate SubstantialCompletion(SC)issuedthedatewarrantystarts
EndofWarrantyInspection conductedoneyearafterSCdate.
050000
073000
Metals
SteepSlopeRoofing
Finishes
Execution
075000
BuiltUpBituminousRoofing
Products
OwnerPreferences
minimum20yearwarrantyagainstfading,crackingorchipping
contractdocumentswillinitiallyrequire5/75yearlimitedwarrantyonroofingsystems,unless
modificationrequiredandassessedbyEmoryPM.Thewarrantyshouldincludealllaborand
materialsrequiredtomakeanynecessaryrepairs.
contractdocumentswillinitiallyrequire20yearwarrantyonroofingsystems,unlessmodification
requiredandassessedbyEmoryPM
20yearTotalSystemWarrantywithoutmonetarylimitationforrepairorreplacementoffailed
materialorworkmanshipwithinwarrantyperiod.(Roofleaksincluded)Includesroofingmembrane,
baseflashings,roofmembraneaccessories,coverboards,allmetalusedonproject,basesheets
andtheirfasteners,windspeedsupto73mph,andothersystemcomponents.Periodbeginson
dateofSubstantialCompletion.
SpecialProjectWarrantydeterminedbyinstallerandmeetsaminimum5yearsfromdateof
Substantialcompletion.Thewarrantyshouldincludealllaborandmaterialsrequiredtomakeany
necessary repairs
Installermustwarrantyfirestoppingforlifeofbuilding,Manufacturermustwarrantyproperly
installedproductsforsustainablelifeofstructure.Lackofwarrantydoesnotreleaseeither's
liabilityforfaultyproduct.
Doorswarrantiedforlifeofinstallation
contractdocumentsrequirea5yearwarrantyoninstalledwindows,unlessmodificationis
requiredandassessedbyEmoryPM
minimum3yearforhardware(exceptdoorclosers);10yearfordoorclosers
Provideinsulatingglassmanufacturer'swarranty;includereplacementinstallationcosts;include
replacementofglassduetonickelsulfideinclusion;warrantiedfor10yearsafterSubstantial
Completionforallglasstypes;lackofwarrantydoesnotreleaseinstallerfromsamerequirements.
078400
Firestopping
WarrantyandContractor
Qualifications
080000
085000
Openings,Doors
Windows
Lifetimewarranty
Requirements
087000
088000
Hardware
GlassandGlazing
Requirements
Warranty
096800
101000
Carpet
GraphicsandSignage
Requirements
Warrantied
211300
FireSupressionSprinklerSystems
AcceptanceTests,
MaximumequipmentwarrantytoOwnerincludingminimum10yearmaterialsandworkmanship.
Documentation,Warranties RepairsduringwarrantycompletedpromptlyatContractor'sexpense.
230514
VariableFrequencyMotorControls
Warranty
236416
263000
CentrifugalWaterChillers
StandbyPowerGeneratorSystems
Warranty
Warranty
283100
FireDetectionandAlarm
Warranty,Subsequent
Service,andInitial
InspectionReports
321216
AsphaltPaving
AcceptanceTests,
Documentation,Warranties 3yearinstallationdefectswarranty,warrantiedrepairscompletedatContractor'sexpense.
321243
PorousFlexiblePaving
AcceptanceTests,
Documentation,Warranties 1yearinstallationdefectswarranty,warrantiedrepairscompletedatContractor'sexpense.
RevisionDate:2013
manufacturer,installerandcontractormustsubmit20yearwarranty
5yearplasticandmetaljoints,5yearinteriorroomsigns,8yearvinylfilms,2yearexteriorpaint
finishes,3yearplasticandmetalpaintfinishes,andatleast1yearelectricalcomponentsandsigns.
Duringwarranty,allreplacementsmustmeetcontractdocumentstandards.
3yearvariablespeeddrivewarrantyafterstartup
Materialandlaborwarrantyforchillerandstarter(variablespeeddrive)lasting15monthsafter
dateoffactorystartupor18monthsfromdeliverydatewhicheveroccursfirst.
5yearextendedwarrantyonnewgeneratorsthatmatchoriginalfactorywarranty
2yearinstallationdefectswarranty,transfermanufacturer'sequipmentwarranty(minimum1
year)toOwner,warrantiedrepairscompletedatContractor'sexpense.
5yearNotifierFirePanelswarranty,manufacturer'smaximumwarrantyforEmory'smainfire
alarmpanel.
Page1of1
FM GLOBAL LOG
SECTION
StandardTitle
ReferencedSubsections
000002 Introduction
OwnerPropertyInsurance
013100 ProjectManagement+Coordination
Commissioning
PreConstructionConference
013323 Submittals,ShopDrawings,ProductData
FMGlobal
019119 FacilityShellCommissioning
DesignPhaseResponsibilities
050000 Metals
QualityAssurance
072000 ThermalProtection
QualityAssurance
Products
073000 SteepSlopeRoofing
075000 BuiltUpBituminousRoofing
QualityAssurance
QualityAssurance
OwnerPreferences:COLDAppliedAssemblies
Execution
076000 FlashingandSheetMetal
QualityAssurance
088000 Glazing
QualityAssurance
211300 FireSuppressionSprinklerSystems
213000 FirePumps
RegulatoryRequirements
211300 FireSuppressionSprinklerSystems
DesignandSprinklerOccupancyGuidelines
213000 FirePumps
FirePumps
283100 FireDetectionandAlarm
References
Detail
AlldesignandinstallationmustincorporatelosspreventionguidelinesasdfinedbyFMGlobalDataSheet
standardsandshouldutilizeFMGlobalapprovedequipmentorsystemswheneveravailable.
AlldesignplansmustbesubmittedtoFMGlobalsAtlantaofficeforreviewwherefinalacceptancewill
besubjecttothelocalFMGlobalengineeringoffice.
Aconsultantresponsibleforspecand/orinstallofanonFMGlobalapproveditemisliableforallcosts
involvedincorrectingthedeviationtotheapprovalofFMGlobal.
EmoryPMwillnotifyFMGlobaloftimeanddateforpumpacceptances,alarmsystemacceptance
testing,specialprotections(FM200,etc.)acceptancetestsandcombustioncontrolacceptancetesting.
FMGlobalwillalsobeinvitedtothepreconstructionconferenceaswellasotherconferencesand
meetingsasdeemednecessarybytheproject.
FMGlobalprovideslosspreventionconsultingandshouldbeinvolvedinthereviewofallplans.
AdditionaldrawingsthatmustbesubmittedtoFMGlobalforreview,ifnotincludedwithGeneral
Constructiondrawings,are:Fireprotectionmaterialsandfirepumplayoutandequipmentspecs,roof
coversystem,integratedexteriorfinishingsystems,preengineeredallmetalbuildingsystems,gasfired
heatingequipment,specialprotectionsystems,andfireprotectionmonitoringandgeneralfirealarm
systems.
TheEcxshallreviewdesignforcompliancewithFMGlobalrequirements.
SteeldeckingutilizedforroofconstructionshouldbeFMGlobalapprovedandlimitedtothespanwidths
underwhichitisapproved.Structuralsteelcomponentsofthebuildingmustcomplywiththe
requirementsofFMGlobal.
Allinsulationproductsand/orsystemsaretobeFMGlobalapproved.
PolyisocyanurateinsulationisFMGlobalspreferredproducttobeusedunderclaytileandlowslope
roofs.
ThedesignofallroofcoversystemsshouldbeindesignedinaccordancewithFMglobalstandards
utilizingaFMapprovedassemblythatisratedfortheassociatedwindhazardswithappropriate
reinforcementattheperimeteredgesandcorners,orwrittenapprovalmustbeobtainedfromthe
EmorysProjectManagertobeinnoncompliancewithFMGlobalrecommendations.TheFMGlobal
Contractor'sApplicationforRoofAcceptanceformmustbesubmittedwitheachroofsubmittal.
ThedesignofallroofcoversystemsshouldbeindesignedinaccordancewithFMglobalstandards
utilizingaFMapprovedassemblythatisratedfortheassociatedwindhazardswithappropriate
reinforcementattheperimeteredgesandcorners,orwrittenapprovalmustbeobtainedfromtheEmory
ProjectManagertobeinnoncompliancewithFMGlobalrecommendations.TheFMGlobalContractor's
ApplicationforRoofAcceptanceformmustbesubmittedwitheachroofsubmittal.
TheroofsysteminstalledshouldbeFMGlobalapprovedaslistedinthemostrecenteditionoftheFM
GlobalApprovalGuide.
Thecontractdocumentsmustincluderequirementsforinspectionandreviewofthesubstratesunder
theroofingsystem(s)andcompletedetailsshowinginstallationoftheroofingsystemincompliancewith
allrequirementsofFMGlobal,UL,governingauthoritiesandcodesandthemanufacturer.
Thedesignofallflashedassembliesandsystemsandmanufacturer'sproductsmustbeapprovedbyFM
Global,referencedatasheet149whichcoversguidelinesforflashinginstallation,orhavethewritten
approvalofEmorysProjectManager.
TheselectionofglassandthedesignofglazingsystemsshallcomplywithFMGlobalrequirements,code
requirementsandwindloadrequirementsfortheprojectsiteaswellasASHRAErecommended
standardstocomplywiththecurrentLEEDrequirements.
AllfireprotectiondesignandinstallationshouldbeinaccordancewithFMGlobalStandards.Alldrawings
shouldbesubmittedtotheEmoryUniversityProjectManagerandFMGlobalforapproval.Field
installationsaresubjecttoFMGlobalacceptanceinadditiontoapprovaloftheAHJ.Workperformed
shallcomplywithFMGlobalApprovalGuideandFMDataSheets.Drawingsandspecificationstobe
reviewedcanbesenttotheattentionofPlanReviewEngineers(forEmoryUniversity),),FMGlobal,
3460PrestonRidgeDrive,Alpharetta,GA30005.
FortheoccupanciesthataretypicaltoEmorybuildings,thereislittledifferenceinthesprinklerdensities
requiredbyFMGlobalandCodes.
Laboratories:FMGlobalrequires0.15gpm/sq.ft.over2500sq.ft.
Mech/SmallStorageRooms:FMGlobalrequires0.15gpm/sq.ft.over2500sq.ft.
ExhibitHallswithunusuallyhighceilings:FMGlobalrequires0.30gpm/sq.ft.over5000sq.ft.
Forotheroccupancies,theFMGlobalplanreviewdepartmentshouldbecontactedat(770)7773084for
guidance.
Firepumpsshallbelocatedinsideatwohourminimumratedroom.Ratedmechanicalroomsare
acceptable.HigherratingofroomshallbedeterminedbyFMGlobaland/ortheFireMarshall.
TBWoodsoranyplasticfirepumpcouplingsareprohibitedbyFMGlobalforthefirepump.
PlansaresubjecttoFMGlobalreviewandinstallationissubjecttoFMGlobalacceptance.Intheevent
thatitissubsequentlydiscoveredthatthework,oranyportionofthework,hasnotusedthenecessary
approvedmaterials,equipment,orservices,orhasotherwisenotbeenperformedinaccordancewithFM
Globalstandards,orforanyreasondoesnotmeetwithFMGlobalacceptance,theContractor
responsiblefortheworkshall,atitsownexpenseandwithoutanycosttoEmoryUniversity,withinforty
five(45)daysofnoticeinwritingofanydeficiency(orwithinsuchtimesasthepartiestothiscontract
haveagreedinwriting),performsuchworkandreplacesuchmaterialsasisnecessarytobringthework
andmaterialsintocompliancewithrelevantFMGlobalstandardsandsecureFMGlobalacceptance.
SECTION
StandardTitle
283100 FireDetectionandAlarm(continued)
ReferencedSubsections
Submittals
RegulatoryRequirements
Detail
One(1)copyshallbesentto:FMGlobal,3460PrestonRidgeRoad,Suite400,AlpharettaGA30005
Equipmentandmaterialsshallbeapprovedfortheirdesigneduseandperformance.Theterm
"approved"shallmeanUnderwritersLaboratories(UL)listedandFMGlobalapproved.
Section 00 00 02
Introduction
Section 00 00 02 Introduction
Purpose
The purpose of these Design and Construction Standards is to provide specific guidelines to architects,
engineers, design consultants, and contractors for all construction activities on Emory University
properties. These Standards are intended to summarize information that is unique to Emory University
either by choice, by the specialized nature of the facility, or by the requirements of the universitys
insurance carrier and to avoid historical problems with construction, operations, and maintenance.
It is recognized that these Design and Construction Standards are not universally applicable to every
project. These standards do not replace professional design analyses and may not be used directly as
contract specifications. Consultants shall conduct independent evaluations, discuss alternatives and
recommendations with the Emory Project Manager, and appropriate Campus Services personnel. The
Emory Project Manager must approve all deviations from these Standards in writing. All references to
Project Manager shall mean Emory Project Manager.
Designers and contractors are to become familiar with and are responsible for all sections of the
Standards, and are to incorporate the appropriate information early in the design and construction
process. In so doing, designers should be able to save time in preparing plans and specifications, as well
as shorten the review time by Emory University personnel. Additional themes running throughout these
Standards is Emory University's building commissioning program, and support of the Universitys
sustainability vision which are an integral part of the Standards.
CSI 2004 Format
Emory University has converted the Design and Construction Standards to the CSI 2004 Format in
support of Campus Services continuing role as an industry leader, to proactively meet standards of
practice, and for its improved documentation capabilities. While Emory has chosen to provide information
to its consultants in this format there is no obligation for the consultant to use this format at this time. It is
understood that the industry is in a mode of transition. Additional information on the new format can be
found at www.csinet.org/masterformat.
2015 Design Update Summary
Attached to these standards is a document titled 2015 Design Standards Review Comments Summary.
This matrix highlight the substantive changes contained within this version of the Design and Construction
Standards. Do not depend on this table to include every change but it should assist with finding many of
the modifications from the previous year.
Comprehensive BIM Management Plan
Emory University is committed to achieving excellence in every aspect of design and construction. It is
our continued efforts for excellence that has led us to add Building Information Modeling (BIM) to our
design, construction and facilities program through our Comprehensive BIM Management Plan,
developed to achieve the highest levels of quality, value and efficiency in our capital programs and
increase the level of service at more efficient cost levels in facilities management and operations.
The BIM process begins with programming and planning, and extends through design and construction,
through turnover, and into facilities management and operations. BIM encompasses all aspects of a
buildings life cycle, including major capital improvements and repairs, energy efficiency, LEED,
remodeling, adaptive reuse and life safety.
Section Page 1 of 3
Section 00 00 02
Introduction
Your participation in the Comprehensive BIM Management Plan helps build an organized, consistent BIM
database for the design, construction and management of facilities at Emory University.
Agreements
Emory University currently uses Emory generated and proprietary contracts for design, engineering, and
construction services. A proprietary short-form contract is also available; however, the use of this
contract is extremely limited. These contracts have been edited to meet Emory's specific policies and
needs. Any additional modification of these documents will require review and acceptance by Emory's
General Counsel. The Emory Project Manager will determine which contracts will be used for the project
and will prepare all contracts that Emory University is a party to.
The Design and Construction Standards must be considered as part of a total contract that may include
other attachments and guidelines depending on the project. These attachments may impact information
presented in these standards and must be evaluated by the consultant with the Emory Project Manager.
Possible attachments include
Program Document
Facilities Condition
Assessment
Feasibility Study
DAR Guidelines
College Classroom
Guidelines
Document Delivery
Standards
BIM Asset Information
Database Spreadsheet
BIM Execution Plan (BEP)
template
Notice of Commencement
Unless Owner direct otherwise, Contractor shall record a Notice of Commencement, on the form provided
in the contract documents with the Clerk of the Superior Court of the County where the Project is located
within fifteen (15) days of physically commencing Work at the Site.
Hazardous Materials
It is the policy of Emory University, that prior to any restoration, alteration, demolition or renovation of any
area the Environmental Health and Safety Office (EHSO) assess the area for environmental hazards.
The Emory Project Manager manages this effort. Examples of environmental hazards are items such as,
but not limited to, presence of: asbestos-containing materials and/or lead-based paint, biological,
chemical including PPCB ballast and florescent light bulbs, and radiation hazards. The presence of
biological, radiation and chemical hazards will be found primarily in the laboratory/research environment.
Presence of asbestos-containing materials and lead-based paint coated surfaces can be found in and on
all types of building materials as well as laboratory-related equipment. For specific requirements
pertaining to the noted hazards, refer to the project manager.
Owner Property Insurance - FM Global
All design and installations should incorporate loss prevention guidelines as defined by FM Global Data
Sheet standards and should utilize FM Global approved equipment or systems when available. All design
plans should be submitted to FM Global's Atlanta office for review, and final acceptance subject to the
local FM Global engineering office.
The consultant responsible for specifying and/or installing an item not approved by FM Global will be
liable for all costs involved in correcting the deviation to the approval of FM Global. This liability includes,
but is not limited to, the cost of re-design, removal and re-installation, project management and Emory
University costs incurred, relocation and accommodation of any users involved, and any possible
additional insurance or risk management coverage that would be required due to the deviation.
Revision Date November, 2014
Section Page 2 of 3
Section 00 00 02
Introduction
Section Page 3 of 3
Section 00 00 03
Basic Program Requirements
Section Page 1 of 2
Section 00 00 03
Basic Program Requirements
Section Page 2 of 2
Section 00 63 00
Clarifications and Proposals
Section Page 1 of 1
Section 01 11 00
Summary of Work Requirements
Section Page 1 of 1
Section 01 31 00
Project Management and Coordination
Section Page 1 of 4
Section 01 31 00
Project Management and Coordination
The BEP shall establish the BIM authoring software to be used on the Project to best facilitate design and
construction analysis, evaluation, scheduling, bidding, fabrication and construction.
BIM Modeling
The Architect/ Engineer shall provide the Design BIM Model. The BEP plan shall provide for the Design
BIM model to be passed from the Architect/ Engineer to the Construction Manager/ General Contractor
for pricing, bidding, scheduling in accordance with the BEP plan. The Construction BIM Model may be
used by the CM/GC and the subcontractors and suppliers for cost estimating, interference checking and
for final bidding, construction sequencing, scheduling, submittals, shop drawings and fabrication through
the construction and for as-built documentation in accordance with the BEP plan.
The BIM model shall be capable of analyzing conflicts and interferences of model components. Survey,
topographic and utilities data for the site are provided by Emory and field verified by the Design Team.
Interoperability between AE and GC
The Design Team and the Construction Team, in their BEP plan, are to adopt open architecture policy
and product data exchange to maximize interoperability between architects, engineers, contractors,
suppliers, consultants and Emory. The team shall mutually agree on a central location to house
collaborative documents.
Interference Checking
Interference Checking using a model or method as determined by the BEP plan on a project by project
basis, shall foster the participation and interaction of MEP subcontractors as well as other prime
subcontractors, the CM/GC and the AE.
Energy Goals and Modeling
The design professionals shall work with the Emory Project Manager to establish the goals for energy,
water, building envelope and HVAC for the Project in conjunction with the Campus Services Design and
Construction Standards and in accordance with the BEP plan established for the Project. Local gas and
electric rates, including peak demand premiums shall be obtained from Emorys Project Manager working
with Energy & Utilities department.
BIM Green Building Goals and Modeling
Sustainability and LEED goals are established in the Design and Construction Standards or as modified
for the Project by Emory University and described in detail in the BEP for the Project.
BIM Asset Information Database (BIM-AID)
The BIM Asset Information Database (BIM-AID) is a spreadsheet database of key building components,
systems and assemblies of the Project organized in BIM categories and containing attributes (data) of
essential information for the long term operation and service of the building. A simplified sample BIMAID is provided in the Document Delivery Standards and the BIM-AID for each specific Project is part of
the BIM Execution Plan for the Project.
Initially, during Schematic Design, Design Development and Construction Documents phases, the BIMAID spreadsheet is populated by the Design Professionals with attributes (data) from the BIM model.
Attributes are added and revised in the BIM categories established in the BEP as the BIM model evolves
through SD, DD and CDs. During the Construction phase, the CM/GC provides and manages the data in
the BIM-AID spreadsheet, as described in the BEP.
Within ninety (90) days after completion of the Project, the AE and the CM/GC shall submit the completed
BIM-AID to Emory in accordance with the BEP.
Section Page 2 of 4
Section 01 31 00
Project Management and Coordination
Project Conditions
The General Contractor is responsible for generating and maintaining accurate Progress Documents
during the progress of the Work to reflect the as-builts or actual in-place construction, referencing all
Changes, Requests for Information, Supplemental Instructions, and Existing Conditions affecting such
Work. Progress Documents should be submitted per the Document Delivery Standard requirements. The
BIM model should be incorporated in the Progress Documents in accordance with the BEP.
The Architect is also responsible for coordinating the Record Documents, the final version of the
Construction Documents that have been modified by Architect/Engineer at Final Completion to reflect the
as-builts or actual in-place construction shown in the final Progress Documents, referencing all
Changes, Requests for Information, Supplemental Instruction and Existing Conditions affecting such
construction. The BIM model should be incorporated in the Record Documents in accordance with the
BEP.
Coordination
Coordinate the work to provide adequate clearances for installation and maintenance of equipment.
Install work to permit removal of parts requiring periodic replacement or maintenance. Arrange pipes,
ducts, raceways and equipment to permit ready access to valves, cocks, traps, starters, motors and
control components. Arrange raceways, wiring and equipment to permit ready access to switches,
motors and controls components. Doors and access panels shall be kept clear. Utilize space efficiently
so that adequate accessibility is retained for future maintenance, repairs, modifications and additions.
Automatic sprinklers will be installed generally throughout all areas. Check the locations selected for all
sprinkler heads and check the Architectural reflected ceiling plans to prevent conflicts between the trades.
In cases where an electric outlet or light fixture and a sprinkler head occupy the same position, the
Architect will decide which shall be shifted. Exposed sprinkler piping in finished areas will not be allowed.
Changes required in the Work of the Contract, caused by the Contractor's neglect to coordinate the work
with others shall be made at the Contractor's own expense.
Commissioning
This project will have selected building systems commissioned by a third party Commissioning Authority
(CxA), hired directly by Emory University. Refer to Section 01 91 13 for General Commissioning
Requirements.
Emorys Project Manager will notify FM Global of the time and date of pump acceptances, alarm system
acceptance testing, special protections (FM200, etc) acceptance tests and combustion control
acceptance testing.
Test and Balance Contractor
The Test And Balance Contractor will be contracted directly with Emory University and will be coordinated
with the CxA as part of the commissioning team. The TAB contractor shall be included in the design and
design review process as part of the commissioning team. The A/E should modify the TAB requirements
to be appropriate for the complexity of the systems to be installed in this building. Refer to Section 01 91
13 for specific coordination requirements with the TAB contractor.
Pre-Construction Conference
The Emory University Project Manager will schedule a preconstruction conference and organizational
meeting at the Project site or other convenient location prior to commencement of construction activities.
The Owner, Architect and their consultants, the Contractor and its superintendent, major subcontractors,
manufacturers, suppliers and other concerned parties shall be represented at the conference by persons
familiar with and authorized to conclude matters relating to the Work. Specific format for meeting notes
and distribution method will be reviewed at pre-construction conference. FM Global will also be invited to
the pre-construction conference as well as other conferences and meetings as deemed necessary by the
project.Projects that could require Outages or Hot Work shall have a pre-construction meeting to discuss
Section Page 3 of 4
Section 01 31 00
Project Management and Coordination
the current procedures. The pre-construction meeting should be scheduled with the Project Manager.
The Emory University Director of Fire Safety shall attend.
Outage Requests
All necessary service interruptions of utilities of any type or magnitude shall be scheduled in advance with
Emory University's Project Manager. Major utility shutdowns shall be scheduled during non-business
hours unless otherwise approved by the Project Manager. Scheduling of outages shall be through
submittal of written request at least 10 business days prior to proposed shutdown, and awaiting approval.
Pre-Installation Conferences
The Contractor shall conduct a pre-installation conference at the site before each construction activity that
requires coordination with other construction. Installers and representatives of manufacturers and
fabricators involved in or affected by the installation, and its coordination or integration with other
materials and installations that have preceded or will follow, shall attend the meeting.
OAC Meetings
Owner, Architect and Construction Manager team meetings will be arranged by the Construction Manager
and scheduled for at least every two weeks (or as approved by the Emorys Project Manager). The
Emorys Project Manager, the Architect, and Contractor shall attend the OAC Meetings and other
appropriate persons familiar with the project and authorized to conclude matters relating to the Work, as
agreed.
1. These meetings shall not reduce the Contractor's responsibility for and control over, as
expressed in the contract, construction means, methods, etc. and for coordinating all portions
of the Work.
2. Coordinate meetings to review Applications for Payment with weekly scheduled meetings.
This will facilitate more timely reviews of Applications for Payment.
3. The Construction Manager is responsible for documentation of meeting minutes.
4. The Progress Drawings (as-builts) will be reviewed at each OAC meeting for completeness
and thoroughness. Applications of payment will not be approved unless Progress Drawings
(as-builts) are current for the month.
Other Meetings
Additional specific construction meetings may also be held for other purposes, such as critical design,
performance or coordination issues, and the like. The Construction Manager will be responsible for
documentation and distribution of meeting minutes.
Section Page 4 of 4
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
Section Page 1 of 6
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
Section Page 2 of 6
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
During Design Development, the CM/GC provides updated (or reconfirmed) construction schedules per
the BEP.
Interference Checking
During Design Development, Interference Checking using a model or method as determined by the BEP
plan established for the Project.
Energy Goals and Modeling
The Design Development phase shall address energy, water, building envelope and HVAC for the Project
as a part of the BEP plan established for the Project or as modified by the Emory Project Manager. Local
gas and electric rates, including peak demand premiums shall be obtained the Emory Project Manager
BIM Green Building Goals and Modeling
Sustainability and LEED goals, established in the Design and Construction Standards or as modified by
the Emory Project Manager and as described in the BEP for the Project, are incorporated into the Design
Development model.
Quality Control
Standards of quality, established in the Design and Construction Standards and in the Schematic
Design used in establishing the Construction Cost Model (Estimate) or GMP, are addressed in Design
Development.
BIM Asset Information Database (BIM-AID)
During Design Development, the BIM Asset Information Database (BIM-AID) continues and is populated
by the Design Professionals with attributes (data) from the BIM model. Attributes are added and revised
in the BIM categories established in the BEP as the BIM model evolves.
BIM Deliverables - Construction Documents Phase
(Note: These BIM Deliverables supplement the Campus Services Document Delivery Standards.)
Construction Documents phase BIM model elements shall include architectural, structural, MEP and civil
elements, modeled as specific assemblies and systems, complete and accurate in size, shape, quantity,
quality, and orientation with assembly and fabrication information included.
In accordance with the BEP and the AE agreement, the AE shall provide a BIM model as a complete
virtual representation of the building with all of the assemblies and systems fully represented.
Provide parametric links of all elements within the BIM model enabling electronic generation of all plans,
elevations, sections, schedules and details of assemblies and systems for interference checking, exact
quantity estimating, detailed cost analysis, energy modeling, Green Building modeling, LEED program
certifications, and construction scheduling and sequencing, in accordance with the BEP.
Revalidate the Program Requirements
During the Construction Documents phase, the Design Team shall revalidate the Program requirements
for the Project including the space use and the performance requirements. The BIM model shall be used
to calculate and indicate assignable area and non-assignable area for each space and overall net and
gross area of the building.
Reconfirm the Construction Cost Model or Guaranteed Maximum Price (GMP)
In accordance with the BEP plan, the CM/GC confirms the Construction Documents Construction Cost
Model or Guaranteed Maximum Price (GMP) as required by the AE and CM/GC agreements and the BEP
based on bids from subs and suppliers of elements, assemblies and systems. The General Contractor
shall provide a complete Schedule of Values for Construction and reconfirm the Construction Cost Model
Section Page 3 of 6
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
or the GMP before completion of this phase. The Schedule of Values for Construction shall be used as
the basis of monthly pay requests during the Construction phase.
Reconfirm Schedule and Project Milestones
During Construction Documents, the CM/GC provides final construction schedule per the BEP. The
CM/GC addresses construction sequencing of specific detailed elements. The CM/GC Construction BIM
Model schedule is to show time scaled elements of specific assemblies and systems of the construction
of the building, including means and methods of construction in accordance with the BEP.
Interference Checking
During Construction Documents, Interference Checking using a model or method as determined by the
BEP plan established for the Project.
Energy Goals and Modeling
Satisfy goals for energy, water, building envelope and HVAC design for the Project as a part of the BEP
plan established for the Project or as modified by the Emory Project Manager.
BIM Green Building Goals and Modeling
Satisfy the Sustainability and LEED goals established in the Design and Construction Standards or as
modified by the Emory Project Manager and as described in the BEP for the Project. Incorporate the
design in the Construction Documents BIM model.
Quality Control
Standards of quality, established in the Design and Construction Standards and in the Schematic
Design used in establishing Construction Cost Model or the GMP, are included in the Construction
Documents.
BIM Asset Information Database (BIM-AID)
During the Construction Documents phase, the AE portion of the BIM Asset Information Database (BIMAID) is completed by the AE and handed off to the CM/GC. Attributes are added and revised in the BIMAID by the CM/GC in the BIM categories established in the BEP as the BIM model evolves through the
Construction Phase.
BIM Model Transition - the AE Design BIM Model becomes the CM/GC Construction BIM Model
At completion of the Construction Documents phase, the AE Design Team shall provide the Owner and
the CM/GC with copies of the AE Design BIM Model, a complete set of the Construction Documents in
the authorized authoring software in accordance with the BEP and the Campus Services Document
Delivery Standards. The Design Team shall also provide a complete set of Bid Documents displaying
each sheet of drawings in PDF format and a complete set of Specifications in MS Word and in PDF
formats, plus any addenda files, in accordance with the BEP and the Campus Services Document
Delivery Standards.
BIM Deliverables - Construction Phase
(Note: These BIM Deliverables supplement the Campus Services Document Delivery Standards.)
In the Construction Phase, the CM/GC shall maintain and keep current the CM/GC Construction BIM
Model as Progress Drawings and shall make as-built notations to the CM/GC Construction BIM
Model. The AE Design Team shall update and maintain concurrently, but separately, the AE Design BIM
As-Built Model as official and authorized Construction Change Directives are issued and as work is
completed.
The CM/GC may use the CM/GC Construction BIM Model for the preparation of shop drawings or as
determined by the BEP. The CM/GC shall also maintain and update the CM/GC Construction BIM
Revision Date June, 2013
Section Page 4 of 6
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
Model with authorized Construction Change Directives as they are issued. The CM/GC shall also update
the CM/GC Construction BIM Model with as-built conditions as they occur and transmit those changes
to the AE. Monthly reports prepared by the CM/GC shall be logged, posted and distributed to the Project
Team in accordance with the BEP.
The CM/GC shall also provide the following deliverables as part of the CM/GC Construction BIM Model
in accordance with the BEP:
Discipline Specific Coordination Models
Shop Drawing Models
Fabrication Models
As-built Models
Schedule Models
Should the CM/GC fall behind on the approved Construction Schedule, the CM/GC shall immediately
provide a makeup schedule to place the Project back on the original Construction Schedule.
Coordination Meetings During Construction
The CM/GC shall conduct coordination meetings for the construction period in accordance with the BEP
or as directed by the Emory Project Manager. The CM/GC shall provide concurrent as-built
documentation in the CM/GC Construction BIM Model throughout construction.
The CM/GC shall conduct Interference Checks at critical milestones in accordance with the BEP.
Interference Checks are to be reported and resolved at the coordination meetings. The reported
Interference Checks and resolutions shall be logged, posted and distributed to the Project Team in
accordance with the BEP.
Building commissioning operations data and performance criteria, including LEED compliance and
certifications are to be linked to the CM/GC Construction BIM Model and the AE As-Built BIM Model and
other data as described in the BEP as commissioning occurs throughout the Project. It shall be the
contractors responsibility to coordinate the information sources and integrate this information into the
CM/GC Construction BIM Model for transfer to the AE for the AE As-Built BIM Model at the completion of
the Project.
BIM Deliverables - Closeout Phase
(Note: These BIM Deliverables supplement the Campus Services Document Delivery Standards.)
During construction, the contractor and subcontractors are to mark up the Construction Documents to
show as-built conditions. These marked up drawings, the Progress Documents, are sent by the CM/GC
to the AE at closeout. The AE then prepares the Record Documents, the final version of the Construction
Documents, reflecting as-built conditions. Upon completion, the Record Documents (the As-Built BIM
Model) for the Project, in accordance with the Emory University Campus Services Design and
Construction Standards and the Document Delivery Standards and the BEP plan for the Project, and
within ninety (90) days of Substantial Completions, is delivered to the Owner in the Original Authoring
Software and in Autodesk AutoCAD software in accordance with the Campus Services Document
Delivery Standards.
Following these guidelines, provide six (6) complete progress documents: one (1) hard copy and five (5)
electronic copies on CDs and/or DVDs. One copy is to be kept in the building, Zone library, and HVAC
Shop. Additional sets will be kept in the Planning, Design and Construction project files as well as the
campus services information management archives. Additional copies are to be requested as needed.
Electronic copies of as built drawings are also to be provided in accordance with the computer aided
Revision Date June, 2013
Section Page 5 of 6
Section 01 32 00
BIM Guidelines Scope, Deliverables & Progress
design requirements (CAD) design requirements manual, which is included as a contract attachment.
Additionally, a marked-up set of progress document control drawings will be submitted to Emory Facilities
Management Control Shop. These prints will be used for trouble-shooting until the completed final
Progress Documents are received.
BIM Data at Closeout The BIM Asset Information Database (BIM-AID)
Upon completion of the construction of the Project, and within ninety (90) days thereafter, and in
accordance with the BEP, the AE and the CM/GC will complete and deliver the BIM Asset Information
Database (BIM-AID) to the Owner. The BIM-AID spreadsheet database of key building components,
systems and assemblies of the Project follows the Emory University BIM-AID Template and is organized
in BIM categories containing attributes (data) of essential information for long term operation,
maintenance and service of the Project.
Certain cells within the spreadsheet shall accommodate URLs with links to warranty information, shop
drawings and other data. The BIM-AID spreadsheet data shall be capable of being mapped by the Owner
directly into the facilities management program currently in use by Campus Services, AIM by Asset
Works. The Unique Identifiers and the asset names on the spreadsheet shall be tied together. The BIM
model drawings may also accommodate hyperlinks to the database for quick and easy access to data
either within the BIM model or to other data outside the BIM model in the 2D drawing sets.
Section Page 6 of 6
Section 01 33 23
Submittals, Shop Drawings, Product Data
Section Page 1 of 2
Section 01 33 23
Submittals, Shop Drawings, Product Data
6. Any special protection systems such as fixed gaseous systems with an Application for
Acceptance" form.
7. Any fire protection monitoring and general fire alarm system drawings
Section Page 2 of 2
Section 01 41 00
Standard of Quality and
Regulatory Requirements
Section Page 1 of 1
Section 01 43 39
Mock-Ups
//
Section 01 43 39 Mock-Ups
Emory values the benefits of mockups as a means of confirming the aesthetic and quality of an assembly,
and as a means of reducing problems and maintenance through proof of performance. The mock-ups
can be field constructed as a stand-alone sample or as part of the actual building depending on
circumstances. The design consultants will review the scope of the project with the Emorys Project
Manager to identify any system, assembly or detail of the construction that may warrant the use of a field
constructed or building mock-up. The design consultant shall also confirm with Emorys Project Manager
the need for applicable water testing. The design consultant must have this information incorporated into
the bidding or pricing documents. The Contractor shall include in the GMP or bid all costs associated
with the construction and demolition of required mockups. Possible mock-ups include:
1. Exterior wall with window
2. Roof edge with roof tile, soffit and gutter
3. Interior millwork or paneling
4. Special flooring or floor patterning
Mock-up construction drawings must be approved in writing by the Emory University Architect at the
completion of Design Development, or earlier if the construction manager notifies the team that they need
the drawings earlier in order to obtain the materials in time to construct the mock-up per the schedule
described below.
The timing of construction for mockups is critical to allow the University adequate opportunity to respond.
Prior to the ordering of materials and construction components, the design consultant, general contractor
or construction manager and Project Manager will address both the scheduling and site placement
(orientation, shading, etc same as the building) criteria of mock-ups in the construction documents.
It shall be the responsibility of the general contractor to prepare a schedule with key milestones for
material selection and design to ensure that mock-up materials can be procured and installed early
enough in the process to allow modifications in the design without causing construction delays or
additional costs.
Section Page 1 of 1
Section 01 50 00
Temporary Facilities and
Contractor Mobilization
Section Page 1 of 4
Section 01 50 00
Temporary Facilities and
Contractor Mobilization
Minimize construction activities within existing building to protect existing buildings. Install protection
before activities begin within existing building or on existing roof. Activate each fire sprinkler alarm valve
system as soon as roof is installed and the facility is protected from freezing conditions. Protect existing
roof from walking, working and equipment. Minimum Method: 3/4-inch exterior plywood.
Construction Parking
Make arrangements for and coordinate construction related parking requirements. Comply with Emory
University traffic and parking regulations, including permitting requirements. Cost for construction related
parking is to be included in the Contract Sum.
Project Identification
Do not erect, exhibit, or display graphic signs or other media device for advertisement or acknowledgment
unless previously approved in form, content and location. Trailers for delivery or otherwise, remaining at
the site overnight or longer, shall bear no identification larger than six inches high located within six feet
above the ground.
Emorys Project Manager will provide and install a Protect Identification sign. The sign will be designed
per the direction of the Project Manager and may be designed by the project Architect or by an
independent graphics consultant hired by Emory. The project and directional signs must be installed prior
to the start of construction.
Prepare directories and other signs to inform the public and persons seeking safe passage around or
entrance to the Project as directed. Temporary signs should be prepared to provide directional
information to construction personnel and visitors. Conform to requirements for Site Sign. Signs must be
installed prior to the start of construction.
Temporary Fire Protection
During construction period, and until time protection needs are fulfilled by permanent facilities, install and
maintain whatever types and forms of fire protection temporary facilities as may be needed to adequately
protect against fire losses. Comply with the applicable recommendations of NFPA "Portable Fire
Extinguishers" for each area of each construction activity when combustible materials, flammable liquids
and similar exposures to possible fires are present. Locate extinguishers where most convenient and
effective for intended purposes, but provide no less than two each floor at or near each usable stairwell or
exit. Store combustible materials in recognizable, fire-safe locations and containers.
Program: Develop and supervise an overall fire prevention and fire protection program. Instruct personnel
in methods and procedures of program; post warnings and information, and enforce strict discipline.
Review needs with local fire department officials and establish procedures to be followed. Maintain
unobstructed access to extinguishers, fire hydrants, temporary fire hydrants, temporary fire protection
facilities, stairways and other access routes for fighting fires. Prohibit smoking in hazardous fire exposure
areas. Provide extraordinary supervision of welding operations, temporary combustion heating units,
and similar sources of ignition for possible fires.
Provide extinguisher equipment of adequate capacity to extinguish fires, prior to use of combustible
material on the job site. Maintain fire extinguishers in working condition with current inspection certificate
attached to each extinguisher.
Performance
Confine equipment, apparatus, and storage of material to work limits. Emory University will not be
responsible for protection of materials and equipment from damage, pilfering, etc.
Noise from construction activities and equipment must be kept within DeKalb County Noise Control
Standards and be controlled to satisfaction of Emory University. Coordinate with Emorys Project
Revision Date August, 2010
Section Page 2 of 4
Section 01 50 00
Temporary Facilities and
Contractor Mobilization
Manager when construction work requires use of air hammers, Rotohammers or other objectionably noisy
equipment or when the longevity of use continues during an activity started later by the Owner.
Construction on Commencement Day, during Final Exam periods, and Alumni Weekend is not allowed.
Construction of certain types and in certain locations may be allowed on a very limited basis. Emory's
Project Manager will provide specific information.
Tree and Plant Protection
Preserve and protect existing vegetation such as trees on or adjacent to the site, which are not to be
removed. Protect trees from stockpiling, vehicle driving, and parking under the spread of tree canopies,
the dumping of refuse or chemically injurious materials or liquids, and continual puddling or running water.
Do not cut more than 6 inches or fill more than 2 inches within 6 feet of trees to be saved. Remove, after
review of conditions with Emorys Project Manager interfering branches and roots without injury to trunks
where required to facilitate the work
Project Site Security
Fencing - provide chain-link or wood privacy fencing with locked entrance gates. Locate vehicular
entrance gates in suitable relation to construction facilities and where it will avoid interference with traffic
on public thoroughfares. Locate pedestrian entrance gates as require providing controlled personnel
entry. Keys to Gate Locks: Deliver 3 labeled sets to Owner and obtain receipt.
Provide a project security program, to Protect Work, stored products and construction equipment from
theft and vandalism. Protect premises from entry by unauthorized persons. Protect Owner's operations at
site from theft, vandalism or damage from Contractor's work or employees. Maintain security program
throughout construction period, until Owner occupancy or Owner acceptance precludes the need for
Contractor security.
Provide control of all persons and vehicles entering and leaving Project Site. Maintain Log of visitors.
Owner will control deliveries and vehicles related to Owner's operations. The contractor is responsible for
securing the site and/or building during all non-working hours; i.e. nights, weekends, holidays. The
security at the site is the responsibility of the contractor but the contractor's plan must be approved by
Emory University's Project Manager, and possibly the Emory Police Department. Security of a site on
Emory University's campus must address securing the construction and equipment from theft or
vandalism as well as barring entry by potential trespassers and protecting pedestrians that pass by and
around the site.
Adjust and Clean
Relocate temporary facilities as required during job progress. Except as otherwise directed, remove
temporary facilities at completion of job. Restore disturbed areas to satisfactory condition, similar to
surrounding areas. Maintain existing temporary roads to the construction area. Restore to satisfactory
condition at completion. Maintain roads and public roads in a clean state at all times.
Emergency Contacts
The contractor must provide Emory University's Project Manager and the Emory Police Department with
emergency contact telephone numbers for 24 hour per day contact with someone in authority with the
contractor. Emergency telephone numbers are also required from the mechanical, electrical, plumbing,
fire protection, fire alarm, and security alarm contractors.
Behavior
1. Contractor and subcontractor staff cannot use existing break rooms for preparation and/or
purchase for food/beverages for meals and/or breaks.
2. Contractor and subcontractor staff cannot engage the students.
Section Page 3 of 4
Section 01 50 00
Temporary Facilities and
Contractor Mobilization
Work Hours
Work hours are covered by the contract and can differ depending on site location, end user, adjacent
buildings, academic calendar and other University events.
Section Page 4 of 4
Section 01 74 00
Cleaning
Section 01 74 00 Cleaning
Summary
Emory University expects that all construction sites be maintained in a clean and orderly manner.
Maintain project in accordance with applicable safety and insurance standards. Store volatile wastes in
covered metal containers. Provide adequate ventilation during use of volatile or noxious substances.
Product
Use only cleaning materials recommended by manufacturer of surface to be cleaned. Use cleaning
materials only on surfaces recommended by cleaning material manufacturer.
Final Cleaning
Before starting final cleaning, meet with the managers that represent Custodial Services. Employ
experienced workers, or professional cleaners, for final cleaning. In preparation for substantial completion
or occupancy, conduct final inspection of sight-exposed interior and exterior surfaces, and of concealed
spaces. Remove grease, dust, dirt, stains, labels, and other foreign materials from exposed interior and
exterior finished surfaces. Remove putty, paint, labels, lubricants, etc., from windows, mirrors, and sash,
and then polish, taking care not to scratch glass. Vacuum carpeting (shampoo where required), removing
debris and excess nap. Repair, patch and touch up marred surfaces to specified finish, to match adjacent
surfaces. Coordinate waxing of vinyl and wood flooring with Emory's Building Services. The Contractor
shall conduct an inspection of sight-exposed surfaces, and all work areas, to verify the entire work is
clean. Replace air conditioning filters where units were operated during construction. Maintain cleaning
until project or portion thereof is occupied by Owner.
Sustainability
Use cleaning products and procedures as outlined in Emory Universitys Green Cleaning Manual, current
edition, as developed by Emorys Building and Residential Services Department. Generally, cleaning and
housekeeping products should meet or exceed Green Seal Standard GS-7.
Section Page 1 of 1
Section 01 75 00
Starting and Adjusting
Section Page 1 of 1
Section 01 77 00
Close Out Procedures
Section Page 1 of 2
Section 01 77 00
Close Out Procedures
functional modifications that may have occurred during that period. Again consult with the Emory
Commissioning Engineer to discuss these requirements.
Construction Close-Out
Construction Project Close-out requires completion of the Construction & Closeout checklist. This is a
comprehensive document that covers all of the areas where documentation is needed before an area or
building is turned over from Planning, Design and Construction to Facilities Management. Completion of
this document requires the participation of the designers, contractor, commissioning consultant, project
manager, and Facilities Management personnel.
End Of Warranty Inspection
An End of Warranty Inspection will be scheduled and conducted at the project site prior to one year from
date Substantial Completion but as close to the end of that year as reasonably possible. Warranty
Inspection will be attended by at least one representative each of Owner, Architect, and Contractor.
Warranty Inspection is intended to be an opportunity for Contractor to become aware of any outstanding
corrections needed pursuant to the basic first-year warranty of Work.
*Note: As-Built documents now referenced as Progress Documents
The General Contractor is responsible for generating and maintaining accurate Progress Documents
during the progress of the Work to reflect the as-builts or actual in-place construction, referencing all
Changes, Requests for Information, Supplemental Instructions, and Existing Conditions affecting such
Work. Progress Document should be submitted per the Document Delivery Standard requirements.
The Architect is also responsible for coordinating the Record Documents, the final version of the
Construction Documents that have been modified by Architect/Engineer at Final Completion to reflect the
as-builts or actual in-place construction shown in the final Progress Documents, referencing all
Changes, Requests for Information, Supplemental Instruction and Existing Conditions affecting such
construction.
Section Page 2 of 2
Section 01 78 23
Operations and Maintenance
Introduction
The following is a cursory introduction to Emory University's operation and maintenance function.
This section is concluded with some general requirements that must be considered and included
in the planning of an Emory facility.
1.1
The Facilities Management department of Campus Services performs Emory University's
facility operation and maintenance. This department is responsible for the maintenance of
the University's grounds, the maintenance and operation of the University's utilities,
including the central steam and chilled water plants and distribution, and the custodial
care, physical maintenance, and operation of the University's facilities. These services
are provided through the five service zones that provide customer-oriented service to the
campus users, along with central support shops that provide the service zones with
specialized resources.
1.2
2.0
All of Emory University's facilities must include adequate space for facility support. The
programming effort must identify the space required for LITS, security systems, custodial,
mechanical, electrical, waste, and building storage support. Building systems and the
serviceability of these systems cannot be reduced to compensate for insufficient funding
or over committed programming or design. The Programmer, Architect, and Consultants
are responsible for identifying budget and program conflicts.
General Observations
2.1
Janitorial Rooms: There must be one janitorial room per floor of a building. The room
must be a minimum of 8 ft. by 10 ft. (80 sq. ft.) unobstructed by pipes and other utilities.
Adjustable steel shelving is required, two sections along the 8 ft. wall. A floor mounted
deep mop sink with a hose bibb, a floor drain, 4 duplex 120V receptacles with at least
one on each wall (design team to confirm adequate voltage for equipment), and wall
mounted brackets for mops, etc. are required per room. An eye wash station is preferred
for Janitorial/Custodial Rooms and should be included in the project unless directed
otherwise by the Emory Project Manager. For Janitorial/Custodial rooms with sheetrock
walls, ensure the walls adjacent to the floor sink are protected with FRP panels to a
height of approximately 4 AFF. Whenever possible, the door into the Janitorial/custodial
room should swing outward to preserve space inside for equipment and supplies.
2.2
Custodial Support Room: Each building there is to be a room, convenient to the loading
dock, for custodial equipment and supplies. Lockable double doors are preferred; the
minimum clearance at the door is 5 feet. One 8 cubic ft. flammable cabinet for
combustibles is required in each of these storage rooms. Provide 4 duplex 120V
receptacles with at least one per eight feet (design team to confirm adequate voltage for
equipment). The size of these storage/ equipment rooms varies according to the size of
the building. A general guide is as follows:
Up to 50,000 sq. ft. = 10'x 10'
Between 50,000 and 100,000 sq. ft = 15'x15'
Between 100,000 and 200,000 sq. ft = 20'x20'
Over 200,000 sq. ft. = 25'x25'
2.3
Custodial Staff Support Rooms: Each building should also provide space for
restrooms, dressing/locker rooms and a break room for custodial staff. Design team
needs to work the Emory Project Manager to clearly understand project needs with
regards to these types of spaces. If it is determined that it will not be possible to include
dedicated space for custodial staff, then space for lockers MUST be provided in the
Section Page 1 of 4
Section 01 78 23
Operations and Maintenance
Custodial Support Room described in section 2.2 above. The locker space should be
separated from the dry storage by a partition.
2.4
Building Maintenance Rooms: Lockable maintenance office and shop space is required
for each building. Design team needs to work the Emory Project Manager to clearly
understand project needs with regards to these types of spaces. A general guide is as
follows:
Up to 50,000 sq. ft. =10'x10' Office and 10x10' Shop Space
Between 50,000 and 100,000 sq. ft. = 15x15' Office and 15'x15' Shop Space
Between 100,000 and 200,000 sq. Ft = 20'x20' Office and 20'x20' Shop Space
Over 200,000 sq. ft. =25'x25' Office and 25'x25' Shop Space.
Maintenance office space should include the following fixtures furnishings and
equipment
Workstation Counter
Drawer Cabinet
Hand Sink
1 Office Chair
File Cabinets
Adjustable steel shelving
Maintenance shop space should have lockable storage for tools, a workbench
and a 10 cubic ft. flammable cabinet for paint and combustibles. Typical electrical
service to be 110V with a special 480 V drop to disconnect and convenience
outlets on 3 circuits
Maintenance office space and shop space shall include one telephone and data
connection. Lighting shall be fluorescent (See Electrical Narrative) with 50 footcandles minimum and include room occupancy sensors. 35% min - 55% max
humidity and 68-74 2F temperature range (See Mechanical Narrative)
Additional architectural considerations should include lockable 3'-0" x 7-0"
minimum door size, VCT floor finish with rubber base, painted wall finish, 2x2 layin acoustical ceiling panels with 9 foot minimum ceiling height.
It is essential that the scope of furnishings supplied and installed by contractor,
owner or any combination be clarified early in the design process.
2.5
2.6
Attic Stock Storage: Different types and colors of finishes; i.e. paint, wall coverings,
ceiling tile, carpet, and other floor coverings, etc. must be minimized. All buildings must
have ample storage space dedicated to store the attic stock of each finish. The size and
specifics of each attic storage space vary according to the size and usage of the building
and these details must be determined with input from the maintenance and building
occupant personnel. The suggested minimum size for buildings up to 50,000 sq. ft. is =
10'x10'. In addition to confirming the size and location of attic stock storage, the actual
Section Page 2 of 4
Section 01 78 23
Operations and Maintenance
materials to be included in attic stock are to be confirmed by the Emory Project Manager.
Provide appropriate shelving in the attic stock storage room to maximize the efficient use
of the space.
2.7
Loading Dock: Loading dock facilities are essential to the maintainability of each new
building and here again specific requirements are to be arrived at with input from facility
management personnel. A minimum of one dock space for large trucks complete with
leveler is required for each building. Each dock area is to have a minimum of a 12' wide
space for a compactor with height and truck accessibility requirements. There shall be
two additional parking spaces for delivery/service vehicles. There shall be a 4 ft. wide
ramp from dock to grade (Use the ADA for minimum design criteria). All service needs
vary with the size and usage of each building. Additional facilities may be required based
on user program needs. If an alternative strategy is utilized for loading dock access, such
as the use of tunnels to connect to existing loading dock facilities, it is essential that the
both the user program and facilities support needs be assessed to insure the adequacy
of the existing facilities. Identify any improvements to existing loading dock or related
facilities necessary to support this concept.
3.0
Emergency Generator
The emergency generator must be located so as to be readily accessible for servicing and
testing. Special care must be used in directing the engine exhaust to prevent fumes being drawn
in to the fresh air system of the building. To the extent practicable generators should not be
located immediately adjacent to storm drains.
4.0
Waste Management
4.1
All service facilities, dock-compactor-generator and transformers, must be located so as
to screen them from view of the building occupants and the general public as much as
possible. Coordinate with the Campus Architect for compliance with the Campus Design
Guidelines and campus master plan issues.
5.0
4.2
4.3
Pad for compactor must be 40' x 10' x 6" 3000lbs. Highway grade wire mesh reinforced
concrete. 30AMP / 460 VOLT - 3 Phase - 60 cycle wired to within 5' of the Compactor
Power Unit. Disconnect must be located outside the building accessible to the driver who
services the compactor.
Support Spaces
5.1
All support spaces must be climate controlled, ventilation is not sufficient. Mechanical
heating and cooling is required. All support spaces must be finished, painted, and the
floors must be sealed/painted at a minimum. No framing or supports, steel or otherwise,
shall be left unpainted.
5.2
All mechanical rooms and areas must be adequately large enough to have any
component in the room serviced or replaced without having to disassemble or remove
other equipment from the room.
5.3
5.4
5.5
Reference all other sections of this document for further information; i.e. the Emory LITS
and MEP sections, etc
Section Page 3 of 4
Section 01 78 23
Operations and Maintenance
6.0
Air Quality
Emory University is located in a non-attainment area for air pollution. If there is any significant,
additional air pollution potential because of a new project, Emory will have to file with the Georgia
Department of Natural Resources for a Title V air emissions permit revision. A significant addition
of air pollution potential that may require a permit revision would include any project that includes
emissions sources such as an emergency generator; fume hood exhausts, boiler equipment, etc.
The project budget must include the cost of this application, which also may require the services
of an Environmental Consultant. Additionally, the type and size of equipment must be determined
as early in the design process as possible (generally at least a year before occupancy or start up)
due to the usually lengthy permit review times by the state.
7.0
Recycling
Recycling space must be considered.
7.1
Provide containers and/or cabinets for trash, aluminum cans, plastics number 1 - 6,
mixed paper, white paper, and composting (optional) in the following rooms as
appropriate and the space allows: break room, event space, copy room, lobby space,
mail room, and either inside or outside classroom spaces. Provide cabinets to hold
containers for trash, aluminum cans, plastics number 1 - 6, mixed paper, white paper,
and composting (optional) in at least one dedicated recycling space per floor. Cabinets
are to be labeled to specify which materials are to be collected in each bin.
8.0
7.2
Each building is to have a recycling room located within the building off of the loading
dock to hold recycling bins. The size of this room is to be based on the size and use of
the building in accordance with Materials and Resources Prerequisite 1 Storage and
Collection of Recyclables under the current LEED rating system. Loading dock spaces
should have a dedicated area for cardboard collections that is sectioned off or fenced.
7.3
7.4
Outdoor receptacles for both waste an d recycling are to be Victor Stanley, Inc.
Steelsites Series A-36 (36-gallon side-door receptacles with welded canopy dome lid and
black liner, latch). Waste cans should be VS-Black powder-coat, and recycling cans
should be VS-Green powder-coat.
Section Page 4 of 4
Section 01 79 00
Demonstrations and Training
Section Page 1 of 1
Section 01 81 13
Sustainable Design Requirements
Section Page 1 of 4
Section 01 81 13
Sustainable Design Requirements
To be able to reference the credits for individual projects, the project must be registered in the Emory
block set up in LEED On-Line. The block number is 1000007945. Other procedures for registering the
project and completion of the credits listed above will be provided by Emory on an individual basis.
NOTE: The current master site credits may not be applicable if the LEED version system 4 is used.
Emory will provide guidance on the issue for each individual project as appropriate.
Sustainable Sites
Because a building site is typically determined during the master planning process, the design team will
have little or no influence on the following credits but should be aware of the information listed.
Brownfield Redevelopment
This credit will require consideration when asbestos may have been removed from the project site (e.g.,
on insulated steam lines or in building materials of a structure that previously occupied the site) or some
other type of environmental remediation within the project boundaries has occurred. Emorys
Environmental Health and Safety Office should be contacted for applicable documentation.
Heat Island Effect - Roof
Green roofs are not yet approved for installation on any Emory building as a main roofing component.
However, smaller green roofs may be considered on logical sections of a building. The design team
should discuss such potential areas with the Emory Project Manager early in the Schematic Design.
Energy and Atmosphere
The following are strategies which, at a minimum, should be reviewed:
The earlier in the process these strategies are tested and incorporated into the design, as appropriate,
the more benefit the entire project will see. For example, determining the level of insulation to be
included in the walls and roof during Schematic Design allows the mechanical engineer to right-size the
HVAC ductwork and achieve capital cost savings as well as improved energy efficiency. While the
addition of insulation has benefits if it is added later in the project, the engineer has already likely sized
the equipment. This results in less capital cost savings and less energy efficiency operation because the
system is then oversized.
Enhanced Refrigerant Management
Most buildings on Emorys campuses will be served by existing chiller plants which can largely comply
with this point. Investigation of available equipment pertaining to this point will necessitate reviewing the
efficiencies, as well.
If it is possible without unreasonable efficiency penalties, the design team should design the HVAC
system to comply with the requirements of this credit.
Revision Date November, 2014
Section Page 2 of 4
Section 01 81 13
Sustainable Design Requirements
There is an alternative compliance path to achieving this credit, also. It takes into account the effects of
both ozone depletion and global warming due to the type of refrigerants to be specified. Attainment of
this credit will take into account the refrigerant, the leakage rate and the estimated equipment life to
determine whether the specific piece of equipment complies. When refrigerant use is mandatory, the
design team should strive to select chiller equipment which will allow the project to obtain this credit.
Measurement and Verification
Under recent guidance provided by USGBC, one Measurement and Verification point can be earned by
simply registering the project in U.S. EPAs Energy Star Portfolio Manager, which should be done. The
appropriate credit form (currently EAc5) as well as option 1 in Project Information Form 1, question 6,
must be completed in order to successfully achieve this credit. Regardless each project must give Emory
the ability to track whole-building utility consumption (steam, chilled water, electricity and potable water).
This is so the collected data can be compared to the energy model developed during design and
calibrated utilizing actual data during the first year. This will be accomplished by the Energy & Utilities
department within Facilities Management working with the Emory Project Manager.
Green Power
At this time, green power credits are typically not pursued by Emory. This situation will be monitored by
the University and may become relevant to LEED certification at a future date.
Materials and Resources
Building Reuse/Materials Reuse
With the exception of certain major renovations, these points have very limited application to projects at
Emory and generally will not apply.
Construction Waste Management
It is Emorys intent to recycle as much construction waste as possible, with a goal of 100 percent
diversion of roadway materials and at least 95 percent of all other materials. Achievement of these
numbers will earn the LEED Construction Waste Management credit, and all projects seeking LEED
certification should meet the intent of that credit and prepare proper documentation accordingly. All other
projects should follow the guidance below:
A recycling plan (generally following the format required by LEED) shall be prepared and
submitted to the Emory Project Manager prior to construction.
Hazardous materials shall be disposed of in accordance with applicable regulations. Recycling
where appropriate is encouraged.
Recycled wastes shall be paid for by the contractor.
Quantities of each recycled material shall be documented along with the receiving agent. All
documentation shall be provided to the Project Manager.
Some materials may be reused on site (e.g., crushed concrete) as approved by the engineer.
Expected recyclable materials include, but are not limited to, metal, wood, cardboard, masonry,
concrete, glass, gypsum board, carpet and asphalt.
Section Page 3 of 4
Section 01 81 13
Sustainable Design Requirements
Depending on the quantity and the cost premium, the University may elect to have wood shipped from a
non-local FSC certified supplier to meet the intent of this credit. The design team should discuss this with
the Emory Project Manager during Design Development.
Indoor Environmental Quality
Low-Emitting Materials: Composite Wood and Agrifiber Products
Emory has had difficulty finding an economical source for these products. As such, the architect, on each
project, should determine whether a suitable product is available and present it to the Emory Project
Manager early in design to determine whether this point will be pursued. The availability of these
products, the cost premium and the affect on the local and regional materials credit should all be
balanced.
Controllability of Systems: Lighting
Emory has not found this credit to be technically or economically feasible in the projects to date. The A/E
team should review the credit requirements and determine whether the current building project can meet
the requirements. These results should be presented to the Emory Project Manager during Schematic
Design.
Controllability of Systems: Thermal Comfort
Emory has not found this credit to be technically or economically feasible in most projects to date. The
A/E team should review the credit requirements and determine whether the current building project can
meet the requirements. These results should be presented to the Emory Project Manager during
Schematic Design.
Daylight and Views: Daylight
This credit is very much dependent upon the geometry of the building and the visible light transmittance
of the glass selected. If the geometry of the building is conducive, every effort should be made to achieve
the requirements of this credit. If possible, support spaces and spaces where daylighting is detrimental
should be placed on the interior portions of the building floor plate.
A preliminary review of the daylighting in the spaces should be performed at the conclusion of Schematic
Design. If the results of this study show the potential for achieving this credit, minor changes should be
made to bring the project into compliance.
Daylight and Views: Views
Similar to the above credit, the layout of spaces should consider offering occupant views of the exterior as
required to meet the credit. The preliminary review, discussed above, should be performed and given the
same consideration by the design team.
Section Page 4 of 4
Section 01 91 13
General Commissioning Requirements
Section Page 1 of 5
Section 01 91 13
General Commissioning Requirements
Section Page 2 of 5
Section 01 91 13
General Commissioning Requirements
Section Page 3 of 5
Section 01 91 13
General Commissioning Requirements
BAS Contractor:
During functional testing by the CxA, alarm routing shall be to a secondary OWS
computer. Upon completion of the functional tests, route the alarms as required to the
primary alarm display in the OWS.
Provide requested trend information to include, at minimum, all major control setpoints to
demonstrate stable and accurate control.
Assist the TAB Consultant and the CxA to optimize static and differential pressure control
setpoints and reset limits.
TAB Consultant:
Assist the BAS Contractor and CxA to optimize static and differential pressure control
setpoints and reset limits.
Assist the CxA to conduct and document pressure mapping of the facility at the design
airflows and at part load conditions to verify pressure relationship across the envelope
and across partitions between all pressure critical zones are per the project requirements.
WARRANTY PHASE
A/E Team:
Continue to assist the Cx Team to resolve any issues or concerns identified during the
first year warranty period.
General Contractor:
Assist in coordination with its Subs to perform seasonal and deferred testing, as required.
All Subcontractors:
Support the CxA to perform any seasonal or deferred functional testing, as required.
Systems to Commission (by the CxA)
The following is a general list of the equipment and systems that are typically commissioned on Emory
projects:
Building Envelope Systems (refer also to Standard Section 019119)
Building Automation Systems, including linkages to remote monitoring and control sites and
integration to other systems
Laboratory Control Systems, including integration to the building automation system
HVAC Equipment and Systems
Revision Date June, 2013
Section Page 4 of 5
Section 01 91 13
General Commissioning Requirements
Section Page 5 of 5
Section 01 91 19
Facility Shell Commissioning
Page 1 of 3
Section 01 91 19
Facility Shell Commissioning
The ECx shall review and approve the mock-up construction drawings prior to distribution to the
Construction Manager for fabrication. The construction mock up shall be designed and constructed for
conducting typical water testing of glazing assemblies.
The ECx shall coordinate site visit(s) with the Owner, Architect and Construction Manager at milestones
during the mock-up construction. The ECx shall prepare a report after each visit. The Architect and
Construction Manager shall provide written response to each deficiency noted in the reports.
The ECx will conduct timely site visits during construction to observe below and above grade
construction. After each site visit, the ECx will provide an associated field report that includes a
continuous deficiency log. The Construction Manager will be expected to address any deficiencies
identified in the field reports and update the deficiency log with written and photographic remedial action
regarding each identified deficiency.
Roofs:
A Registered Roof Observer (RRO), as recognized by RCI Inc., is required to:
1. Complete a minimum of three inspections per week to ensure the work is being completed as
specified. At a minimum the RRO shall report to the General Contractor, Project Manager and
Roofing Contractor with the following daily field report information.
a. Account Name
b. Date
c. Account Address
d. Project Name
e. Report Number
f. Roof Designation
g. Weather
h. Personnel present at site
i. Contractor Information
j. Roofing System
k. Daily Activity and General Notes
l. Contractor foreman signature
m. Inspector signature on each daily form
n. Roof Top Drawing of daily work
o. Progress Photos
p. All reports and photos will be emailed to client and contractor on a weekly basis
2. All field reports, warranties and specifications will be loaded into the roof management database.
Tests
The contract documents shall require the contractor to demonstrate water tightness on a reasonable
number (15% is a guideline) of the installed window systems. The contractor shall assist and coordinate
with the ECx regarding the level of support required (i.e., person lifts, water hoses, water, chamber
construction, etc.)
In general, the ECx will perform the following tests on a representative sample of envelope openings:
Nozzle testing per AAMA 501.2
Static Pressure Chamber testing per ASTME 1105
The contract documents shall require low slope buried roof assemblies green roofs be tested using
electronic field vector mapping.
Page 2 of 3
Section 01 91 19
Facility Shell Commissioning
Roofs:
Per Section 07 50 00 Built-up Bituminous Roofing special commissioning section agency is to witness
and attest to the result of the flood testing on roof drains for low slope waterproofing systems as well as
low slope conventional built-up roof systems.
Page 3 of 3
Section 01 94 00
Facility Decommissioning
Section Page 1 of 1
Section 02 62 00
Hazardous Waste Recovery Processes
Section Page 1 of 1
Section 03 00 00
Concrete
Section 03 00 00 Concrete
General
Concrete design shall meet or exceed American Concrete Institute (ACI) standards. Structural drawings
to be sealed by a registered structural engineer in the State of Georgia and contain the following:
1. Specify all loads used for design with complete strength calculations
2. Shop drawings required for fabrication, grade, and placement of reinforcement, including joint
locations and sealing compounds. Provide certification from (an independent testing laboratory)
that mechanical connectors for steel reinforcing comply with applicable codes and engineering
calculations.
Concrete Finishing
1. Concrete slab construction shall have a moisture content test prior to the installation of any
finishes. Curing components and sealers shall be compatible with intended finishes.
2. Exterior or interior exposed concreted should be coated with a finish material, such as plaster,
stucco, synthetic acrylic stucco, etc. Emory must approve all finishes.
3. Exterior or interior exposed concrete to be left as exposed surfaces shall be left true to line and
plane, and free from form marks and other imperfections. Cosmetic coatings used to disguise
underlying defects are unacceptable.
Concrete Formwork
Formwork to be designed by a professional engineer registered in the State of Georgia. Material should
have sufficient strength to resist hydrostatic head without bow or deflection in excess of allowable
tolerances. Provide chamfered edges and corners at exposed locations.
Concrete Materials
1. All Portland Cement to be Type I, unless otherwise specified and approved by Architect. All
admixtures must be approved.
2. Cement substitutes and additives in the concrete design that promotes the use of recycled
materials such as fly ash is recommended.
Concrete Testing
All concrete material testing to be performed by an independent testing laboratory selected and
contracted by the owner. Contractor to submit a schedule indicating type, quantity, and number of site
visits to coordinate material testing with independent testing laboratory.
Walks, Ramps, and Traffic Areas
1. Provide all exterior concrete ramps, walks, loading docks, aprons, and other such surfaces
subject to weather with a non-slip broom finish.
2. Sidewalks and pedestrian pavements shall include fibermesh reinforcement or an approved
equal. Welded wire mesh is not an acceptable reinforcement.
Sustainability
All Emory projects, including major renovations, shall attempt to meet and exceed the requirements of
Materials and Resources Credit 4 Recycled Content and Credit 5 Regional Materials under the
current LEED rating system for this material. Generally, the use of cement substitutes and additives in the
concrete design that promote the use of recycled materials such as fly ash and slag shall be considered.
Concrete materials and products should be extracted, recovered and manufactured within 500 miles of
Emory University.
Section Page 1 of 1
Section 04 00 00
Masonry
Section 04 00 00 Masonry
Reviews
1. The Emory Project Manager must approve all masonry veneers and mortar selections.
2. Contract documents shall require contractor to erect a mock-up of masonry assemblies for review
by Emory University prior to commencement of exposed masonry work. The materials used in all
mock-ups must be identical to those to be used on the building.
3. All mock-ups should be constructed in same orientation as final building/structure whenever
possible.
4. All mock-ups shall be completed and approved at least 14 days prior to the scheduled
commencement of masonry installation.
Cleaning
1. MSDS information must be provided to The Emory Project Manager before any cleaning activities
may begin. Cleaning solution shall be tested on the mock up prior to its use on the main
structure.
2. Contractor shall be responsible for preventing the runoff from any cleaning operations from
entering nearby storm sewers or tributaries.
Masonry Anchors
1. Corrugated metal ties are not to be used on masonry veneers.
2. Anchors shall be made of corrosion-resistant materials, or stainless steel when anchoring natural
stone or stone veneers.
Mortar Net
Mesh designed to catch and hold mortar droppings in an irregular pattern shall be used. The mesh shall
not trap moisture or water and shall not support mold or fungus.
Weeps
1.
2.
3.
4.
Weep tubes shall be installed at all holes except at grade where weep ventilators are installed.
Keep weep holes and area above flashings free of mortar.
Install cavity mortar drainage net in cavity behind wicks.
Plastic or metal weep hole accessories shall have insect screens to prevent insects from entering
the masonry cavity.
Renovations
1. Reuse of existing bricks and pavers is a goal of the typical project. If new bricks and/or pavers
are required then they should match the existing as close as possible.
2. The Emory Project Manager must approve mortar joint profiles, and mortar colors for any
renovation project
Boric Acid
All exterior walls and walls for animal holding are to have a medium dusting of boric acid powder put into
the walls for pest control purposes immediately prior to sealing of walls. This scope of work shall be
provided by the General Contractor. General Contractor shall provide documentation of application.
Site Work
Refer to Division 32 and Division 04 for specific information for Granite Rubble Wall or Site Masonry Work
Sustainability
All Emory projects, including major renovations, shall attempt to meet and exceed the requirements of
Materials and Resources Credit 5 Regional Materials under the current LEED rating system for this
material. Masonry materials and products should be extracted, recovered and manufactured within 500
miles of Emory University.
Revision Date August, 2011
Section Page 1 of 1
Section 05 00 00
Metals
Section 05 00 00 Metals
General
Properly protect handrails, stairs, and other items incorporated into the work in the early stages of
construction from weather, falling mortar, concrete, debris, water and other abuses. When damaged,
make proper repairs, or where damage is extensive, replace the items.
Quality Assurance
Steel decking utilized for roof construction should be FM Global approved and limited to the span widths
under which it is approved. Structural steel components of the building must comply with the
requirements of FM Global.
Sprayed On Applications
1. Prefer that structural steel and steel decking be protected with gypsum board sheathing, rather than
sprayed fireproofing systems. Where gypsum board sheathing protection is not practical, use
sprayed fireproofing systems with a sealer overcoat.
2. Where conditions require, sprayed thermal insulation can be used in conjunction with sprayed
fireproofing that has a sealer overcoat.
Finishes
All structural steel products which have an exterior exposure or which are designed for use in an area
with high humidity or with possible exposure to caustic chemicals shall be galvanized, except where such
design has been reviewed and approved by Emory University on a case-by-case basis.
All exterior, exposed metal, such as soffits or spandrels shall be aluminum and finished with a baked on
Kynar 500 type paint with a minimum 20 year warranty against fading, cracking or chipping. Other metals
or finishes must be reviewed and approved by Emory University on a case-by-case basis.
Testing
Emory University will engage an independent testing and inspection agency to perform testing, inspect
and evaluate connections, and prepare test reports. The contract specifications shall require access to
the steel fabrication shop for the testing and inspection agency.
Exterior Handrails
The design of exterior handrails shall comply with the Emory University Campus Design Guidelines and
must be in compliance with the ADA Accessibility Guidelines and all governing codes. Where vertical
supports extend into a concrete surface, Completely grout hole in concrete around the vertical support
and slope grout away from support. There should be no opportunity for water to puddle around the
support.
Ceiling-Hung Toilet Compartments
Provide structural steel above the ceiling in restrooms designed to support the ceiling-hung toilet
compartments. Coordinate loads with toilet compartment product requirements.
Sustainability
All Emory projects, including major renovations, shall attempt to meet and exceed the requirements of
Materials and Resources Credit 4 Recycled Content and Credit 5 Regional Materials under the
current LEED rating system for this material. Generally, the use of metal material substitutes and
additives in the metal design that promote the use of recycled materials shall be considered. Materials
and products should be extracted, recovered and manufactured within 500 miles of Emory University.
Section Page 1 of 1
Section 06 00 00
Wood, Plastics, and Composites
Section Page 1 of 2
Section 06 00 00
Wood, Plastics, and Composites
The design team should determine if a suitable product is available and present it to the project manager
early in design to determine whether or not such product is appropriate for the project. Local/regional
product availability and any associated cost premium should be considered.
Section Page 2 of 2
Section 07 20 00
Thermal Protection
Section Page 1 of 1
Section 07 30 00
Steep Slope Roofing
Section Page 1 of 2
Section 07 30 00
Steep Slope Roofing
(Standard Field Test Procedures For Determining The Withdrawal Resistance Of Roofing
Fasteners).
The results of these tests will be compared to the FMG Property Loss Prevention Data Sheet 128 and 1-29 requirements to determine if adequate pull-out resistance is achieved. The results of
these tests will be either pass or fail.
Additional References:
1. ASCE Standard 7-98, Minimum Design Loads for Buildings and Other Structures
2. Data Sheet 1-9, Roof Anchorage
3. Data Sheet 1-31, Metal Roof Systems
4. Data Sheet 1-49, Perimeter Flashing
5. Data Sheet 1-52, Field Uplift Testing
6. Manufacturers independent testing results
Execution
The contract documents shall require that Emory University receive a 5 year labor and material warranty
provided by installer/ 75 year materials warranty for clay tile or slate materials on roofing systems, unless
a modification to this requirement has been reviewed and approved by Emory University on a case-bycase basis.
Sustainability
Emory encourages the use of lower heat island effect roof materials and colors. Design team will review
options with Emory Project Manager.
Section Page 2 of 2
Section 07 50 00
Built-Up Bituminous Roofing
Low-slope roofing membrane systems which are capable of serving as waterproofing systems
shall be flood-tested for water-tightness after installation over low-slope roof decks is complete.
o The Contractor shall plug all roof drains and/or erect temporary dams in the roof areas
being tested and flood the areas with water up to a maximum depth of two (2) inches at
the high point. Maintain this water level for a minimum of twenty-four (24) hours or as
required by the manufacturer.
o If structural calculations indicate an unacceptable hazard in flooding roof areas with
associated drains plugged, the Contractor shall instead apply continuously flowing water
over the waterproofing membranes. If this option is used, the Contractor shall allow water
to flow over the membrane for a minimum of twenty-four (24) hours or as required by the
manufacturer without closing any drains or erecting dams.
o Repair or replace any areas that allow water infiltration.
o Repeat test until there is no water leakage.
Conventional low-slope roofing membrane systems (i.e., non-green, non- PMR, non-IRMA, etc.,)
shall also be tested for water-tightness.
o The Contractor shall flood areas at the roof drain sumps. After completion of membrane
installation, plug roof drains and fill with water to the edge of the drain sump for eight (8)
hours.
o If present, do not plug any secondary overflow drains at the same time as adjacent
primary drains.
o To ensure some drainage from roof, do not test all drains at the same time.
o The Contractor shall measure water at the beginning and end of the test period. If water
level falls, remove water, thoroughly dry the drain area, inspect the installation and the
corresponding underside of the deck penetration, and repair or replace roofing at drain to
provide for a properly installed and watertight flashing seal.
o Repeat test until there is no water leakage.
o When precipitation occurs during the test period, the Contractor shall repeat the test.
Products
Specifications for products included in this Section and accessories shall meet the ANSI and ASTM
criteria for each material, shall be UL listed and labeled, and shall meet the NRCA Roofing and
Revision Date November, 2014
Section Page 1 of 4
Section 07 50 00
Built-Up Bituminous Roofing
Waterproofing Manual recommendations. The roofing system design shall meet the criteria to be listed for
a UL Class A exposure. The contract documents shall require that Emory University receive a 20-year
warranty on roofing systems, unless a modification to this requirement has been reviewed and approved
by Emory University on a case-by-case basis.
Roof material, insulation, felts, flashing, seaming or patching mastics, paints or any roof component
system used at Emory shall not contain asbestos. Verification from the manufacturer shall be submitted
to Emory in letter form stating such information. Emory Environmental Health and Safety Office retains
the right to randomly collect samples prior to their installation and have the material sampled. An
accredited laboratory will then analyze these samples. Should said materials contain asbestos it shall be
the responsibility of the contractor to replace with materials found not to contain asbestos.
Roof flashings, solder, scuppers, downspouts and paints shall not contain lead due to the leaching
potential from rainwater and the possibility of lead contamination to the surrounding environment.
Verification from the manufacturer of stated items must be received in writing prior to installation and
found to be acceptable to Emory.
The following products have been reviewed and approved by Emory University:
Johns Manville
Tamko,
Tremco
Siplast
Other manufacturers may only be considered if reviewed and approved by Emory University prior to the
start of any construction activity on the project. The system design must be specified and detailed with all
components illustrated including substrate preparation, vapor retarder, insulation, roof membrane, base
flashings, roof asphalt, roof accessories and roof ballast.
System specifications must be equal to or exceed the following:
Hot Applied Assemblies: Johns Manville 4 Ply built up roof with ASTM 1863 surfacing and/or 3 plies of
Type IV fiberglass felts and an ASTM D 6163 Modified Bitumen Cap sheet.
Cold Applied Assemblies: Solvent free, Cold Process, modified bitumen roof systems shall be 100%
solvent free including all insulation, membrane, flashing and related adhesives. The roof system shall
consists of a one plus one built-up modified bitumen roof system roof system assembly with the following
minimum performance criteria for the base ply, cap sheet and flashing assemblies:
Roofing Membrane/Flashing Ply Sheet: ASTM D 6164, Grade S, Type I or II, polyester-reinforced, SBSmodified asphalt sheet; smooth surfaced; suitable for application method specified with the following
minimum physical properties at tested by ASTM 5147.
1.
Mil Thickness: 94
2.
3.
4.
5.
78
80
35%
35%
Roofing Membrane/Flashing Cap Sheet: ASTM D 6164, Grade G, II, polyester-reinforced, SBS-modified
asphalt sheet; granular surfaced; suitable for application method specified, and with the following
minimum physical properties at tested by ASTM 5147.
Revision Date November, 2014
Section Page 2 of 4
Section 07 50 00
Built-Up Bituminous Roofing
1.
2.
3.
4.
5.
6.
148
115
45%
45%
The roof system installed should be FM Global approved as listed in the most recent edition of the FM
Global Approval Guide.
Single-ply roofing systems are typically not acceptable, but may be considered in special circumstances
upon prior written approval by the Emory University Project Manager.
Built up bituminous roofing systems shall, at a minimum, meet the following performance standards: multiply SBS assembly, 20 year total system warranty as outlined below, minimum slope of roof deck per
foot and no ponded water after 24 hours.
Warranty: Manufacturer's Total System Warranty without monetary limitation, in which manufacturer
agrees to repair or replace components of roofing system that fail in materials or workmanship within
specified warranty period. Failure includes roof leaks warranty includes roofing membrane, base
flashings, roofing membrane accessories, cover boards, all metal used on project, base sheets, base
sheet fasteners, wind speeds up to 73 mph, and other components of roofing system.
Warranty Period: 20 years from date of Substantial Completion.
Special Project Warranty: Roofing Installer's warranty, on warranty form, signed by Installer,
covering Work of this Section, including all components of roofing system roofing membrane, base
flashings, roofing membrane accessories, roof insulation fasteners, cover boards, all metal used on
project, base sheets, base sheet fasteners, wind speeds up to 73 mph, and other components of
roofing system for the following warranty period:
Warranty Period: Five years from date of Substantial Completion. Execution
The contract documents must include requirements for inspection and review of the substrates under the
roofing system(s) and complete details showing installation of the roofing system in compliance with all
requirements of FM Global, UL, governing authorities and codes and the manufacturer. A representative
of the manufacturer shall be available to inspect the roofing installation upon request by Emory University
and shall inspect and approve roofing installation before acceptance by Emory University.
Sustainability
Emory supports the use of lower heat island effect roof materials and colors. The design team is
encouraged to meet and exceed the requirements of Sustainable Sites Credit 7.2 Heat Island Effect:
Roof under the current LEED rating system and should review options with the Emory Project Manager.
Generally, the A/E team should review roofing products which meet the Energy Star and emissivity
requirements of the credit. Even if the roof to be installed cannot meet the 75% threshold, consideration
should be given to specifying it anyway in order to decrease the overall heat island effect of the building.
Revision Date November, 2014
Section Page 3 of 4
Section 07 60 00
Flashing and Sheet Metal
Section Page 1 of 1
Section 07 84 00
Firestopping
Section 07 84 00 Firestopping
Scope of Work
This section includes all firestopping applications through rated assemblies including their penetrations,
joints, and/or gaps that are to be protected with Underwriters Laboratory (UL) tested firestop system and
UL listed firestop material.
Regulatory Requirements
All Firestopping material must be tested in accordance to nationally recognized test standards for
firestopping systems set by American Society of Testing and Materials and Underwriters Laboratories,
and comply with all code and regulatory requirements. The following test standards and code
requirements shall be used for firestopping materials and systems.
1. ASTM E 814 for through penetration firestopping.
2. ASTM E 1966 for construction joint firestopping.
3. ASTM E 2307 for perimeter edge fire stopping.
4. UL 1479 for through penetration firestopping, L ratings, aging and environmental exposure.
5. UL 2079 for construction joint firestopping.
6. IBC Section(s) 712 and 713
The Current Adopted Building Code Edition
Quality Assurance
All firestopping systems must be tested and listed by Underwriters Laboratories, approved by Emory
University, and the authority having jurisdiction on the project the materials are used. All systems must
be tested in accordance to UL and ASTM E standards to provide F and T ratings. Penetrations through
rated floor assemblies must provide firestop systems with F and T ratings equal to the hourly rating of the
floor penetrated. All firestop products must be free from harmful chemicals, asbestos, ethylene glycol,
PCBs, and lead; materials must not require hazardous waste disposal nor chemicals or solvents for clean
up. Firestop material must be able to be installed per manufacturers written instructions in temperatures
ranging from 35 degrees F to 120 degrees F, and have the ability to be frozen, thawed and still be
useable.
Products
Specifications for products included in this section must have written documentation from Underwriters
Laboratories of passing UL accelerated aging and environmental exposure testing. Firestop material is to
be manufactured in the United States and comply with all specified requirements.
1. Firestop Caulks, Mastics and Sealants:
a. Intumescent Sealant is to be water based and free from ethylene glycol available in
systems joints and through penetrations. Basis of design Metacaulk 1000.
b. Elastomeric Sealant is to be water based and be capable of protecting joints and through
penetrations. Basis of design Metacaulk 1200 Caulk Grade
2. Intumescent Wraps and Collars:
a. Intumescent material is to have UL verification of passing Accelerated aging and
environmental exposure testing. Pipe collars must have permanently affixed attachment
tabs from the manufacturing. Basis of design Metacaulk Wrap Strips and Pipe Collars.
3. Firestop Sprays and Mastics:
a. All materials are to be elastomeric water based with zero solvent content. Material must
not re-emulsify when exposed to water. Basis of Design Metacaulk 1200 Spray and
1100 Spray.
4. Membrane Penetration Protection:
a. Intumescent putty pads, intumescent box inserts or intumescent cover guards that are
listed in the UL directory for membrane penetration protection CLIV. Putty pads and
box inserts must allow for back to back box installation. Basis of design Metacaulk Putty
Pads, Box Inserts, and Cover Guards.
5. Cast in Place Device:
Revision Dated July, 2008
Section Page 1 of 2
Section 07 84 00
Firestopping
a. Cast in Place firestop device is to be a standalone firestop unit tested and listed by UL to
protect blank openings, metallic, plastic, cable, insulated metallic and mixed multiple
penetrations in a single device. Cast in Device must be available in 2.5 inch to 6 inch
diameter round as well as oval configurations. Basis of design Rectorseal Cast in Place
Device.
6. Cable Pass-Through Device:
a. Pass-through device shall be a standalone factory made firestop sleeve allowing all
series of cable penetrations through the device including but not limited to data,
telephone, low voltage, high voltage, power cables, as well as metallic pipe, EMT,
metallic conduit, plastic pipe, ENT, insulated metallic pipe, and mixed multiple
penetrations through gypsum and masonry walls and floors. Device must be available in
round and square configurations and every device must be applicable to new installation
and retro fit designs. Sleeve must have a separate wall bracket assembly available in
single, double, triple, and six plex configurations. Device must have L ratings of less than
5 cfm with device only, no putty. Basis of design Rectorseal Pass-Thru Cable Sleeve.
Warranty and Contractor Qualifications
Firestop installer must warrant the installed firestopping for the life of the building, lack of manufacturers
warranty does not release installer from specified warranty. Firestop manufacturer shall provide a written
warranty for products properly installed in building for the sustainable life of the structure, lack of written
warranty does not release manufacturer from liability for faulty firestop products. Installing contractor
must have a minimum 3 years experience installing firestop in projects of similar scope and size,
contractor must have certification from the firestop manufacturer in the form of a qualification card to show
competence in installing firestop material from that manufacturer.
Sustainability
Firestop installer must complete a LEED worksheet for all materials and components of installed firestop
systems detailing products eligible for LEED points in MR 4.1, 4.2, 5.1, 5.2; EQ 3.1, 3.2, 4.1, 4.2.
Section Page 2 of 2
Section 08 00 00
Openings & Doors
Section Page 1 of 2
Section 08 00 00
Openings & Doors
Steel doors and frames must meet all standards as established by the following references and must be
rated and labeled accordingly:
American National Standards Institute (ANSI) A115.1 Door and Hardware Preparation
National Fire Protection Association (NFPA) 101 Life Safety
Building codes (latest edition)
NFPA 80 Fire Doors and Windows (latest edition)
Architectural Woodwork Institute Quality Standards, Section 1300 (latest edition)
Americans with Disabilities Act (ADA) ADAAG4.13
The minimum door opening shall be 3-0.
Flush doors shall be specified.
Fire-rated doors required to be B-Label classification shall be made of metal.
On labeled fire doors, all closers shall be of a non-hold-open type approved by Underwriters
Laboratories (UL).
Doors that open to corridors and contain glass shall use UL fire-rated tempered glass or wire
glass.
All Doors Including Entrance Doors
Specialty doors or featured entrance doors are allowable under certain circumstances but must be
approved by the University Architect and Project Manager. Additional door requirements:
1. Are to be a height of either 6-8 or 7-0
2. If double 3-0 doors are used, a removable center mullion with a door coordinator must be
included
3. In 6-0 openings, a 4 door and a 2 leaf secured by flush bolts may be used
Automatic Sliding Doors (Sliders) may be used. The only accepted manufacturer of sliders is
Horton Lab Doors
1. One 4-0 door is preferred to a 3-0 with a 1-0 leaf
2. If a 3-0 with a 1-0 leaf is used, an overlapping Astragal is preferred
All voids in doors and frames must be filled and sealed
Dirtt Wall and Door Systems
Do not use DIRTT or similar wall and door systems when there is a possibility the area will need to
be secured by locking hardware or access control.
Owner Review
The installation of the first 6 door frames shall be reviewed for rigidity, square, and plumb and approved
by PD&C and Security Systems representatives prior to proceeding with the balance of the project.
Final acceptance of all automatic fire doors is subject to an acceptable test of automatic operation.
Warranties
Doors shall be warranted by the manufacturer to be free of manufacturing defects for the life of the
installation. The manufacturers warranty shall be submitted to the Consultant for transmittal to the Owner.
Section Page 2 of 2
Section 08 50 00
Windows
Section 08 50 00 Windows
Warranty Requirements
The contract documents shall require that Emory University receive a 5-year warranty on installed
windows, unless a modification to this requirement has been reviewed and approved by Emorys Project
Manager on a case-by-case basis.
Quality Assurance
Provide windows bearing AAMA Certification labels showing compliance with AAMA testing applicable to
style and construction of window. The Architect and a representative of the window manufacturer shall
inspect all delivered window units to reject any units that have had damage to the thermal seals. All units,
which show subsequent failure of the thermal seals during the warranty period must be replaced, or reglazed (if appropriate).
Testing
The contract documents shall require the Contractor to perform tests on a minimum of 15% of the
installed windows to verify that each unit and its installation are watertight. The Architect and
Emory University shall witness these tests. Refer also to Section 01 91 19 Facility Shell
Commissioning.
Products
Products by EFCO, Graham Architectural Products, TRACO Custom Window Company, and Pella have
been reviewed and approved by Emory University. Other manufacturers may only be considered if
reviewed and approved by Emory University prior to the start of any construction activity on the project.
All glazing is to be as clear as possible unless authorized otherwise by the Emory Project Manager.
Sealants
Sealants shall be specified to be non-hardening, non-shrinking, and non-migrating materials. Hardware
shall be specified to be corrosion-resistant.
Residential Halls
Emory University prefers the use of non-opening windows except for residential hall applications where
the design team must commit to features that maximize safety and energy stewardship.
1. Limit range of window openings.
a. Consider limits on first and top floors or windows with roof access.
b. Reduce impact of outside environment on building mechanical systems.
2. Incorporate the use of vandal resistant insect screens using heavy-duty mesh of stainless steel
cloth with 0.23 & 0.28 non-painted finishes.
Window Shading Devices
The design team needs to take care to ensure compatibility between mechanically operated window
shading devices and lighting control systems if integrated.
Section Page 1 of 1
Section 08 70 00
Hardware
Section 08 70 00 Hardware
Scope of Work
The Architect shall specify for the provision and installation of all items known commercially as builders
hardware or door hardware. This shall include, but is not limited to, hinges, continuous hinges, pivots,
locks, latches, exit devices, cylinders, cores, keys, automatic or manual flush or surface bolts, door
closers, overhead door stops/holders, floor stops and holders, wall stops, thresholds, weather-stripping,
door coordinators and silencers.
Quality Assurance
The contract documents shall indicate that the installation requirements of the devices and materials in
this Section shall be coordinated with work of other related manufacturers and installers (i.e. doors,
windows, frames, security systems, etc.) to assure complete installation and operation.
The contract documents shall require that the Hardware Supplier meet the following criteria:
1.
A recognized company with documented experience, specializing in the supply of
commercial door hardware with a minimum of three (3) years in business.
2.
Be equipped with warehousing facilities within a 50-mile radius from Emory University.
3.
Employ an Architectural Hardware Consultant (AHC) to properly handle, detail and
service hardware in a satisfactory manner.
4.
The Hardware Manufacturer should be a company specializing in manufacturing door
hardware with a minimum of ten (10) years experience.
Prior to building occupancy, the Architectural Hardware Consultant shall inspect and certify that all
hardware has been furnished and installed in accordance with manufacturer's instructions and is
functioning properly. The written record of this inspection shall be delivered in writing to the Architect and
Emory University.
Submittals
The Architect shall require the submission of and review all submittals, including Product Data, Shop
Drawings, Samples, Quality Assurance Submittals (Test Data, Certifications), O & M Submittals, and
wiring schematics and locations for power sources and electric controls
Warranty Requirements
Provide a minimum three (3) year warranty for all hardware items with the exception of door closers. Door
closers shall have a ten (10) year warranty.
Products
All hardware shall be ADA compliant. ALL LOCKING INSTALLATIONS REQUIRE A KEY CYLINDER
OVERRIDE Permanent cores will be purchased and installed by the owner. The Contract documents
shall require that the Contractor provide special wrenches and tools applicable to each different or special
hardware component and provide maintenance tools and accessories supplied by each hardware
component manufacturer. The following information is the minimum acceptable criteria for each device.
Variations or modifications to these criteria must be reviewed and approved by Emory University.
1.
Hinges And Pivots: Provide number of hinges indicated but not less than three (3) hinges
for door leaf of 90" or less in height and one additional hinge for each 30" of additional
height. Provide only template-produced units. Provide Phillips flat-head or machine
screws for installation of units, except furnish Phillips flat-head wood screws for
installation of units into wood. Finish screw heads to match surface of hinges or pivots.
Approved manufacturers are Hager, Stanley, and McKinney.
a.
Hinge Pins: Tips shall be flat button and matching plug, finished to match leaves.
Hinge pins, except as noted, are to be provided as follows:
Section Page 1 of 3
Section 08 70 00
Hardware
i.
ii.
iii.
iv.
v.
vi.
b.
c.
2.
Lock Cylinders And Keying: Acceptable manufacturers for cylinders and housings, are
Schlage, and Best. Acceptable lock cores must be 7 pin small format and the only
accepted manufacturers are Medeco and Best (PKS system). Medeco Key blanks are
available through the Facilities Management Lock Shop. For more information regarding
locks and keys contact Emory Universitys Lock Shop Supervisor, (404) 727-7495.
i.
Construction of lock cylinders, housings and interchangeable cores are
to be brass, bronze, stainless steel or nickel silver. Cylinders and
housings shall match the lockset finish.
ii.
Locksets & Latchsets: Schlage L9000 series Mortise Locks (No
Equivalent Allowed)
iii.
Cylindrical TypeSchlage D Line and Best 93K are the only accepted
locksets (No Equivalent Allowed)
3.
Exit Devices: Von Duprin 98/99 Series exit devices are the approved devices. (No
Equivalent Allowed) The Von Duprin 33 series can be used on narrow stile applications
but should be approved by the Emory Security Systems Supervisor. Due to security and
maintenance concerns, use of vertical or concealed rod exit devices is discouraged. Use
of these devices should be approved by Emory University Architects, the Emory Project
Manager and the Emory Security Systems Supervisor.
4.
Closers: LCN 4040 series is the approved closer. (No Equivalent Allowed). LCN 4600 &
4800 series are to be used for power assisted applications (No Equivalent Allowed). Thru
bolts and sex nuts are required for closers installed on wood doors. Because of
maintenance concerns, concealed overhead and concealed floor closers are discouraged
and should be approved in writing by the Emory Project Manager and Emory University
Security Systems Supervisor.
5.
Section Page 2 of 3
Section 08 70 00
Hardware
cylinder but no outside trim and door is reverse bevel, provide cylinder pull. Rockwood 90
or equivalent will be acceptable.
6.
7.
8.
Electric Strikes: The only acceptable manufacturers of electric strikes are Von Duprin
and HES unless otherwise approved in writing by the Emory University Security Systems
Supervisor.
Execution
The contract documents shall require the installation of each hardware item in compliance with the
manufacturer's instructions and recommendations. Wherever cutting and fitting is required to install
hardware onto or into surfaces that are later to be painted of finished in another way, each item shall be
installed completely and then removed and stored in a secure place during the finish application. After
completion of the finishes, each item shall be reinstalled. Do not install surface mounted items until
finishes have been completed on the substrate. All hardware shall specify to be installed to comply with
ANSI A117.1 for positioning requirements for the handicapped.
1.
2.
Protection & Cleaning -- After installation, the contract documents shall require the
Contractor to clean all metal surfaces on both the interior and exterior, of all mortar, paint
and other contaminants. After cleaning, the installed work shall be protected against
damage.
Final Adjustment -- Whenever hardware is installed more than one month prior to
occupancy or acceptance, the contract documents shall require the AHC / the Hardware
Supplier to return during the week prior to acceptance or occupancy and make a final
inspection and adjustment of all hardware items.
Section Page 3 of 3
Section 08 80 00
Page 1 of 3
Section 08 80 00
Submittals
Submit manufacturer's product data showing thermal performance characteristics of all exterior glass and
glazing systems.
Submit two samples of each type of glass specified, 12" x 12" in size, illustrating glass, unit, and
coloration. Indicate range of variation to be expected for color and "waviness" in final position.
Submit product data for LEED credit EQ 4.1: for glazing sealants inside of the weatherproofing system,
including a printed statement of VOC content.
Submit product certificates from the manufacturer for glass and glazing products.
Submit the preconstruction adhesion and compatibility test report.
Submit a sample of each warranty type.
Products
Acceptable manufacturers:
1. AGC Glass Company
2. Guardian Industries.
3. LOF Glass, Inc.
4. PPG Industries, Inc.
5. Viracon
Acceptable Fabricators:
1. J.E. Berkowitz
2. Oldcastle Building Envelope
3. Trulite Glass & Aluminum Solutions
4. Viracon
Minimum Performance Characteristics for Exterior Glass:
U-value
0.27
SHGC
0.27
VLT
64%
LSG
2.37
General Notes:
1. The design shall not include individual pieces of glass that exceed 96 in width or 142 in height.
2. Tempered glass shall only be used where required by code. Heat strengthened glass should be
used elsewhere.
Clear Float Glass:
Type I, Quality q3, Class 1 clear, 1/4" thick except as otherwise required to comply with
applicable codes and regulating authorities.
Page 2 of 3
Section 08 80 00
Page 3 of 3
Section 09 20 00
Plaster and Gypsum Board
Section Page 1 of 1
Section 09 30 00
Tile
Section 09 30 00 - Tile
References
The design, specifications, materials, and installation method should adhere to all applicable ANSI and
ASTM codes and standards, in addition to the Handbook for Ceramic Tile Installation, Tile Council of
America (TCA).
Quality Assurance
1. Submittals: Product Data, Shop Drawings, Samples, Tiles, Trim and accessories, Stone
thresholds, Edge strips, Quality Assurance
2. Submittals: Test Reports, Certifications, Master Grade Certificates, and Qualifications.
3. Materials: Furnish each type, finish and color of tile and accessory from a single supplier.
4. Installer: Company to have not less than 5 installations of tile work similar in size and complexity.
5. Tile Mock-up: Provide a detailed Mock-up for each tile type that will be representative of the
quality of the full installation.
6. Project Conditions: Provide temperatures during installation and after completion as required by
manufacturer's instructions.
Materials
1. Standards: For all ceramic tile, meet or exceed the requirements of the ANSI A137.1 standard.
Also adhere to ANSI standards for all tile installation materials. All tile trim and accessories
should match the color and finish of adjoining flat tile. Materials should be certified as compliant
with the current FloorScore standard.
2. Attic Stock: Provide 2% extra of each type of tile material to the owner at the end of construction.
Provide Owner with manufacturer's stock and color numbers for all materials.
3. Adhesives Tile setting adhesives and grout must meet current South Coast Rule # 1168 by the
South Coast Air Quality Management District (see Sustainability requirements below).
Execution
1. Tile Installation Standard: Follow the requirements found in ANSI A108 and the TCA "Handbook
for Ceramic Tile Installation" for setting and grouting materials.
2. Field Inspection: The tile contractor is to verify that the substrate is level and ready for tile
application, and that the tile has been blended to achieve uniform color range from tile package to
tile package. The contractor is also responsible for protecting installed tile until the building is
turned over to the owner.
Sustainability
All Emory projects, including major renovations, shall meet and exceed the requirements of Materials and
Resources Credits 4 Recycled Content and 5 Regional Materials and Indoor Environmental Quality
Credits 4.1 and 4.3 Low-Emitting Materials-Adhesives/Sealants and Flooring Systems under the current
LEED rating system.
Preferences
1. Use colored grouts in lieu of white grout unless approved in writing by the Emory Project
Manager.
2. Use color impregnated grout sealer unless approved in writing by the Emory Project Manager.
3. Tile floors with floor drains are to be sloped towards drain.
4. The use of tile in residence hall bathrooms requires epoxy mortar and grouts.
Section Page 1 of 1
Section 09 51 00
Acoustical Lay-In Ceilings
Section Page 1 of 1
Section 09 65 00
Resilient Flooring
Section Page 1 of 2
Section 09 65 00
Resilient Flooring
Execution
1. Verify that substrates are level and meet the flooring manufacturer's requirements. Perform
manufacturers recommended moisture tests on all concrete substrates.
2. Waste - All field waste is to be removed from the project site by the installer and recycled or
disposed of.
Sustainability
All Emory projects, including major renovations, shall meet and exceed the requirements of Materials and
Resources Credits 4 Recycled Content and 5 Regional Materials and Indoor Environmental Quality
Credits 4.1, 4.2 and 4.3 Low-Emitting Materials-Adhesives/Sealants, Paints/Coatings and Flooring
Systems under the current LEED rating system.
Preferences
1. Epoxy flooring preferred in laboratory spaces; Emory Project Manager can authorize use of
Chemical resistant VCT
2. Linoleum, VCT or similar product is the preferred floor finish for hallways.
3. Hard surfaces like natural stone or terrazzo is the preferred floor finish for building entrances,
vestibules and major public lobbies.
Section Page 2 of 2
Section 09 68 00
Carpet
Section 09 68 00 Carpet
References
All materials, installation procedures and job site conditions should conform to the applicable codes and
standards contained in the AATCC, ASTM, NFPA and UL guidelines.
Submittals
Contractor to submit to owner and architect product data, manufacturer's stock numbers, samples,
manufacturer's qualifications, installer's qualifications, manufacturer's certification, and maintenance
instructions.
Special Warranty Requirements
The manufacturer, installer and contractor must submit a written warranty to correct failures that occur
within 2 years.
Products
1. Manufacturers -- Obtain all materials of a type from a single manufacturer. Carpet and carpet
pad (as applicable) should meet the testing and product requirements of the Carpet and Rug
Institute Green Label Plus program.
2. Accessories -- Use the carpet manufacturer's recommended accessories. All specified edge
guards shall be rubber. The specified carpet separator shall be noncombustible.
3. Attic Stock-- Provide 5% extra of each type of carpet or carpet tile and 5% of specialty
manufactured carpet to Emory University at the completion of the project. Emory does not
promote the installation of customer carpet.
Execution
Follow carpet manufacturer's recommendations to prepare substrates, and install all carpet and carpet tile
according to the manufacturer's instructions. Place seams in inconspicuous areas.
Installation
1. Run carpet into recessed areas.
2. Cutting carpet.
3. Glue-down carpet and carpet tile with low VOC adhesives, as determined by South Coast Rule #
1168, by the South Coast Air Quality Management district (see Sustainability requirements
below).
4. Special Field Verification/Preparation Requirements
5. Maintain temperature and relative humidity.
Waste
The contractor is responsible for removing all waste from the project site regularly during installation, and
at the completion of the job. The contractor is also responsible for recycling of the waste in an appropriate
fashion.
Sustainability
All Emory projects, including major renovations, shall meet and exceed the requirements of Materials and
Resources Credits 4 Recycled Content and 5 Regional Materials and Indoor Environmental Quality
Credits 4.1 and 4.3 Low-Emitting Materials-Adhesives/Sealants and Flooring Systems under the current
LEED rating system. In addition to recycling carpet waste, Emory prefers the use of carpets with high
recycled contents, that are modular, and that are manufactured within a 500 mile radius of campus and
that is manufactured, transported, maintained and ultimately disposed of in manners reflective of the
Universitys sustainability vision and initiatives.
Preferences
It is preferred that all offices and classrooms have carpet as the floor finish.
Revision Date August, 2011
Section Page 1 of 1
Section 09 90 00
Paints and Coatings
Page 1 of 6
Section 09 90 00
Paints and Coatings
Submittals
Submit copies of manufacturer's product data, specifications and installation instructions for all paint
materials required, including certifications and laboratory reports as required to show compliance with the
specifications. Provide color & texture samples for each coating system, color and texture and applied to
representative substrate samples. Prepare samples to show bare, prepared surfaces and each
successive coat.
Submit samples with opaque finishes that match the architect's color chips on 5" x 7" primed cardboard,
with color, texture and sheen duplicated to simulate actual conditions. Re-submit sample boards as
necessary for selection by Architect.
Delivery, Storage and Handling
Deliver products to site in seated and labeled containers; inspect to verify acceptance. Container must be
labeled with the manufacturer's name, type of paint, brand name, brand code, coverage, surface
preparation, drying time, clean up, color designation, and instructions for mixing and reducing.
Store paint materials at a minimum ambient temperature of 45 degrees Fahrenheit and a maximum of 90
degrees Fahrenheit in a well-ventilated area, unless required otherwise by manufacturer's instructions.
Place paint or solvent soaked rags, waste, or other materials, which might constitute a fire hazard in a
sealed, water-filled metal container and remove from premises at the close of each day's work. Take
every precaution to avoid damage by fire.
Products
Owner Preferences -- Except as otherwise specified, Duron / Sherwin Williams is the Acceptable
Manufacturer for the following products: Paint, Varnish & Urethane, Stain Fillers & Primers, Chlorinated
Rubber & Field Catalyst Coatings
1 For interior Paint Finishes, use S.W. ProMar 200 0 VOC Flat for ceilings, S.W. ProMar 200
0 VOC Eggshell or Semi-Gloss for walls, S.W. Pro Industrial, Pre-Catalyzed Waterbased
Epoxy Semi-Gloss for doors, jambs and trim. The contractor shall provide all paint products.
2 Other manufacturers colors can be specified, but must be cross-matched to a Duron or
Sherwin Williams product. All Emory projects shall attempt to meet and / or exceed the
requirements of Indoor Environmental Quality Credits 4.1 and 4.2 Low-Emitting MaterialsAdhesives/Sealants and Paints/Coatings under the current LEEDv3.0 NC rating system.
Generally, primers and sealers must be low or no VOC, such as ProMar 200 0 VOC Primer
unless approved otherwise by the Emory Project Manager. This is in effort to reduce the
quantity of indoor air contaminants that are odorous, irritating and/or harmful to the comfort
and well-being of installers and occupants.
3 When mechanical equipment is located in an area with an elevated slab and occupied space
below it such as a mechanical penthouse, Sherwin Williams Armorseal Tread-Plex or Owner
approved equal should be applied to the concrete.
Questions regarding product selection should be directed to the Project Manager in collaboration with
Campus Services Interior Design department, paint shop and Sherwin Williams representative.
Materials
1. All items of painting materials shall be proprietary products of specified manufacturers. Such
material shall be used without adulterations and only with such thinning as called for in the
manufacturer's directions. All colors scheduled shall be factory-mixed, and exactly match the
approved samples.
2. Materials selected for a coating system for each type of surface shall be the products of a
single manufacturer, except where otherwise required by the contract documents. Where
shop-primed materials are to be finish-painted or prime-coat materials are by a different
Page 2 of 6
Section 09 90 00
Paints and Coatings
manufacturer than the finish-coat materials, confirm compatibility of the primers with the
manufacturer of the finish-coat paints.
3. Use only primers and undercoats that are suitable for each surface to be covered and that
are compatible with the finish-coat required.
Attic Stock
1. Provide one gallon of each specialty color and texture to the owner at the completion of each
phase.
2. Label each container with color, texture, room locations and product description in addition to
the manufacturer's label.
3. Provide owner with an 8-1/2 X 11 card, painted on one side, paint color formula on the
other, and availability information on any "custom" product for each paint color and texture
used in the project.
Execution
Inspection -- Examine surfaces scheduled to receive paint and finishes for conditions that will adversely
affect execution, permanence or quality of work and which cannot be put into acceptable condition
through preparatory work as included in Paragraph Preparation of Surface.
1. Do not proceed with surface preparation or coating application until conditions are suitable.
Report any conditions that may potentially affect proper application.
2. Measure the moisture content of surfaces using an electronic moisture meter. Advise the
project manager if the moisture content is not acceptable. Do not apply finishes unless the
moisture content of surface is acceptable to receive the specified paint coating material.
3. Beginning of application of any paint or primer coating means acceptance of existing surfaces
or substrate.
4. The Emory Paint Shop Supervisor shall review and approve the prime coat prior to applying
the finish coat. The contractor shall be responsible to coordinate this requirement with the
Emory Project Manager.
Site Preparation -- Remove or protect hardware, plates, trim for mechanical work, lighting fixtures and
similar items placed prior to painting. Disconnect equipment adjacent to walls, where necessary, and
move to permit painting of wall surfaces. Following completion of painting, replace and reconnect.
1. Protect the work of all other trades against damage or injury by use of suitable covering
during the progress of the painting and finishing work.
2. Repair damage to other surfaces caused by work of this section.
3. Remove empty paint containers from the work site.
4. Post "No Smoking" and "Wet Paint" signs are required or directed.
5. Provide sand, extinguishers and other protective equipment in the event of a fire created by
any paint-related rags or materials.
6. Provide continuous ventilation and heated facilities to maintain surface and ambient
temperatures above 45(F. for 24 hours before, during, and 24 hours after application of
finishes, unless required otherwise by manufacturer's instructions.
7. Minimum Application Temperature for Latex Paints: 50(F. (10(C.) for interiors; 50(F. (10(C.)
for exteriors, unless required otherwise by manufacturer's instructions.
8. Paint shall not be applied in rain, snow, fog or mist, or when the relative humidity exceeds 85
percent. Paints, other than water thinned coatings, shall be applied only to surfaces that are
completely free of surface moisture as determined by sight, touch and moisture meter, as
specified. In no case shall paint be applied to a surface upon which there is visible ice or
frost.
9. Minimum Application Temperature for Varnish Finishes: For best results, apply when the
surface and air temperature is between 65(F. and
10. 90(F. Do not apply below 50(F.
11. Where the paint manufacturer's specifications or instructions differ from the above
specifications, the more stringent requirements shall apply.
Revision Date November, 2014
Page 3 of 6
Section 09 90 00
Paints and Coatings
12. Adequate lighting must be available prior to the application of any paint coating to
approximate 80-foot candles measure mid-height at substrate surface.
Surface Preparation -- Clean all surfaces to be painted as required to remove dust, dirt or other surface
contamination, and then properly prepare surfaces to receive paint or natural finish.
1. Remove mildew by scrubbing the surface with a solution of 4 ounces of pure tri-sodium
phosphate, 3 quarts of water and 1 quart of bleach. Allow this solution to remain on the
surface for 10 to 15 minutes, then rinse with clean water and allow surface to dry. Wear
protective glasses and waterproof gloves when using this solution. Quickly wash off mixture
that touches skin.
2. Asphalt, Creosote, or Bituminous Surfaces Scheduled for Paint Finish: Remove foreign
particles to permit adhesion of finishing materials. Apply a latex-based, compatible sealer or
primer.
3. Insulated Coverings: Remove dirt, grease and oil from canvas and cotton using high-pressure
air and solvent cleaner as required to obtain a sealing coat.
4. Concrete Floors: Remove contamination, acid etches, and rinse floors with clear water. Verify
required acid-alkali balance is achieved. Allow to dry. Some floors may require mechanical
abrasion, for example, "shot blasting". Concrete floor surfaces are properly prepared for
application of most coatings when the surface profile has a "grainy, medium sandpaper
texture," the concrete has a neutral acid alkali balance, and the surface is dry.
5. Copper Surfaces Scheduled for a Paint Finish: Remove contamination by steam, water, high
pressure or solvent washing.
6. Galvanized Surfaces: Remove surface contamination and then wash with clean, lint-free cloth
saturated with mineral spirits or lacquer thinner. Wipe dry with clean, lint-free cloths. Apply
coating of applicable primer.
7. Shop-Primed Steel Surfaces: Sand and scrape to remove loose primer and rust. Feather
edges to make touch-up patches inconspicuous. Clean surfaces with solvent. Prime bare
steel surfaces.
8. Interior Wood Items Scheduled to Receive Finish: Wipe off dust and grit prior to priming. Seal
knots, pitch streaks, and sappy sections with sealer. Fill nail holes and cracks after primer
has dried; sand between coats.
9. Uncoated Steel and Iron Surfaces: Remove grease, scale, dirt, and rust. Where heavy
coatings of scale are evident, remove by wire brushing or sandblasting; clean by washing
with solvent. Apply a treatment of phosphoric acid solution; ensuring weld joints, bolts and
nuts are similarly cleaned. Spot prime weld repairs with a rust inhibitive metal primer.
10. Concrete and Concrete Masonry Units: Thoroughly clean concrete surfaces of all loose
particles, sand, efflorescence, laitance, form oil, curing compounds or other contaminants by
appropriate methods and be sure surface is dry before any paint is applied. Methods of
surface preparation and cleaning shall be determined by the contractor as required in each
case to ensure satisfactory paint application and performance.
11. Gypsum Drywall: Repair all surface defects in gypsum drywall with drywall joint finishing
compound or spackling compound filled out flush and sanded smooth. Clean all surfaces and
taped joints of dust, dirt and other contaminants and be sure they are thoroughly dry before
applying vinyl wall primer/sealer (drywall primer) to insure good adhesion of finish coats.
12. Gypsum Plaster: Cut out cracks, holes, indentations and other imperfections in plaster
surfaces to the extent necessary to provide a good bonding surface. Fill with patching plaster
or spackling compound, and sand smooth and flush with adjacent surfaces with fine
sandpaper.
13. Before applying paint, clean plaster surfaces of all dirt, dust, grit and other contaminants.
New plaster or new plaster repairs must be allowed to age 30 days. Verify that surfaces are
dry and that the moisture content does not exceed 15 percent when measured by a moisture
meter.
Page 4 of 6
Section 09 90 00
Paints and Coatings
14. Exterior Wood Scheduled to Receive Paint Finish: Remove dust, grit and foreign matter. Seal
knots, pitch streaks and sappy sections. Fill nail holes with exterior caulking compound after
prime coat has been applied. Sand any mill glaze areas to wood that can be painted.
15. Glue-Laminated Beams: Prior to finishing, wash surfaces with solvent, remove grease and
dirt.
16. Wood and Metal Doors Scheduled for Painting: Seal top and bottom edges with primer.
17. Glazing and Caulking: Apply primer on all work before glazing or caulking. Paint must overlap
glass 1/16 inch on all coats.
18. Wallcoverings: Prime all surfaces to receive wallcoverings with an adhesive vinyl primer.
Application - Apply products in accordance with manufacturer's instructions.
1 Apply paint, enamel, stains and varnishes with suitable brushes, rollers or spray equipment
that has been kept clean, free from contamination and suitable for finish required.
2 Rate of application of coating shall not exceed that as recommended by the paint
manufacturers data page.
3 Comply with required drying time between coats as directed by manufacturers data page.
4 Sand between each coat to remove defects visible from 5 feet. Finish coats shall be smooth,
free from brush marks, streaks, laps, sags, skips, holidays, etc.
5 Do not apply additional coats until completed coat has been inspected and approved by the
Architect. Only inspected coats of paints will be considered in determining number of coats
applied.
6 Before applying succeeding coats, primers and undercoats shall be completely integral and
shall perform the function for which they are specified. Properly prepare and touch up all
scratches, abrasions or other disfigurements and remove any foreign matter before
proceeding with the following coat. All spot priming or spot coating shall be feather-edged into
adjacent coatings to produce a smooth and level surface.
7 Do not apply final coats until after other work with operations that would be detrimental to
finish painting have been finished in the area to be painted and the areas have been released
for painting.
8 Shellac and/or spot-prime with industry accepted "stain killers" any marks that may bleed
through surface finishes. Ink markings of PVC piping can be removed with denatured alcohol.
9 Make edges of paint adjoining other material or colors clean and sharp with no overlapping.
10 Change colors at doorstop corner where colors differ between adjoining spaces or rooms and
where door frames match wall colors.
11 Refinish whole wall where portion of finish has been damaged or is not acceptable.
12 Back prime all interior wood trim.
13 Stained and natural finishes shall be adjusted to obtain identical appearance.
Cleaning -- Promptly remove paint where spilled, splashed, or spattered.
1 During progress of work, maintain premises free of unnecessary accumulation of tools,
equipment, surplus materials and debris.
2 Collect cotton waste, cloths, and material which may constitute a fire hazard, and place in
closed water-filled metal containers and remove daily from site.
Finishing Mechanical and Electrical Equipment
1 Refer to ANSI Code Z53.1 and A13.1 for color-coding and identification banding of
equipment, ductwork, piping and conduit.
2 Access panels, electrical panels, air diffusing outlets, supply and exhaust grilles, louvers,
exposed conduit, primed outlet covers, primed wall and ceiling plates and other items in
painted areas shall be painted to match the areas in which they occur unless specified
otherwise in the schedules.
3 Paint the backsides of access panels, removable or hinged covers.
4 Do not paint nameplates on equipment. Replace identification markings on mechanical or
electrical equipment when painted accidentally.
Page 5 of 6
6
7
Section 09 90 00
Paints and Coatings
Paint interior surfaces of air ducts, and convector and baseboard heating cabinets that are
visible through grilles and louvers with one coat of flat black paint, to limit of sight line. Paint
dampers exposed behind louvers, grilles, and convector and baseboard cabinets to match
face panels.
Paint the plywood backboards for electrical and telephone equipment before installing
equipment.
Replace electrical plates, hardware, light fixture trim, and fittings removed prior to finishing. In
general all unfinished and ungalvanized ferrous metals shall be painted according to the steel
and iron specifications. This includes all exposed metals which includes all exterior metals
and metals exposed to view in interior rooms such as mechanical rooms, electrical rooms, IT
rooms, custodial rooms and storage rooms.
Page 6 of 6
Section 09 95 00
Wall Coverings
Prerequisite:
Wall coverings shall not be used unless approved in writing by the Emory Project
Manager.
References
AA DAF-45
ASTM E 84-96a
FS CCC-W-408A
FS CCC-W-408C
Building Materials Directory, Underwriters Laboratories Inc. (UL)
Section Page 1 of 1
Section 10 10 00
Graphics and Signage
1.2
B.
C.
Interior Signs: All interior signage shall be selected from one of the several established
Interior Sign Standards maintained by PDC graphic design staff. The interior and graphic
design staff of PDC will assist the customer with the available choices and determine the sign
types needed for the project. A budgetary allowance for signage should be determined at the
projects schematic design stage so that adequate funds are set aside for static signage. If an
allowance is built into the project for electronic directories, PDC will assist with the planning
for these products during the design stages of the project.
Submittals: The following outlines submittal requirements unique to this section of the work,
especially shop drawing content and samples.
A.
Shop drawings:
1. Unique sign layouts or hardware not illustrated in the Sign Standards require a submittal.
The submittal shall include material samples, layout drawings, or other explanatory
material as appropriate to convey the contractors intent.
2. For finishes, indicate manufacturer, brand name, quality and type paint or finish for each
surface.
3. Indicate connection and suspension details; computations shall be prepared and
drawings stamped by a Registered Professional Engineer licensed in Georgia covering
all members, connections (welds, bolts, etc.) and footings, indicating such meets the
Design Specifications for Sign Structures stress requirements and dead load deflection
tolerances. For exterior signs, wind load designs shall meet the requirements of the
American Society of Civil Engineers standard #ASCE 7-98 for computing for sign
structure wind loads and any local standards whichever is greater.
4. Submit patterns for letter sets or inscriptions on buildings. Submit full-size white paper
patterns for each different location or typical condition of individual surface or wallmounted letters. These shall be reviewed on site and returned and may be submitted
separately from the main shop drawing submittal described above. Also indicate
mounting details for mounting the plaque to wall surface or substrate.
B.
Prototypes are not required for signs found within the Interior Sign Standards, Regulatory
Sign Standards or the Wayfinding Master Plan. Anything unusual may necessitate a
prototype but this requirement will be planned into the signage order if its needed.
C.
Maintenance data: Submit maintenance recommendations and instructions for each material
used as part of contract close-out. Include recommendations for cleaning procedures,
intervals and touch-ups.
Section Page 1 of 6
D.
1.3
A.
B.
1.4
1.5
A.
Section 10 10 00
Graphics and Signage
Scheduling: Submit the final schedule for construction of work and installation within ten (10)
days of sample approvals. Indicate dates of completion for prototypical units for approval,
dates of partial deliveries and total completion. Dates given shall be consistent with the time
requirements submitted with the bid.
Quality Criteria
Acceptable fabricators shall meet the following criteria:
1. Sign contractors, suppliers, and/or subcontractors shall have been regularly engaged in
the manufacture, fabrication and installation of sign systems of comparable scope and
quality for a minimum of five (5) years.
2. Sign contractors with an established project and purchasing history with Emory University
are to be used for signs within the Standards.
Industry standards: Where referenced in this section, the work shall comply with
requirements of the following standard specifications, unless otherwise specified.
1.
Aluminum Association (AA): "Standards for Aluminum Mill Products," "Designation
System for Aluminum Finishes," and "Standard for Anodically Coated Aluminum Alloy
for Architectural Applications."
2.
American National Standards Institute (ANSI).
3.
American Society for Testing Materials (ASTM)
4.
American Welding Society (AWS) "Recommended Practice for Resistance Welding,"
and "Structural Welding Code."
5.
Sections pertaining to signs in the Americans with Disabilities Act Design Guidelines
(ADADG) currently adopted edition, the Georgia Accessibility Code and those
included in the International Building Code.
6.
The Manual on Uniform Traffic Control Devices (MUTCD) published 2003 by the U.S.
Dept. of Transportation, Federal Highway Administration.
Job Conditions
Field measurements: Take field measurements to determine exact sizes before fabrication.
Indicate exact dimensions on shop drawings. Verify locations and conditions considered
questionable, unclear, or not drawn to scale.
B.
Environmental requirements:
1.
Comply with manufacturer's recommendations regarding environmental conditions
under which materials may be applied.
2.
Apply no adhesive or coating materials in spaces where dust is being generated.
C.
Coordination: Coordinate work with other trades to ensure that surfaces to receive signs are
properly completed, inspected, and approved prior to commencement of work.
Commencement of work in any space shall constitute acceptance by the Contractor of
surfaces to receive signs.
A.
Warranties
Warrant the joints in plastic and metal construction for a period of five (5) years from Date of
Substantial Completion against failure or de-lamination.
B.
Warrant all interior room signs for a period of five (5) years from Date of Substantial
Completion against discoloration and de-lamination of any portion of the sign.
C.
Warrant vinyl film for a period of eight (8) years from Date of Substantial Completion against
de-lamination from the substrate.
Section Page 2 of 6
1.6
Section 10 10 00
Graphics and Signage
D.
Warrant exterior paint finishes for a period of (2) two years from fading, discoloration or
peeling.
E.
Paints, inks and finishes shall be guaranteed not to cause discoloration, deterioration, or delamination of any materials used in fabrication. Warrant paint finishes on metal and plastic
materials for a period of three (3) years from the date of substantial completion.
F.
Warranty Provisions: During the warranty period, restore defective work to the standard of
the contract documents without cost to the Owner, including all labor, materials, refinishing
and all costs incidental to the work.
G.
Warrant all electrical components and signs for a period of at least one year, parts and labor,
or greater if stipulated elsewhere in the specification section for electrical work.
A.
Part 2 Products
2.1
Metal Regulatory Signs and Posts
A.
Sign panels: all panels for regulatory (traffic, vehicle and pedestrian) shall be aluminum in
0.090 thickness with premium grade reflective vinyl film graphics in accordance with
MUTCD. Follow Emorys preferred layouts in the Sign Standards document. The rear face of
all sign panels shall be painted with a durable black paint finish.
1. Standard rectangular signs (size 12 x 18 are used for parking restrictions, parking
designations, speed limit, fire lane. A set of standard layouts is depicted in the Regulatory
Sign Standards.
2. Other regulatory sign shapes such as Stop, Yield, and pedestrian crosswalk are depicted
in the Sign Standards and shall be followed.
3. Exceptional conditions will be considered and should be submitted for clarification by
PDC graphic design staff.
2.2
B.
Sign posts: The required post is the NEX octagonal post from S-Square Tube Products of
Commerce City, Colorado along with these accessory parts:
1. posts shall be 12 gauge, 2 diameter
2. powder coated black
3. use S-square sign panel brackets (flag or face mount as appropriate) painted black
4. Galvanized post anchor and wedge from S-Square; post anchor is buried plumb and set
in a concrete footing that extends a minimum of 18 below grade. The post anchor shall
not protrude above grade.
5. Black plastic post cap from S-Square Tube Products.
C.
Back-of-house conditions: For loading docks and staff-only areas, a stamped steel post may
be used, but other requirements for panels are not waived.
D.
Coordination: Most standard layouts are addressed in the Standards document, however,
special parking conditions or regulatory conditions shall be clarified with Parking Services and
or PDC staff.
Building Identification and signs
Section Page 3 of 6
2.3
Section 10 10 00
Graphics and Signage
A.
Campus exterior signs: PDC graphic design staff administers the Wayfinding Master Plan
and proposed sign locations for a building site shall be coordinated with PDC during the early
design stages of a project. Final on-site locations will be coordinated in the field by the Emory
Project Manager and PDC graphic design staff. Various sizes are used depending on
conditions and include identification of service/loading docks and secondary entrances.
B.
The University does not list individual offices or programs on building identification signs.
Sign text includes the Emory wordmark, the name of the building, and the street address
number. All building names used must be approved by the Naming and Inscriptions
Committee of the Board of Trustees.
C.
Inscriptions: The University inscribes each new academic building with the name of the
building inscribed in the exterior stonework in a prominent location. The University also
requires a cornerstone inscription of the year of completion of a building. Architectural
consultants may suggest locations for the inscriptions in the design phases of the project.
The letter style for inscriptions is Sabon Large and Small Capitals. PDC will provide
assistance and review of the layout and a paper template is required (full size) before the
inscription is done. This template will be reviewed by the University Architect and PDC.
D.
Dimensional letters as inscription: If a new building does not feature a marble faade where it
can be inscribed, individual letterforms may be used. The size and proportion of these letters
must be approved by the University Architect from a recommended design by PDC graphic
design staff. The style of letters to be used is Sabon Large and Small Capitals and materials
considered are: cast aluminum, fabricated aluminum, or cast bronze.
E.
Wall mounted identification signs: Renovated service buildings and ancillary structures may
be identified with wall mounted sign panels and the design of these is provided under the
auspices of the Wayfinding Master Plan administered by PDC graphic design staff. Typically,
primary academic structures on campus receive an inscription and a free-standing building
sign depending on location.
F.
Map graphics used on wayfinding directories are provided by PDC graphic design staff.
These sign types are under the auspices of the Wayfinding Master Plan. North and South
oriented maps are to be used. Do not orient signs with an East /West placement. All maps
are oriented on signs with straight ahead direction as up on the map.
A.
B.
Section Page 4 of 6
Section 10 10 00
Graphics and Signage
3.2
B.
Commencing of work in any space constitutes acceptance by the Contractor that surfaces to
receive sign units are in a satisfactory condition to permit an acceptable installation. If the
Contractor's inspection of such surfaces discloses unsatisfactory conditions, contractor will
notify PDC Project Manager in writing and await further instruction; otherwise, no claims will
be considered for unsatisfactory work due to real or alleged faulty surfaces. Precautions shall
be taken by the construction manager to protect installed work from damage.
C.
Confirm all utility locations with local utilities protection council or other such coordinating
body and as required by local ordinances and for safety.
A.
B.
C.
Clean exposed metal work with cleanser recommended by manufacturer of materials and
rinse with clean water. Do not use harsh chemicals or abrasive. Surfaces with stains that
cannot be removed by cleaning shall be refined or replaced to the satisfaction of Emory at no
additional cost.
D.
Signs shall be free of tape, packing paper, dirt, smudges, and other foreign material and
spatters, drippings, smears, and / or spray shall be completely removed.
E.
Touch up work after installation shall be performed by the sign manufacturer and approved
by Owner.
Section Page 5 of 6
F.
3.3
A.
Section 10 10 00
Graphics and Signage
Work in progress shall be protected at all times from staining, scratching, chipping or other
damage until acceptance by the Owner.
Fabrication and Construction:
Sign units shall be fabricated with precision and high standards of quality craftsmanship. All
seams, where necessary, shall be hairline. All removable panels shall operate smoothly and
fit accurately. All edges shall be sanded and corners slightly rounded. Polyester (catalyst
activated) filler, where used, shall be sanded smoothly and painted to achieve an
undetectable smooth effect. Fasteners shall be hidden, or if visible, shall be countersunk and
painted to match the surrounding finish. Flawed or faulty workmanship is subject to rejection
by the Owner and shall be replaced with an acceptable unit. Allow for thermal movement
resulting from changes in ambient temperature in the design, fabrication, and installation of
installed metal assemblies to prevent buckling, opening up of joints, and overstressing of
welds and fasteners. Base design calculations on actual surface temperatures of metals due
to both solar heat gain and night time heat loss.
B.
Form metal fabrications from materials of size, thickness, and shapes indicated but not less
than that needed to comply with performance requirements indicated. Work to dimensions
indicated or accepted on shop drawings, using proven details of fabrication and support. Use
type of materials indicated or specified for various components of each metal fabrication.
C.
Ease exposed edges to a radius of approximately 1/32 inch, unless otherwise indicated.
Form bent-metal corners to smallest radius possible without causing grain separation or
otherwise impairing work. Remove sharp or rough areas on exposed traffic surfaces.
Fabricate joints that will be exposed to weather in a manner to exclude water, or provide
weep holes where water may accumulate.
D.
Form exposed connections with hairline joints, flush and smooth, using concealed fasteners
wherever possible. Use exposed fasteners of type indicated or, if not indicated, Phillips flathead (countersunk) screws or bolts. Locate joints where least conspicuous.
E.
Provide the necessary blocking for signs in the design documents for the building and
coordinate with PDC Project Manager for these provisions or a waiver thereof.
Section Page 6 of 6
Section 10 21 13
Toilet Compartments
Section Page 1 of 1
Section 10 28 13
Toilet Accessories
Section Page 1 of 1
Section 10 44 00
Fire Protection Specialties
Section Page 1 of 2
Section 10 44 00
Fire Protection Specialties
5. In new research and medical buildings, provide a spare extinguisher station with minimum of
two mounted portable extinguishers to be kept as spares in the building mechanics office
space.
6. New computer server rooms shall have at least one clean agent portable fire extinguisher.
Carbon dioxide extinguishers are prohibited.
7. Nominal Class D 30 lb extinguishers and other extinguishers which have a gross weight of
more than forty pounds needed for special locations shall be provided with wheeled cart to
facilitate transport.
Section Page 2 of 2
Section 11 24 29
Facility Fall Protection
Section Page 1 of 1
Section 11 53 13
Fume Hoods
Section Page 1 of 1
Section 11 53 53
Biological Safety Cabinets
Section Page 1 of 1
Section 14 20 00
Elevators
Section 14 20 00 Elevators
Use non-combustible construction for elevator hoistways and machine rooms. Provide
minimum two-hour fire rating for hoistway, elevator control rooms, and/or elevator
machine room.
1.1.3
1.1.4
Access to machine room (or control room) shall be short and direct from the hoistway
except as pre-approved by the Emory Project Manager. Per the elevator safety code,
access shall not be through another secured area, which will prevent ready access to
emergency and elevator personnel. Door to machinery spaces shall be "B Label," fire
rated, self-closing and self-locking, able to be opened from inside with no key, and keyed
with BestLock. The door should swing out of the machine room, except as approved by
Owner where all safe working conditions are maintained. See machine room location and
access below.
1.1.5
No sprinklers shall be located over elevator shaft or elevator machine room or control
room complying with 1.1.2 above. In a fully sprinkled building, a sprinkler shall be
installed in the pit. If a separate valve is installed for the pit sprinkler the sprinkler in the
pit shall be monitored with flow and tamper switches located outside the hoistway, and
water flow in the pit shall initiate elevator recall to the upper egress landing. Storage shall
be absolutely forbidden in elevator machine spaces, except in a fire-safe cabinet for
supplies related to that elevator (which does not infringe on required working clearances).
1.1.6
New elevators shall have lobbies. Smoke detectors, which will initiate elevator recall, will
be installed in each machine room, shaft, and elevator lobby.
1.1.7
Section Page 1 of 14
1.2
Section 14 20 00
Elevators
1.1.8
Dedicated emergency phone line and ADA compliant phone is required for each elevator
car. With few exceptions, Emory University elevator emergency phones ring Emory
Police directly at all times. Provide phone with capability to automatically dial minimum
two numbers and with a telephone number for calls into the elevator phone. Phone shall
have the capability for responder (Emory Police) and others authorized to call if need
arises. Provide elevator phone extension in machine room for communication between
machine room and elevator car.
1.1.9
An elevator shall not be used as the main security gateway between or into separately
secured areas. If elevator secured access is used as a restrictive gateway, a substitute
egress route must be available in a building. Whenever a secured access system
includes a card reader inside the car to affect elevator operation by restricting access to
floors, a cut out switch for trouble-shooting shall be installed in the elevator machine
room near or inside the elevator controller. Secured access arrangements (such as a
lobby key switch or lobby card reader) that affect only the hall buttons shall not have
wiring or equipment inside the hoistway or machine room.
References
Include but are not limited to the following. (Use edition to be enforced by Authority Having
Jurisdiction)
1.2.1 Designs, clearances, construction, workmanship and material, unless specifically
accepted for the record, shall be in accordance with ASME ANSI A17.1.
1.2.2
2.0
2.1
All new elevators shall have on-board diagnostics and any special diagnostic tools, including SIM
cards, and instructions needed for advanced troubleshooting shall be included with purchase.
In buildings three stories or less, or where car travel does not exceed 40 feet, use hole-less
hydraulic elevators or consider MRL traction with the Emory Project Manager pre-approval for
specific design.
2.1.1 In buildings four and five stories tall, where the travel does not exceed 50 feet, and where
elevator use is minimal, use hydraulic elevators, (hole-less is preferred), or consider MRL
traction elevators, with Owner pre-approval for specific design.
2.1.2
In building four or five stories tall, where elevator use is heavy, consider traction elevators
or MRL traction (with Owner pre-approval for specific design).
2.1.3
In buildings six stories or greater, use traction elevators or MRL traction (with Owner preapproval for specific design).
2.1.4
Provide Elevator Service Car with heavy duty interior to serve all floors.
2.1.5
Section Page 2 of 14
2.1.6
2.2
2.3
2.4
2.5
Section 14 20 00
Elevators
To facilitate maintenance and to provide redundancy for elevator outages, the provision
of single elevators in buildings is discouraged. Empty hoistways are recommended for
future additional elevators in new buildings with single elevators. Hoistways for future
elevators shall be confirmed to be clear and plumb with variations not to exceed 1 inch in
100 feet measured from any point and shall include the overhead machine beams.
Traction elevator machine room should be located directly above, or as near as possible
to, the top of the hoistway. If a basement type machine is necessary, provide ready
access to all overhead equipment in the hoistway, or governor must be located in
machine room or pit. (Pit depth may be affected)
2.2.3
Access to machine room shall be short and direct as possible from the hoistway and
have adequate lighting. Route for access to machine room shall always have minimum
clearance of 42 inches by 7 feet. Door to machinery spaces shall be "B Label," fire rated,
self-closing and self-locking, able to be opened from inside with no key, and keyed with
BestLock. The door should swing out of the machine room, except as pre-approved by
Owner.
2.2.4
So called machine-room-less (MRL) elevators may have a machine room above the
hoistway. For elevator maintenance efficiency, a machine room above the hoistway with
access to the governor, controller, and drive machine is preferred.
2.3.4
For elevators installed for service cars, or for primarily handicapped access, side sliding
doors may be used for door openings up to 42 inches.
2.3.5
Use center-parting doors for all passenger elevators. For passenger elevators larger than
minimum size with center parting doors, specify duplex car stations.
2.3.6
For service elevators, specify tall cars (9 6 to car ceiling). For all elevators, especially
single passenger elevators in a new building, consider tall cars.
Speeds
2.4.1 Hydraulic speeds up to 3 floors: Specify 125 feet per minute.
2.4.2
2.4.3
Traction elevators up to 5 floors: Specify 200 feet per minute or, for premium, 350 ft per
min.
2.4.4
2.4.5
Speeds ranges may vary for unique situations with the Owners written approval.
Section Page 3 of 14
2.6
2.7
Section 14 20 00
Elevators
2.5.1
One elevator for 50,000 square feet gross space. . (For maintenance and for
redundancy, single elevators are discouraged.)
2.5.2
2.5.3
2.5.4
2.5.5
Elevator study should be performed for each building to verify number of cars needed.
2.6.6
A building which is designed to house research animals shall have a service elevator
dedicated to the use of the Department of Animal Resources.
2.6.7
Consider spare hoistway for future elevator in any new building with single or minimal
elevator provisions
Architectural Considerations
Manufacturers: Specify Schindler, Otis, ThyssenKrupp, or Fujitec Elevator for standard traction
and hydraulic elevators, for renovating of existing elevators, GAL Galaxy is also an approved
elevator controller manufacturer. So-called MRL designs to be pre-approved by Emorys Energy
& Utilities department for specific design and application. Elevator Contractors pre-acceptance of
Emory University standard elevator maintenance service contract is required. See section 2.11.6
2.6.1
Fireman's key box for each elevator or lobby group shall be flush mounted in wall in each
main egress floor elevator lobby. Firemans keybox shall be two-inches deep. (Elevator
Firemans Keybox is Quality Elevator Supply part #FKBC-F-2 (1-800-222-3688) for flush
mounting 2 deep box, and key number is #2546 for standard State of GA key)
2.6.2
In buildings 4 floors and above, use hall lanterns with audible signal. In medical patient
buildings and others as specified, use voice annunciation.
2.6.3
Use main and auxiliary car stations in passenger elevators with center parting doors.
2.6.4
Use stainless steel or bronze faceplates, #4 or #8 finish. Avoid highly finished surfaces
such as etched, anodized, sandblasted, etc.
2.6.5
All elevator lobbies in parking decks shall be enclosed for refuge space, to facilitate the
operation of elevator fire service, and to protect the elevator from the effects of weather.
2.6.6
Specification shall not favor a single vendor by shape of hoistway, pit, and/or control
room. Elevator hoistway and machine space right-of-ways, which allow for competitive
bidding, may be returned to user space after elevator is chosen.
2.6.7
To prevent energy waste, elevators which are not on the same riser shall be located at
least fifteen feet away from each other to discourage the practice of calling both elevators
separately for the same ride
2.6.8
Elevator hoistways shall be non-combustible construction and all elevator machine and
control spaces shall be minimum 2-hour fire rated. Hydraulic elevator machine rooms
shall be insulated for noise control when located near areas such as classrooms and
offices.
Cab Interiors
2.7.1 Materials inside cabs must be Class A Fire Rated.
Section Page 4 of 14
Section 14 20 00
Elevators
2.7.2
Use removable applied panels when possible for car interiors. Avoid soft material such as
wood or padding. Consider laminate, marble, and stainless steel. Tufted materials must
be short nap and meet flame and smoke spread requirements.
2.7.3
Provide handrails on sides and rear conforming to ADA and IBC heights.
2.7.4
Ceiling treatment shall not interfere with rescue hatch access. Safety hatch and ceiling
access shall be minimum 400 square inches (16x25 inches). Rescue hatch shall not be
operable from inside the car.
2.7.5
Specify manufactures standard cab with applied removable panels, or for premium,
specify National Elevator Supply or other approved vender holding the required State
certificate of competency.
2.7.7
Specify durable vandal-resistant car and lobby stations with lighted buttons.
2.7.8
Specify separate independent service keyed switch in the car station, not located behind
a locked cabinet with other switches. This keyswitch shall be Bestlock if possible.
2.7.9
Provide properly sized interior protective pad for each elevator and each elevator shall
have permanently mounted pad hanger pegs.
2.8.10 Elevator interior renovations are required (by the State) to be permitted and inspected,
Elevator interior installations by other than the elevator manufacturer shall be performed
only by Elevator specialists registered with the State of Georgia Elevator Inspections
Department.
2.8.11 Lighting in car shall be maintainable and repairable from inside the car without the
assistance of an elevator mechanic to provide access above the car ceiling. Elevator car
shall have 5 foot candles of light minimum measured at the threshold with the doors
closed
2.8
Hoistway Entrances:
2.8.1 Recommended materials: stainless steel or bronze with #4 or #8 finish, C.R. steel with
baked enamel finish.
2.9
Machine room door and route of access to machine room shall be minimum 42 inches by
7 feet tall.
2.9.3
Access to machine room door shall have same minimum dimensions as machine room
door. Access to machine room door shall not be through another restricted access area,
such as restrooms, storage rooms, locked offices, etc. Access to the machine room shall
not be by a wood ladder.
2.9.4
Elevator room shall have controlled environment. When elevator machine room is
located in mechanical basements and attic spaces and/or away from fully conditioned
building areas, target 75 degrees F in the elevator room, and relative humidity shall not
exceed 90%.
Section Page 5 of 14
Section 14 20 00
Elevators
2.9.5
Provide waterproof pit floor finished smooth to drain any water into sump in pit. Provide
sump recess (18 inches by 18 inches by 24 inches deep with a flush grate cover).
Provide permanent sump pump. Elevator sump pump discharge may terminate into an
oil separator but not directly into sanitary or storm sewer.
2.9.6
All hoistways in buildings with sleeping quarters four stories and above shall be ventilated
with 3 square feet of vent opening to outside, or 3.5% of total hoistway area, whichever is
greater,
2.9.7
Provide hoisting beam at the top of all hoistways including each hydraulic elevator shaft.
2.9.8
Provide Class C minimum 10 pounds fire extinguisher mounted near the lock side of the
door inside the elevator machine room.
2.9.9
Provide wall block outs for flush mounted hall pushbutton stations, hall lanterns, position
indicators, main lobby firemans keybox, etc.
2.9.10 Provide wall block out for flush mounted Fireman's Key Box in each main egress elevator
lobby.
2.9.11 Hoistway shall be clear and plumb, two hours fire rated, and with variations not to exceed
one inch within 100 feet vertically at any point. Avoid projections and setbacks 2 inches
and greater.
2.9.12 Seal fireproofing to prevent flaking.
2.9.13 Machine room floor and pit floor shall be painted and sealed.
2.9.14 The owner may allow temporary use of the elevator during construction if certain criteria
are met. See Construction Period.
2.9.14 For hydraulic elevator: Provide secondary containment around oil reservoir(s) if 55gallons or greater in capacity. Pit containment shall be considered adequate if elevator
pit sump drains to an oil/water separator. If reservoir(s) are in a mechanical room where
leakage could reach an open floor drain outside of the space, a concrete curb or other
form of secondary containment shall be provided where it does not create a trip hazard.
2.10
Electrical
2.10.1 Refer to Elevator Power Supply Confirmation Data Form provided by elevator supplier.
2.10.2 Provide insulated equipment grounding conductor in all elevator feeders sized to comply
with NEC Article 250.
2.10.3 Provide at least one battery emergency light in each machine room. Provide a minimum
of two enclosed fluorescent light fixtures in each machine room, for at least one light
fixture for each elevator controller, for a minimum of 15 foot candles at floor. Pit should
have at least one vapor proof light fixture with a switch near pit ladder, for minimum of 10
foot candles at floor.
2.10.4 Provide individual 120-volt, 20-amp circuits for GFCI machine room and GFCI pit
receptacles.
2.10.5 Provide single receptacle for the sump pump. Receptacle should be located near sump.
Section Page 6 of 14
Section 14 20 00
Elevators
2.10.6 Provide three-phase heavy duty industrial fused disconnect for each elevator. Main line
disconnects for elevator installations shall be located near as possible to the door, before
the controller, and within sight of the controller. Provide required safe electrical working
clearances specified by National Electrical Code (NEC).
2.10.7 Provide dedicated 120-volt circuit for car lighting with disconnect switch located near the
main line disconnect. Use emergency circuit if emergency power is provided. Comply
with NEC clearances.
2.10.8 Provide separate lockable 3 phase door disconnect if required by elevator system for
heavy duty doors.
2.10.9 Select overcurrent protective devices for elevator main line disconnects so that the
protective device closest to the affected controller will operate and will not affect other
elevators.
2.10.10 Install minimum of four pairs of fire alarm wires in conduit (which will initiate elevator
recall) for each elevator lobby group, from the fire alarm panel, to each elevator machine
room. Dry contacts which initiate elevator recall shall be located in the machine room.
2.10.11 Conduits containing elevator circuits should be dedicated to elevator circuits only from
electric panel of origin to the elevator machine room.
2.10.12 All new traction elevators shall be capable of utilizing generator back-up and shall have
software ready to utilize generator power. When emergency backup power is provided for
the elevator(s), unless the transfer switch is closed transition type, install minimum four
#12 AWG conductors in conduit, from the auxiliary contacts in the emergency transfer
switch, to each single elevator controller, and to the lead controller of each group of
elevators.
2.10.13 Power-loss emergency lowering shall be provided for hydraulic elevators, except those
served by an emergency generator. Elevator disconnects for hydraulic elevators shall
include auxiliary contacts in the disconnect handle to prevent automatic operation of
lowering system when disconnect is turned off manually.
2.10.14 All wiring, conduit, and equipment in the hoistway and elevator machine room shall be
directly related to the elevator. Systems related to the elevator (such as smoke detector
wiring, or card reader security systems), but installed by other trades, shall have no
service points in the hoist-way.
2.10.15 Electrical Consultant shall verify that building service and main line elevator feeders are
adequate for the elevator equipment. The starting characteristics of the elevator drive
motor shall not cause a perceptible dimming of the building lights.
2.11.
Section Page 7 of 14
Section 14 20 00
Elevators
2.11.4 Include separate independent service keyed switch in the car station which is not in a
cabinet with other switches
2.11.5 All new elevators shall be capable of utilizing generator power and shall have software
installed for possible emergency power back-up.
2.11.6 One year free warranty and maintenance service is included. For all new elevator
designs, three subsequent inspection service visits at approximate one-year intervals are
included with the purchase price whether or not elevator vendor is awarded subsequent
maintenance after the warranty year. Elevator vender shall accept Emory University
standard elevator service contract, which is a premium service arrangement and includes
24 hour free callbacks for all new elevators during the warranty year, a forgiveness
clause equal to four normal hours or $640 whichever is greater (for callbacks outside the
Contractors control), and 24 hour free mechanical callbacks for all residential elevators,
all parking deck elevators, and others as specified. Cost of three (3) years of subsequent
maintenance (purchase price includes one free warranty year with 24-hour free
mechanical callbacks) shall be submitted as an addendum to purchase price for review
by Owner before purchase. Owners free warranty and maintenance service year shall
begin at Owner acceptance and occupancy.
2.11.7 Elevator Secured Access: Traveling cables shall include minimum 4 (four) pair of
shielded #18 wire for future secured access systems for elevator in the traveling cable
and between two car stations. Elevator security key switches shall be BestLock and not
the elevator manufacturers standard key switch.
2.11.8 Any available electrical and mechanical noise control from the elevator vender shall be
included.
2.11.9 Provide alarm bell in car station that is clearly audible outside the elevator on all floors.
2.12
2.13
Hydraulic Elevators.
2.13.1 Include battery-operated lowering system for power outages unless elevator is served by
generator power.
2.13.2 Include a means to maintain oil temp within normal operating range. (Viscosity control).
Hydraulic elevators in new residence halls shall include oil coolers.
2.13.3 Provide constant speed lowering section on valve on all buildings 4 stories or higher.
2.13.4 Provide sound isolation couplings and muffler.
2.13.5 Isolate pumping unit form building structure with neoprene or other isolating materials.
2.13.6 Provide isolation between oil lines and building walls or other building members.
2.13.7 Provide isolation soft start (electronic) motor starting, not open transition-y-delta, starting.
2.13.8 For single hydraulic elevators, include motor rated at minimum 100 starts per hour on
buildings four stories or greater.
Section Page 8 of 14
Section 14 20 00
Elevators
Traction Elevators:
2.14.1 Use VVVF control for up to 5000-pound capacity elevators. Provide filters, chokes, and
reactors to minimize harmonic line distortion. Renovations of existing motor-generator set
traction elevators may use SCR drives.
2.14.3 Use roller guides on car and counterweight above 250 feet per minute...
2.14.4 On basement type traction machines, and for new MRL designs, coordinate governor
access with architect. Safe, legal access, minimum 24 inches by 24 inches, to the
governor for elevator maintenance and testing is required.
2.14.5 Sleeve governor cable and all cable holes to 12 inches below the ceiling of the hoistway.
2.14.5 All traction elevators including MRL designs shall have a 52 inch minimum toe guard
measured from the door sill.
2.15
Construction Period Temporary Use by Contractors.
When the elevator installation is substantially complete, the owner may allow temporary use of the
elevator during construction if certain criteria are met. Requirements for Temporary Use Include: The
owner shall receive the elevator in new condition with a full one-year warranty and one year free
maintenance. Temporary use of the elevator during construction shall not reduce the Owner's One-Year
warranty period. General Contractor shall have full insurance coverage on the elevator and is responsible
for damages during the construction period and shall refurbish car if needed before turnover to Owner. If
the elevator is used before final acceptance by Emory University, the elevator shall be safely operated
under control of the manufacturer, and the manufacturer shall provide ongoing maintenance and
supervision of the equipment at the expense of the Contractor. Obtain prior approval from the State
Department of Labor Safety Engineering Section for temporary use. Two- way emergency
communications for the elevator car is required. If the ADA compliant emergency phone is not yet
operable, an operator with a two-way radio must be inside the car during use.
2.16
Training
A 3 hour training session for the elevator equipment and review of the elevator deliverables is included
and shall be conducted by a qualified trainer or adjuster of the elevator manufacturer. This training will be
conducted at a time convenient to the Owner. Owners manuals with part lists and troubleshooting codes
and shall be provided and available during this training session.
2.17
Maintenance
One Year's Free Maintenance with 24-hour free mechanical callbacks for Emory University is included in
the purchase price which shall generally commence for all elevators in a new building on Owners
acceptance of the building.
See section 2.11.6 for maintenance requirements of Owner
3.0-3.4 Intentionally Omitted
3.5
Submittals:
Submit Owners manual with parts list and trouble-shooting guide for approval. Submit power
Confirmation Sheets: Include hp, code letter, full-load running and accelerating current, demand factor
and regenerative loads (if required) and S.C.R. noise (harmonic) for applicable motors.
3.6
Section Page 9 of 14
Section 14 20 00
Elevators
3.6.1.1 When one or more elevators have been installed to a stage near completion and
declared ready for service, the Owner or General Contractor may accept the
elevators for interim use and place them in service before the entire installation
of all elevators has been completed and accepted. Owner or General Contractor
shall also have the right to obtain any such elevators for temporary use for
themselves or additional Subcontractors for work other than by the General
Contractor. The General Contractor shall provide or compensate the Elevator
Subcontractor for temporary car enclosures, all cleaning, repairs or replacement
of materials as necessary to restore each elevator to its original condition. The
maintenance and warranty periods herein shall not commence for units accepted
on an interim basis. Prior approval for temporary use shall be obtained from the
State Department of Labor Safety Engineering Section.
3.6.2
3.6.4
Existing Elevators
3.6.4.1 The use of existing elevators by the Contractor shall not deviate in any fashion
from the standard and normal use of this equipment. If deviation is required, the
Owner's Project Manager shall request the assistance of Emorys elevator
service provider. This company shall become involved, at the Contractor's
expense, in operating or monitoring the elevator's function during the time when
the unusual use is planned to occur. The Contractor is also responsible for the
cost of any repairs required due to the unusual use of the elevator. Use of an
existing elevator as a construction elevator usually necessitates a special
cleaning in elevator spaces at the expense of the Contractor at the end of the
project.
3.7
3.8
Operation
3.8.1
3.8.2
Door Closing: The door closing times shall not be less than those permitted by the A17.1
Code. Closed loop control is preferred. Include adjustable nudging cycle.
Section Page 10 of 14
3.8.3
3.9
3.10
Section 14 20 00
Elevators
Controller: UL/CSA labeled. Hinged cover is preferred. Compartment -Securely mount all
assemblies, power supplies, chassis switches, relays, etc., on a substantial, selfsupporting steel frame. Completely enclose equipment covers. Ambient temperature
shall be maintained between 55 and 85 degrees F. Relay Design -Magnet operated with
contacts of design and material to insure maximum conductivity, long life and reliable
operation without overheating or excessive wear. Provide wiping action and means to
prevent sticking due to fusion. Contacts carrying highly inductive currents shall be
provided with arc deflectors or suppressors.
3.9.3
Hoistway Equipment
3.10.1 Guide Rails: Planned steel T-sections suitable for the application, car weight,
counterweight, with brackets for attachment to the building structure. Formed or bent
sheet metal rail brackets are not acceptable.
3.10.2 Governor and Encoder Pit-Tensioning Sheaves: Mount sheaves to pit support members
or guide rails with guides or pivot points to enable free vertical movement. The governor
tension sheave shall always be weighted, not a spring.
3.10.3 Hoist and Governor Ropes: Use8x19or8x25 sealed construction traction steel type. Use
3/8" minimum diameter for all hoist ropes.
3.10.4 Interlocks: Provide operable without retiring cam. Provide fire-resistant wiring, N.E.C.,
Type SF-2 or equivalent. Interlocks that are visible and conspicuous when doors are
open shall be painted flat black.
3.10.5 Provide 10% spare conductors minimum in the traveling cable at final acceptance,
including minimum 8 pair shielded #18 wire for elevator security arrangements in the
traveling cable and between auxiliary and main car stations.
3.11
Car Equipment
3.11.1 Door Control Devices: Infrared Reopening Device -Black, high-impact plastic or metal
device extending full height of car door panels. Full screen infrared matrix or multiple with
minimum of 40 beams extending vertically along the edge of each leading door panel.
Three-dimensional infrared curtain is preferred. Device shall reverse doors at normal
opening speed if beams are obstructed while closing, except during nudging operation.
Section Page 11 of 14
Section 14 20 00
Elevators
3.11.2 Return Panels and Car Operating Panels: Provide firefighters' telephone jack with bezel
matching adjacent controls and owner's if supported by building interface. Provide black
paint filled engraving or approved etching with letters minimum 1/2 inch tall and style
approved by the Architect as follows: a) Phase II firefighters' operating instructions on
main operating panel above corresponding key switch. b0 ) Provide and install two
inspection holders: One for full sized operating certificate and business card inspection
holder. All tamper-resistant fasteners on exposed fasteners.
3.11.3 Include minimum 4 (four) spare shielded #18 or pair of data wires in the traveling cable.
These are to be used for the installation of a key access system, either initially or at a
later date.
3.12
Signals
3.12.1. Hall Lantern: Provide at each passenger entrance to indicate travel direction of arriving
elevator. Illuminate indicators with shielded lights, and sound adjustable level electronic
tone mechanism. Sound level shall be adjustable from 0 -80 dBa measured at 5'-0" in
front of corridor pushbutton and 3'-0" off the floor. Illuminate up to down lights and sound
tone (twice for down travel) prior to car arrival at floor. Illuminate light until the elevator
doors start to close. Provide advanced hall lantern notification to comply with ADA
corridor call notification time. Minimum 2 1/2" in the smallest dimension, without
faceplates.
3.14
3.15
Owner's Information
3.15.1 Performance Guarantee: The specification should define tests to be performed to confirm
the performance of the elevators. Should these tests develop any defects or poor
workmanship, any variance or noncompliance with the requirements of the specified
codes and/or ordinances or any variance or noncompliance with the requirements of the
specifications, the following work and/or repairs shall be completed at no expense to the
Owner. a) Replace all equipment that does not meet Code or specification requirements.
b) Perform all work and furnish all materials and equipment necessary to complete the
specified operation and/or performance. c) Perform all retesting required by the
Governing Code Authority and the Owner to verify the specified operation and/or
performance.
3.15.2 Provider shall submit the following information, before the final acceptance of the
installation, for the Owner's file.
3.15.2.1 Wiring diagrams: Three sets of "As Installed" straight-line wiring
diagrams showing the electrical connections of all equipment and all
modifications to the control circuits Generic drawings shall be
corrected.
Section Page 12 of 14
Section 14 20 00
Elevators
Section Page 13 of 14
Section 14 20 00
Elevators
Section Page 14 of 14
Section 21 13 00
Fire Suppression Sprinkler Systems
Scope of Work
This section details the minimum level of practice and procedures for the design and construction of new
fire protection systems: Piping, valves, fire pumps, accessories, and other components charged with
water to suppress fire.
Regulatory Requirements
All fire protection design and installation should be in accordance with FM Global Standards. All drawings
should be submitted to the Emory University Project Manager and FM Global for approval. Field
installations are subject to FM Global acceptance in addition to approval of the AHJ. Approved drawings
shall be submitted to the Emory Project Manager. Work performed shall comply with all applicable Emory,
local, state, and National Fire Protection Association Standards below:
1. FM Global Approval Guide and FM Data Sheets
2. Drawings and specifications to be reviewed can be sent to the attention of Plan Review
Engineers (for Emory University), FM Global, 3460 Preston Ridge Drive, Alpharetta, GA 30005.
General Requirements
1. Methods and materials shall be high quality commercial. So-called residential methods or
materials shall not be used. Systems designed in accordance with 13R in new buildings are not
acceptable to the Owners Insurance Carrier. Plastic sprinkler piping shall not be used for any
new sprinkler system.
2. The installer shall permanently and clearly label all valves and fire protection piping such as
standpipe distribution piping that is not obvious for its purpose. Identification for control valves
shall identify the area which is controlled. Contractor shall label all drains for their purpose and
label the location of drain outlet at the test valve for ease of test and maintenance.
3. Installer shall permanently mount signage indicating system hydraulic design and water supply
demands
4. All sprinkler heads shall have a frangible bulb unless otherwise instructed by Emory University.
Where extreme conditions are unsuitable for glass links, sprinklers with solder links shall be preapproved by the Owner.
5. See section 019113 General Commissioning Requirements
Fire Pumps
See Section 21 30 00
Design and Sprinkler Occupancy Guidelines
1. General information: For the occupancies that are typical to Emory buildings, there is little
difference in the sprinkler densities required by FM Global and NFPA 13.
2. For most areas, the occupancy is light hazard and requires a sprinkler density is 0.10 gpm/sq. ft.
over the most remote 1500 sq. ft. with 250 gpm reserved for hose stream use.
3. Laboratories: FM Global requires 0.15 gpm/sq. ft. over 2500 sq. ft. Review with FM Global
before design.
4. Mech/Small Storage Rooms: FM Global requires 0.15 gpm/sq. ft. over 2500 sq. ft. Review with
FM Global before design.
5. Exhibit Halls with unusually high ceilings: FM Global requires 0.30 gpm/sq. ft. over 5000 sq. ft.
Typical auditoriums and theaters require 0.15 gpm/sq. ft. over 2500 sq. ft.
6. For other occupancies, the FM Global plan review department should be contacted at (770) 7773084 for guidance.
7. Hazard Classification 2 (Ordinary Group I hazard) shall be designed to provide 0.20 gpm over the
most remote 2,500 square feet with 250 gpm for outside hose allowance
Revision Date November, 2014
Page 1 of 5
Section 21 13 00
Fire Suppression Sprinkler Systems
8. Hazard Classification 3 (Ordinary Group II hazard) shall be designed to provide 0.30 gpm over
the most remote 2,500 square feet with 500 gpm for outside hose allowance.
9.
Design of sprinkler system, contractor shall perform (at the same time) a 24 hour static test and
fire flow test. System to be designed for lowest pressure recorded during 24 hour period. Where
need for a fire pump is indicated, Contractor shall perform a second 24 hour test to help prevent
the use of an anomalous low pressure for the fire pump sizing and system calculations.
10. Any water mains installed underground shall be a minimum of 8 pipe.
11. All sprinkler heads in residence halls shall be concealed type. Exceptions shall be pre-approved
in the design stage by the Director of Operations and Maintenance.
Contractors Qualifications
1. Sprinkler Contractor shall be licensed and, insured per Emory University requirements, and shall
employ a Certificate of Competency holder. Sprinkler contractors must have approved references
for satisfactory performance on similar projects of similar size and must have been in business
with the same business name for at least five years. Exceptions to this requirement shall be preapproved in advance in writing by the Emory Project Manager.
Acceptance Tests, Documentation, and Warranties
2. Upon completion of any sprinkler system, aboveground or underground, Contractor shall perform
and document the tests required by Code and shall provide the appropriate signed and
completed Contractors Material and Test Certificates to the Emory Project Manager. Original
acceptance tests shall include full trip tests of deluge systems, dry systems, and pre-action
systems and pressure tests required by Code. Contractor shall transfer the maximum equipment
warranties to the Owner, and shall warrant materials and workmanship for a minimum of one
year. Defects discovered during the warranty year shall be repaired at the Contractors expense.
Contractor shall return promptly to repair leaks.
3.
Owner will conduct an annual sprinkler inspection during the warranty year. If the first Annual
Sprinkler Inspection has deficiencies, the installing contractor shall make corrections and repairs
at the earliest convenience of the Owner and shall promptly produce a satisfactory annual
inspection performed by a licensed qualified inspector and shall provide the report to the Owner
at the Contractors expense.
4. Copy of as built-record in auto cad format complying with Campus Services Document Delivery
Standards and including hydraulic calculations shall be provided to Emory project manager. Hard
copy of as-built sprinkler system shall be installed in a permanently mounted PVC tube near the
main fire alarm panel, or near the main riser or fire pump controller, if any. An 8X11 size
laminated or framed schedule (list) of valves shall be provided in the pump room or at the main
riser. Hydraulic placards shall be installed on all fire sprinkler risers.
Test Headers
Fire suppression sprinkler systems shall use equipment and devices that are UL listed and FM Approved.
See Section 21 30 00
Fire Department Connections (FDC)
Fire Department Connections and outdoor sprinkler control valves shall be visible and accessible. All
freestanding FDCs shall be installed with a fixed identification sign and have a minimum of 3 feet
clearance from obstructions per the International Fire Code. If the FDC is not readily visible from the front,
a sign shall be provided to direct the fire department to the FDC.
Revision Date November, 2014
Page 2 of 5
Section 21 13 00
Fire Suppression Sprinkler Systems
Stand-alone Fire Department Connections (Siamese FDC) shall drain into an accessible dry well.
Any underground check valves on FDC piping shall be accessible. Contractor shall install a means for
drainage of water trapped in underground piping. This method may include the installation of a ball drip
within a vault or pea gravel. Method must be approved by Emory University prior to installation.
Valves and Back flow Preventers
1. The use of quick-opening valves is not permitted on main drains or test headers
2. Fire protection valves shall be accessible and shall not be located in the fire area that they
control. They should be in an area that is easily accessible under all conditions. Locations above
suspended ceilings shall be avoided with the exception of valves which control a single sprinkler
head, such as an elevator pit sprinkler head. Fire protection valves shall be located in stairwells,
or in stacked sprinkler or mechanical spaces which permit ready access and floor to floor riser
piping. Fire protection valves shall not be located in custodial closets or customer closets or
conference rooms as these rooms are keyed differently from mechanical spaces at Emory. If
absolutely necessary to install valves above ceilings, the valve location shall be accessible and
labeled on the ceiling grid or access panel.
3. Fire protection control valves in stairways and hallways shall be readily accessible but shall be
lockable with Emorys Bestlock padlock or key. Valves shall not be located within the clear width
of egress.
4. All control valves shall be indicating (post indicator, indicating butterfly, or OS&Y), high quality,
and listed for their purpose. Test header valves shall be OS&Y gate valves. OS&Y valves shall
be used in the fire pump room and for sectional valves, except butterfly valves are permitted for
the fire pump flow meter. If butterfly valves are used where space does not permit OS&Y valves,
their use shall be pre-approved by the Owner and only high quality butterfly valves are permitted
(Nibco, Kennedy or equivalent pre-approved in writing by the Project Manager) and the indicator
shall be visible from the floor. The use of quick opening valves and non-indicating gate valves is
not permitted. All valves shall be lockable with the owners Bestlock padlock or key.
5. All outdoor sprinkler test and control valves and headers shall have minimum of 3 feet clearance
for tests and maintenance.
6. All sprinkler valves, including backflow preventer valves, shall be electrically supervised by the
fire alarm system. All sprinkler valves shall be lockable with Emory University Bestlock padlock or
key.
7. Back flow preventers for sprinkler systems shall be full size and shall be either a Watts Model
709 or a Watts Model 757. The standard model shall be used if installed in a building on an
Emory water main. The DCDA models shall be used if installed outside and on a DeKalb County
water main.
8. Multistory buildings shall have control assemblies for each floor.
Drains
1. All fire protection drains (with the possible exception of fire pump casing relief valves and packing
gland drain which may be piped separately and directly to a floor drain) shall be piped to the
outside of the building. Drains shall never be piped to an interior sink. Routing to interior floor
drains shall be avoided. If absolutely necessary, routing to interior drains shall only be utilized
when the floor drain is minimum 4 inch and has proven capacity in excess of the combined
maximum flow of all of the fire protection drains routed to it, and a second valve shall be installed
near the floor drain to help control flow in the event of an obstruction in the drain. Auxiliary drains
(low point drains for a minimal amount of water) which have no permanent drain piping shall have
a threaded hose hub with a plug installed.
2. Plastic piping shall not be used for drains.
3. Connection of drain cup piping or water motor gong discharge to the 2 drain shall be avoided.
When such an arrangement is absolutely necessary, a swing check valve (in horizontal piping)
should be installed to prevent backflow during 2 draining.
Revision Date November, 2014
Page 3 of 5
Section 21 13 00
Fire Suppression Sprinkler Systems
4. In a multistory building, all fire protection drains shall be piped into a drain riser and piped outside
the building. Drain shall exit the building no higher than 12 inches above finished dirt grade, or six
inches above finished concrete. All exterior drain pipe and associated fittings shall be galvanized.
A sight glass shall be installed on control assemblies to verify the flow of water during testing.
5. Interior ball drips on test headers and FDC piping shall be installed at lowest point of piping and
piped to outside of building. Use additional or individual header ball drain valves if necessary for
complete draining for freeze protection
Pre- Action sprinkler systems
1. When a pre-action sprinkler system is required, it shall be a double interlock pre-action system
that uses a combination of pneumatic and electrical action to release the sprinkler system valve.
2. A double interlock pre-action system requires two smoke detectors in cross zoned mode (second
detector is for verification) and a mechanical pneumatic actuator (for electric pneumatic actuation
of system sprinkler valve). Electric/electric methods are not acceptable (cross zoning the smoke
detector and electrical air pressure switch, called low air switch, alone is not acceptable and does
not result in a true double interlocked pre-action system). Low air pressure switch is for
supervision of the integrity of sprinkler piping, and not for activation of the valve in a double
interlock pre-action system.
3. A separate releasing panel should be used. When a separate releasing panel is used, it shall be
installed in the same area of the releasing valve or in the protected area, with proper working
clearance, with clear permanent signage indicating area served by the pre-action system.
Releasing panel shall be listed for releasing purposes and shall be listed for use with solenoid
valves used on deluge valve trim.
4. If the main fire alarm panel is accessible near the hazard, it may be used as the sole control for
the preaction system, if it is listed for releasing service. For a pre-action system containing
twelve or fewer sprinklers, a Viking releasing panel is acceptable. For systems containing more
than twelve sprinklers, use Notifier or Fike addressable panels with addressable detectors.
5. In cases where a separate releasing panel is used, pre-action supervisory functions (i.e. valve
tamper switches) shall be monitored by the main fire alarm panel. The releasing solenoid shall
be connected to the releasing panel.
6. Pre-action valve shall have clear permanent signage indicating pre-action sprinkler system and
area protected.
Other
1. Alarm pressure switches shall be installed in vertically as per manufacturers instructions.
2. All escutcheons used with semi-recessed sprinkler heads shall be two-piece semi-recessed
mounted.
3. Where freezing is likely, a dry sprinkler system or dry sprinklers shall be installed if a dry exterior
sprinkler system is used, sprinkler piping shall be galvanized. Passive heat from service lines and
equipment or heat tape shall not be used to prevent freezing in a sprinkler system.
4. Contractor shall install spare parts cabinet with minimum 6 heads (at least one of each head
installed in the building) and the necessary wrench(s). Contractor shall include at least one pair of
escutcheons for each type of spare head. If flexible sprinkler drops are used, provide a spare
flexible drop strapped to the spare sprinkler cabinet with an additional mounting bracket and lock
nuts. Locate said cabinet adjacent to alarm check valve or fire pump.
5. CPVC Piping or any plastic piping shall not be used in new sprinkler systems, even if permitted
by local codes
Revision Date November, 2014
Page 4 of 5
Section 21 13 00
Fire Suppression Sprinkler Systems
6. All sprinklers in the same ceiling area (with the same ceiling construction) shall be the same
make and model and installed per manufacturers instructions. All sprinklers shall also be the
same response type. Quick response sprinklers hall not be installed in the same area with
standard response sprinklers. All Pendant heads in the same area shall be the same distance
below the ceiling.
7. Sprinklers shall not be located over non-combustible elevator hoist ways or elevator equipment
spaces which are rated two-hour minimum. A sprinkler is generally required within 24 inches of
the floor on the wall in the pit; location to be coordinated with elevator contractor. Such rooms
and spaces shall have smoke detectors.
8. Hydraulic calculation plaques shall be installed for each sprinkler system and at the building
main.
9. Spaces designed for server rooms shall be protected with true double interlock pre-action
sprinkler systems.
10. Wet stand pipes shall have tamper resistant or lockable caps or covers.
Page 5 of 5
Section 21 30 00
Fire Pumps
Section 21 30 00 Fire-Pumps
Regulatory Requirements
All fire protection design and installation should be in accordance with FM Global Standards. All drawings
should be submitted to the Emory University Project Manager and FM Global for approval in addition to
the AHJ, and field installations are subject to FM Global acceptance. Approved drawings shall be
submitted to the Emory Project Manager. Work performed shall comply with all applicable Emory, local,
state, including and not limited to the following Codes and National Fire Protection Association Standards
below:
1. FM Global Approval Guide and FM Data Sheets
2. Drawings and specifications to be reviewed can be sent to the attention of Plan Review
Engineers (for Emory University), FM Global, 3460 Preston Ridge Drive, Alpharetta, GA 30005.
General Requirements
See Section 01 91 13 General commissioning requirements.
Fire Pumps
1. A system designed to deliver adequate fire suppression water without a fire pump is preferred. If
a fire pump is necessary to comply with the design, pump flow rating design shall be based on
the maximum anticipated fire protection demand flow, but limited such that the flow at 150% of
pump rating shall not drop the city pressure below 20 PSI. Fire pump pressure demand rating
design shall be based on a net discharge pressure that does not exceed 175 PSI. This is to
ensure that the design of the system does not exceed the working pressure of the sprinkler piping
and fittings. Except where pressures must exceed 175 PSI, pressure relief devices shall not be
used for pressure control (exception multistory buildings) If excess pressure is required to
accomplish roof top standpipe demands, pressure reducing valves shall be installed at each floor
in lieu of using a pressure relief device on the pump.
2. Alternately an approved variable speed pump can be utilized, as permitted by codes.
3. A pressure regulating device may be installed on the standpipe system, however this installation
is not preferred and must be approved by FM Global, Emory University and the authority having
jurisdiction.
4. The use of suction control valves shall be approved by Emory University prior to installation.
5. Fire pump designs shall limit the available flow to fire suppressions system demands to 125% of
the rated capacity of the fire pump.
6. For diesel engine fire pumps, water coolant temperature shall be monitored in accordance with
NFPA 20.
7. Fire pumps should be located at or above grade level. To avoid excessive pressures on lower
floors, fire pump may be provided for upper floors only.
8. If a fire pump is required, power supply to the pump shall be upstream of any building power
main disconnects, so it will not be shut down when the building power is isolated during a fire.
9. Fire pumps shall be accessible via an outside door into the pump room or a protected corridor
path to the pump room. Fire pumps should be located adjacent to an outer wall. Any exceptions
shall be pre-approved in the design stage by the Emory Project Manager. Fire pump rooms shall
be dedicated to fire protection equipment.
10. Fire pumps shall be located inside a two hour minimum rated room. Rated mechanical rooms are
not acceptable. Higher rating of room shall be determined by FM Global and/or the Fire Marshall.
11. Fire Pumps, Controllers, and Jockey Pumps acceptable manufacturers: Fire Pumps shall be
horizontal pumps manufactured by Patterson, Peerless, or Fairbanks Morse. Patterson Pumps is
the preferred fire pump manufacturer. Fire Pump manufacturer shall have local support. Jockey
Pumps shall be manufactured by Grundfos. Fire Pump controllers shall be manufactured by
Firetrol or equivalent pre-approved by Emory Project Manager. Fire pump controllers which have
an integral transfer switch shall have an integral ASCO transfer switch. Fire pump controller shall
Revision Date November, 2014
Section Page 1 of 3
12.
13.
14.
15.
16.
17.
18.
19.
Section 21 30 00
Fire Pumps
have local manufacturers support. Use soft start (electronic) starter (instead of standard acrossthe-line) fire pump controller.
Casing relief valves shall be high quality Clay valves. Drain lines from packing glands and from
the casing relief valve shall be piped completely separately to a drain or to the outside. Only the
packing gland drip drain and the casing relief valve drains for the fire pump may be discharged
into a floor drain in the pump room. If required, fire Pump pressure relief valve shall discharge
outside in a safe location and not into the pump room nor into the pump suction side of the pump.
If required, fire pump pressure relief shall discharge preferably where it might discharge into an
existing or new cistern outside the building. The fire pump relief valve discharge location shall be
specifically discussed with the Emory Project Manager.
Suction lines should avoid excessive vertical runs prior to the fire pump that may result in
collection of air pockets that may affect the operation of the fire pump. If these installations are
necessary, automatic air release valves shall be installed.
For water conservation and diagnostic test purposes, fire pumps shall be installed with a flow
meter between the discharge side and the suction side of the fire pump.
Consideration shall be made by the designer and the Contractor for reclaiming pump test
discharge water to the maximum extent possible. Such water may be collected for reuse for
irrigation purposes, and collection shall be coordinated with Emory Universitys Exterior Services
and Sustainability department within Facilities Management. If a water recovery system exists
adjacent to and downstream of the building being tested, the fire pump test header should be
located within fifty feet from the drain to the recovery cistern to facilitate water reclamation.
Training of the fire pump and fire pump controller shall be required in the specifications.
Manufacturer representatives of each shall conduct the training.
Demonstration shall be required of the fire pump integration to other systems, such as
emergency power and fire alarm, as required. Complete monitoring of the fire pump by the fire
alarm system, including pump running and power loss, shall be verified.
TB Woods or any plastic fire pump couplings are prohibited by FM Global for the fire pump. Fire
pump shall be perfectly aligned and alignment confirmed by the pump manufacturers
representative after installation at the initial acceptance test.
The fire pump base plate shall be grouted in place after installation per the applicable codes.
Test Headers
1. Main Test header valves shall be straight-through OS&Y gate valves.
2. Ball drips on test headers shall be installed at lowest point of piping and piped to outside of
building or floor drain. Use additional or individual header ball drain valves if necessary for
complete draining for freeze protection
3. Test headers shall be accessible outside and shall have a minimum three feet clearance for
working space and a clear route for laying out hoses for annual testing. Test headers shall be
located for safe and convenient flow of water at 150% of pump capacity.
4. Test headers shall be located outside the building so that no more than 50 feet of fire hose is
needed to direct safe and convenient discharge without damage to building or grounds. If
necessary to accomplish this, test header piping shall be upsized per Code.
5. New installation shall include hose valves for testing purposes
6. Test header connection shall be tied into the pump discharge line upstream of fire pump
discharge valve.
Warranty and Contractors Qualifications
The warranty and service agreement shall include the following:
1. Labor, parts and equipment for all components of the sprinkler system for a minimum of one
year. Fire pumps shall have maximum Manufacturers warranty. Defects discovered during the
warranty year shall be repaired at the Contractors expense. Warranty for the fire pump shall
commence on the day of the initial satisfactory acceptance test
Revision Date November, 2014
Section Page 2 of 3
Section 21 30 00
Fire Pumps
2. Owner will conduct an annual fire pump test and inspection by others during the warranty year. If
the first fire pump test performed by the Owner has deficiencies, the installing contractor shall
make corrections and repairs at the earliest convenience of the Owner and the Contractor shall
schedule a follow-up test to be performed by a fully licensed and qualified inspector. Test shall be
performed at the Owners convenience (outside normal hours) and a satisfactory annual fire
pump test and inspection report shall be submitted to the Owner at the Contractors expense.
3. Installing contractor shall be licensed, insured per Emory University requirements, and shall
employ a Certificate of Competency holder. Installing contractor has references for satisfactory
installations of a similar nature and must have been in business with the same business name for
at least five years. (Exceptions to this requirement shall be pre-approved in advance in writing by
the Emory Project Manager.)
Acceptance Tests and Documentation
Installing Contractor, Pump Manufacturer Representative, Fire Pump Controller Manufacturers
representative, and Owners representative shall be present at the initial fire pump acceptance test. A
Manufacturers Representative for the fire pump and for the fire pump controller, as well as the installing
contractor, shall sign the initial test for the Owner. Installing contractor shall submit an original, signed,
and legible initial fire pump test to the Emory Project Manager; Copy of as built shop records in AutoCAD
format complying with Campus Services Document Delivery Standards and a hard copy shall be provided
to Emory Project Manager. Hard copy shall be placed in a permanently mounted PVC tube near fire
pump controller.
Section Page 3 of 3
Section 22 00 00
Plumbing
Section 22 00 00 Plumbing
2.01
A.
Hose Spigots
Provide frost-proof devices. In general, one exterior freeze protected hose spigot shall be
provided for each facade of the building. Provide a 1-1/2 diameter hose spigot connection at
every cooling tower location. Provide one hose spigot connection in each mechanical room in
the building. Consideration must be given also for cleaning DX condensing coils. Locate a
hose spigot within approximately 50 feet of a condensing unit. If the condensing unit is located
on the roof, consider either a hose spigot on the roof, or near the roof hatch of a penthouse.
For bathrooms with gang showers, provide a hose spigot connection under the closest available
lavatory.
2.02
A.
B.
2.03
A.
2.04
2.06
A.
Waste Systems
For laboratory buildings, provide separate lab and sanitary waste systems until point of exit from
building. For animal holding areas, provide waste system separate from lab waste systems due
to clogging of neutralizing system from animal hair and wastes.
1. Roof Vents: Minimize roof penetrations through the use of manifold sewer system roof
vents.
2. If possible, avoid the use of waste systems lift stations. Because of previous issues, please
discuss specific manufacturers with the Emory Project Manager prior to developing
specifications.
2.07
Section Page 1 of 5
A.
Section 22 00 00
Plumbing
Atlanta Gas Light Company provides gas through high and low-pressure distribution systems
depending on location. The Designer should review the preliminary gas system design with the
Emory Project Manager early in the design process.
2.08
A.
2.09
A.
2.10
A.
Backflow Preventers
For higher hazard applications, use reduced pressure zone Watts 909. No substitutions will be
allowed. Install two half-sized (based upon design building flow) backflow preventers in parallel
for main building service. For secondary higher hazard applications in the building, one full size
back flow preventer is adequate. For reduced pressure zone Watts 909, provide air gap device
piped full size to an appropriately sized floor drain. For certain lower hazard applications, use
Watts 007, Watts 709 or Watts 757. Provide a strainer (with valved blow-down line) upstream
of all backflow preventers with a stop valve upstream of the strainer. Provide pressure gauges
upstream and downstream of backflow preventer.
B.
Backflow devices shall be tested by the Contractor prior to acceptance by Emory University the
Contractor shall provide a record of the test. A DeKalb County certified tester must perform the
test.
C.
The Contractor shall flush the water line prior to testing the backflow device to prevent damage
to the seals from accumulated sediment.
D.
Use Watts vacuum breakers on all interior and exterior hose connections.
E.
Provide a threaded 2-1/2 ball valve connection with plug between the back flow preventer
assembly and the building pressure reducing valves for an emergency water connection.
2.11
A.
2.12
A.
Pumps
Grundfos or Bell & Gossett shall manufacture all plumbing circulation pumps. (Under 3 hp)
Provide pressure gauges upstream and downstream of all circulating pumps.
Section Page 2 of 5
2.13
A.
B.
C.
Section 22 00 00
Plumbing
Piping
Soil, waste, vent and rainwater below floor hub and spigot cast iron, service weight. Provide
sleeves at building footings.
Soil, waste, vent and rainwater - above floor - 8 and less - no-hub cast iron. Provide sleeves
at building footings.
No-hub fittings - Heavy-duty mechanical compression 4 band type couplings.
D.
Domestic water piping - Shall be copper. Type L above ground and Type K below ground.
Provide sleeves at footings. Pro Press style fittings and couplings may be used pending
specific building review. In no case shall Pro Press style fittings be used underground.
E.
F.
Refer to 23 05 00 for valve tags, diagrams and piping identification requirements. Also refer to
this section for applicable piping and other material requirements.
2.14
A.
Plumbing Fixtures
All plumbing fixtures shall be as manufactured by American Standard, Crane, Eljer, Kohler,
Zurn or Toto. Flush valve type fixtures are preferred over tank type fixtures.
Toilets - Toilets shall have a dual flush flush valve or a dual flush tank type.
Urinals - Urinals shall be low flow 0.125 gallons per flush and manufactured by Zurn, Sloan or
Toto. The urinal flush valve shall be the automatic type.
Flush valves - flush valves shall be manufactured by Sloan, Zurn or Toto and shall be
designed to match the appropriate fixture. The Sloan Optima model shall not be used.
B.
C.
D.
2.15
A.
Faucets
Provide kitchen faucets and lavatory faucets manufactured by Moen. Acceptable alternates may
be Zurn, Toto, Sloan, Kohler or Chicago. Provide laboratory faucets and accessories
manufactured by Moen. Acceptable alternates are Chicago and T&S. Automatic faucets
should be used for all restroom lavatory faucets. Electrical powered automatic faucets are
preferred. . An exception would faucets in residential facilities. These faucets should be
manual. Consult with the Emory Project Manager for pre-approval regarding any modifications
to these requirements.
2.16
A.
B.
Water Heaters
Electric - Shall be as manufactured by Rheem, Ruud, Bradford White, A.O. Smith or State.
Steam - Steam instantaneous water heaters as manufactured by Aerco or Leslie are preferred
where applicable.
2.17
A.
Water Meters
See Section 23 05 19 - Utility Metering.
2.18
A.
Branch Lines
All branch lines that supply a specific area of the building (such as a toilet room complex or a
group of labs) shall be valved near the mains so that these areas may be isolated from the
systems for repairs without having to shut down the whole building.
Section Page 3 of 5
Section 22 00 00
Plumbing
2.19
A.
Floor Drains
In general floor drains shall be provided for mechanical rooms, laboratories, rest rooms, and in
general locations to accommodate release of water from fire protection systems. (See Section
21 13 00 for fire suppression system drains. Main drains from fire protection systems shall be
run to the outside if possible) The Designers shall discuss floor drain locations with Campus
Services Engineers during the design phase. In general, floor drains in mechanical rooms shall
be minimum 4. Care must be taken to ensure that all general floor drains are installed at the
low points in the flooring. Floor drains in areaways shall include the beehive type fitting.
2.20
A.
2.21
A.
Trap Primers
Trap primers shall be manufactured by PPI or Owner approved equal
2.22
A.
2.23
A.
2.24
Expansion Tanks - All vertical expansion tanks shall be secured to the housekeeping pad by
clips or brackets so as not to weld on the tank itself. All expansion tanks will have a tank purge
valve to facilitate venting the water pressure from the tank for checking the air charge pressure.
We prefer using a full acceptance bladder tank.
2.25
PRVs - Provide pressure gauges upstream and downstream of all PRVs. In all facilities over
40,000 square feet and in all residential and research laboratory facilities, specify a parallel set
of PRVs. All strainers associated with a PRV station will have valved blow-down lines. All
PRVs shall be manufactured with a bronze body.
2.26
Plumbing insulation Refer to Section 23 07 00 HVAC Insulation for standards that apply to
plumbing insulation.
2.27
Grease Traps Grease traps should be located on the exterior of a building for easy servicing.
Lids on smaller units should be lock-and-lift with minimal fasteners. Fasteners should be
stainless steel or brass. All units shall be airtight. Three steps with the county FOG inspector
shall be specified: 1. Contact the inspector during project design for a trap size evaluation; 2.
Request an inspection when the trap arrives on site but prior to install; 3. Request an inspection
after the trap has been installed but prior to becoming operational. It is critical all 3 of these
steps are taken and documented.
Strainers all strainers will have valved blow-down lines.
2.28
2.29
Insulation refer to section 23 0700 for basic insulation requirements that also apply to
plumbing insulation.
Section Page 4 of 5
2.30
A.
Section 22 00 00
Plumbing
Sustainability
Following this guidance will help enable the project to achieve the required Water Efficiency
Prerequisite 1 Water Use Reduction credit and possibly the Water Efficiency Credit 3 Water
Use Reduction under the current LEED rating system.
Section Page 5 of 5
00 00
Section 23 00 00
Mechanical Systems Narrative
Section Page 1 of 4
00 00
Section 23 00 00
Mechanical Systems Narrative
Boilers
Most of the campus is served by 125 psig steam from the Central Steam Plant. This is the preferred
method of heating if possible. Boilers for stand-alone buildings are to provide redundant capability to the
greatest degree possible. In buildings where animals are housed, 100 percent redundant capability for all
animal areas is required.
Chillers
Three separate chiller plants serve the majority of campus. This is the preferred method of cooling. In
these plants, the design intent is for peak load requirements to be met when the largest unit is not in
operation. Chillers for stand-alone buildings are to provide redundant capability to the greatest degree
possible. In buildings where animals are housed, 100 percent redundant capability for all animal areas is
required. Generally water cooled chillers are preferred over air cooled chillers and DX type of systems.
Emory has specific requirements for centrifugal chillers as found in section 23 64 16. Scroll type chillers
are preferred in their applicable size ranges. Currently, the gap between the scroll machines and the
centrifugal machines is filled with screw machines manufactured by Carrier, Trane or York.
Substitutions
The Engineer shall not use the phrase or equal in the specifications, but rather Owner approved equal.
Any substitutions shall be addressed by discussions between the Owner and the Engineer in a case by
case manner.
Document Content
In general, mechanical sections of the construction documents shall contain technical specifications,
equipment schedules, flow diagrams, riser diagrams, plans, large scale mechanical room partial plans,
sections and details. Underground utilities shall include plans upon a topographic background and profile
drawings of the utility routing. Utility routing shall include dimensioned fitting locations and elevations.
HVAC design equipment schedules, HVAC controls input/output summaries, HVAC/BAS control
diagrams, and equipment sequences of control shall be located on the mechanical drawings. The
Engineer shall make sure that all abbreviations used on the design drawings are defined on a legend
page. Mechanical room plans shall clearly show access requirements needed for such things as coil
pulls, access around electrical devices, etc. These partial plans shall be drawn at a scale of not less than
=1-0. The Engineer shall include an air flow schematic diagram that indicates air handling units,
exhaust fans, etc. with air flow rates. This drawing shall show how air is distributed on a floor by floor
basis. Typically Campus Services Engineering Services would like to review available documents at the
schematic design stage, design development stage, 60% stage and 90% stage. A meeting is typically
held during schematic design and/or design development to discuss general methods of heating and
cooling and air distribution.
Design Coordination
The design team shall perform coordination between above ceiling MEP versus the ceiling and soffit
designs based on access for maintenance of valves, valve actuators, filters, motors, control panels and
disconnects. Above ceiling equipment shall be no higher than 3 feet above the ceiling.
Building Considerations
The use of hard type ceiling is discouraged. Lay in ceilings are much preferred to allow access to above
ceiling components. If the use of hard type ceilings is unavoidable, the Engineer shall locate adequately
sized access panels on the drawings. Mechanical rooms shall be laid out so as to have adequate access
for maintenance. Mechanical rooms must have adequate lighting, electrical outlets, a hose faucet, fire
extinguisher and shall have painted walls. The Designers shall provide electrical outlets, a wash down
faucet and lighting near all cooling towers. Care must be taken to provide a walking path for operation
and maintenance of equipment. The Engineer shall design so as to eliminate head knockers and trip
hazards such as drain piping. The Engineer shall locate enough hub drains to eliminate piping running
across the floor. Wall mounted fire extinguishers shall be provided for every mechanical room. In
Revision Date November, 2014
Section Page 2 of 4
00 00
Section 23 00 00
Mechanical Systems Narrative
general floor drains shall be provided for mechanical rooms, laboratories, rest rooms, and in general
locations to accommodate release of water from fire protection systems. The Designers shall discuss
floor drain locations with Campus Services Engineering Services during the design phase. Doors to
mechanical rooms larger than 200 square feet shall have an opening of 6 feet. For buildings 100,000
square feet or larger, penthouse mechanical rooms shall be served by an elevator. Mechanical room
elevator access requirements shall be discussed with Emory Facilities Management and Engineering
Services prior to completion of the building layout design. The elevator cab is to be large enough to
facilitate the removal of the largest part of the equipment in the mechanical room. For penthouse
mechanical rooms that are not served by an elevator, a monorail and trolley are to be provided to
facilitate the removal of equipment through a floor hatch or opening. For equipment located on a roof, the
Architect/Engineer shall consider the use of a manual hoist to be able to remove the heaviest piece of
maintenance equipment, ie motor or compressor, not the entire chiller. In cases where the Engineer must
place a condensate return unit in a pit for proper drainage, the pit must be sized with a minimum of one
foot clearance around the unit to allow maintenance to occur without removing the entire unit. Sufficient
space to service all equipment in the room is required including removing the cooling and heating coils.
Mechanical rooms and spaces shall be designed to be waterproof by the use of curbs,
drains and waterproofing materials as required. Water shall flow to and out of the drains
and not pond on the floor. Flood testing shall be required to demonstrate effectiveness of
waterproofing. All air handling units on upper floors are to have secondary containment
through the use of a secondary condensate pan, dikes or a similar method. The area
inside of the dikes is to be waterproofed and flood tested. The drain in the diked area is
to be positioned so that the water flows to it. Drain covers with the center at least 2
inches higher than the edges are required to reduce the possibility that these will be
completely obstructed by debris. Where secondary drain pans are used, these are to be
designed so that normal foot traffic from maintenance personnel will not damage the pan.
Lab Considerations
Occupied air changes for Labs should be a minimum of eight. Six air changes in the unoccupied mode is
acceptable.
Fume hoods shall be VAV where applicable and have an occupied design of 100 lfpm at 18inches sash
height and an unoccupied set back of 60 lfpm at any sash height.
ASHRAE 15
The Engineer shall be responsible for bringing any mechanical room (new or existing) up to the ASHRAE
15 Code, Latest Edition (Safety Code for Mechanical Refrigeration) if appropriate.
Air Emissions
Emory University is located in a non-attainment area for the pollutants nitrous oxides and volatile organic
compounds. Emory University is considered a major source of NOx pollutants. Currently if there is an
additional amount of air pollution due to the burning of fossil fuels, Emory University has to file a permit
amendment with the State of Georgia. The project budget must include the cost of this work, which also
may require the services of an Environmental Consultant.
Clean Steam Generators
The use of clean steam generators should be approached cautiously. Many mistakes have been made
over the last 20 years. Consult with Emory University Engineering Services. Verify the actual need for a
clean steam generator.
Restricted Use HVAC Systems
Water source heat pumps should only be used in very particular circumstances and are generally
prohibited. The use of City Multi refrigerant systems should only be used in very particular circumstances
Section Page 3 of 4
00 00
Section 23 00 00
Mechanical Systems Narrative
and are generally prohibited. Consult with Emory University Engineering Service prior to schematic
design.
Installation Tests
Test the following systems and have the Contractor create certificates documenting the test.
A.
Soil, waste, vent and rainwater systems
B.
Domestic cold and hot water
C.
Fire protection systems Generally test these systems with a hydrostatic test. For systems in
certain occupied buildings such as data centers or libraries, do a preliminary test with air. Do
not exceed 20 psig for the preliminary air pressure test.
D.
Natural gas systems
E.
Compressed air systems
F.
Steam and condensate systems
G.
Heating hot water systems
H.
Chilled water systems
I.
Air tests shall only be used for preliminary tests on fire protection piping in certain occupied
buildings, natural gas systems and compressed air systems. For other systems Contractors
must do a hydrostatic test. Any exceptions must be approved by the Engineer and the Owner.
Equipment Submittal / Shop Drawing Review Process
Engineering Services (ES) and Emorys third party commissioning consultant (CxA) shall be copied on
construction phase equipment and shop drawing submittals when the submittals are sent to the design
team for review. ES and CxA comments will be routed to the design team. The design team will prepare
the final list of comments to distribute back to the construction team. The design team will inform ES and
the CxA as to how their respective comments were incorporated.
Project specifications shall require all deviations be noted on a submittal transmittal sheet or cover letter.
Project specifications shall also require that a line-by-line specification compliance be provided with each
submittal applicable to the equipment or system being submitted. Project specifications shall state that
failure of the subcontractor or its supplying manufacturer to state deviations or provide line-by-line
specification compliance will be returned revise and resubmit without review by the design team, ES or
the CxA.
Suppliers of major equipment such as chillers and boilers shall also provide a letter stating that they have
reviewed and understand the design control intent of the equipment and certify that their equipment will
function according to the design intent, and if not, request deviation to the intended control.
Section Page 4 of 4
Section 23 05 00
Basic Materials & Methods
General
This section is intended to include basic general information on piping and pipe fittings,
valves, gages, instrumentation, supports, anchors, motors, vibration isolation, sound
isolation and basic acceptable construction methods.
1.02
Piping Guide
The Emory University Piping Guide is a listing of the preferred pipe material for most
common applications. Obtain specific approval from Engineering Services prior to
deviating from the Emory University Piping Guide or specifying any piping, fittings, and
valves not listed in the Emory University Piping Guide. Underground piping is a special
service that is addressed in Section 33 60 00. In general do not use 3-1/2 and 5 piping.
Do not use 1-1/4 steel piping; copper is OK. Pro press fittings are allowed for copper
piping pending specific building review. In no case, shall Pro Press fittings be used
underground.
Service
Steam
Condensate
Chilled Water
Chilled Water
Htg. Hot Wtr.
Htg. Hot Wtr.
Condenser Wtr.
Condenser Wtr.
Condenser Wtr
Comp. Air
Comp. Air
Domestic Wtr.
Fuel Oil
Natural Gas
1.03
1.04
Class
150
150C
125WA
100CU
125WA
100CU
125WA
100CU
PVC
125WA
100CU
100CU
150F
150G
Combined Limitations
155 psig, 368 deg. F
155 psig, 368 deg. F
125 psig, 200 deg. F
(for 2and smaller line size, within buildings)
125 psig, 200 deg. F
(for 2and smaller line size)
125 psig, 200 deg. F
(for 2and smaller line size)
see 23 65 13; 1.5
175 psig, l50 deg. F
(for 2and smaller line size)
50 psig, 100 deg. F
240 psig, 200 deg. F
Material
Copper
2-1/2 & up
A53, Grade B
Section Page 1 of 5
1.05
Section 23 05 00
Basic Materials & Methods
Material [ASTM]
Pipe
2 & under
A53, Grade B
Schedule 40
ERW is acceptable.
Pipe
2-1/2 & up
A53, Grade B
Fittings
2 & under
Fittings
2-1/2 & up
Bolts
Suit Flange
Al93, Grade B7
Heat treated
Nuts
Suit Bolt
Al94, Grade 2H
Heat treated
Gaskets
all 1/16
Flexitallic
Valves
2 & under
Valves
2-1/2 & up
1.06
1.07
Material (ASTM]
A53
A53
1.08
1.09
Valves
A. Make sure all valves have steel or malleable iron handwheels. Pot metal handwheels are
not acceptable. In general valves should have rising stems.
B. Acceptable valve manufacturers: Stockham, Nibco, Milwaukee, Crane, Hammond and
Powell.
C. Steam valves Note that the Emory steam system is a 150 pound class system. We do
not want cast iron valves. The steam valves for 2-1/2 and above shall be cast steel.
1.10
1.11
Section Page 2 of 5
A.
Section 23 05 00
Basic Materials & Methods
1.12
1.13
Concrete Pads
Provide reinforced concrete housekeeping pads for each piece of mechanical equipment.
Barring any specific structural requirement or condensate drainage requirement, the pads
shall be a minimum of 3 tall with chamfered edges. When a condensate tank is
recessed into the floor to improve condensate drainage, there shall be 1 clearance
between tank and side of excavation all around the tank.
1.14
1.15
1.16
1.17
Starters
Section Page 3 of 5
Section 23 05 00
Basic Materials & Methods
Access
1.19
Branch Lines
All branch lines which supply a specific area of the building (such as a floor of fan coil
units, etc.) shall be valved near the mains so that these areas may be isolated from the
systems for repairs without having to shut down the whole building.
1.20
Equipment Identification
A.
Mechanical equipment requiring preventive maintenance is to be permanently identified.
This includes but is not limited to the following: air handling units, exhaust fans, VAV and
PIU terminal units, pumps, main sprinkler valves, chillers, boilers, hot water heaters, air
compressor, vacuum systems, heat exchangers, underground storage tanks, backflow
preventers and pressure reducing valves.
B.
For equipment located above the ceiling, in addition to a label on the device, labels are to
be permanently affixed to the ceiling grid as near to the item as possible using glue.
Where hard ceilings are used, the label is to be affixed to the frame of the access panel
for the unit. Labels are to be black core white or beige Bakelite. The lettering is to be
3/8 high. The minimum label size is wide by 2 long. Variable air volume boxes, and
powered induction units shall be identified as follows (VAV or PIU air handling unit
number, floor number and unit number. (Example: VAV-3-5-7). The thermostat that
controls each terminal unit or fan coil unit shall be identified with an identical but
appropriately sized label. Labels for other types of equipment are to identify the item and
designation.
C.
The Mechanical Engineer for the project will prepare an equipment list of all equipment in
the building to be included in the preventive maintenance program for the Preventive
Maintenance Coordinator. Each item is to be identified by equipment type, designation
and location. Exhaust fans shall have tags affixed that note the rooms served. Room
numbers must match the as-built conditions. Air handling units shall have tags affixed
that note the areas or floors of the building served.
D.
All mechanical equipment, starters, etc. shall be identified.
1.21
1.22
Piping Identification
Provide piping identification system in accordance with ANSI A13.1, latest edition,
Scheme for the Identification of Piping Systems. In general, provide piping identification
and flow direction arrows at the ends of piping runs, on each side where piping
All mechanical equipment and control devices must be accessible for maintenance or
service. Sprinkler lines, smoke detectors, light fixtures, cable trays or any other devices
cannot block access. All mechanical equipment must be located so that it can be
accessed using standard ladders and standard personnel lifts. Access panels if used
should b 24 x24.
Section Page 4 of 5
Section 23 05 00
Basic Materials & Methods
penetrates walls and floors, at approximately 30 feet on center in long straight runs and
after each fitting as appropriate in mechanical rooms.
1.23
Framed Diagrams
The Contractor shall install DDC control diagrams in a frame of Plexiglas and aluminum
in a prominent location in the main mechanical room.
1.24
1.25
Mechanical Rooms
Mechanical rooms are to be designed to be accessible as well as to protect areas below
or adjacent to the mechanical room from water damage in the event of a frozen coil or
leak. In addition to condensate pans, all air handling units are to have secondary
containment through the use of a secondary condensate pan, dikes or a similar method.
The area inside of the dikes is to be waterproofed and flood tested. Refer to Section 23
00 00 Mechanical Systems Narrative for additional information not covered in this
paragraph. The drain in the diked area is to be positioned so that the water flows to it.
Drain covers with the center at least 2 inches higher than the edges are required to
reduce the possibility that these will be completely obstructed by debris. Where
secondary drain pans are used, these are to be designed so that normal foot traffic from
maintenance personnel will not damage the pan. Sufficient space to service all
equipment in the room is required including removing the cooling and heating coils.
1.26
Thermometers
A.
Thermometers on general hydronic systems shall be Weiss Model DVU or Trerice Model
SX9.
B.
1.27
Thermometers located at chillers shall be Tel-Tru digital Model D5A with well probe
adaptor.
Motors
As a result of poor performance observed on campus, do not use WEG brand motors and
do not allow these motors to be used on equipment skids. Motors shall be rated for
inverter duty when used in a variable speed application. Motors over 20 horsepower
used in variable speed applications shall have an Aegis grounding ring installed in the
factory or the field.
Section Page 5 of 5
Section 23 05 14
Variable Frequency Motor Controls
Section Page 1 of 1
Section 23 05 19
Utility Metering
Steam Metering
A.
All steam meters will be specified and sized by the Emory Utility Engineer. All steam meters
will be installed per manufacturer recommendations. Mechanical contractors need to review
installation plans with the Emory Utility Engineer.
B.
Yokogawa Vortex meters with the remote converter, an indicator and Brain communication,
will be used. Sizing will be based on design flow rates for building and not by design steam
pipe sizing. Straight pipe lengths upstream and downstream of flow meter must comply with
manufacturer recommendations. The remote converter will be mounted no higher than 5
feet above the floor.
1.02
1.03
1.04
1.05
Electric Metering
See Section 262000 1.2.1.1 for electric metering at switchboards and Section 261000 1.7.1
for electric metering at transformers.
1.06
Section Page 1 of 1
Section 23 05 93
Testing, Adjusting & Balancing for HVAC
Installation Tests
See the Mechanical Narrative and Information Section for Installation Tests
1.02
1.03
Section Page 1 of 1
Section 23 07 00
HVAC Insulation
Asbestos
Asbestos is never to be used for any type of insulation. All products must be certified asbestosfree.
1.02
1.03
1.04
Exterior Insulation
Fiberglass shall not be used for exterior insulation. Calcium silicate, foam glass or mineral wool
shall be used for exterior applications. The insulation shall be covered with aluminum lagging of
0.020 thickness. Lagging shall be held in place with aluminum straps, stainless steel wire or
stainless steel screws. Aluminum lagging fittings shall be used. Seal all lagging laps with Foster
95-44 or Childers CP-76 sealant to prevent water entry. The texture of the lagging shall be stucco
embossed for both straight runs and fittings. Stucco embossed fittings can be procured from
Shur-Fit Products, Shieldmetal, Chesnutt Insulation Associates or Owner approved equal.
1.05
1.06
Steam Manholes
Piping in steam manholes and tunnels shall be insulated with calcium silicate with lagging as
shown in Item 5 above in 0.020 thickness.
1.07
Insulation Fittings
In general, insulation for fittings shall be pre-formed and/or full thickness of the same material as
the insulation on the piping. Sectional pieces of standard insulation may be used on the larger
size fittings. The use of fiberglass duct wrap at fittings is not allowed. PVC fittings covers shall
not be used. All below ambient pipe fittings, valves, flanges and elbows shall be coated with
Foster 30-65 or Childers CP-34 vapor barrier coating and Foster Mast a Fab or Childers Chil
Glass No. 10 reinforcing mesh fabric.
1.08
Test Ports
Insulation for test ports and areas that must be accessed for maintenance or testing should be
insulated using techniques that allow for easy removal and reinstallation without re-insulating.
Section Page 1 of 2
Section 23 07 00
HVAC Insulation
1.09
1.10
Section Page 2 of 2
Section 23 08 00
Commissioning of HVAC Systems
Section Page 1 of 1
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 1 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Specifically, sequences shall clearly describe all required functions, define and quantify normal operating
setpoints and decision criteria, identify any special alarms to be reported, and shall define all operating
variables, including high/low limits for setpoints and resets, as appropriate. Project Input/Output
summaries must be carefully coordinated with the sequences of operation. The following are specific
sequences of operation to be incorporated, as appropriate, within each project:
Air Handling Units
Exhaust Systems
Section Page 2 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 3 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Quality Assurance
Quality assurance for automatic controls systems shall be accomplished through the installing
contractors normal start-up, calibration, and quality control procedures and confirmed during the
commissioning process (see also Section 011913 General Commissioning Requirements) consisting of
submittal review of system engineering work, documented pre-functional testing and initial checkout,
documented functional performance testing, operator training and O&M documentation.
Submittals
Specifications shall require a complete, coordinated submittal package including the following items. At
the Contractors option, control valves and control dampers may be submitted in a separate submittal in
advance of the other items to maintain project schedule.
Control valve data: including manufacturers product data and schedule indicating body type,
size, flow rate, pressure drop, Cv, actuators and motors, end switches, normal (failure) position,
and maximum differential pressure at which valve is capable of full closure for each valve.
Control damper data: including manufacturers product data and schedule indicating damper
type, size, flow rate, pressure drop, leakage rate, actuators and motors, end switches and normal
(failure) position for each damper.
System architecture:
provide a drawing of the proposed system architecture showing
configuration and locations for DDC controllers, terminal unit controllers, connection to the Emory
network, local DDC operator station, if required, power and control wiring for each device, and
hardware and wiring for connections to networks external to the building. Provide floor plans
locating equipment coordinated with the work of other trades.
DDC system data: including proposed system manufacturer's data sheets on DDC controllers,
sensors, meters, relays, actuators, motors, terminal unit controllers, protection devices, and other
devices specified herein. Include data on system software packages to be and illustrations of
proposed graphics displays.
Diagrams: separate field wiring diagrams for each system, including any required pneumatic
piping, motor starting and interlock wiring, ladder diagrams, control wiring, interior electrical
circuits of control instruments with terminal and control device designations, actuators and
motors, colors of wires, locations of instruments and remote elements, interfaces with
communications equipment provided with equipment specified in other Sections, and normal
position of relays. Each diagram shall have terminals labeled as they will be marked on the
installed equipment. Each diagram shall delineate between existing piping, wiring or equipment,
and new piping, wiring, and equipment, as appropriate.
The control submittal is to include schematic control drawings showing the configuration of the
unit, the location of all sensors, monitoring inputs, and controlled devices and any equipment that
the control system monitors, enables or controls, even if the equipment is primarily controlled by
packaged or integral controls.
Provide a full points list with at least the following included for each point:
o Controlled system
o Point abbreviation/acronym
o Point description
o Engineering unit to be displayed with the point
o Control point or set-point (Yes / No)
o Monitoring point (Yes / No)
o Calculated point (Yes / No)
Proposed Graphics: contractor proposed graphic display examples are to be submitted for Emory
review and approval. Submittal should include all proposed display examples as required by the
project documents and specifications. Note also, and as required by Section 019113, the
commissioning acceptance tests shall be conducted via the final, approved graphics. Each
graphic page shall include a link to the Sequence of Operation for the equipment on the graphic.
Sequences of operation: complete detailed sequences of operation, including: a narrative of the
system operation and interactions and interlocks with other systems; notations indicating whether
interlock or interaction is accomplished through software or hard-wired connections; detailed
delineation of control between packaged controls and the DDC system; and sequences of
operation for packaged controlled equipment that interfaces with the DDC system describing what
points the DDC system monitors only and what points are control points and are adjustable.
The Contractor shall submit a list of all network variables. The submittal shall include a detailed
points list for the BACnet data being passed to/from controllers and to/from the web-server with
the point name, purpose, type, object ID, Device ID, Object Name, and I/O Type. Provide
Section Page 4 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Protocol Implementation Conformance Statement (PICS) for each type of controller in system,
including the unitary controllers.
BACnet Naming and Addressing: The BAS Contractor shall submit the BACnet naming and
addressing for the system. Emory has an existing BACnet Device Object Naming Convention
(DONCP) and an existing BACnet Device Numbering convention that is BAS specific and needs
to be updated on a project-by-project basis. The BAS contractor shall consult with Engineering
Services on a project-by-project basis during the submittal process for the most up-to-date status
of the DONCP and BACnet device numbering convention in place.
o
Device Object Naming Convention: The BAS contractor shall submit a BACnet Device
Object Naming Convention Plan (DONCP) to the owner and consulting engineer during
the submittal process. The plan must be approved by the owner and consulting engineer
prior to implementation. It is the responsibility of the BAS contractor to coordinate the
DONCP with the owner and consulting engineer. The DONCP shall be designed to
eliminate any confusion between individual points in a facility/campus wide BAS system.
It will also be designed to allow for future expansion and consistency.
Object Name Property Text: The BAS contractor shall submit the Object Name property.
Assign Object Name properties with descriptive, plain-English names descriptive of the
application.
BACnet Device Numbering Convention: The BAS Contractor shall submit the BACnet MAC Address,
network numbering, device object identifier property number. Each device on the BACnet internetwork
(including other manufacturers devices) shall have a unique device number.
Part 2 Product Requirements
Preferred Supplier
The acceptable manufacturers of DDC systems are Siemens Corporation and Automated Logic
Corporation (ALC). The controls for a project will be provided by controls vendor acting as a
subcontractor to the mechanical contractor. During the bidding process, the price for the controls
installation will be the same to all mechanical contractors.
Networking & Communications
Emory maintains a campus wide intranet and prefers the networking of the building control systems be
accomplished using this intranet. Emory will typically provide a TCP/IP based Ethernet connection for the
contractors use for each field panel in making this network connection. Coordinate this connection
requirement and its location(s) with the Emory University Library and Information Technology Services
(LITS) department.
Contractor will be responsible for all equipment, cables, installation, and
programming to accomplish the required interface to the Emory intranet.
If a campus intranet connection is NOT available, the contractor will be responsible for providing
communication wiring to the nearest point of connection to the DDC control network. Typically this is
done via a CAT 5e wire or a fiber optic cable. Wiring is to be installed in underground PVC conduit with
the other support utilities and should include sufficient capacity to allow the installation of additional
communication cable in the future. Network communications wiring installation is to be terminated in a
panel, a mechanical room, or a building mechanic's office if there is one. Dial-up or other telephone
communication links will NOT be allowed.
The DDC system shall be a peer-to-peer networked, stand-alone, distributed control system using the
ANSI/ASHRAE Standard 135-2004 BACnet communication protocols. For each BACnet device, the
device supplier must provide a PICS document showing the installed device's compliance level. Control
products, communication media, connectors, repeaters, hubs, and routers shall comprise a BACnet
internetwork. Controller and operator interface communication shall conform to ANSI/ASHRAE Standard
135-2004, BACnet (see Attachment 1 for network-BACnet definitions).
Revision Date November, 2014
Section Page 5 of 30
Section 23 09 00
Instrumentation and Control for HVAC
DDC network installations shall include a watchdog device, either hardware or software, monitored by
the central operator station, periodically updated to indicate the status of the communications link from
each building. This watchdog shall be in addition to any DDC system communications monitoring and
reporting functions.
Controllers
DDC controllers are to be field programmable, microprocessor-based devices incorporating direct digital
control and energy management functions. Each DDC controller shall perform its assigned control,
monitoring and energy management functions as a stand-alone unit. Each DDC controller, including
associated input/output modules, is to be configured and installed with a minimum of 25% spare input and
output points of each type installed, but no less than one point of each type.
[Consult with Engineering Services on a project-by-project basis regarding the requirements of this
paragraph] Provide manual hand-off-automatic (HOA) override switches and means for manually
adjusting the analog output of outputs connected to each DDC controller other than terminal unit
controllers and application specific controllers for minor equipment. HOA switches and manual
adjustments rated for and compatible with the connected controlled device and shall be capable of
generating the full range of control output when in the Hand mode. HOA switches shall be alarmed to the
front end, and adjustable overrides are to be either of a key operated design with switches keyed alike
and utilizing the same keying system used for other outputs, or otherwise protected from unauthorized
access by a key locked enclosure.
DDC controllers shall be provided for each major air handling or mechanical system, as identified in the
project I/O summaries. The DDC controller shall be configured to contain all points necessary for the
proper operation of that system to be connected to the panel. If multiple panels are required to
accommodate the required input/output functions or the specified sequence of operations, the point
distribution shall be arranged to keep all points necessary for a specific control loop in the panel
executing that control loop or function. Each DDC controller shall perform its full control and energy
management functions, regardless of condition of communications link with other system components.
These stand-alone capabilities shall be implemented and shall include, but not be limited to, closed loop
control functions (P, PI, PID, incremental, floating) and energy management functions.
DDC controllers shall be arranged and installed to allow controllers to share global data. This global data
shall include, but not be limited to: time-of-day, outside air temperature and humidity, and electrical meter
and demand information. If DDC controllers are not configured in a communication network to share this
data, then each DDC controller shall be provided with sensor inputs to implement sequences specified
herein when operating in a stand-alone mode. The inclusion of a DDC controller schematic showing the
arrangement and locations of the DDC controllers shall be required..
BACnet Requirements for DDC Controllers
DDC Controllers must either be BACnet controllers and conform to ANSI/ASHRAE 135-2004 as installed
or be capable of being converted to a BACnet controller that conforms with ANSI/ASHRAE 135-2004 by a
software/firmware upgrade.
Uninterruptible Power Supply (UPS)
Provide a self-contained UPS designed for installation and operation at each DDC controller other than
terminal unit controllers and application specific controllers for minor equipment, sized to provide a
minimum of 5 minutes of full operation of the controller and input/output modules connected to that
controller. For non-critical areas control equipment connected to the UPS should not be affected in any
manner by a power outage of duration less than the rated capacity of the UPS. For critical areas UPS
shall not have any interruption of power including switchover from primary power to UPS power. UPS
shall be complete with necessary power supplies, transformers, batteries, and accessories and shall
include visual indication of normal power operation, UPS operation, abnormal operation and visual and
audible indication of low battery power. The BAS system shall monitor each UPS in order to indicate
whether the UPS is on primary power or UPS battery power. Provide outlets with twist-lock type plugs for
connection of the UPS to primary power.
Terminal Unit Controllers
An individual terminal unit controller shall be provided for each terminal unit and shall interface to the
DDC system. Each terminal unit controller is to be accessible from the central or local operator station
and remote operator's terminals for purposes of control parameter and setpoint adjustment and
Revision Date November, 2014
Section Page 6 of 30
Section 23 09 00
Instrumentation and Control for HVAC
monitoring. An operator's terminal connected to any DDC controller on the network should have access
to the terminal unit controllers.
Terminal unit controllers shall also be accessible through a
communications port at the space sensor.
DDC terminal unit actuators are to provide complete modulating control for the full range of damper
movement. Actuators shall be de-energized when the damper has reached the operator or system
determined position. Actuators shall be removable for servicing without removing the terminal unit. If
required by the failure mode or for smoke control or pressurization control, actuators shall be nonstall
spring return type. Terminal units for all Research animal housing and procedure rooms shall be Normally
closed unless approved by Emory Engineering.
Transient surge suppressors
Suppressors shall be solid state, operate bi-directionally, and have a turn-on and turn-off time of less than
one nanosecond, and shall provide the protection specified herein, either as an internal part of the DDC
controllers or as a separate component. Suppressor manufacturer shall have available certified test data
confirming a fail short failure mode.
Communication or Signal Conductor Transient Suppressors shall require the following:
Field Sensors
Specify sensors for appropriate ranges and accuracy:
Temperature: chilled water, hot water, outside air and duct temperature sensors are to be RTDs
or thermistor type specific make/model are identified below. Chilled water sensors used for BTU
calculations or control decisions as indicated on the I/O summaries shall have an accuracy of
0.25F at 32F and should be matched pairs at the calibration point.
o Air temperature sensing shall be provided by duct insertion type sensors for supply duct
temperatures downstream of fans or return duct temperatures in ducts of less than 9
square feet and by extended element averaging type for plenums and all ducts in excess
of 9 square feet area and coil entering or leaving temperatures.
o Provide a discharge temperature sensor downstream of every coil or HVAC equipment
subject to DDC control (AHUs, VAVs, PIUs and FCUs).
o Provide thermowells and insertion type sensors for water temperature sensing.
All temperature sensors provided shall be capable of field calibration and shall be
demonstrated to the project commissioning agent that the senor is calibrated within
allowable limits.
Space temperature sensors: Provide for occupant adjustment of the operating setpoint.. The
setpoint adjustment should be capable of being limited or locked out, overridden, or limited as to
time or temperature in software from the central or local operator's terminal. Normal limits are 6878 F. Temperature setpoints for heating and cooling and night setback shall be independent of
each other and shall provide a zero energy band between heating and cooling modes. Precision
thermistors may be used in space temperature sensing applications. Sensor accuracy over the
application range shall be minimum 0.5F between the range of 32 to 150F including sensor
error and A/D conversion resolution error. Thermistors are to be pre-aged and inherently stable.
Bead thermistors shall not be used. Space temperature sensors shall include a communications
port for local connection of a portable test/terminal device for communications/programming
access to the associated DDC controller. Space temperature sensors shall have blank covers
and accessible means of setpoint adjustment.
Sensors shall be an approved model
manufactured by Vaisala, or a sensor that can be field calibrated.
Humidity sensors: industrial quality, bulk polymer type, with replaceable element and an
accuracy of 2% RH in the range of 20-90% when used for control applications. The sensors
should be capable of calibration. Saturation shall not alter calibration. Sensors for space
humidity measurement may have an accuracy of 5% RH in the range of 20-90% unless the
application requires higher precision. Space humidity sensors should have the same appearance
as space temperature sensors. Sensors shall be an approved model manufactured by Vaisala,
Section Page 7 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Pressure sensors:
Designed for media sensed and for static or differential pressure
measurement, as appropriate. The sensor should be capable of withstanding an overrange
pressure limit of 300% of the normally expected value. Sensor should incorporate a transducer
with non-interacting zero and span adjustments. The span shall be continuously adjustable from
0 to 125% of the expected full pressure or full flow differential pressure. The zero shall be
continuously adjustable on outputs. Acceptable manufacturer for static and differential pressure
measurement is Setra Sensing Solutions. Contractor shall coordinate with mechanical contractor
water differential meters to include high and low line isolation valves and parallel pressure gage
piped to read high and low pressures independently.
Water flow meters: turbine, insertion type, with isolation valve and packing gland for removal
under full line pressure. Wetted parts shall be corrosion-resistant. Range shall be selected to
match the application, with sufficient flow velocity to assure accurate measurement at both the
low and high expected values. Accuracy should be 3% at any operating point within this range.
Current sensing relays: current sensing relays shall provide a normally open contact rated at a
minimum of 50V peak and 0.5 amperes or 25 VA with an adjustable setpoint. There shall be a
single opening for passage of current carrying conductors. Relays shall be sized for operation at
50% rated current based on the connected load. Voltage isolation shall be a minimum of 600V.
Current sensing relays shall be split core type wherever possible.
Air Quality: [Verify with Engineering Services the use of Air Quality sensors] For spaces with
variable people loads or high outside air requirements, include either an interface to occupancy
sensors or air quality sensors to vary outside air requirements and/or terminal unit air flow
minimums.CO 2 sensors shall be dual channel infrared type, with 10 micron filter to prevent
particulate contamination of sensing element. Sensor shall have an accuracy of 5% of reading
up to 10000 ppm, with a repeatability of 20 ppm and a maximum drift of 10 ppm per year, and
a recommended calibration interval of 5 years. Sensor shall have a response time of no more
than 2 minutes to a 90% of full scale change. Sensor and transmitter shall provide a 4-20 mA
analog output proportional to gas concentration and a relay output indicating sensor setpoint has
been exceeded. Manufacturer: Engelhard Corporation, Veris, or Tel-Aire
Safety/Limit devices
o Low Temperature Limit provide hard wired safety function interlock to equipment
starter. Provide additional dry contact for monitoring by the DDC system. Low
temperature detection shall be present in every square foot of the coil or duct it is
protecting.
o High Temperature Limits provide hard wired safety function interlock to equipment
starter. Provide additional dry contact for monitoring by the DDC system.
o Low and High Static pressure Limit provide hard wired safety function interlock to
equipment starter for each side of fans over 2,000 CFM. Provide additional dry contact
for monitoring by the DDC system.
o High Humidity Limit provide hard wired safety function interlock to humidifier control
valve. Provide additional dry contact for monitoring by the DDC system.
o End Switch provide hard wired safety function interlock to equipment starter. End
Switch shall be secured to shaft of equipment being monitored to provide actual status of
equipment. Integral end switches to actuators shall not be permitted. Provide additional
dry contact for monitoring by the DDC system.
o Flow Switch provide hard wired safety function interlock to equipment starter. Provide
additional dry contact for monitoring by the DDC system. Use of non magnetic flow
switches is preferred.
Control Devices
Control valves: brass-trimmed; 2" and smaller, bronze bodies with screwed connections; over 2",
Section Page 8 of 30
Section 23 09 00
Instrumentation and Control for HVAC
cast iron bodies with flanged connections. Steam valves operating at pressure differentials
greater than 25 psi and water valves operating at pressure differentials greater than 40 psi shall
have stainless steel trim and replaceable seat ring.
o Valves shall be capable of full closure against 150% of design pump head, or a 50 psig
(gauge) differential pressure, whichever is greater.
o Valves for water shall have equal percentage flow characteristics. Modulating control
valves shall be sized for a pressure drop of 3 to 5 psi, unless indicated otherwise on the
Drawings. Two-position valves shall be line size.
o Ball valves used for modulating service shall have a replaceable flow characterizing disk
to provide the required flow characteristics.
o Steam valves shall have linear characteristics.
o At the Contractor's option, control valves may be butterfly type for chilled and condenser
water service in piping 2" and larger. Modulating butterfly valves shall be sized for
required flow at 60 degrees opening with a pressure drop of 2-4 psi. Two-position control
valves shall be line size. Valves 8" and larger shall be provided with either worm-gear
electric actuators or high pressure pneumatic actuators sized for 150% of the torque
required to unseat the valve from the closed position. Valves shall be rated for bubble
tight closure at a differential pressure equal to the valve body rating.
Control dampers: single-blade up to 8" high, multiblade over 8" high; minimum 80% free area
based on damper frame outside dimensions.
o
o
o
o
o
o
o
o
o
o
o
o
o
o
Actuators:
o Include the requirement for spring return if a definite position is required for failure mode
or a smoke control system.
o Siemens systems shall install Siemens brand actuators or actuators manufactured by
and carry the name brand Belimo.
o ALC systems shall install actuators manufactured by and carry the name brand Belimo.
o DDC terminal unit actuators: nonstall spring return type, providing complete modulating
control for the full range of damper movement. Actuators shall be de-energized when the
Section Page 9 of 30
Section 23 09 00
Instrumentation and Control for HVAC
damper has reached the operator or system determined position. Actuators shall be
supplied to the terminal unit manufacturer for factory mounting and calibration. Actuators
shall be removable for servicing without removing the terminal unit. Actuators shall be
provided with transformers for proper operation from the terminal unit controller power
source.
Other actuators (if pneumatic devices are required): diaphragm or piston type; sized to
provide required starting torque and to control the driven apparatus smoothly. Actuators
shall have spring return. Modulating valve and damper actuators in control sequences
involving 2 or more devices or stages controlled from a single output shall be provided
with a positive positioning device. Where actuators are operating at 75% or more of their
rated capacity, provide a positive positioning device. Positioners shall be capable of
applying maximum actuator effort to maintain the operator position called for by its
related controller.
Solenoid Valves:
o Acceptable manufacturer and model of solenoid valves is ASCO RedHat.
Control Transformers:
o Control transformers shall be Class 2 transformers and have manual reset over-current
protection. Acceptable manufacturer is Kele.
Control Relays:
o Control relays whenever possible shall be manufactured by Functional Devices.
Acceptable models are the Relay In a Box (RIB) series.
At least six columns of data can be viewed on the screen at once and can be graphed using a
graphing program integral to the control system, with at least six parameters graphed against
time on the same graph. The columnar format shall have time down the left column with columns
of data to the right (one column for each parameter).
Without any special or difficult conversions, this data shall be able to be storable as an ASCII
delimited file in the same columnar format for use in graphing with normal commercial
spreadsheet software.
The BAS contractor shall coordinate the schedule of trend data collection over the network with
Engineering Services on a project-by-project basis. The trend log data is automatically
downloaded at the time of day provided by Engineering Services and shall be at an interval of no
more than once per day onto the hard drive when space in the central computer or field cabinets
becomes full, so that no data is lost. This is done without the user having to calculate the size of
the trends and download frequency.
Any limitations in the trending as to speed of sampling versus number of sampled points in a
given trend, and the effect on actual sampling rate and simultaneousness of the sampling across
parameters shall be clearly explained in writing. Programming and trending setup examples of all
representative situations shall be provided.
The trends shall be capable of being set up to start sampling all trended points in a given trend or
group of trends at the same exact time.
Specifications for standard trends shall be able to be set up by the user and be saved by a name
and initiated by only recalling the name. The BAS contractor shall assist the operators in setting
up at least six standard trends during training.
Ideal, but not required, shall be the capability to graph with the control system software, one or
more points against another, rather than just against time.
Trending features shall be capable of easily monitoring the parameter value both on a time basis
and on a change-of-state basis.
A key for the names and definitions of all point abbreviations (both physical and virtual) shall be
provided.
Analog points shall be trended in intervals. Analog trends shall not be set up for less than five
minute intervals with a maximum of 300 samples per point to be stored at the panel, Network
Section Page 10 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Mount space condition sensors at the following heights, aligned vertically or horizontally with
adjacent light switches or, if no light switch, with receptacles:
Adjustable
Concealed adjustment
Concealed setpoint adjustment type space temperature sensors that have occupant
override push buttons shall be classified as adjustable type devices. Coordinate final
location with the furniture layout and the architectural layout.
Revision Date November, 2014
Section Page 11 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Align vertically or horizontally with adjacent light switches or, if no light switch, with receptacles.
Coordinate final location with the furniture layout and the architectural layout.
Remote element type: mount on a vibration free surface 5' above the floor, unless specified
herein to be mounted on a control panel. Where installed at a coil or in a duct, provide 1 linear
foot of element to sense the temperature of each square foot of the coil face. Install in a
serpentine arrangement across the entire face of the coil.
Averaging and low limit safety type elements: install in a horizontal sine curve manner to sense
temperatures across the entire face of the coil, and support independently from the coil by
stainless steel bands or multibulb holders. Provide 1 linear foot of element for each square foot
of coil area. Provide 0.5" metallic raceway or 0.375" hard copper rails for support of elements,
both top and bottom, for plenum or duct width greater than 36".
Under window fan-coil unit thermostats: mount so that adjusting knob is accessible through
access panel.
Provide insulated bases for thermostats and temperature sensors installed on exterior walls or
walls to unconditioned spaces.
Provide sealed bases were wall mounted devices mount to walls that produce negative pressure
relationships such as a lab space with a negative offset requirement.
Current sensing relays: fan and pump status shall be sensed by a current sensing relay wired on the load
side of each fan and pump. For constant speed fans and pumps, the current sensing relay trip setpoint
shall be set at 10% below the motor's normal operating speed and corresponding current draw. For
variable speed fans and pumps, the current sensing relay trip setpoint shall be set 5% below the lowest
operating speed and corresponding current draw, as determined by the commissioning process (typically
20%).
Static Pressure Sensors: Install sensors in the associated air handling unit control panel and use
extended sensing lines. Sensor may be installed in field if location is approved prior to installation and is
determined to be easily accessible. Provide taps for calibration purposes (barbed tee adapter at a
minimum at each sensor).
Hydronic Pressure Sensors: Coordinate with mechanical contractor to install sensors adjacent to
measurement points, with sensing lines extended to accessible locations. Mechanical contractor to
provide test points equipped with Schrader valves in each sensing line for calibration purposes.Sensor
piping shall be copper or brass. Steel or black iron shall not be permitted. Sensor piping shall be tapped
from the sides of the main pipes being measured. Taps shall not be from the top as this could trap air.
Taps shall not be from the bottom as this could catch debris and clog the sensor piping.
Meter Installation- See section 23 05 19
Sensor Piping
Tubing shall be concealed except in mechanical rooms
Tubing installed inside control panels and equipment enclosures, and above ceilings shall be tied and
supported.
Fasten tubing with clips at regular intervals and run parallel to building lines. Attach concealed tubing
above suspended ceilings to structure or ductwork supports.
Nonmetallic tubing run in mechanical rooms and concealed in inaccessible locations shall be run in
metallic raceways. Make connections to hot equipment with copper tubing.
Revision Date November, 2014
Section Page 12 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Copper bends shall be tool made. Provide unions at final connections to apparatus. Provide separation
between dissimilar metals.
Test tubing at 30 psig (gauge) for pressure loss of not more than 1 psi in 1 hour.
Sensor and Meter Calibration
Calibration of DDC sensors and metering devices shall be included as part of the pre-functional checklists
according to the following procedures and shall be verified during the Functional Testing of the
commissioning process:
General: verify that sensors with shielded cable are grounded only at one end.
Sensors without external transmitters: take a reading with a calibrated test instrument within 6"of
the sensor installation and verify the sensor reading is within the specified tolerance. If not, install
offset, calibrate, or replace sensor to obtain required accuracy.
Sensors with external transmitters: disconnect sensor from transmitter input and connect a signal
generator in place of sensor. Using manufacturer's data, simulate minimum measured value.
Adjust transmitter potentiometer zero until minimum signal is read. Repeat for the maximum
measured value and adjust transmitter until maximum signal is read. Reconnect sensor. Make a
reading with a calibrated test instrument within 6" of the sensor installation. Verify that the sensor
reading is within the specified tolerance. If not, repeat the process until specified accuracy is
achieved, or replace the sensor and repeat process.
Paired sensors: for sensor pairs that are used to determine a temperature or pressure difference,
calibrate both sensors to a common measurement and verify they are reading within 0.25F for
temperature and within a tolerance equal to 2% of the sensor reading for pressure.
Proper calibration of sensors shall be demonstrated and documented as part of the
commissioning process.
Thermometers
Provide at each remote temperature sensor and element location.
specified in other Sections.
Mount thermometers in piping, ducts, and equipment in positions adjusted to be accessible for reading.
Use angle and adjustable types where straight type would not be readable.
Fill thermometer wells with thermally conductive material.
Control Dampers
For outdoor air damper assemblies, stage the opening of each section to prevent stratification and poor
mixing of outside and return air.
Control Valves
Valves shall be installed to use the full range of the modulating control signal to position the valve through
its full range of travel.
Emory discourages the use of pneumatic valves on all but the largest equipment. Where applicable
provide high pressure air and connecting piping for valve actuators.
Coordinate with the mechanical contractor location of PT plugs or pressure measurement taps, equipped
with Schraeder valves, before and after each modulating control valve.
The use of pressure independent chilled water control valves are required for air handlers in buildings
connected to a chiller plant. Manufacturers should be Flow Control, Bray, Belimo or Danfoss. Pressure
independent control valves are not required in fan coil units.
Wiring
Materials and installation of wiring and electrical devices shall be in accordance with NFPA 70-2002, and
Revision Date November, 2014
Section Page 13 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Division 23.
[Engineer - Choose 1 of the following 2 paragraphs. Allowing plenum cable can save cost but must be
acceptable to the Owner. Plenum cable can be easily damaged and is difficult to get installed in a neat
manner. Get Owner's approval before deciding]:
1 - Control and sensor wiring shall be installed in conduits and shall be separate from ac wiring of
any voltage. Conduits to devices in finished spaces shall be concealed.
2 - Exposed control and sensor wiring shall be installed in conduits and shall be separate from
power wiring. Plenum rated cable may be used in concealed spaces if run parallel to structural
grid and supported by cable trays or tie wraps, and identified in a manner consistent with the
documentation of the system every 30'. Conduits to devices in finished spaces shall be
concealed.
Provide control transformers or filters for operation of automatic temperature controls from building power
circuits.
Provide control relays, control transformers, control fuses and interlock wiring as required to accomplish
the sequences specified herein.
Wiring for emergency fan shutdown from fire alarm system and manual stations shall be separate from
control and sensor wiring and devices.
[Engineer Regarding the following requirement - Coordinate the availability of electric circuits for DDC
controllers, terminal unit controllers, and other power consuming devices. Specific circuits should be
identified on the Electrical Drawings. These circuits should be extended to specific locations shown on
the Drawings and terminated in j-box enclosures for the DDC systems use.]
Provide power wiring to DDC controllers, terminal unit controllers, flow measuring devices, and
other power consuming devices of the DDC control system from adjacent junction box provided,
installed, and wired back to electrical distribution panel by others.
[Engineer- Regarding the following requirement - Coordinate the availability of emergency power and the
connection of equipment with the Emory Project manager and the HVAC Shop Manager.]
Branch circuit wiring and conduit furnished under this Section for control equipment power shall
be separate from other power wiring. Each circuit shall be extended by others to 120V branch
circuit panel, and identified 120V, 20 ampere, single-pole branch circuit breaker furnished in the
panel to serve the circuit. DDC controllers shall be connected to emergency power circuits if the
controlled equipment is connected to emergency power.
Low voltage control and sensor wiring shall be continuous without splicing.
Compressed Air Supply
[Engineer Regarding the following requirements - Delete if pneumatic devices are not specified.]
Compressed air piping shall comply with requirements specified herein for sensor piping.
Main instrument air distribution shall be through high pressure air mains (tank pressure). Air mains shall
be extended to each temperature control panel and air handling unit. Minimum line size shall be 0.375"od
with a maximum allowable pressure drop, at design air flow, of 10 psig (gauge) to the farthest point.
Provide final regulators at each point of use, with isolation valves and gauges for both high pressure and
regulated pressure.
Provide high pressure to equipment where required for performance specified herein.
Provide a valved high pressure connection at each air handling unit for use by the variable volume
pressurization controls systems.
Revision Date November, 2014
Section Page 14 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Existing copper tubing may be reused at the Contractor's option. Main control air lines to new
connections, beginning at the existing air compressors, shall be cleaned with dry nitrogen for moisture
removal. If tubing is found to be contaminated with oil, it shall be replaced. Cleaning and reworking of
control tubing shall be coordinated with building occupancy requirements. Temporary compressors shall
be installed to continue operation of systems where shutdown cannot be scheduled.
Provide easily visible and accessible pressure gauges on control air system at each unique actuating
mechanism (i.e. if 4 actuators work one damper set, provide only one gauge) Pneumatic gauges are not
required for individual terminal unit installations.
[Engineer Regarding the following requirements - Show location on the drawings, and coordinate power
with Electrical.]:
A dual desiccant dryer with standby cell shall be provided for exterior pneumatic air piping and
devices.
Install a gauge on each controlled device except room thermostats. Gauges may be mounted in
or on the control panel if the controlled device is within sight from the panel.
On positive positioning devices, provide gauges for both pilot input and actuator signals.
Hand-Off-Automatic and Controller Bypass Switches
Provide hand-off-auto selection switches or override capability for all critical DDC system outputs. These
include primary and secondary pumps, research and animal quarters AHU VFDs and Exhaust fans,
Tertiary pumps and other critical user defined equipment. All HOA switches shall generate an alarm on
the front end when not in Auto mode.
Safety devices, including fire alarm system relays and emergency fan shutdown stations, shall be wired in
series with the motor controller holding coil circuit and shall be active in the hand and automatic positions
and in the bypass position, if appropriate for the installation.
Interlocking with other fans, equipment, or systems other than those required for the operation of the
specific equipment shall be through automatic positions only.
Remote control from the DDC system shall be through automatic positions.
Hand position shall be for maintenance operation only.
Operation in hand position shall energize associated dampers and equipment necessary to allow
operation.
Provide a means for manual adjustment of analog outputs when in the hand position.
Sequences Of Operation
The following items apply to control sequences specified herein:
Variable Speed Controls:
Variable frequency drives shall start at low speed.
When 2 or more variable speed pumps operate in parallel, their speeds shall be synchronized and controlled from a common signal.
Variable frequency drives shall not operate below the minimum speed set on the control
panel. Minimum speed setting shall be determined during system commissioning and
shall not be lower than the motor manufacturers recommendation.
Equipment safeties shall be wired into variable frequency drive control circuits.
Revision Date November, 2014
Section Page 15 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 16 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Alarms associated with animal rooms shall be reviewed and agreed by Emorys Department of Animal
Resources.
The system shall be capable of contacting individual occupants as defined per project with notification
alarms contacting via phone, text and/or email. These areas are not typical and will be handled on a case
by case basis specific to individual rooms and equipment.
Graphics
The control vendor shall provide Emory approved graphics as described herein.
In general the following shall be provided:
Section Page 17 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Software shall be provided to allow operator modification of graphic displays provided with the
system and to allow operator creation and storage of new graphic displays.
Graphic displays shall be a white or gray background with discrete, solid colors for the graphic
elements. Color gradients shall not be used. Text shall be a consistent dark color. Identifiers for
digital commandable points shall have a blue or green background to show the commanded
state. Analog commandable points shall have a colored background to indicate they are
adjustable. Data and reporting points shall have color coded backgrounds to indicate their status
or that they are in their normal operating range. Points in an alarm condition shall change to a
flashing red text or be displayed in a high contrast color against a flashing red background. No
other points shall use this color or a red background.
Graphic displays shall be basic mechanical system schematics which reflect the actual
configuration of the equipment portrayed, with all major components in their correct relative
locations. Equipment identifiers, data, and commandable points shall be located adjacent to the
graphic element they are associated with. Tabular displays of the equipment data and setpoints
shall be used whenever appropriate. If the equipment or system is extensive enough to require
multiple graphics to display all required data, individual graphic displays shall contain ALL data
required to evaluate the portion being displayed, even if data appears on multiple graphics.
Graphic displays shall be arranged to correspond to the flow of the equipment or system.
Graphic and data shall progress in a logical pattern from the entry point of the system to the final
delivery point of the system.
A graphical page shall be linked to and provided for each VAV AHU system that shows all
associated terminal unit damper positions and zone temperatures.
Each facility shall include a main summary page. This page shall include:
o A picture or architectural rendering of the entry elevation of the building.
o A summary of the status of the facility and the major systems and equipment. The
location of the status points shall be shown in the general vicinity on the graphic of the
installed location of the equipment.
o Links to all major equipment and systems.
o Links to each facility floor plan.
o A link to the metering and energy consumption information for the facility.
o A link to the latest sequence of operation for all controlled and monitored equipment.
o A link to a summary of all points in operated or operator-overridden priority.
Section Page 18 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Provide the services of control technicians at start-up to check-out the system, verify and calibrate
sensors and outputs, input data supplied by the Owner and place the system in operation. Verify proper
operation of each item in the sequences of operation, including hardware and software.
Check-out each system for control function through the entire sequence. Check actuator travel on
dampers and valves for action and extent. Verify that control dampers and valves open and close
completely. Check calibration of instruments. Calculate and verify instrument setpoints.
Calibration and testing: calibrate sensors and monitoring inputs and verify proper operation of outputs
before the system is placed on-line. Check each point within the system by making a comparison
between the operator console and field device. DDC control loops, failure modes, interlocks, sequences,
energy management programs, and alarms shall be debugged, tested, and stable operation verified.
Control loop parameters and tuning constants shall be adjusted to produce accurate, stable control
system operation. Before obtaining permission to schedule the functional test, provide written
documentation of system calibration and certification that the installed complete system has been
calibrated, verified, and is ready to begin testing.
Specific to Siemens systems, confirm all Initial Values saved in the control database are per the design
and/or commissioned requirements, and that no value is saved in an operated or overridden state.
Refer also to the requirements below regarding Pre-functional tests.
Commissioning Support Requirements
The commissioning process is vital to the Emory project close-out and acceptance process. The
involvement and support of the controls contractor is vital to the success of the process. As a result, the
project specifications must include the expectations and obligations of the controls contractor in support
of the commissioning effort. The project specific expectations will be developed by the CxA, and will
generally follow the requirements in Section 019113 General Commissioning Requirements. The
following are specific requirements to the general requirements listed in Section 019113:
The contractor is to include the cost of CxA support in the contract price.
Preparation of a written start-up and initial checkout plan indicating in a step-by-step manner the
procedures that will be followed to test, check-out, and adjust the control system prior to
beginning functional testing. Submit the proposed plan to the Commissioning Authority for review
and approval prior to startup.
Provide the Commissioning Authority complete system logic diagrams, describing the proposed
system programming, with programmed attributes shown. These diagrams shall be updated with
field modifications from the start-up, check-out, and pre-functional testing prior to the beginning of
the functional testing of the DDC system. Provide a copy of each proposed graphical interface
screen with interface points shown for the entire system.
Provide assistance to the
Commissioning Authority in preparing the specific functional performance test procedures
required, to include normal cut sheets and shop drawing submittals of commissioned equipment
and any additional requested documentation, prior to normal O&M manual submittals. Review
test procedures to ensure feasibility, safety and equipment protection and provide necessary
written alarm limits to be used during the tests.
Pre-functional tests: Verify and document the proper installation, addressing, calibration,
programming, operation, and failure mode of DDC control points, sequences, and equipment and
provide a copy to the commissioning authority. Provide a signed and dated certification to the
Commissioning Authority upon completion of the check-out of each controlled device, equipment,
and system that installation, set-up, adjustment, calibration, and system programming is complete
and as indicated on the Drawings, except functional testing. Completed pre-functional
documentation of the system verification shall be submitted to the Commissioning Authority and
Commissioning Supervisor for review and approval prior to the functional testing of the DDC
control system or its being used in the testing of other equipment or systems, or other purposes.
Copies of final field check-out sheets and trend logs shall be provided to the Commissioning
Authority for inclusion in the Commissioning Report.
Meet with the testing, adjusting, and balancing contractor prior to beginning the test, adjustment,
and balance process and review the test, adjusting, and balancing plan to determine the
capabilities and requirements of the control system in completing the testing, adjusting, and
balancing process. Provide the testing, adjusting, and balancing contractor with the appropriate
software and any needed unique instruments for setting terminal units and instruct the testing,
adjusting, and balancing contractor personnel in their use. Assist and cooperate with the testing,
adjusting, and balancing contractor by providing a qualified technician to operate the controls as
required to assist the testing, adjusting, and balancing contractor in performing the work, or
alternatively, provide sufficient training for the testing, adjusting, and balancing contractor to
Section Page 19 of 30
Section 23 09 00
Instrumentation and Control for HVAC
operate the system without assistance. Verify the proper operation of affected controls at the
completion of the test, adjustment, and balance procedure.
Address current A/E punch list items before functional testing. Air and water TAB shall be
completed with discrepancies and problems remedied before functional testing of the control
systems for the respective air- or water-related systems.
Functional tests:
conduct and document a functional test under the direction of the
Commissioning Authority of the complete installed DDC control system. Functional testing is
intended to begin upon completion of a system but may be conducted in phases or sections, as
defined by the requirements of the Functional Test, or as approved by the Commissioning
Authority. The DDC system, or applicable portions of the system, shall have completed prefunctional testing and be approved by the Commissioning Authority and Commissioning
Supervisor before being used for other purposes, such as test and balance measurements, or in
support of the functional testing of other systems.
Provide technicians and or knowledgeable programming personnel as required to conduct the
required functional testing. Assist the Commissioning Authority in resolving issues found during
the functional testing process.
Assist in the functional testing of equipment and systems by implementing trend logs and
equipment monitoring as specified in the contract documents. The monitoring and data logging
capabilities of the DDC system shall be available for use in the commissioning process. Assist
the Commissioning Authority in the testing and documentation process by using the data logging
and trending capability of the DDC system in monitoring the testing effort and recording the
performance of systems and interpreting the monitoring data, as necessary.
If the project does not include an operator station, and the building is not connected to the
campus network at the time of functional testing for commissioning, the controls contractor shall
coordinate with the Emory IT department and provide and set up a temporary testing operator
station to allow full operator station interface with the system during the entire functional testing
process. This temporary operator station shall provide all functions required of the system at the
operator station, including real time graphic displays and report generation.
Correct deficiencies (differences between specified and observed performance) as interpreted by
the Commissioning Authority and Engineer and retest the equipment.
Seasonal Adjustment: Assist the Commissioning Authority with the seasonal adjustment process.
During this effort the Commissioning Authority will test and verify control sequences for proper
operation for the season. Where deficient operation or defective equipment is discovered, provide
corrective measures as required by the warranty provisions specified herein.
Warranty requirements
Execute seasonal or deferred functional performance testing, witnessed by the CxA, according to the
specifications.
Correct deficiencies and make necessary adjustments to O&M manuals and as-built drawings for
applicable issues identified in any seasonal testing.
Coordinate with equipment manufacturers to determine specific requirements to maintain the validity of
the warranty.
DDC System Training
Provide a training plan for review 4 weeks before the planned training. The format and training agenda in
The HVAC Commissioning Process, ASHRAE Guideline 1-1989R, 1996 is recommended.
Training shall occur after functional testing is complete, unless approved otherwise by the Project
Manager.
Provide training for designated Owner personnel on the control system. The intent is to clearly and
completely instruct the Owner on the capabilities of the control system. The training shall be tailored to
the needs and skill-level of the trainees.
The trainers shall be knowledgeable on the system and its use in buildings. For the on-site sessions, the
most qualified trainer(s) will be used. The Owner shall approve the instructor prior to scheduling the
training.
The standard operating manual for the system and any special training manuals shall be provided for
each trainee, with a copy included in each copy of the operation and maintenance manual. In addition,
copies of the system technical manual shall be demonstrated during training and a copy included in each
Revision Date November, 2014
Section Page 20 of 30
Section 23 09 00
Instrumentation and Control for HVAC
copy of the operation and maintenance manuals. Manuals shall include detailed description of the
subject matter for each session. The manuals shall cover control sequences and have a definitions
section that fully describes relevant words used in the manuals and in software displays.
Training program must include:
Use of the printed installation, operation and maintenance instruction material included in the
O&M manuals.
A review of the written O&M instructions emphasizing safe and proper operating requirements,
preventative maintenance, special tools needed and spare parts inventory suggestions. Training
is to include all explanatory information included in the O&M manuals and the location of all plans
and manuals in the facility.
Hands-on training shall include start-up, operation in all modes possible, including manual,
shutdown and any emergency procedures and preventative maintenance for all pieces of
equipment.
Common troubleshooting problems and solutions.
Discussion of any peculiarities of equipment installation or operation.
For any controls provided by the control contractor, they shall fully explain and demonstrate the
operation, function and overrides of any local packaged controls, not controlled by the central
control system.
Discussion of relevant health and safety issues and concerns.
Discussion of warranties and guarantees.
Copies of audio-visual materials used in the training program shall be delivered to the Owner, by
the General Contractor
Accurate scaled floor plans showing the locations of all installed control equipment, sensors,
monitoring points, and equipment connected to the DDC control system. Floor plans shall locate
any electrical panels that provide power to the system or that are monitored or controlled by it.
Space sensors shall be located on these floor plans. Equipment shall be identified on these floor
plans by its control system designation.
A control schematic showing the location of all sensors, monitoring devices, and control outputs,
an accurate Bill of Materials identifying the installed equipment, and floor plans showing the
installed locations of all control equipment and the locations of electrical panels supplying power
to control equipment.
Full as-built sequence of operations for each piece of equipment, reflecting any changes made to
achieve the required system performance.
Full point list. - An updated points list, identifying all points, actual and virtual, installed in the
system. Provide the following information for each point:Point type, Point identifier, Point address
A listing of all terminal controllers, with the following information for each device:
o
Associated air handler unit ID and air terminal unit tag ID
o
Floor, room number, and room name where located and reference drawing number
showing location
O
Terminal unit tag identification, as implemented in the installed control system.
O
Heating and/or cooling valve tag identification.
O
Minimum cfm.
O
Maximum cfm.
o
Calibrated flow coefficient.
Valve Schedule reflecting the actual equipment installed, with the following information for each
device:
o
Floor, room number, and room name where located and reference drawing number
showing location.
o
Associated coil served and heating and/or cooling valve tag ID
Section Page 21 of 30
Section 23 09 00
Instrumentation and Control for HVAC
o
Normal position (Normally open/Normally closed)
o
Maximum gpm
o
Valve flow coefficient (Cv)
o
Expected pressure drop at design flow
o
Associated valve actuator
Damper Schedule, reflecting the actual equipment installed, with the following information for
each device:
o
Floor, room number, and room name where located and reference drawing number
showing location
o
Associated equipment served and device tag ID
o
Normal position (Normally open/Normally closed)
o
Maximum cfm
o
Expected pressure drop at design flow
o
Associated damper actuator
Controller/module data shall include building project specific control sequence functions, features,
and modes specified herein and other features of this system. Copies of the building specific
programming and customizing control loops and algorithms shall be included (hardcopy printout
and software copy on DVD or thumb-drive).
Control Equipment Data: The data of this section shall include its own tables of contents and/or
index to the information provided.
o
Control equipment data should include the manufacturer's maintenance, set-up, testing,
calibration, operation, and repair data sheets on all DDC controllers, sensors, meters,
relays, actuators, motors, terminal unit controllers, protection devices, and other devices
provided as a part of the installed DDC system. This data must include specific step by
step instructions on how to perform all routine servicing and maintenance procedures
recommended by the device manufacturer.
Provide specific sensor calibration
procedures and recommended calibration intervals for each device used in the installed
system.
o
Data must include the detailed technical manual for programming and customizing
control loops and algorithms. Specific procedures and instructions for applying all
functions, features, modes, etc. of the equipment are required.
o
In addition, include data on system software packages provided, documenting all
functions and providing guidance on their use.
o
Thermostats, sensors, switches, and timers, including maintenance instructions and
sensor calibration requirements and methods by sensor type.
o
Full as-built documentation of software programming, including fully commented software
program including English language comments describing the operation of the controller
programming. Documentation shall include all schedules, set points, and alarm limits
established during the commissioning and acceptance testing of the system. Provide an
electronic copy of programming and database information for this facility, sufficient to
restore the facility to full operation.
Section Page 22 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 23 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 24 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 25 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 26 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 27 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 28 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 29 of 30
Section 23 09 00
Instrumentation and Control for HVAC
Section Page 30 of 30
Section 23 21 23
Hydronic Pumps
In-Line Pumps
Pumps less than 3 hp shall be mounted in-line and shall be as manufactured by Grundfos or
Bell & Gossett. In-line pumps over 3 hp shall be manufactured by Aurora, Armstrong, Bell &
Gossett, Patterson or Taco.
1.02
1.03
1.04
1.05
Vibration
To reduce wear and noise, specify that rotating equipment 5 horsepower and larger must be
dynamically balanced, tested and measured by the Contractor for displacement in X-Y-Z
horizontal, vertical and axial directions. To be acceptable, work shall comply with ISO
standards for velocity. Contractor shall provide a report of vibration readings in the closeout
documents.
1.06
Pressure gauges
Pressure gauges around the pumps shall be installed with copper tubing (including the manifold
used to check DP across pump and strainer). Reference also Section 23-05-00, 1.14 Test
Ports & Gauges.
Section Page 1 of 1
Section 23 22 00
Steam & Condensate Specialties
B.
1.02
A.
B.
C.
1.03
Condensate Receivers
All condensate receivers shall be equipped with duplex pumps and shall be vented to the exterior
of the building through an acceptable side wall location or the roof. Condensate receivers shall
have a full size drain. Piping at the outlet of each pump will include in order union-pressure
gauge-circuit setter-check valve and gate valve. Condensate tank accessories will include a
sight gauge, temperature well with insertion temperature gauge, pump suction shutoff valves,
inlet basket strainer. Condensate receivers shall be as manufactured by Aurora, Bell & Gossett,
Marshall Engineered Products (MEPCO), Peerless, Shipco, or Weinman. If the tank will be
recessed into the floor, a minimum 1 clearance between sides of tank and wall of pit shall be
provided.
1.04
A.
Steam Separators
Install a steam separator at entrance to building downstream from the building steam shut off
valve.
Steam separator must be rated for maximum operating conditions of at least 150psig.
B.
1.05
A.
B.
1.06
Section Page 1 of 3
A.
B.
1.07
A.
B.
Section 23 22 00
Steam & Condensate Specialties
All steam pressure gauges will mounted on a siphon tube and include an isolation valve.
Place steam gages in appropriate locations including mechanical room entrances, before and
after PRV valves, before and after control valves.
Documentation Content
Include schedules for PRV valves, safety relief valves and steam traps showing size, capacity
and set pressures.
Include detail drawings for:
Medium/High Pressure Steam Supply Drip Leg and Steam Trap Station
Low Pressure Steam Supply Drip Leg and Steam Trap Station
Steam Coil Drip Leg and Steam Trap Station
Shell and Tube Heat Exchanger Drip Leg and Steam Trap Station
Steam Condensate Return Tank
We need the detail drawings to include all the information covered in Sections 23 22 00
and 23 57 00 as part of the drawings or as notes listed with each drawing.
Section Page 2 of 3
Section 23 22 00
Steam & Condensate Specialties
Section Page 3 of 3
Section 23 25 00
HVAC Water Treatment
Section Page 1 of 7
Section 23 25 00
HVAC Water Treatment
3. Recirculate both Closed Loop and Cooling Towers for 24-48 hours.
4. Open and drain mud legs and low points periodically during the cleaning process to sanitary
sewer only.
5. After the cleaning period locate a system drain up stream of the system make up and open
the drain to sanitary sewer only. Allow the system to drain and refill while circulating for 48
hours. A and W Technologies will inspect the system water and verify system contents are
equal to make up water. Verifying system flushs success.
6. Upon completion of the flush process all system strainers shall be pulled, cleaned and
replaced by contractor.
a. Recharge cooling tower systems with AWC 209, heating water systems with AWC
226, and chilled water systems with AWC 206
7. A service report will be generated by A and W Technologies, certifying that the systems have
been cleaned in accordance with the above procedures and shall be copied to the
mechanical contractor. A copy of the service report will also be forwarded to the associated
Emory University Facilities Management HVAC Shop Supervisor.
Closed Systems
1.0 General
Contractor will furnish and install all equipment, chemicals and service necessary to provide a complete
Water Treatment Program. A and W Technologies water treatment company shall provide all products
and services for undivided responsibility throughout the warranty period. Provide a minimum of 5 days
notice for pricing services from A and W Technologies. This company shall have a regional accredited
laboratory, research and development facilities, plus technical service representatives located within the
trading area of the job site.
The water treatment products and services shall be provided by: A and W Technologies
2.0 Chemical Feeding Equipment (Hot/Chilled)
For each closed system the contractor shall provide and install the following apparatus (including isolation
and drain valves): One (1) Pot Filter/Feeder with filter, Neptune model #FTF-5. The feeder shall be
rated for 200 psi service. Consult A and W Technologies on proper locations.
3.0 Water Treatment Chemicals
Furnish a one year's supply of a liquid closed loop inhibitor for control of scale and corrosion in a closed
recalculating system. A closed loop is a re-circulating system, which has less than 10% makeup/year
when compared to its system volume. A one-year supply of corrosion inhibitor will be provided at start up.
Formulations shall not contain any ingredients that may be harmful to system materials of construction.
The corrosion inhibitor shall contain a multi-functional blend of tolytriazole, anionic polymer and buffering
agent such A and W Technologies AWC 206 for chilled water systems and AWC 226 for hot water
systems. Provide MSDS sheets on all chemical products. No system shall be operated without the
benefit of chemical protection. Once the recommended chemical residual is achieved, any additional
chemicals required to re-treat the system due to water loss or to accomplish other work shall be provided
by the Mechanical Contractor.
4.0 Water Treatment Service Program
Provide startup service and monthly service visits to include the following:
1. Installation and system start-up procedures and recommendations.
2. Initial treatment dosages.
3. Training of operating personnel on proper feed and control techniques.
4. Service visits and consultation meetings monthly with General contractor and HVACr Shop.
5. A and W Technologies to record and maintain all necessary logs and records and submit
reports to HVACr Shop on bi-weekly basis.
6. Any required laboratory and technical assistance (as needed).
Revision Date October, 2012
Section Page 2 of 7
Section 23 25 00
HVAC Water Treatment
Two (2) Pulsatron series A plus 10-24 gpd and (1) Stenner pump for the oxidizing
biocide 5-24 gpd, Pumps shall be furnished with 1/4- /8 inch tubing connections, foot
valves and injection fittings. Contact A and W Technologies for proper sizing.
Section Page 3 of 7
3.2
3.3
Section 23 25 00
HVAC Water Treatment
One (1) Seametrics Contacting head Water Meter and cable complete with dry contact
register sized to meter the maximum makeup water rate of the system. Or meter specified
in the Emory Standards
Three (3) Chemical tanks suitable for mounting chemical fed pumps on top surface with
secondary containment basins. Material composition shall be white polypropylene. Label
shall be placed on secondary container specifying capacity in gallons. Contact A and W
Technologies for sizing.
Section Page 4 of 7
Section 23 25 00
HVAC Water Treatment
The intent of this document is to insure that all mechanical systems requiring water treatment are flushed,
cleaned and treated in a timely manner for proper system operation.
1.1. It shall be the general contractors responsibility to coordinate communication between all
parties involved in the installation of mechanical systems requiring flushing, cleaning, and
the introduction of water treatment chemicals effectively coordinate these processes.
1.2. The General Contractor will utilize Emory Universitys New Building Chemical Station Turn
Over found at the end of this section to insure that all above sequences were followed.
1.3. It shall be the General Contractors responsibility to insure that no system in whole or part is
operated for more than a period of two days before proper water treatment is brought on
line.
1.4. Any mechanical system requiring flushing, cleaning, or treatment that is brought on line in
part can be flushed in part. Said systems must not be operated in whole until flush is
signed off. Systems operated as a whole without proper flushing, cleaning, and treatment
sign off will require an entire system flush.
2.0 Requirements
The following requirements must be documented on the Emory University New Chemical Station Turn
Over Form, attached within this section. The A/E should incorporate this form, along with the
requirements of this section, into the project specifications.
2.1 Emory University understands that prior to system start-up, flushing and leak testing are
required prior to treatment. However, beyond this period, if systems are allowed to operate
untreated or with inadequate protection for more than a period of 48 hours, the General
contractor must provide an extended warranty period for system. This section is designed
to insure that immediately after flushing, chemical passivation and cleaning will occur,
followed by continuous chemical treatment.
2.2 The General contractor will be responsible for any cost incurred for the re-flushing and/or
re-cleaning and treatment of any system allowed to run untreated or with inadequate water
treatment. This shall include chiller condenser, evaporator tubes, and cooling towers.
2.3 Upon completion of open and closed loop systems, systems shall be treated as per
specifications or drained and secured until placed into service.
Section Page 5 of 7
Section 23 25 00
HVAC Water Treatment
48"
Corrosion Coupon
Holder
Flow Switch
875
Union
Union
Liquitron DC4500
Isolation Valve
uS
Flow Indicator
24"
Flow
Isolation Valve
Sample Valve
Corrosion Coupon
Holder
System Components
ITEM QTY.
1
2
3
4
5
6
7
8
9
1
1
1
1
2
DESCRIPTION
24" * 48" * Black PE Board
PVC Piping with Two Isolation Valves and Three Injection Points
DC4500-111A-3, LMI Controller Asm
5130, 0-10 GPM Flow Indicator
CCH, Corrosion Coupon Holders
DRAWN BY:
REVISIONS
REV
A
DESCRIPTION
DATE
5/24/2012
SCOTT MANN
Part #:
PF-CD-2393-E
Customer:
A&W/Emory
Description:
Pre-Fab Asm
LMI Pumps
Section Page 7 of 7
Section 23 30 00
HVAC Air Distribution
2.02
Humidification
A. If humidification is used, locate downstream of the cooling coil unless simultaneous
humidification and cooling is not allowed.
B. Unless otherwise denoted humidifiers should be disabled during the cooling season.
2.03
Fiberglass
A. Do not use fiberglass as a duct lining anywhere upstream of the terminal units. Use silencers
or double wall ductwork constructed with a perforated steel liner to achieve sound attenuation
only in the case of special acoustical need. Minimal use of duct lining is acceptable for
general acoustical purposes using following guide specification:
1. Duct lining shall be Elastomeric flexible Duct liner. Internal flexible, closed-cell nonwicking elastomeric liner shall be pinned, fabricated factory-applied duct insulation with a
self-adhering backing in sheet form. Liner shall meet the requirements of ASTM C 534 for
elastomeric insulation. Insulation shall be made with an EPA registered, anti-microbial
agent to guard against potential growth of fungus and bacteria and shall meet UL181 for
mold growth, and ASTM G21 and G22 for fungi and bacterial resistance. with surface
suitable for duct velocities to 6000 f.p.m. without erosion. Thermal conductivity shall not
exceed 0.27 at 75F and a maximum water vapor transmission of 0.08 perm-inches. Liner
shall be manufactured without the use of CFCs, HFCs or HCFCs and shall be
formaldehyde free, low VOC, fiber free and dust free. Duct liner shall be 1 thick,
minimum 3lb density,per square footLining and accessories shall have a composite flame
spread rating of not more than 25 and smoke developed rating of not more than 50 when
tested in accordance with ASTM E 84.
Manufacturers shall be Armacell (Armaflex) or Rubatex .
Location: Do not install liner in medium pressure ductwork. Do not install liner downstream
of any high efficiency filters. Do not install liner induct within 12 feet downstream of any duct
mounted humidifier, cooling coil or outside air intake.
3.00
3.01
Section Page 1 of 2
Section 23 30 00
HVAC Air Distribution
C. If 1 filters are used in any equipment they should be the standard sizes stocked by Emory
University as seen below.
D. If 2 filters (30% efficiency) are used in any equipment they should be one of the following
sizes; 12x24x2, 15x20x2, 16x20x2, 16x24x2, 16x25x2, 18x24x2, 20x20x2, 20x24x2,
20x25x2, 24x24x2. Air filters supplied with equipment do not need to be manufactured by
AAF. Nor does the replacement filter installed by the Contractor just prior to substantial
completion. These filters must just match standardized and stock size requirements.
3.02
3.03
Duct Spin-Ins
Spin-in connections may be used. Typically a manual balancing damper downstream of the duct
connection is used. The use of scoops is prohibited.
3.04
Terminal Units
A. These include variable air volume boxes, fan powered induction units, constant volume
boxes, and similar devices. Devices located above suspended or hard ceiling must be
accessible for maintenance and service. One-inch racks and throwaway filters must be
provided for all fan powered induction units. Sufficient room must be provided to allow filters
to be replaced without bending the filter. Sufficient room must be provided to allow the coils
to be cleaned, fans to be replaced, and the controls to be serviced. Valves and drain
connections are to be provided for heating and cooling coils to allow isolation for service and
removal. Strainers shall be included at all hot water coils. Fan blades and blower wheels are
to be constructed of aluminum or galvanized steel. In general, fan powered parallel type
induction units are used on all perimeter zones with VAV units on most interior zones.
Typically both types of units have hot water coils, in VAV units the coil is in the reheat
position. In the fan powered units, the coil may either be in the reheat or the pre-heat
position. The hot water coil in terminal units shall be sized to discharge a minimum of 95F
LAT with 160 degrees F heating hot water. Terminal units shall be as manufactured by
Carrier, Krueger, Metal-Aire, Price, Tempmaster, Titus, Trane, York, Tuttle & Bailey or
Envirotec.
B. Each manufacturer has particular requirements regarding the length of straight inlet duct
upstream the airflow station. Ensure the plan view layout accounts for the straight inlet
requirements of the design basis equipment. Require in the specifications the mechanical
contractor coordinate all manufacturer recommended clearance requirements and straight
inlet duct length if the design basis equipment is not installed.
3.05
Duct Sealants
Use water based, non fribated, low VOC duct mastic/sealants. VOC shall be a maximum of 50
grams per liter (less water). Use Foster 32-19, Childers CP-146 or Duro Dyne SAS.
3.06
Smoke Dampers
Access to smoke damper actuators can be problematic. For smoke dampers in non-ducted
return air openings, consider the type with the actuator in the airstream. Provide for access to all
duct mounted smoke damper actuators and ensure the actuator can actually be removed from
the damper rod without conflict.
3.07
Flexible Duct
Where used between low pressure ductwork and supply grilles, flexible duct shall be no longer
than eight feet.
Section Page 2 of 2
Section 23 50 00
Central Heating Equipment
2.02
2.03
Expansion Control
Control expansion stresses with the piping configuration and with piping expansion loops to the
greatest extent possible. Where necessary use slip joint type expansion joints as manufactured
by Advanced Thermal Systems.
Section Page 1 of 1
Section 23 57 00
Heat Exchangers for HVAC
1.02
Section Page 1 of 1
Section 23 60 00
Central Cooling Equipment
Products
2.01
Chillers
A. Refer to Section 23 64 16 for a specification for electric centrifugal water chillers. Other
chillers to be used are application and location specific. Chillers to be used include scroll,
reciprocating, helirotor and screw. Check with Emory University Engineers in the schematic
design and design development phases. Chillers shall be manufactured by Carrier, Trane or
York.
B. Refrigerant monitors shall be as manufactured by MSA (Model Chillguard RT), Yokogawa, or
Bacharach.
2.02
2.03
2.04
Section Page 1 of 1
Section 23 63 13
Refrigerant Condensers
Unless approved by Emory University Engineering, all air cooled refrigerant condensers shall be
designed for a minimum of 105 degree ambient temperature. Higher ambient temperature design
can be warranted in certain applications. All condensers shall contain king valves, solenoid
valves, Low pressure cutout protection, Liquid Line filter driers, and sight glasses.
Page 1 of 1
Section 23 64 16
Centrifugal Water Chillers
Bids must be submitted on or before the Official Bid Date of (time) on (date) to:
Section Page 1 of 12
Section 23 64 16
Centrifugal Water Chillers
Questions regarding this package must also be directed to the person noted above.
After review of the bid data, the Owner intends to issue a Purchase Order to the selected
manufacturer. The Contractor shall be responsible for scheduling the exact delivery date and
time, taking delivery of the machine, inspecting the chiller prior to unloading, arranging and
paying for crane service, unloading the chiller, installing the chillers, and scheduling the factory
start-up.
The quoted price for each machine is to be F.O.B. job site, Full Freight Allowed (F.F.A.). Seller is
to retain risk of loss and damage until delivery is made at the jobsite or the Contractor's Atlanta
yard, as stipulated on the purchase order. Equipment shall be delivered on flatbed trailer. The
Seller shall provide 48 hours notice to the Contractor prior to actual delivery.
Please note that the Emory University has several-posted load limit bridges that shall not be
crossed with loads exceeding their capacity.
PART 1 - GENERAL
1.01
DESCRIPTION
A. General provisions and other HVAC systems are specified in other Sections of Division 23.
B. HVAC commissioning is specified in Section 01 91 13, Building Commissioning Requirements
and Section 23 08 00, Commissioning of Mechanical Systems. These Sections include
responsibilities and obligations in support of the commissioning process specified therein.
1.02
PROPOSALS
A. Proposals will be evaluated by the Owner and Engineer with consideration toward first costs, fullload and part-load energy efficiency, delivery schedule, and compliance with LEED NC 2009
Energy and Atmosphere Credit 4, Fundamental Refrigerant Management.
B. Proposals for centrifugal chillers shall include the following information:
1. Lump sum cost to furnish, assemble, start up, and perform training for the chiller as
specified and scheduled herein.
2. ARI computer selection printouts for proposed chillers, including ARI certified NonStandard Part Load Value (NPLV). Selection copy shall identify all components such as
tube bundle sizes, tube material, thickness and configurations, gear sets, compressor
identification, impeller size and type, and other data to completely identify machine
components.
3. Dimensional information including overall chiller width, length, and height.
4. Written statement indicating minimum evaporator flow per chiller.
5. Written statement indicating pounds of refrigerant charge to be provided per chiller.
6. Written statement regarding the available delivery schedule for the chillers.
7. Written statement listing deviations, if any, from these Specifications. If no deviations,
provide statement as such.
8. Written statement acknowledging that the chiller manufacturer understands that the
anticipated award date is
and the anticipated delivery/installation
date is
.
C. Multiple proposals for alternative chiller models from the same manufacturer will be acceptable
and are encouraged.
Revision Date November, 2014
Section Page 2 of 12
Section 23 64 16
Centrifugal Water Chillers
1.03
QUALITY ASSURANCE
A. Conform to the following:
1. International Energy Conservation Code-2006 with Georgia State Amendments-Latest
edition.
2. International Mechanical Code-2006 with Georgia State Amendments-Latest edition.
B. Warranty:
1.
The chiller and starter shall be factory warranted against defects in material and labor,
including refrigerant, for a period of 15 months from the date of factory startup or 18 months
from date of delivery, whichever occurs first. An extended parts only warranty shall be
provided for the motor compressor gearbox assembly (to include shaft seals) for 5 years
from startup, not to exceed 5 years and 6 months from shipment. All parts covered under
this extended warranty shall be delivered F.O.B. jobsite with full freight allowed.
C. Chiller Factory Performance Test:
Note to Engineer: Chiller performance test will not be required for each project. A chiller
performance test will be required depending on the manufacturer, the specific chiller
model and our experience with that model. Please consult with Emory Engineering
Services.
1.
2.
3.
4.
A factory chiller performance test shall be provided. The chiller shall be tested at the
Manufacturer's factory in accordance with the latest edition of the American Refrigeration
Institute standard ARI 550 on a laboratory type calorimeter to check and verify unit
performance including capacity (tons and kW), vibration, operating controls and safety
cutout performance. The Owner shall be given written notice ten (10) days prior to the
performance of this test. The test shall be witnessed by the Owner or the Owner
representative. The Manufacturer shall provide to the Owner a notarized certification,
signed by an officer of the company with authority to legally bind the company, of this test
prior to the contractor's invoicing/payment request.
The factory performance test shall be performed at a minimum of four unique operating
points, which, unless otherwise directed in writing by the purchaser, shall be the same
operating points, and corresponding conditions as defined by the ARI standard as required
to develop the actual Non-Standard Part Load Value (NPLV). In addition to these four
certified test points, the manufacturer shall provide a demonstration, including test data, of
stable operation without surge and without stall at 40% load and 85 degrees condenser
water temperature.
Upon completion of the test(s) the Manufacturer shall calculate the actual Non-Standard
Part Load Value (NPLV) and submit it as a part of the documentation to the Owner with a
copy forwarded to the Engineer.
Please include all costs associated with performance testing as a breakout option price.
PART 2 - PRODUCTS
2.01
CENTRIFUGAL CHILLERS
A. Hermetic or open centrifugal type, designed and constructed in accordance with ASHRAE 152007, complete with compressor, motor, lubrication system, heat exchangers, purge system,
insulation, motor controller, control panel, refrigerant charge, oil charge, and steel mounting base
with maximum of four assembly mounting points.
B. Refrigerants: R-123 or R-134A.
Revision Date November, 2014
Section Page 3 of 12
Section 23 64 16
Centrifugal Water Chillers
C. Rating certification: capacity rating shall be certified in accordance with ARI 550/590-2003. A
direct copy of the ARI computer selection printout at each of the conditions specified herein
shall be provided to the Architect upon request.
D. Chillers shall be designed to operate continuously without surge, pulsation, or hot-gas bypass at
design leaving chilled water temperature at all of the following conditions:
1.
E.
F.
G.
H.
Throughout a load range from 100% to 15% load with condenser water conditions that vary
from 85F at full load to 65F at 15% load with maximum condenser water design flow rate.
2. Throughout a load range from 100% to 40% load with condenser water conditions that are
constant at 85F with maximum condenser water design flow rate. The chiller manufacturer
may be asked to demonstrate this capability in the same factory performance test specified
herein. If the chiller manufacturer has to use hot-gas bypass to meet these performance
conditions, the chiller manufacturer shall define the full boundary of the operation of the
hot-gas bypass using graphical means.
3. Throughout a load range from 100% to 15% load with condenser water conditions that are
constant at 70F with maximum condenser water design flow rate.
Compressor: centrifugal type complete with rotor assembly, impeller, and capacity control. The
rotor assembly shall consist of a heat-treated alloy steel drive shaft and impeller shaft with
lightweight high strength, cast aluminum, fully shrouded impeller. The impeller shall be balanced
for balanced thrust and be static and dynamically balanced and over speed tested for smooth
operation. Capacity control shall be provided by fully modulating variable inlet guide vanes. The
kW input at 15% of the rated machine tonnage capacity shall not exceed 25% of full-load rated
kW.
Motor: refrigerant- or air-cooled, 2-pole squirrel cage induction type designed in accordance with
Part 31 of NEMA MG 1-2006 (R2007) for use with variable frequency drives. The motor kW input
shall not exceed nameplate rating. Starting inrush current shall not exceed one-third of nameplate
locked rotor current rating. Motors shall have a certified minimum efficiency of 94% and a minimum
power factor of 0.90 at full load. Units shall be designed to prevent refrigerant contamination in the
event of a motor failure. Refrigerant cooled hermetic motor/compressor assembly motors must
utilize motor winding temperature RTDs, one per phase, interlocked with the chiller control
panel for unit safety shutdown and display the motor winding temperature at the chiller
control panel. The motor shall include motor shaft grounding rings (Aegis or Owner approved
equal) and/or other methods to control motor shaft electrical currents to prevent motor bearing
fluting and other deterioration.
Lubrication system: unit shall be provided with a factory-installed means of oil recovery under lowload and low-head conditions including the internal electric circuit for the oil heater.
Heat exchangers: shell and tube type with seamless nonferrous tubes designed in accordance
with ANSI/ASHRAE 15-2004. Vessels shall also be designed, constructed, certified and stamped
in accordance with ASME BPVC-VIII-1-2010 for a minimum water side rating of 150 psig working
pressure. Where internal enhancement of tubes is provided, it shall be spiral rifling to permit
brush cleaning. Upon Owner request, the chiller manufacturer shall provide tube samples for
each heat exchanger. The refrigerant side shall be tested at 1.5 times the maximum working
pressure. The water side shall be tested at 1.5 times the maximum design working pressure.
Heat exchangers shall include waterside taps for vents and drain connections. Shells shall be
formed of carbon steel plate. End sheets and intermediate tube supports shall be carbon steel
and drilled for tube installation. Intermediate tube supports shall be 0.375" thick, spaced no
more than 4 feet apart, welded to the vessel shell, and fully self-supporting. Each tube shall be
Section Page 4 of 12
Section 23 64 16
Centrifugal Water Chillers
roller expanded in the tube sheets providing a leak proof seal. Each tube shall be individually
cleanable and replaceable.
1.
Evaporators:
a. Tube Thickness: not less than 0.028" wall thickness at root of fins and not less than
b. 0.046" wall thickness at tube land.
c. Design Fouling Factor: 0.0001 ft2Fh/Btu
d. Maximum water velocity in tubes: 12 feet per second.
e. Evaporator water velocity shall be selected for variable flow with minimum flow as
indicated on the Drawings.
f. Suction baffle or aluminum mesh eliminator shall in the evaporator be provided to
prevent liquid carryover into the compressor.
g. Sight glass shall be provided and located such that the proper refrigerant charge is near
the center of the glass with the unit off.
h. Oil eductors, capable of returning oil to the oil sump, shall be provided on the
i. evaporator
j. Standard water boxes with removable water heads that permit brushing of tubes from
either end of chiller.
2. Condensers:
a. Tube Thickness: not less than 0.035" wall thickness at root of fins and not less than
0.046" wall thickness at tube land. Condenser tubes shall have no more than 16 rib
starts per inch.
b. Design Fouling Factor: 0.00025 ft2Fh/Btu
c. Maximum water velocity in tubes: 12 feet per second.
d. Marine water boxes with removable cover plates and side piping connections designed
for tube inspection and cleaning without removing piping. End plates of condenser
boxes shall be attached to davits that are part of and attached to the machine.
I.
Purge systems: For chillers using refrigerant R-123, the chiller manufacturer shall provide a highefficiency, air cooled, refrigerated purge system for each chiller, either factory installed or field
installed by the chiller manufacturer. The purge shall include the following features and
capabilities:
1. Both automatic and manual operating modes. Air shall be purged and refrigerant returned to
the system automatically in either mode.
2. Operation to be independent of chiller operation such that manual purging may occur
without operating compressor, oil pump, and/or water (chilled or condenser) pumps.
3. Minimum purge efficiency shall provide for exhausting a maximum of 0.8 pounds of
refrigerant per pound of air purged when the chiller is operating at a 100F condensing
temperature at standard room conditions.
4. Purge shall be refrigerated to maintain a maximum dew point (dryness) in the chiller at
normal operating conditions of 10F.
5. Provide for collection, storage, measurement, and manual removal of water. A filter dryer is
not a substitute. Provide a sight glass with moisture indicator.
6. Provide an alarm light with relay for remote monitoring for detection of excessive purging.
7. Refrigerant being returned to the machine shall be piped through a replaceable core,
desiccant filter/dryer.
Section Page 5 of 12
Section 23 64 16
Centrifugal Water Chillers
Refrigerant isolation valves shall be provided on all types of chillers to facilitate the removal of the
refrigerant charge. Refrigerant isolation valves shall be used at all points where sensors and field
devices are mounted. All devices shall be able to be replaced and/or serviced without the loss of
refrigerant or the introduction or air into the unit. If applicable for the chiller, provide refrigerant
isolation valves to store the entire refrigerant charge in either the evaporator or condenser
K. Insulation: factory-applied 0.75" flexible elastomeric sheet secured with full coverage of adhesive.
Insulation shall cover the evaporator shell, evaporator water boxes, and all surfaces subject to
condensation at a relative humidity up to 90% and dry bulb temperatures ranging from 50F to
90F. Paint exposed insulation with two coats of vinyl paint to match the machine color, allowing
a minimum of two hours dry time between coats.
L. Motor controller: factory-supplied, variable frequency drive package mounted on the chiller.
Package shall vary the compressor motor speed by controlling the frequency and voltage of the
electrical power to the motor. The package shall include adaptive capacity control logic to
automatically adjust motor speed and compressor pre-rotation vane position independently. The
control system shall provide maximum operating efficiency at all loads and water temperatures
by analyzing information fed to it via sensors located throughout the chiller.
1. Drives shall be pulse-width modulating type utilizing insulated-gate bipolar transistors
(IGBTs) with a power factor of 0.95 or better at all loads and speeds. Drives that do not
provide power factor correction are not acceptable.
2. The variable frequency drive shall be unit mounted in a NEMA-1 enclosure with all power
and control wiring between the drive and chiller factory installed, including power to the
chiller oil pump. Field power wiring shall be a single point connection and electrical lugs for
incoming power wiring shall be provided. The entire chiller/drive package shall be UL listed.
The chiller/drive assembly shall undergo an electrical and mechanical run test prior to
shipment.
3. The following features shall be provided:
a. A door interlocked circuit breaker, capable of being padlocked.
b. UL listed ground fault protection.
c. Over voltage and under voltage protection.
d. 3 phase sensing motor over current protection.
e. Single phase protection.
f. Insensitive to phase rotation.
g. Over temperature protection.
h. Digital readout at the chiller unit control panel of:
1) Output Frequency
2) Output Voltage
3) 3 phase output current
4) Input Kilowatts (kW) and Kilowatt-hours (kWh)
5) Self-diagnostic service parameters
Revision Date November, 2014
Section Page 6 of 12
Section 23 64 16
Centrifugal Water Chillers
6) Separate meters or displays on the drive for this information shall not be
acceptable. All information shall be displayed at the chiller control panel,
available for remote monitoring via a BAS connection. If a drive with a separate
display is provided, the chiller manufacturer shall provide a translator for BAS
connection to provide information listed above.
4. Harmonic distortion control: harmonic distortion control shall be provided to limit total
harmonic distortion (ITHD) at input terminals of variable frequency drive controller to 5% or
less meeting IEEE Standard 519 Latest Edition. Variable frequency drive shall utilize an
18-pulse multiple bridge rectifier converter with integral phase-shifting autotransformer.
Harmonic distortion control equipment shall be unit mounted within the same NEMA-1
enclosure and shall be UL listed.
a. The following digital readouts shall be provided at the chiller unit control panel as part of
the variable frequency drive controller package:
1) Input KVA
2) Total power factor
3) 3 phase input voltage
4) 3 phase input current
5) 3 phase input voltage total harmonic distortion (THD)
6) 3 phase input current total demand distortion (TDD)
7) Self-diagnostic service parameters
8) Separate meters for this information shall not be acceptable. All information
shall be displayed at the chiller control panel, available for remote monitoring via
a BAS connection. If a drive with a separate display is provided, the chiller
manufacturer shall provide a translator for BAS connection to provide
information listed above.
M. Control panel: unit mounted, microprocessor based control panel consisting of
temperature/pressure sensor input/output boards, power supply board, main processor board and
interface board with alphanumeric display and keypad. All devices and sensors required to
perform provide the following functions shall be factory wired and mounted. Panel shall provide
operating, safety, diagnostic and display values as recommended by the manufacturer. The panel
shall provide the following minimum functions:
1. Operating controls:
a. On-Off-Remote Switch
b. Automatic start-up from control system and after shutdown by leaving chilled water
controller. Auto-restart after power failure through start-to-start anti-cycle timer including
any safety relays in the starter and controls for a minimum of two (2) consecutive restarts after a power failure. Manufacturer shall demonstrate compliance with this
requirement during the start-up procedures.
c. Compressor soft loading upon startup.
d. Adjustable manual current/demand load limit switch, 40% to 100% of full load current.
e. Manual reset button for critical safety controls.
f. Automatic capacity control from electronic sensor in leaving chilled water
Revision Date November, 2014
Section Page 7 of 12
Section 23 64 16
Centrifugal Water Chillers
g. Control to emit signal linear with percent of RLA. Output signal shall be 010 V DC or 420 mA.
h. For non-emergency shutdown, the chiller shall unload the compressor prior to actual
shutdown and stopping of the chilled water or condenser water flow.
i. The chiller manufacturer shall provide two (2) interfaces for each machine for connection
to the DDC system. The first interface shall be a leaving chilled water reset, which shall
accept a 4-20 mA or 0-10 V DC remote signal and then reset the leaving chilled water
temperature by up 10F. Reset shall be continuous, linear and proportional between the
limits. The second interface shall be a remote demand limit which shall accept a 4-20
mA or 0-10 V DC remote signal and then reduce the machine's amperage draw to a
maximum of 40% of design. Remote demand limiting shall be continuous, linear and
proportional between the limits. If the DDC Controls Interface Option is selected as
specified herein, these two interfaces may be incorporated in that hardware and
software.
j. The chiller manufacturer shall provide head pressure control through controlling the
condenser water flow rate. The chiller manufacturer shall provide the required control
valve performance requirements for purchase by the DDC system manufacturer and
shall provide the appropriate outputs to control head pressure.
2. Safety controls:
a. General: The control panel shall monitor safeties and take adaptive measures to attempt
to correct condition(s) without shutdown. This shall include adaptive microprocessor
control to keep the machine running at lower loads without shutdown.
b. Startup: The chiller manufacturer shall provide a written description of the following
sequence of startup and interlocks, for use by the DDC system manufacturer:
1) Chilled water flowing (differential pressure switch supplied by the chiller
manufacturer).
2) Oil pump operation, oil pressure, established oil temperature at set point and
capacity control vanes fully closed.
3) Vanes open slowly on startup regardless of load.
c. Shutdown: upon sensing any of the following conditions the chiller control panel shall
shut down the chiller:
1) Chiller low differential oil pressure.
2) High oil temperature.
3) High bearing temperature for each bearing.
4) High motor winding temperature.
5) Extended compressor surge.
6) Actuator drive fault.
7) Low refrigerant and chilled water temperatures.
8) High condenser pressure.
9) Motor current overload.
10) Low evaporator flow.
11) High discharge temperature.
d. Evaporator and condenser differential pressure devices:
1) For the evaporator and condenser, provide opposed diaphragm type with
magnetically actuated switches, dial-type differential pressure readout and
Revision Date November, 2014
Section Page 8 of 12
Section 23 64 16
Centrifugal Water Chillers
shutoff and null valves selected to operate at the minimum flow differential and
to withstand 1.25 times the maximum flow differential. Maximum range shall be
0 - 15 psi and switch shall operate in the middle 80 percent of the range. Proof
pressure shall exceed the static pressure of the installed system. Switch shall
not drop out at high differential pressures. Manufacturer shall be Orange
Research 1516 DGS series.
e. Diagnostics: display fault when detected and retain fault time and date of occurrence
within the unit control memory until cleared.
3. Display values: The unit control panel shall display the following information:
a.
b.
c.
d.
e.
f.
g.
h.
i.
j.
k.
l.
m.
n.
o.
p.
q.
r.
s.
Section Page 9 of 12
P.
Q.
R.
S.
Section 23 64 16
Centrifugal Water Chillers
T. Sound data: the centrifugal chiller sound pressure Level (Lp), in decibels (dB), with a reference
pressure of 20 micro-Pascal's, shall not exceed the values listed below. All values shall be
measured in accordance with ARI-575-2008, "Method of Measuring Machinery Sound Within
Equipment Space." No reduction in entering condenser water nor raising of leaving chilled water
temperatures shall be allowed in the sound data. Making such temperature adjustments does not
represent the loudest operating condition the chiller will experience while on the job, and could
mask sound problems that would otherwise occur. A minimum of 75% of the sound data points
shall be taken along the longest sides of the machine and 75% established as the minimum
percentage of total possible points used to determine sound levels. Provide sound attenuation as
necessary to meet specified sound levels; sound attenuation items to be installed by the
Contractor.
% LOAD
100
50
25
dB, A WEIGHTED
87
84
84
Section Page 10 of 12
Section 23 64 16
Centrifugal Water Chillers
V. Schedule:
EQUIPMENT NUMBER
Capacity, Tons
Maximum Full Load
Efficiency
Maximum Part Load
Efficiency (NPLV)
Evaporator EWT
Evaporator LWT
Evaporator Flow Rate
Maximum Evaporator Water
Pressure Drop
Evaporator Passes
Direction of Evaporator Water
Flow*
Condenser EWT
Condenser LWT
Condenser Flow Rate
Maximum Condenser Water
Pressure Drop
Condenser Passes
Condenser Water Box
Connection Side*
Condenser Water Box Inlet
Connection*
Condenser Water Box Outlet
Connection*
Power Characteristics
460V-3-60Hz
460V-3-60Hz
Section Page 11 of 12
Section 23 64 16
Centrifugal Water Chillers
PART 3 - EXECUTION
3.01
CENTRIFUGAL CHILLERS
A. Installation:
1. Each machine shall be factory-assembled, tested and shipped as one complete assembly.
Any field-assembly, exclusive of external water, power and automatic controls systems,
shall be performed exclusively by factory-trained technicians in the direct employ of the
chiller manufacturer or vendor and under the direct supervision of the factory.
Subcontracting this work to another party will not be permitted.
2. Oil cooler shall be connected to cooling source in accordance with manufacturer's
recommendations.
3. Piping connections and control sequence shall conform to the manufacturer's specific
requirements.
4. Minimum clearance between bottom of insulation and top of foundation pad shall be 2".
5. Wiring shall be installed in ducts or conduits running horizontally or vertically. Vertical
runs shall be bent to conform to machine surfaces. Free hanging capillaries and wires
shall not be accepted.
B. Chiller manufacturer shall provide:
1. Initial charge of refrigerant and oil to make each chiller operate as designed.
2. One quart of touch up paint in factory color
3. One set of factory maintenance manuals for each chiller. This set is in addition to the
typical operating and maintenance bulletins that are provided by the chiller manufacturer
and shall include complete teardown information together with a complete listing of all
internal parts. Each set shall include installation, assembly operation and maintenance
instructions, parts list, recommended spare parts and prices, maintenance and inspection
schedules and a listing of all components including starters with identifying description and
serial numbers. Each manual shall include one copy of the contractor's control and
interlock diagram; to include diagnostics of the chiller control panel operation. Complete
payment will not be made to the chiller manufacturer until this documentation is received.
C. Start-up service, training and chiller commissioning shall be performed by factory-trained
technicians in the full-time employ of the manufacturer. Technicians shall:
1. Inspect the completed installation, including power wiring, interlock wiring, controls and
piping.
2. Supervise testing, evacuation, charging, and start-up of the chillers.
3. Observe a minimum of two hours of operation for each chiller and submit a log of all chiller
operating conditions during this period.
4. Submit a statement that the chillers are installed in accordance with the manufacturer's
recommendations, and that safeties and controls are operating properly.
5. Provide a minimum of 4 hours of on-site training to the Owner.
END OF SECTION
Section Page 12 of 12
Section 23 65 13
Cooling Towers
1.05
1.06
1.07
Package cooling towers shall be as manufactured by Evapco, Marley or Baltimore Air Coil. We
prefer the induced draft counter flow type of cooling tower.
Package cooling towers shall have stainless steel cold water basins. Hot water basins shall be
galvanized with an additional appropriate surface treatment.
The cooling tower level control shall be electric type, consisting of electric stainless steel probes
housed in a grounded wave suppressor and a NEMA 4 enclosure. Consult with Engineering
Services for remote sensing applications.
The designer shall use Schedule 80 PVC piping on the condenser water return piping from the
cooling tower connection downstream to a point where the water reaches equilibrium during
cooling tower shutdown. The idea is to have PVC piping in locations that see intermittent wet and
dry conditions. I.E., for applications with a control valve to isolate the cooling tower from service,
the piping from the control valve to the cooling tower flange connection shall be PVC.
The outlet from the cooling tower shall come down with a full size tee fitting. The through side of
the configuration shall have a blind flange with a 2 full port ball valve with plug tapped into the
blind flange. The branch side of the configuration shall have a full size butterfly valve before
going on to the chiller as condenser water supply. This piping arrangement allows us to clean out
the cooling towers at the roof level and not contaminate the piping risers. The risers are cleaned
separately.
Consult with Engineering Services to determine the need for vibration switches on these cooling
towers.
The Designer shall consider access to cooling tower components requiring regular maintenance.
All access ladders shall be specified to extend to within 2 of the roof deck. All components
requiring regular maintenance 6ft above roof deck shall have a painted steel catwalk and rails for
fall protection. All components will be certified to 300lbs capacities.
Section Page 1 of 1
Section 23 65 23
Field-Erected Cooling Towers
Cooling Towers
1. The fill and fill support lintels shall be guaranteed against un-serviceability for a period of 20
years.
2. The drift eliminator and hot water distribution system shall be guaranteed against un-serviceability
for 5 years.
3. Remaining internal components shall carry the manufacturer's standard warranty of 1 year of
service.
Lintels:
Fill support lintels shall be made of heavy-duty cast iron or fiberglass structural shapes. Fill Shall be poly vinyl chloride (PVC) thermoplastic, especially formulated for use in cooling
tower applications. The top and bottom edges of the individual sheets shall be folded over a
minimum of 1/2" inch to improve strength. The finished individual fluted sheets shall be
solvent-bonded at all contact points and shall be 27 mils thick with minimum flute
openings. The fill shall be Munters 19060 or equal by Brentwood.
Drift eliminators:
Drift eliminators: shall be of the wave formed PVC type, 15-mil minimum sheet thickness, UV
protected. Support shall be of pultruded FRP structural shapes sufficiently sized and spaced
to permit a loading of 50 lbs./sq. ft. and shall be suspended from 5/16" diameter (minimum)
brass or stainless steel rods connected to stainless steel embeds in the underside of the roof
deck. Drift eliminators supported on the hot water distribution piping shall not be permitted.
Allowable drift shall be limited to 0.0005% of circulating water flow. Provide a framed
stainless steel access door for passage through the eliminators to the fill. Provide a 24" wide
FRP grating maintenance walkway from access opening to the center of each cell. A hot
dipped galvanized maintenance access ladder shall be provided from walkway to gearbox.
Gearboxes:
A vibration switch shall be supplied to protect mechanical equipment against excessive
damage due to a malfunction of rotating members. The vibration switch shall be mounted on
the gear reducer. The cooling tower manufacturer shall also supply a control module which
automatically provides a 15 second time delay upon fan start up to prevent false shut down.
An oil level switch shall be provided by the cooling tower manufacturer to provide protection
for sudden loss of oil or low oil level in the gear reducer.
a. An oil level sight glass, fill/drain line, and vent line shall be installed, terminating
outside the fan stack. All piping shall be stainless steel.
b. The gear box shall be manufactured by Amarillo.
Fan Assembly:
The fan shall be of a multi-blade design. The fan blades shall be wide-chord" FRP type with
hot dipped galvanized steel plate hub. Manufacturer shall be Hudson.
Drive Connection:
The motor shall be coupled to the gearbox by means of a flexible coupling. The motor shall
be located outside the airstream, and the drive shaft shall be the full floating type with flexible
couplings at both ends. The drive shaft shall be made of a composite material and
manufactured by Addax.
Water Distribution System:
The water distribution system for each cell shall consist of a centrally located header,
complete with side laterals, fittings and nozzles. All piping and fittings shall be schedule 40
PVC. Nozzles are PVC or ABS. Pipe laterals shall be secured to the tower walls with
stainless steel saddles.
Revision Date November, 2014
Section Page 1 of 2
Section 23 65 23
Field-Erected Cooling Towers
Tower Access:
A hot dipped galvanized steel access door shall be provided for roof deck access by
manufacturer. A hot dipped galvanized ladder shall be furnished by the manufacturer for
access from the fan deck level to the fill.
All components requiring regular maintenance 6ft above deck shall have ladders, a painted
steel catwalk and rails for fall protection. All components will be certified to 300lbs capacities.
Manufacturer: Tower Engineering
Level control:
The cooling tower level control shall be electric type, consisting of electric stainless steel
probes housed in a grounded wave suppressor and a NEMA 4 enclosure.
Section Page 2 of 2
Section 23 70 00
HVAC Equipment
1.02
1.03
Energy Conservation
A.
General: Emory has a sustainability goal of reducing total energy use by 25 percent per
square foot from 2005 levels by 2015. To help meet this goal, new construction and
renovation projects, as applicable, shall attempt to realize increased levels of energy
performance that contribute to achieving the required Energy and Atmosphere Prerequisite 1
Minimum Energy Performance credit and possibly Energy and Atmosphere Credit 1
Optimize Energy Performance under the current LEED rating system. The design team is
encouraged to evaluate strategies such as enthalpy wheels as discussed in section 1.15.
B.
Zoning: Zoning of building HVAC system into subsystems serving areas with common
environmental and occupancy requirements is typically required. Give consideration to
zoning techniques that accommodate individual after hour occupants with minimum operation
of areas not in use.
1.04
Laboratories
Section Page 1 of 4
A.
B.
Section 23 70 00
HVAC Equipment
In laboratories, excellent air circulation and ventilation is needed to create the correct
environment for research and for safety. Consult with Emory University Engineering
Services and Environmental Health & Safety Office early in the design phase for
applications for particular laboratories.
All BSL-3 labs shall have N+1 parallel and gas tight dampered filtration sets with DOP ports
for decontamination located in a secured secondary containment room adjacent to(or in
very close proximity) to the lab. Ducting shall be minimized between the lab and filtration.
Provide moisture eliminators in bag-in/bag-out enclosures if needed by the process. Any
booster fans or additional equipment requiring servicing in the ducts upstream or down shall
be N+1 as well, monitored by the controls front end and isolated with gastight dampers.
1.05
1.06
1.07
Transformer Rooms
Provide ventilation or mechanical cooling.
1.08
1.09
1.10
1.11
Section Page 2 of 4
Section 23 70 00
HVAC Equipment
coils should be sized so as to deliver 50 degree F air (as mixed) to the cooling coil at the
heating design ambient condition with the maximum specified outside air flow.
1.12
Vibration
To reduce wear and noise, specify that rotating equipment 5 horsepower and larger must be
dynamically balanced, tested and measured by the Contractor for displacement in X-Y-Z
horizontal, vertical and axial directions. To be acceptable, work shall comply with ISO standards
for velocity. Contractor shall provide a report of vibration readings in the closeout documents.
1.13
1.14
HEPA Filters
When HEPA filters are used, please do not install bag in and bag out type filters. Our
Environmental Health and Safety Office prefer to have standard HEPA filters in a standard type
housing. They prefer to do on-site decontamination procedures during filter change out. A
duplex parallel and redundant HEPA filter system to keep the laboratory functional during filter
changes is preferable.
1.15
Enthalpy wheels
The use of enthalpy wheels is encouraged in order to meet energy conservation targets and to
help achieve Energy and Atmosphere Credit 1 Optimize Energy Performance under the current
LEED rating system. As each case is specific, consult with Engineering Services on each
individual project to discuss DDC control and the layout of the enthalpy wheel system, including
what areas are to be exhausted, and to discuss manufacturers for a particular size range. In
most size ranges the wheel shall be manufactured with aluminum. General acceptable
manufacturers are Semco, Seibu Giken and Thermotech. Wheel control shall be accomplished
through the building automation system. No proprietary controllers shall be use. The variable
speed drive controlling the wheel must be located outside the unit cabinet. For manufacturers of
the energy recovery unit cabinet refer to the air handling unit section.
1.16
1.17
Expansion tanks
Use only bladder tanks with a full acceptance bladder. All vertical expansion tanks shall be
secured to the housekeeping pad using clips or brackets so as not to weld directly to the tank
itself. Accessories required at each expansion tank include a pressure gauge, valves to allow the
tank to be isolated and the water in the bladder blown down.(similar to function of B&G tank
purge valve) Acceptable manufacturers are Bell and Gossett, John Wood Company, Wessels
Company, Amtrol.
1.18
Section Page 3 of 4
Section 23 70 00
HVAC Equipment
required. Strive to locate these lines above a sink so that finishes are not damaged. Use of
emergency float switches can be considered as long as provided with an alarm output to the BAS
system. If not BAS system is readily available such as in a residence hall, the emergency float
switch shall shut down the fan coil unit. Fan coil units shall be located in an area that is
accessible for maintenance and service. One-inch filter racks and throwaway filters must be
provided for all fan coil units. Each coil is to have an isolation valve on the supply and return
side. The coils are to be connected with unions to facilitate easy removal. A twenty mesh strainer
is required on the hot and chilled water supply lines downstream of the isolation valve. The
strainer shall include a blow-down valve with cap. The piping shall include a standard hose drain
connection for flushing. Sufficient room must be provided to allow filters to be replaced without
bending the filter. Fan blades and blower wheels are to be constructed of galvanized steel or
aluminum, and shall be easily removable. Control valves shall be two-way non-modulating type
with actuators that are snap in pop-top type valve with quick connect wiring connections. Standalone thermostats that are used with fan coil units shall be 24 volt, have heating, cooling and off
switches and be able to be programmed for a specific temperature range that is not easily User
changed. If condensate pumps are required, the pumps must have a check valve. Fan coil unit
heating coils shall be sized for a 95F minimum LAT with 160F EWT. Fan coil units shall be
insulated with closed cell foam insulation. Fan coil units shall be as manufactured by Magic Air,
Trane, Carrier, International, Price, or McQuay.
Section Page 4 of 4
Division 26
Electrical Systems Narrative
Electrical Design
1.1 Electrical equipment shall be selected based on the life cycle cost. Alternatives may be
chosen with the approval of the university electrical engineer.
1.2 A typical new building at Emory University will require the following. Each building on the
main campus will be served from the Emory University 20 kV distribution system. It will be
served by a pad-mounted transformer(s) which is served by a 20 kV, G&W, pad-mounted
loop switch with enclosure. Primary and secondary cables shall be installed in concrete
encased, re-bar reinforced PVC duct bank with dyed red concrete. Limit the ductbank pour
to that required for the encasement. It is unacceptable to dump excess left over concrete
in the excavated area. The primary cables shall receive power from a re-connectable
Elastimold splice in the closest manhole. The primary cable shall have a fault detector
installed around the outer jacket of the cable with a fiber optic cable visible from enclosure
exterior. (Do not cut the jacket or tape shield to install the fault detector.) The secondary
cable in concrete encased duct shall enter underground and terminate in either insulated
case or metal clad switchgear. On the secondary only use PVC elbows to turn up into the
transformer compartment. On the primary only use Galvanized Rigid Elbows to turn up into
the transformer compartment.
Engineer shall review the secondary service entrance
routing method with the Emory Electrical Engineer. If the switchgear is below grade do not
come in the top! On buildings where ground fault is required on the main breaker there
shall also be ground fault on all feeder breakers in that gear. The transformer shall be
furnished with an Emory standard electric kwh/ kw demand meter and c.t.'s installed. The
meter shall be capable of being read remotely. Landscaping shall be placed around the
pad-mounted transformers and loop switches but shall not interfere or be placed within 10
feet in front of doors or within 4 feet in front of the meter.
1.2.1
For new buildings located on the east side of Clifton road, the utility may be
Georgia Power through a network-underground feed. Determining which utility
will be used should be discussed with Emory Energy and Utilities.
1.3 The design for each new building must include the design of the above requirements in the
scope of services. The pad-mounted transformer shall be installed at least 10 feet from the
building and 14 feet from exterior doors. There shall be at least ten feet clear space in front
of the doors of each transformer and loop switch. In large research buildings where
feasible, provide two pad-mounted transformers with double-ended switchgear with a
secondary tie-breaker to ensure continuity of service. Vault transformers and indoor
substation transformers are unacceptable.
1.4 The proper selection of all 20 kV equipment and service equipment is extremely critical at
Emory University. Refer to our more detailed design guide and standard 20 kV
specifications for all equipment in this area.
1.5 Emory University requires the use of pre-approved specific 20 kV splicers and preapproved meter technicians to verify proper connection and operation of meter. See the
Emory University Engineering Services for approval. Emory University also requires
independent testing of high voltage cable after installation and before energization by
Hood, Patterson and Dewar.
2.0
Design Conditions
2.1 The Emory University Campus Underground Distribution System is a 19.8 kV [19,800
Volts], 3 phase. 4 wire, solidly grounded wye connected system with source fault capacity
of 350 MVA. Insulation level shall be not less than 125 kV BIL.
3.0
Section Page 1 of 4
3.2
Division 26
Electrical Systems Narrative
space and equipment. This section is also a part of this design guide that links to the LITS
standards.
Route conduit for a data drop at each main HVAC digital control system control panel.
Coordinate with the mechanical discipline for locations.
4.0
Building Distribution
4.1 Building distribution shall be planned on a project basis based on the specific needs and
requirements of that building. Usually we see a 480/ 277, 3 phase, 4 wire switchgear with
main breaker with bus risers with dry type transformer(s) installed at each floor. The riser
requirement will change frequently based on job circumstances and we are not opposed to
conduit risers. On most Emory University buildings (all but very small buildings) we want to
see electrical rooms with panelboards at both ends of the building or in the building center.
In some cases with two electrical rooms on a floor a smaller closet may be allowed at one
end if approved by Engineering Services. Electrical rooms must be stacked to utilize
vertical chase arrangements, etc. It is unacceptable to feed an entire floor from only one
end of a large building. All corridors that are adjacent to these electrical rooms (sources of
power) must have accessible lay in ceilings. It is unacceptable to place an electrical room
behind a lobby area which contains a hard or inaccessible ceiling unless spare conduits
with a number and size as determined in consultation with Emorys Electrical Engineer are
installed to bridge this space. The spare conduits allow for future circuits to be run across
the hard ceiling. A typical requirement is for 10 each inch and 1 each 3 inch EMT
conduits across each hard ceiling space.
4.2 All electrical rooms must have at least 25% usable spare wall space after all equipment is
installed including miscellaneous control systems, Access Control Panel, Fire Alarm, etc.
They must be at least 6 feet wide by 8 feet deep with only electrical equipment installed
there unless a smaller closet is approved at one end of the building by Engineering
Services. Careful attention must be given to NEC Code Clearances. No laundry sinks,
storage provisions, etc. shall be permitted in these electrical rooms. Utilities that do not
serve this room shall not be routed through it. At least one 120 volt duplex receptacle shall
be installed in each electrical room. An unswitched or fail-safe emergency light of some
type must be installed in every electrical room and in every mechanical room in the
building. In addition a battery pack with two self-contained heads must be installed in the
main switchroom aimed at the front of the switchgear. Install another emergency wallpack in the Emergency Power Room aimed at the Control Panel. An updated copy of the
building riser or single line shall be mounted on the wall in the main switchroom in a frame
behind a clear plastic covering. When any changes are made to the electrical infrastructure
in a building, these changes must be shown on this riser.
4.3 On all new buildings, the Electrical Engineer shall do a thorough analysis of the nature of
building layout and load requirements and determine if more than one electrical room is
required per floor.
5.0
Section Page 2 of 4
5.2
5.3
5.4
5.5
5.6
5.7
Division 26
Electrical Systems Narrative
No electrical feeder conduits or service entrance conduits shall be run in the concrete floor
slab. Feeder circuits are defined by the NEC and include but are not limited to circuits
which serve panelboards, switchgear, dry type transformers, etc. All feeders shall be run
above ceilings through spaces after the slabs are poured. Individual branch circuit conduits
shall be allowed to be poured in the slab as long as one of the following is adhered to. The
conduit shall be inch EMT conduit or less. For the ground floor slab on the earth PVC
conduit shall be used. No electrical flexible nonmetallic tubing (smurf tube) shall be used.
No conduits shall cross in the slab.
Branch circuits 3/4 inch or less shall be permitted to be installed in the slab in a star pattern
spreading out from the panels if the following painting guidelines at the time of installation
are followed. The top of the bottom form which supports the poured slab must have a
release agent on it. The conduit path shall be sprayed with orange paint onto the top of the
form under each branch circuit conduit after installing conduit so that the paint outlines the
conduit location and hence routing path against the form. In most cases concrete is
actually pored the following day after this paint stripe has dried. When the slab is poured
and the form is removed the conduit route will then be painted on the bottom surface of the
slab by virtue of the wet concrete contact with the painted stripe. The paint will adhere to
the surface of the concrete and mark the routing of the conduit. This process is successful
even though the paint is dry when the concrete is poured. It is acceptable to use MC Cable
for branch circuits between the Panelboard and the last ceiling mounted junction box which
serves receptacles, switches, etc as long as it is not used above hard ceilings.
In lieu of the above painting scheme, it is acceptable to run the branch circuit conduits
down corridors and along walls when poured in the slab. It is also acceptable to run branch
circuits in EMT conduit exposed in ceilings. Provide maintenance duplex receptacles to
support maintenance functions around cooling towers, chiller coils and sufficient outlets in
all mechanical areas. Outlets shall be of the type approved for the particular location and
the environment. Use ground fault outlets in all locations required by the latest NEC.
Provide as built drawings of the electrical systems in all elevator systems to Emory.
The A/E shall in every case provide for access to lighting. All lighting fixtures must
be accessible using standard vertical devices such as standard size A-frame ladders
no taller than 14 foot, extension ladders no taller than 25 foot and only then if the
fixture is wall mounted with space to use the ladder and one-person lifts if needed
without the use of scaffolding, outriggers or special equipment. Any special
requirements must be brought to Emorys attention and be approved prior to Final CD
Issue. Articulated lifts are very expensive and are impractical to use at Emory. If person
lifts are required, they shall be provided as collateral building equipment. Storage space
for this equipment shall be provided in a logical place within this building. The Design
Team including the Architect, Interior Designer, Electrical Engineer and Lighting Consultant
must address maintainability as a part of the design process as described in the lighting
section of this Design Guide.
Indoor Lighting Further Clarification and Limitations: Ceiling lighting higher than 30 feet is
unacceptable. In stairwells lighting shall be installed so that it is mounted underneath the
landing above or on the wall. In either case the fixture shall be mounted no more than 16
feet above the landing. For fixture mounted higher than this above stairs a winch system
must be provided to raise and lower fixtures. All lighting must be controlled automatically
as required per the latest Energy Codes and ASHRAE Standards. This shall normally be
accomplished by using motion detectors in every space. If there is a special purpose
space, which the consultant thinks that a lighting relay system must be used, the Emory
Electrical Engineer must approve this and that system shall be a Wattstopper system. Use
of the Building Automation System to control lighting should be investigated but must be
specifically approved by Engineering Services.
Outdoor Lighting: For outdoor lighting at Emory the emphasis should be placed on security
lighting but at the same time we want to minimize the up light and eliminate lighting
Section Page 3 of 4
5.8
Division 26
Electrical Systems Narrative
trespass to the neighborhood surrounding the campus with the primary goal of providing
good security lighting. Avoid using light fixtures which are pointed so that the lighting is
directed upward. Emorys campus standard Mainstreet lampposts shall be provided with a
side shield, cone shaped top shield kit, and night sky cap. (Outdoor lighting shall be high
pressure sodium unless color is critical to illuminate a sign or the face of a building. In
only those cases metal halide is acceptable. Emory is using LED in various applications
and we would like the consultant to specify as an alternate the use of 3500 degree Kelvin
Color Temperature LED fixtures for some exterior applications. These applications include
wall sconces, wall packs and floodlighting. Bollards and recessed ground mounted
fixtures are unacceptable. Fixtures in handrails and fixtures in trees are unacceptable.
Step lights use shall be minimized and only used for stairs, etc. where there is no other
alternative. The preferred method for walkway or area lighting is either Campus Standard
Lampposts in the area or wallpack fixtures with Uplight cutoff mounted on the building.
Directional HPS floodlights must be approved where required. We are transitioning to LED
in limited instances, but all applications must be approved by Engineering Services in
advance. The Emory University Campus Standard Lampposts or an approved LED
replacement shall be used for all lamppost applications. See the Emory University
Electrical Engineer for standards and any deviation must be approved. For parking deck
design and construction, please note that Emorys Transportation and Parking Services
maintains specifications for lighting in these areas.
In general all Emory Buildings must be designed and constructed in accordance with the
latest LEED (Leadership in Engineering and Environmental Design) Requirements. Emory
has a very structured process whereas a LEED Consultant is used for planning and
evaluating buildings for LEED Compliance. In some cases it may be the architect on the
project if they are qualified.
Section Page 4 of 4
Section 26 00 00
Electrical General Requirements
1.3
Electrical Permits
Require the Contractor to obtain electrical permits from DeKalb County. Absolutely no work may begin
without first obtaining the proper permits. Emory High Voltage Electrical Shop will not open switches for
outages until DeKalb Electrical Inspector has signed off.
1.3.1 Control of Hazardous Energy Program: Emory University has developed, in conformance with
OSHA requirements and Federal Regulations 29 CFR 1910.147 and 1910.331-335, procedures
for the isolation of all energy sources prior to the servicing or maintenance of equipment and
machinery. This program applies specifically to outside contractors and requires that anyone
hiring outside contractors inform the contractor of the existence of the program. In addition, the
following three activities must occur.
1.3.1.1 Outside Contractors must inform the Emory University Project Manager of any lockout
activity that they will be performing, along with the procedures they will be using as well
as the name of all persons who will be working on Emory gear.
1.3.1.2 The Emory University project Manager must inform the outside Contractors of the same
information regarding any lockout/tag out activities that Campus Services is engaged in
while the outside contractor is on site.
Section Page 1 of 7
Section 26 00 00
Electrical General Requirements
1.3.1.3 Campus Services and outside Contractors both shall lock-out/tag-out equipment to
ensure the safety of everyone involved in the project.
1.3.2
Keep in mind that the "Control of Hazardous Energy" includes sources of electrical, mechanical,
hydraulic, pneumatic, chemical, thermal or any other energy that is stored and can be released to
harm people. Obviously, to conform with the above requires coordination with the entire project
team. The Designer is encouraged to pursue this early in the Project with the Emory University
Project Manager.
1.4
1.4.1
Avoid Repetitions
Do not repeat or contradict information contained in the project "front end" [Division 00 - Bidding
Requirements, Contract Forms, and the Conditions of the Contract and Division 01 General
Requirements]
1.4.1.1 The project "front end" establishes the rules, procedures, and policies under which all of
the work of the Contract will be executed. Division 26 must not have its own "front end" or
rules, procedures, and policies.
1.4.1.2 The Emory University "front end" has been carefully crafted to include requirements and
procedures important to Emory University. The Emory University "front end" has been
reviewed and approved by Emory University's legal and insurance counselors. The
Emory University "front end" includes information with potentially significant legal
consequences, which should not be modified or superseded cavalierly, and the Emory
University front end should include all of the information applicable to Division 26 and all
other "technical" divisions.
1.4.1.3 The contention that "electrical subcontractors do not read the project front end" is not
acceptable and recapitulating portions of Divisions 00 and 01 in Division 26 only assures
the subcontractor that they have no reason to review Divisions 00 and 01.
1.4.1.4 Section 26 00 00 - Electrical General Requirements should clearly reference the project
"front end" for all information related to administration of the Contract, rules, procedures,
and policies including, without limitation, bidding procedures, submittal requirements,
substitution requirements, record document requirements, maintenance manual
requirements, definitions of terms, instruction of Owner's personnel, and general
warranty information [specific warranty requirements must be specified in the section
specifying the item to be warranted].
1.5
1.5.1
Special Warranty
In general, Emory University wants a complete, comprehensive written warranty from the General
Contractor agreeing to repair and provide complete service of all electrical systems in their
entirety for one year from Date of Substantial Completion, except as indicated below. The
General Contractor will likely require an identical warranty to itself from its electrical
subcontractors.
1.5.1.1 Normal routine Owner maintenance is sometimes excluded from the warranty and if so,
must be clearly itemized to prevent disputes about service provided by the Contractor
and maintenance provided by Emory University.
1.5.1.2 Complete service and maintenance by the Contractor for one year is required for some
electrical equipment as directed by Emory University Project Manager.
1.5.1.3 Warranty and Service Start Dates: See Guideline Divisions 00 and 01. In general, all
warranties and service agreements shall start on Date of Substantial Completion of
project or the date the system is fully installed, tested, and accepted in writing by Emory
University, whichever is later.
Section Page 2 of 7
Section 26 00 00
Electrical General Requirements
2.0
2.1
2.1.1
Products
Power Outlets
The following general guidelines apply to power outlet locations.
2.1.1.1 Corridors and Lobbies: Space duplex outlets not over 25 feet apart in any direction. Do
not combine on the same circuit corridor and lobby outlets with office outlets to avoid
interference with office equipment and computers. Corridor and lobby outlets should be
on a separate circuit so that these outlets can be switched off at the breaker panel.
2.1.1.2 Closets and Storage areas: Provide outlet(s) in all storage areas including GFCI
receptacles if sink is present.
2.1.1.3 Not used.
2.1.1.4 Elevator Cabs: Provide duplex outlet for cleaning and maintenance. Provide as built
drawings of the electrical systems in all elevator systems to Emory.
2.1.1.5 Offices: Provide at least one duplex convenience power outlet on each wall and space
not over 10 feet on center.
2.1.1.6 Rest rooms: Provide at least one GFCI receptacle in every restroom.
2.1.1.7 Mechanical Equipment Areas: Provide maintenance duplex receptacles to support
maintenance functions around cooling towers, chiller coils and sufficient outlets in all
mechanical areas. Outlets shall be of the type approved for the particular location and the
environment. Use ground fault outlets in all locations required by the latest NEC.
2.1.1.8 Laboratories: Each lab should have at least one duplex convenience power outlet on the
emergency power system. Outlets shall be hospital grade red. Assume emergency
power outlet load of 1500 watts unless otherwise approved or directed. Space nonemergency power duplex outlets at 3 feet on center, except space 12" on center for
plugmold [see 26 05 00 for additional plugmold requirements]. Provide Ground Fault
protection receptacles for outlets in labs at benches with sinks where personnel can
become part of circuit to ground. Provide maximum of four duplex outlets per circuit. All
freezers, incubators, cold rooms, etc. shall be on emergency power.
2.1.1.9 Separation: Separate power wiring raceways away from communication raceways by one
foot (12") minimum to avoid noise to computer work stations caused by EMI.
2.1.1.10
Electrical Receptacles that serve Water Coolers and water bottle-refilling stations
shall be GFCI.
2.2
2.2.1
2.2.2
2.3
2.3.1
3.0
3.1
3.1.1
Execution
Building Considerations
Security and Access Control: Some doors may need electrically connected security and access
control. Review final door schedules with Emorys Security Systems Shop and ensure that
electrical requirements for electrically connected doors are properly covered.
3.1.1.1 Corridor Smoke/Fire Doors: May need power and interconnection with smoke alarm
system. Freestanding systems shall be 120 VAC. System components shall be 24 VDC.
Obtain approval of type of door hardware and power characteristics from Emory
University Electrical Supervisor through the Emory University Project Manager.
Section Page 3 of 7
Section 26 00 00
Electrical General Requirements
3.1.1.2 Exterior doors: most exterior doors will have handicap control or other electrical
requirements. When this is not the case, care must be taken to make future provisions
so that an electrical feed can be extended in the future. This issue is critical in glassenclosed lobbies or other spaces where no apparent conduit path is available. This
requirement should be coordinated with the Architectural Section 08 00 00 Openings and
Doors.
3.2
3.2.1
Building Considerations
Emory University requests that the Consulting Electrical Engineer coordinate with the architect to
insure that all of the following is included architecturally. If there are any questions about
compliance or deviations from these requirements consult the Emory University Electrical
Engineer. All deviations must be discussed and approved.
3.2.1.1 All electrical rooms on every floor, including the main switchroom shall have at least 25%
usable lateral spare wall space at the conclusion of construction. This is after all
equipment is installed including miscellaneous control systems, Access Control Systems
Panel(s), Fire Alarm, etc. This space shall be allocated for the future addition of
panelboards at the normal mounting height. All sprinkler piping, heads and fittings shall
be located so that they are not directly above any electrical equipment. Egress doors in
all electrical rooms with a panel or switchgear rated 1200 amperes or more must open in
the direction of egress and must contain panic hardware.
3.2.1.2 There must be dedicated electrical rooms in appropriate locations on each floor to house
panelboards, dry type transformers, etc. These electrical rooms should be located as
close to the center of the building areas served and should be stacked to utilize vertical
chase arrangements etc. All electrical rooms must be at least 6 feet wide by 8 feet deep
or larger if required with only electrical equipment installed there. Careful attention must
be given to NEC Code Clearances. No laundry sinks, storage provisions, etc. shall be
permitted in these electrical rooms. Utilities that do not serve this room shall not be
routed through it. At least one 120-volt duplex receptacle shall be installed in each
electrical room. An unswitched or fail-safe emergency light of some type must be
installed in every electrical room, every mechanical room and in every security closet in
the building. In addition a battery pack with two self-contained heads must be installed
in the main switchroom aimed toward the main switchgear. In the Emergency Power
Room a head shall be aimed toward the Control Panels. On all new buildings the
electrical engineer shall do a thorough analysis of the nature of building layout and load
requirements and determines if more than one electrical room is required per floor. In
some cases an electrical closet may be approved for a remote location after careful
consideration. This special case must be approved by Emory Engineering Services.
Power to the Access Control Panel shall be provided by a cord connection to a dedicated
120 volt receptacle below the panel. Reference the Electrical Narrative Section of these
design standards for further building considerations.
3.2.1.3 All lighting fixtures must be accessible using standard vertical devices such as
standard size A-frame ladders no taller than 14 foot, extension ladders no taller
than 25 foot and only then if the fixture is wall mounted with space to use the
ladder and one-person lifts if needed without the use of scaffolding, outriggers or
special equipment. Any special requirements must be brought to the Emorys
attention, and be approved prior to Final CD Issue. Articulated lifts are very expensive
and are impractical to use at Emory. If person lifts are required, they shall be provided
as collateral building equipment. Storage space for this equipment shall be provided in a
logical place within this building.
3.2.1.4 Indoor Lighting Further Clarification and Limitations: Ceiling lighting higher than 30 feet is
unacceptable. In stairwells lighting shall be installed so that it is mounted underneath the
landing above or on the wall. In either case the fixture shall be mounted no more than 16
feet above the landing. For fixture mounted higher than this above stair landings a winch
system must be provided to raise and lower fixtures. All lighting must be controlled
Section Page 4 of 7
Section 26 00 00
Electrical General Requirements
automatically as required per the latest Energy Codes and ASHRAE Standards. This
shall normally be accomplished by using occupancy (vacancy) sensors in every space. If
there is a special purpose space, which the consultant thinks that a lighting relay system
must be used, the Emory Electrical Engineer must approve this and that system shall be
a Wattstopper system. Do not use the Building Automation System to Control Lighting
unless specifically approved by Engineering Services.
3.2.1.5 Put spare conduits in all recessed panelboards to receive future cables from these spare
breakers. Run these spare conduits from the panelboards to the lay in ceiling above or
below. There are some cases depending on the project where, because of Value
Engineering for a particular building, Emory may agree to allow MC cable for each feeder
from the panel to the first junction box at the area of utilization, although MC cable is not
acceptable above hard ceilings. If that occurs on a project and that is allowed it is even
more imperative that spare conduits from the panel to the lay in ceiling above be
installed. In places where this did not occur it is almost impossible without extensive
wall board work to come out of the panel in the future.
3.2.1.6 Dry type transformers, etc. must be placed in respect to panelboards and other
equipment so that an electrician does not have to reach over the transformer, etc. to
operate a breaker or service a panel, etc. It is unacceptable to put a dry type transformer
on the floor directly underneath a panelboard.
3.2.1.7 All electrical equipment shall be installed with adequate spacing around electrical
equipment in accordance with the NEC. In the case of equipment facing each other with
an aisle between, assume that both surfaces are live for the purpose of establishing the
spacing in front of this equipment. In all cases proper spacing must be coordinated
between disciplines and trades during design and construction. If bus duct is used for
risers, then adequate code clearance must be provided in front of plug in breakers to the
front of equipment on opposite walls.
3.2.1.8 The 120-volt circuit to the elevator including the conduit shall be dedicated to the
elevator. All wiring in the hoistway or Elevator Machine Room must be directly related to
the elevator.
3.2.1.9 The building single line shall be framed behind clear plastic and mounted on the wall in
the main switchroom and shall be updated upon renovations the electrical infrastructure.
3.2.1.10
The architectural room numbers shown on the plans must agree with the actual
final room numbers that are assigned
3.3
3.3.1
3.3.2
3.3.3
3.3.4
3.3.5
3.3.6
3.3.7
Drawing Content
Show voltages, breaker sizes and wire and conduit sizes on riser diagram. Always show a riser
diagram.
Furnish a separate single line which shows how the new building ties into the existing 20 kV
distribution system.
Furnish an electrical site drawing which shows the transformer, loop switch and generator in
inch or 1/8 inch scale.
Show a single line on the grounding. Also include special grounding requirements on any
specialized equipment. Don't leave this design to the contractor.
Include lighting fixture schedules on the drawings. Schedules must specify as a minimum the
fixture type, manufacturer, part number, voltage, wattage, and lamp type.
Furnish a full panelboard schedule for each panel indicating spares, spaces and load information.
Indicate spares on this schedule. Furnish a minimum of 20 to 25 percent spare breakers or
space in each panel or at each panel location. This applies to both 480 volt and 208/120 volt
panels. There are no exceptions to this rule. Add additional panels if required to accomplish this.
All circuits must be labeled in the panelboard. At the conclusion of the construction all final
actual room numbers must be used on the final panelboard schedules. A note must be put on all
panel schedule drawings to reflect this.
For all new construction and renovations involving demolishing or installing new panelboards, a
Fault-Current Study must be completed for the affected area. The Available fault current (AFC)
Section Page 5 of 7
Section 26 00 00
Electrical General Requirements
must be shown on the electrical riser diagram or on the associated electrical panelboard
schedules.
3.4
3.4.1
3.5.1
Section Page 6 of 7
Section 26 00 00
Electrical General Requirements
the Contract Documents to clearly show all deviations from the original Contract
Drawings, the precise location of each item of work, and all field changes. Progress
Drawings must be submitted to and approved by Emory University as a prerequisite to
final payment to the Contractor. See Division 01 - Internal Requirements and Campus
Services Document Delivery Standards for more detailed Progress Drawing preparation
and submission requirements.
3.5.1.5 Electronic Drawings: Provide electronic copies of all as-built record documents, both
drawings and specifications. Drawings shall be compatible with the latest Auto Cad
edition that Emory is using at the time and specifications and written documents shall be
Microsoft Word compatible. Refer to the Campus Services Document Delivery Standards
for more detailed information on generation and format of Auto Cad drawings
3.6
3.6.1
Section Page 7 of 7
Section 26 01 00
Basic Electrical Systems Testing
by Electrical Contractor
Cleaning
1.1.1 Upon completion of the work and prior to testing and commissioning where applicable,
require the Contractor to thoroughly clean all electrical devices to remove grease, metal
cuttings, dirt, protective covers, and other foreign substances.
1.2
Testing
1.2.1 Require the Contractor to test all work for shorts, grounds, and open circuits.
Require the Contractor to make the following inspections and tests, and certify in writing
that all tests and inspections have been made, and that all problems and defects have
been properly corrected. The transformer secondary cables must be checked with a
megger for shorts and/or phase rollovers prior to energizing the transformer for the first
time.
1.2.1.1
Visually check all cables and connections.
1.2.1.2
Make continuity checks for all power. control, and signal cables and
conductors
1.2.1.3
Make insulation resistance tests for all 600V power cables and conductors.
1.2.1.4
Check all AC and DC control circuits for open and short circuits.
1.2.1.5
Exercise all motor starters from motor control center push buttons.
1.2.1.6
Check motors for proper rotation and measure motor current under load.
1.2.1.7
Comply with Guideline Section 26 30 00 for testing of emergency power
generators.
1.2.1.8
Test Procedure: In general, comply with National Electrical Code NFPA 70
Article 700-4 [a] through [e].
1.2.2 Require the Contractor to hire an independent testing agency to perform infrared
scanning of all conductor terminations to all equipment shown on the building riser
diagram. This testing must be done a couple of months after the building is occupied.
Furnish a written report which includes the image and description of each problem area.
1.3
Commissioning
1.3.1 Contact the Emory University Electrical Engineer, through the Emory University Project
Manager, before energizing any 19,800V, 240V, 480V and 208V main power distribution
equipment. Any new building which is energized from the Emory System for the first time
must have approval by the DeKalb County Electrical Inspector and the Emory Electrical
Engineer. One week minimum notice is required prior to the date that the building is
energized.
1.4
Test Reports
1.4.1 Reports, operations and maintenance manuals and progress (as-built) drawings shall be
submitted to the Emory University Project Manager. Include two copies minimum for the
Electrical Engineer. Refer to Division 01 for additional as-built drawing requirements.
1.5
Section Page 1 of 1
Section 26 05 00
Basic Electrical Materials and Methods
Clearance
1.2.1
NEC code clearance must be provided around all electrical equipment including that
furnished by the mechanical contractor.
1.3
1.4
Fireproofing
1.4.1
Fireproof all exposed primary cables in manholes in accordance with the project
specification.
1.5
Circuit Breakers
1.5.1
Provide breakers rated by a fault coordination study; minimum interrupting capacity
shall be determined by a coordination study. Breakers shall be power quick-make,
quick-break, trip free, circuit breakers with inverse time characteristics and bolted bus
connections [plug-in breakers are not acceptable]. Panelboard and Switchgear
manufacturers: Square D, General Electric, Cutler Hammer and Siemens.
1.5.1.1
Provide minimum 20 ampere circuits for lighting and power. Keep all
lighting and power circuits separate with dedicated separate
lighting and power panels, unless impractical and approved by E.U.
Electrical Engineer. The electrical distribution and metering
arrangement must comply with the Georgia Energy Code, which requires
special metering considerations, which may lead to special distribution
system layout.
1.5.1.2
Provide common trip for all multiple pole breakers. Do not use single
pole breakers for Multi-pole applications.
Section Page 1 of 4
1.5.1.3
1.5.1.5
Section 26 05 00
Basic Electrical Materials and Methods
Ground Fault Circuit Interrupters: Provide ground fault interrupters for all
exterior circuits including outdoor lighting of all types and all circuits in
wet areas such as Toilet Rooms, Kitchens, Wet Labs and for Water
Coolers.
Provide ground fault protection on all feeder breakers in the Main
Service Switchgear or Switchboard where we have ground fault on the
main breaker.
1.6
1.7
Motors
1.7.1
1.8
Nameplates
1.8.1
Provide mechanically attached [not adhered] engraved white on black nameplate
with minimum 1/4" high lettering on each panelboard and disconnect switch.
1.8.1.1
Circuits: Label each receptacle plate with panel number and circuit
number.
1.8.1.2
Equipment Nameplates: Clearly identify each field component with
supply panel number.
1.9
Lighting Fixtures
1.9.1
When installed in Accessible Ceiling Grids shall be secured to both the structure and
the grid.
1.9.2
Flexible whips from Junction boxes to fixtures shall not be longer than 4 foot.
Provide high-energy efficiency motors appropriate for use and location. Dedicated
motors used for systems such as fire pumps and smoke exhaust fans may not need
to be energy efficient. For multi-speed motors, select motor and speed control and
selection devices for high efficiency at all expected operational speeds, not only
maximum or design speed. Variable Speed Controls shall be furnished so that
resonant frequencies, which would cause damage to mechanical equipment, shall be
blocked out.
1.7.1.1
Motors less than 1/2 HP: Generally, provide single phase, 120 VAC, 60
Hz.
1.7.1.2
Motors 1/2 HP and Larger: Generally, provide 480 VAC, 3 phase, 60 Hz
where available.
1.7.1.3
Coordination Required: Coordinate motor selection with mechanical and
other equipment's requirements for high-energy efficiency and low
maintenance.
1.7.1.4
Emory University's standard variable speed drive shall be used.
Section Page 2 of 4
1.9.3
Section 26 05 00
Basic Electrical Materials and Methods
All fixtures shall have supply-side quick disconnects for maintenance purposes.
1.10
1.11
Plugmold
1.11.1
Plugmold 2000 is not typically approved for use at Emory University. Use Plugmold
3000 WM, 4000 WM or 6000 WM unless otherwise approved by Emory University.
1.12
1.13
1.14
Section Page 3 of 4
1.14.3
1.14.4
Section 26 05 00
Basic Electrical Materials and Methods
walk through mode if available on the sensor. Disable the photosensitivity control
mode also. Acceptable manufacturers are Greengate, Hubbell, Sensor Switch or
Wattstopper.
On some projects relay panels may be required because of the nature of the special
purpose space but should be kept to a minimum. If relay panels are required they
shall be Wattstopper.
Daylighting controls can be used in lobbies and other areas with large windows.
Acceptable manufacturers are those noted in above under occupancy sensors.
1.15
Conduit
1.15.1
1.16
Equipment Identification
1.16.1
For equipment located above ceiling, in addition to a label on the device, labels are
to be permanently affixed to the ceiling grid as near to the item as possible using
epoxy glue. Where hard ceilings are used, the label is to be affixed to the frame of
the access panel for the unit. Labels are to be black core white or beige Bakelite.
The lettering is to be 3/8" inches high. The minimum label size is 3/4' wide by 2"
long. Labels for equipment are to identify the item and designation.
1.17
Use EMT conduit inside buildings including that in the slab unless subject to physical
damage. Use Rigid Schedule 40 PVC in the basement slab. If subject to physical
damage use rigid galvanized or IMC conduit. MC cable is not allowed unless
approved by the E.U. Electrical Engineer. Non-metallic flexible conduit is not
acceptable. A pull string must be left in all spare conduits. Conduit shall not be
supported from the ceiling grid system but from the building structure instead. In
cooling tower locations Sunlight Resistant Schedule 40 Rigid PVC Conduit is allowed
unless the Consulting Engineer determines that it is subject to physical damage.
Section Page 4 of 4
Section 26 08 00
Commissioning of Electrical Systems
Section Page 1 of 1
Section 26 10 00
Medium-Voltage Electrical Distribution
(Above 600 Volts)
1.3
Primary Power
1.3.1
The Emory University Campus Distribution System is 19.8 kV [19,800 Volts], 3
phase. 4 wire, solidly grounded wye connected system with source fault capacity of
350 MVA. Insulation level shall be not less than 125 kV BIL.
1.4
Service Connection
1.4.1
Every building must include electrical 20 kV design from an existing manhole to a
new building. The Consulting Engineer shall determine which manhole to secure 20
KV service feed from, verify splice possibilities, and shall route the ductbank on
power plans as to the exact routing. Manholes shall be no more than 400 feet apart
and shall have oversized 32-inch diameter covers to facilitate wire pulling. A typical
service for a new building shall consist of a 20 kV G&W pad-mounted loop switch
with enclosure, pad mounted transformer(s) and primary and secondary cables that
shall be installed in a concrete encased, re-bar reinforced PVC duct. On the
secondary, only use PVC elbows to turn up into the transformer compartment. On
the primary only use Galvanized Rigid Elbows to turn up into the Transformer and
Loop Switch.
1.4.2
The pad-mounted transformer shall be installed at least 10 feet from the building and
14 feet from doorways. There shall be at least ten feet clear space in front of the
doors of each transformer and loop switch. Provide pad-mounted transformers.
Supply each transformer with a feeder coming from the loop switch. In large
research buildings where feasible, provide two pad mounted transformers with
double-ended switchgear with a secondary tie-breaker to ensure continuity of
service. Use Emory Standard Specifications. The service capacity of the
transformers must be determined based on a load analysis of the connected building
loads. The transformer must have 50% spare capacity over calculated load. Any
new building which is energized from the Emory System for the first time must have
approval by the DeKalb County Electrical Inspector and the Emory Electrical
Engineer. One week minimum notice is required.
1.4.3
Pad-Mounted Primary Service Loop Switches: Provide one 3 pole, 27 kV, 630 amp,
40,000 Amperes A.I.C. fault current rated loop switch for each building. Provide at
least one spare position to accommodate future primary circuit connections. Each
loop switch shall contain fault detectors on each phase of each feeder. Fault
Detectors shall be Power Delivery Products, Inc. Model 20-0456-1000A for 500 MCM
cable and Model 24-0450-400A for 1/0 cable. Fault detectors shall be approved prior
to installation. The loop switch shall be manufactured by G&W Electric Co.
1.4.4
The re-connectable splices and elbows shall be manufactured by Elastimold.
Section Page 1 of 3
1.4.5
Section 26 10 00
Medium-Voltage Electrical Distribution
(Above 600 Volts)
1.5
Twenty kV Equipment
1.5.1
All 20 kV equipment including loop switches, pad mounted transformers, primary
cable, lightning arrestors, cable elbows, 20 kV splices, primary ductbank and
manholes shall be specified using Emory University's Standard Guide Specification.
See the Emory University Engineering Department for these specifications. All of our
20 kV cable, devices and equipment is tightly specified and we expect full
compliance with Emory University's standards by the Consulting Engineer.
Complete actual details shall be shown for splice locations in the manholes, etc.
Simplified typical details are not acceptable.
1.6
Drawings Depicting 20 kV
1.6.1
Emory University standard details shall be used for manhole construction, ductbank
construction, transformer/ pad installation and loop switch/ pad installation. For new
buildings the placement within the loop shall be depicted on a partial 20 kV single
line drawing. Manhole splicing details shall be shown for every manhole, which is
impacted by the project. 'Typical' splice details are not acceptable. Show the actual
configuration including modifications, which is required by the project. The actual
configuration shall include physical location of all splice locations and cable locations.
Both before and after configurations shall be shown. There shall be at least 3/4 wrap
by the cable between the splice and the point of cable exit from the manhole.
Elevations of all duct banks including wire content of conduit must be shown where
leaving manholes, loop switches, transformers, etc. All cables in manholes shall be
fireproofed. Splice bodies shall be properly grounded in manholes.
1.6.2
We would like for one person from the Consulting Engineering firm to be closely
involved with every project from a 20 kV standpoint. This person would formally
review and check all drawings and specifications for compliance with Emory
University's standard.
1.7
Metering
1.7.1
1.8
Each pad-mounted transformer shall have the most current model of General Electric
kV Multifunction Electricity Meter with 4-Channel recorder, advanced power quality,
fast voltage monitor and harmonic analysis functions activated. Include KYZ output
board. Current transformers for use with the meters will have minimum accuracy of
1.0%. Normal and Alternate display modes will provide the standard program for
factory programmed kV Meters. See Emory Energy Engineer for current type and
specifications. Install a 1 inch PVC conduit containing an 18 gage twisted pair cable
between the meter on the transformer and the main switchgear in the building. On
all new buildings the Electrical Contractor shall arrange for the Emory Utility
Engineer to check final wiring connections on the electric meter and to certify the
proper operation.
Section Page 2 of 3
1.8.1
1.8.2
Section 26 10 00
Medium-Voltage Electrical Distribution
(Above 600 Volts)
The 25 kV cable shall have copper conductor, EPR - 100% level insulation, and
copper tape shield with an overall jacket. See Emory Electrical Engineer for more
detailed information. All new cable must be Hi-pot tested to the full level
recommended by the manufacturer. Tested shall be done by Hood Patterson and
Dewar or an independent electrical testing company approved by the Emory
Electrical Engineer. The reports shall be sent to the Consulting Engineer and Emory
University within 5 working days of the test. On all new buildings the Electrical
Contractor shall use a 20 kV cable splicer approved by the Emory Electrical Engineer
to do all splicing.
The 25 kV high voltage cable shall be manufactured by Okonite, Southwire,
Prysmian, Aetna, or General Cable. All cable must be manufactured in the USA.
1.9
1.10
Section Page 3 of 3
Section 26 20 00
Electrical Service and Distribution
1.3
Section Page 1 of 3
1.3.1.2
1.3.1.3
1.3.1.4
1.3.1.5
1.3.1.6
1.3.1.7
1.3.1.8
1.4
Section 26 20 00
Electrical Service and Distribution
Section Page 2 of 3
1.4.1.5
Section 26 20 00
Electrical Service and Distribution
panelboard size and circuit capacity for all laboratory and potential
laboratory modules.
Emergency Shut-Off of Power: Computer and data processing rooms,
and shop panelboards shall have emergency shut-off devices located
away from telephones and light switches. Clearly label as "Power
Disconnect".
1.5
Voltage Regulation
1.5.1
Design voltage regulation to maintain voltage to within 5% at all outlets. Finer
regulation will be provided to accommodate specific users on an as needed basis
through the use of voltage regulating equipment provided as part of the specific user
equipment. Equipment voltage must be specified to match building. For example,
do not use 230 V equipment on a 208 V system.
1.6
Grounding
1.6.1
Provide green equipment grounding conductor in each building riser, in each feeder
circuit, to each 3 phase motor circuit, to each fixed device branch circuit, to each
receptacle circuit, and to each lighting circuit. 'Quiet' power systems will require
'quiet" grounding. The use of conduit as a sole means of grounding is unacceptable.
1.6.2
All flexible metallic conduit shall be type MC with a green wire ground. Lengths shall
not be greater than 10 feet unless otherwise approved.
1.7
1.8
Neutral Conductors
1.8.1
All neutral conductors for lighting and power shall be full size and treated as currentcarrying conductors.
1.8.2
Oversize neutrals to 200% if the application dictates the use of a K Rated
transformer or where serving computer servers and mainframe equipment.
1.9
Transformers
1.9.1
Low voltage distribution transformers should be K-rated where the Consultant
determines they are required in server rooms or AV equipment, etc. depending on
load type. Generally, low, medium and high non-linear harmonic loads should have
K-4, K-13, and K-20 rated transformers, respectively. The type of dry type
transformer required shall be determined and specified by the consultant.
Section Page 3 of 3
Section 26 29 00
Variable Speed Drives
Section Page 1 of 1
Section 26 30 00
Standby Power Generator Systems
Section Page 1 of 3
1.1.7
1.1.8
1.1.9
Section 26 30 00
Standby Power Generator Systems
1.2
1.3
Section Page 2 of 3
1.3.4
1.3.5
1.3.6
Section 26 30 00
Standby Power Generator Systems
main switchgear. In the Emergency Power Room install emergency power heads aimed
at the Control Panels. These battery packs are required even in buildings which contain
a generator for emergency lighting.
Environmental Control Rooms: Environmental control rooms, such as warm rooms, cold
rooms, and freezers are not always supported by emergency power but often are. They
may need to be supported by the emergency power system on a project specific basis.
Laboratories: In each lab at each bench provide at least one 120 VAC, 20 ampere outlet
supported by the emergency power system to maintain operation of critical experiments,
equipment, refrigerators and other items. Additional emergency power outlets may be
needed as described in project program. Outlets supported by emergency power
system should be red color hospital grade. Emergency lighting in each lab must also be
put on the emergency circuit with controls to provide lab users capability to override the
emergency lighting if they must 'black out' the room.
Consider UPS back-up for critical system supported by generator power. NFPA allows up
to 10 seconds for generator and transfer system to provide full voltage after loss of
normal power.
1.4
Identification
1.4.1 Systems supported by emergency power must be clearly identified and labeled. Provide
emergency power labels on emergency lighting system light fixtures and all emergency
power panels. Show panelboard and circuit numbers on a label at each receptacle.
1.5
Testing
1.5.1 Emergency power systems must be tested by load bank to full load capacity. Require
the Contractor or generator subcontractor to provide the load bank, all equipment, all setups, all testing, and written documentation and test report. There will also be an
additional test as soon as the building is occupied. Emory will open Loop Switch serving
the building with the Architect, Consulting Electrical Engineer, Consulting Mechanical
Engineer, General Contractor, Electrical Contractor, Mechanical Contractor, Fire
Protection Contractor, Emory maintenance personnel, and Building Occupants present
for this true test of the emergency system. We will verify that all loads that are
supposed to be on the generator are on it and also will monitor the actual loading of the
generator throughout the entire test to verify the minimum 25 percent spare capacity.
1.6
Section Page 3 of 3
Section 26 50 00
Lighting
Section 26 50 00 Lighting
1.0
Interior Lighting
1.1
General
1.1.1 All interior Lighting Shall conform to ANSI/ASHRAE/IESNA 90.1 2010 Edition.
1.1.2 Field Verification of Existing Conditions: When making connections to existing
Emory University electrical lighting or power panels, the Designer must confirm and
show evidence that the existing panel capacity is capable of supporting the load to
be connected in the new design.
1.1.3 Most if not all Emory buildings will be LEED certified, so projects shall attempt to
meet and exceed lighting strategies that contribute to achieving Energy and
Atmosphere Credit 1 Optimize Energy Performance under the current LEED rating
system.
1.1.4 Standards
1.1.4.1 All Local, State and federal codes are to be followed as well as Dark-Sky
compliance, UL Listing, DLC Certification, RoHS compliance, as well as
efficiency guidelines required for LEED projects.
1.1.5 Maintainability
1.1.5.1 All lighting fixtures must be accessible using standard vertical devices such
as standard size A-frame ladders no taller than 14 foot, extension ladders
no taller than 25 foot and only then if the fixture is wall mounted with space
to use the ladder and one-person lifts if needed without the use of
scaffolding, outriggers or special equipment.
1.1.5.2 Any special requirements must be brought to the Emorys attention, and be
approved prior to Final CD Issue. If person lifts are required, they shall be
provided as collateral building equipment. Storage space for this
equipment shall be provided in a logical place within this building.
1.1.5.3 Emory requires a written document and statement at Design Development
Issue and also at Final CD Issue either by email or otherwise that lists all
areas with maintainability concerns. These usually occur because of
location, mounting height, or other situations that may cause maintenance
problems because of access concerns.
1.1.5.4 When fixtures are installed in challenging spaces, such as stairwells,
lobbies or others, take care to design with maintainability in mind. This may
include: remote ballasts, longer life lamps, and hanging fixtures that can be
lowered.
1.1.5.5 Efforts shall be made to use standard lamps already in use on campus and
in specific buildings when renovations are occurring in them.
1.2
Fixtures
1.2.1 Campus Standard Fixtures
1.2.1.1 Manufacturers
1.2.1.1.1
Troffers: The new campus standard troffer is the (Columbia
EPC, Lithonia RT8, Metalux 2AC, Pinnacle Converj) Volumetric
2-Lamp fixture. Alternates must be approved prior to
submittals.
1.2.1.1.2
LED: LED fixtures and the LED modules themselves must meet
LM80, LM79, and TM21 testing standards. LED fixtures are the
encouraged technology choice in all spaces.
1.2.1.1.3
Exit signs shall be LED and meet LED testing standards.
1.2.1.2 Where pendant mounted Parabolic Up/ Downlight Fixtures are used
continuous rows shall have self-aligning joints, no visible fasteners and
louver shall be attached with safety chains.
1.2.1.3 Food Service Lighting: All lamps in food service areas are required to be
plastic coated to prevent the glass from shattering in the event of breakage.
Section Page 1 of 3
Section 26 50 00
Lighting
1.2.2
2.0
Lamps
1.2.2.1 Color Temperature
1.2.2.1.1
New Construction: In new buildings where there is no need to
match an existing temperature, 4000 Kelvin will be used.
1.2.2.1.2
Renovations: When renovations to existing spaces occur, take
care to match the building or space standard which already
exists. If there is the opportunity to execute a complete relighting of the floor, 4000 Kelvin temperature will be used.
1.2.2.2 Color Rendering Index: The minimum CRI shall be 80.
1.2.2.3 Lamp Type: Super-T8 Lamps are the campus standard and T5 Lamps shall
only be used if the fixture design, in architectural fixtures, requires this type
of lamp.
1.2.3 Ballasts
1.2.3.1 Ballasts shall be electronic type.
1.2.3.2 Low ballast factor (0.88) ballasts should be used as a standard unless
lighting calculations call for some higher light output
1.2.3.3 The power factor of the ballast shall be above 0.90
1.2.3.4 The THD of the ballast shall be less than 10%
1.2.3.5 All ballasts should be programmed start or instant-start.
1.2.3.6 Emergency battery ballasts are to be used in lieu of centralized UPS
systems for non-generator buildings. Battery maintenance is an important
consideration and longer-life batteries are required.
1.3
Lighting Levels: Light levels and Max/Min ratios should meet the recommendations called out
in the most recent edition of the IESNA handbook for the 25-65 age group.
1.4
Controls
1.4.1 Lighting Control Systems
1.4.1.1 Step Dimming
1.4.1.1.1
Emorys campus standard ballast is a programmed-start stepdimming ballast.
1.4.1.2 Lighting Control Panels
1.4.1.2.1
Lutron Grafik Eye is basis of design and alternates must be
approved prior to submittal. Training for any and all new control
panels must be included whenever a panel is installed.
Integration into the Building Automation System (BAS) is
encouraged, but the Emory Controls Engineer and Mechanical
Engineer must be informed prior to the completion of
Construction Documents.
1.4.1.2.2
The Consulting Engineers Specification shall call for the
dimming package to be priced separately from the lighting
package.
Exterior Lighting
2.1
General
2.1.1 For outdoor lighting at Emory the emphasis should be placed on security lighting but
at the same time we want to minimize the up light. Avoid using light fixtures which
are pointed so that the lighting is directed upward.
2.2
Fixtures
2.2.1 High Pressure Sodium Pole Fixtures: The campus standard fixture is the Mainstreet
SL100, black, 150 watt HPS fixture with acrylic lens w/ Night Sky Cap. House-side
shields are required where applicable. High Pressure Sodium lighting utilizing dual
arc tube lamps with 40,000 hour life is preferred.
2.2.2 LED Pole Fixtures: The campus standard LED Fixture is the Philips S55-SFOK with
49W LED cells.
2.2.3 Bollards and Step Lighting: The use of Low-level lighting is discouraged.. If these
are required for some reason, maintainability and lamp-life are important factors.
Section Page 2 of 3
Section 26 50 00
Lighting
2.2.4
3.0
Building Sconces & Wallpacks when used as an architectural feature, care must be
made to minimize up-light from sconces.
2.2.5 Street and surface parking: Bronze Cobra head cut off fixtures, on 30 foot fiberglass
poles are acceptable for street or parking lot lighting where the number of poles must
be minimized and cost is a factor.
2.2.6 Flagpole, Signage, Soffit, & Feature lighting: The only place where in-ground flood
lighting is acceptable is for the flagpole in the center of the quad. If up lighting is
required, no stray light or light trespass is allowed.
2.2.7 Other Fixtures: No fixtures shall be placed on trees or any temporary structures.
2.3
Light levels
2.3.1 Security concerns are of utmost importance at Emory. We intend to meet the intent
of Sustainable Sites Credit 8 Light Pollution Reduction under the current lighting
zone which Emory is in but in the event of security concerns, the security concerns
shall prevail.
2.4
Controls
2.4.1 All outdoor fixtures must have an integral or shared photocell for controls. Time
clocks or building controls are not acceptable. Approved manufacturers are: Tork or
Intermatic.
2.4.2 The campus standard lampposts should be served by a disconnect switch mounted
on the side of the pad mounted transformer
Emory Parking Decks
3.1
For Parking Decks, Emory Transportation and Parking Services maintains a standard fixture
list and specifications that must be consulted.
Section Page 3 of 3
Section 26 60 00
Special Electrical Systems
Section Page 1 of 1
Section 27 00 00
Emory LITS Building Specifications
Section Page 1 of 1
Section 28 10 00
Electronic Security Systems (ESS)
General
1.0.1 The architect will include an Emory approved security system designer on their team.
ESS design and construction documents will be included in the architects standard
submittal packages. The Contractor will use these documents to request competitive
bids from an Emory approved list of vendors. Emory Security Systems department will
review bids and participate in the contractor selection. The Access Control Contractual
Agreement for work will be between the Contractor and the Access Control Company to
whom the bid is awarded.
1.0.2
Definitions
1.0.2.1 Electronic Security Systems (ESS) is the comprehensive term used to
describe systems that include access controls, video surveillance and intrusion
detection systems.
1.0.2.2 Access Controls Systems (ACS) is the specific term used to describe the
integrated solution that includes software, control panels, devices and
associated cabling infrastructure devices that makes a complete and properly
functioning card entry system. Lenel Systems International is the chosen
manufacturer for this solution with no exceptions.
1.0.2.3 Video Surveillance, herein referred to as Closed Circuit Television (CCTV) is
the specific term used to describe the integrated solution that includes,
software, recording hardware, cameras and associated cabling infrastructure
that completes a properly functioning video surveillance system Interlogix
Truvision (formerly GE Security) is the video management software used to
access live and recorded video, and to configure the recorders and cameras.
All CCTV hardware shall be compatible with the Interlogix Truvision video
management system.
1.0.2.4 Intrusion Detection, herein referred to as Intrusion Detection System is the
specific term used to describe the integrated solution that includes software,
hardware and cabling infrastructure.
1.0.3
1.0.4
Section Page 1 of 12
1.0.5
Section 28 10 00
Electronic Security Systems (ESS)
The Security Design and Construction Documents will reflect the general requirements
listed on the following pages. The design and construction documents shall be
organized based on the following drawing numbering system:
Drawing Numbering Organization
ES-001
Title sheet
Schedules
ES-100
Drawings index, Cable Index, Devices Legend, Master Equipment List
ES-101
Reader Schedule, Reader Hardware Sets
ES-102
Alarm and Intercom Schedules, Alarm Hardware Sets
ES-103
CCTV Schedule, CCTV Hardware Sets
Block Diagram/Risers
ES-200
Access Control System Block Diagram
ES-201
Access Control System Diagram (1 of x)
ES-202
Access Control System Diagram (2 of x)
ES-20X
Access Control System CCTV Riser Diagram
Floor Plan Device Layout
ES-300
Security Device Plan Site Plan
ES-301
Security Device Plan Level 1
ES-302
Security Device Plan Level 2
ES-30X
Security Device Plan Level X
Floor Plan Cable Layouts
ES-400
Security Cable Plan Site Plan
ES-401
Security Cable Plan Level 1
ES-402
Security Cable Plan Level 2
ES-40X
Security Cable Plan Level X
Access Control and CCTV Wiring and Mounting Details
ES-500
Access Control Door Elevations (1 of X)
ES-501
Access Control Door Elevations (2 of X)
ES-520
Access Control Device Wiring Details
ES-521
Access Control Device Wiring Details
ES-550
Access Control Device Addressing and Termination Details
ES-600
CCTV Mounting Details
ES-700
Video/Intercom System Wiring Details
ES-701
Burglary Panel System Wiring Details
ES-800
Wall Elevation Details ACS Security Room
ES-802
CCTV Headend Rack Elevation
Section Page 2 of 12
1.0.7
Section 28 10 00
Electronic Security Systems (ESS)
The drawings shall use the symbols as indicated on the following legend:
Section Page 3 of 12
Section 28 10 00
Electronic Security Systems (ESS)
1.1
1.2
The system installation shall be in accordance with, but not limited to the Specifications
stated herein and requirements of the current National Electrical Code (NFPA 70).
1.2.2.1 Emory University shall be notified in writing of any conflicts between applicable
codes and the Emory University requirements.
1.2.2.2 If the Security Contractor desires to use an installation method or practice,
which is contrary to the Specifications, prior written approval shall be obtained
from Emory University before such installation commences.
1.2.2.3 Electric Permits: All contractors are required to obtain electrical permits from
DeKalb County. Absolutely no work may begin without first obtaining the
proper permits.
1.2.2.4 Equipment boxes, cabinets, card readers, and devices shall be mounted firmly
in place utilizing fasteners, which provide the required safety and support. The
Security contractor shall ensure that all equipment and devices are installed
and mounted plumb square.
1.2.2.5 All installations and modifications shall be neat and workmanlike.
1.2.3
1.2.4
Terminal Cabinets:
1.2.4.1 All System cabinets shall be locked and shall be equipped with a monitored
tamper switch.
1.2.4.2 Terminal strips shall be clearly & uniquely identified in each cabinet.
Section Page 4 of 12
1.2.4.3
Section 28 10 00
Electronic Security Systems (ESS)
1.2.5
System:
1.2.5.1 Control panels shall be the state of the art type and/or approved by Emory
University. Location for control panels shall be in an area remote from entrance
door so not to obstruct access or aesthetically displease.
1.2.5.2 Keypad controls shall be located adjacent to the entrance of the secured area.
1.2.5.3 Motion detectors shall be of the dual technology type All systems shall be
electrically grounded.
1.2.5.4 If loss of power occurs, the system shall automatically restore to operating
status.
1.2.6
Optional Features: The system shall have audit trail capability. System Response:
System shall detect any alarm condition within one (1) second.
1.2.7
1.2.8
Acceptance Testing: The Security contractor shall demonstrate the operation of all
systems, including all peripheral devices, to Emory University.
General Requirements
It is the responsibility of contractor to review the Emory construction drawings that relate to the proposed
construction project. Sections referenced include but may not be limited to:
08 00 00 - Door Openings
08 70 00 - Hardware
28 10 00 Electronic Security Systems
Warranty
The warranty period for ESS parts and labor shall be no less than one year. Vendor shall provide Emory
with procedures for receiving credit or replacement items which fail.
Code Compliance
Installation must meet the requirements listed in the current editions of the following:
NFPA 70 - National Electrical Code
NFPA 101 Life Safety Code
UL 294 Access Control Systems
UL 1076 Proprietary Burglar Alarm Units & Systems
American with Disabilities Act (ADA)
Federal Communications Commission (FCC)
Contractor Qualifications:
The minimum requirements to qualify as a responsible contractor for RFPs. . Proof of certification and
qualifications shall be included in contractors response:
3.2.1 Lenel Certified OnGuard Value Added Reseller
3.2.2 Interlogix Authorized Dealer and Certified Installer
3.2.3 3.2.4 State of Georgia Low Voltage Contractors License
Section Page 5 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Product Requirements
ACS System Controller The System Controller shall be the Lenel LNL-3300 with Dual path
communications. NO EQUIVALENT ALLOWED
ACS Door Interface Modules The access door control module shall be the Lenel LNL-1300 reader
interface module. ADA Doors shall be the LNL-1320. NO EQUIVALENT ALLOWED
Enclosures CPU Enclosures shall be Lenel LNL-CTX or LNL-CTX-6 enclosures. NO EQUIVALENT
ALLOWED.
READERS Access Control Readers shall be HID MultiCLASS SE Dual Readers, model number RP10
Mini-Mullion, RP15 Mullion, RP30 Square, RP40 Gang Box, and RP40KP Key Pad Gang Box depending
upon mounting requirements. HID MultiCLASS SE Biometric Dual Reader will be utilized when
available. Use of these readers shall be approved by the Systems Security Shop. NO EQUIVALENT
ALLOWED
Lenel Power Supply CPU power supply shall be the Lenel LNL-0LS-75CTX, AL600ULACMPD8 or PD16
, AL1012 or 24 ULXPD PD8 or PD16. NO EQUIVALENT ALLOWED.
Request to Exit Devices Request to Exit devices where request to exit function is not included as part of
Division 08 Door hardware shall be Bosch model DS150i. NO EQUIVALENT ALLOWED
Door Contacts Door contacts shall be Sentrol 1078C for recessed mount applications and Sentrol 2505
series for surface mount applications. NO EQUIVALENT ALLOWED.
Door Hardware Power Supply Power supplies utilized for powering door hardware and CPU shall be
the Altronix AL600ULACMPD8 OR PD16. NO EQUIVALENT ALLOWED
Door Operators: Door Operators used with access control system will be wired through the Lenel System
for push plates on the exterior of the building and be wired directly to the door operator for all interior
push plates. Door Operators used with access control will also be programmed to function with IOs to
allow for activation with a card read. Wiring diagrams must be included with submission of drawings.
CAMERAS shall be compatible with Interlogix digital recorders, network recorders, and encoders.
Cameras shall be vandal-resistant unless mounted at a location that is reasonably out of reach. Outdoor
cameras shall be vandal and weather-resistant. All cameras shall be capable of wide dynamic range
(helps with lighting problems) and in areas with poor lighting the camera shall have built-in infrared
illumination.
Fixed Analog cameras and Pan/ Tilt/ Zoom cameras, whether IP or Analog, shall be Interlogix Truvison or
Speco cameras, with the designer choosing the specific camera determined by working with the ECC
Department and Project Manager.
IP cameras shall be Interlogix Truvision cameras or a product approved by Interlogix.
Specialty cameras (such as license plate cameras) will be an option is approved in the design process.
All outdoor camera locations that are not mounted to the exterior of the building and are mounted on
camera poles, lamppost or Emergency Call Stations shall be connected to the head end by fiber optic
cable.
Analog Indoor Fixed Dome Style Cameras shall be Interlogix model TVD-7120VE-2-N
Analog Indoor Fixed Bullet Style Cameras shall be Interlogix model TVB-4102
Analog Indoor Pan / Tilt / Zoom Cameras shall be Interlogix model TVP-4101
Analog Outdoor Fixed Dome Style Cameras shall be Interlogix model TVD-7125VE-2-N
Section Page 6 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Analog Outdoor Fixed Bullet Style Cameras shall be Interlogix model TVC-BIR6-HR
Analog Outdoor Pan / Tilt / Zoom Cameras shall be Interlogix model TVP-4102
IP Based Indoor Fixed Dome Style Cameras shall be Interlogix model TVD-3102
IP Based Indoor Fixed Bullet Style Cameras shall be Interlogix model TVB-3101
IP Based Indoor Pan / Tilt / Zoom Cameras shall be Interlogix model TVD-3102
IP Based 3 Megapixel (PoE) Outdoor Fixed Dome Style Cameras shall be Interlogix model TVB-3102
IP Based 5 Megapixel (PoE) Outdoor Fixed Bullet Style Cameras shall be Interlogix model TVC-M5225E-3M-N
IP Based Outdoor Pan / Tilt / Zoom (HD - 20x Optical Zoom) Cameras shall be Interlogix model TVP-3104
Section Page 7 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Project Documentation
ESS Pre-Installation Submittals Contractor shall submit two (2) hard copy sets and three (3) electronic
copies for review and approval by Emory prior to start of installation
Installation Shop Drawings These drawings shall show point to point riser wiring diagrams for all
system components used in the system. ACS detail shall be separate from CCTV detail. Wiring detail
shall include riser each cable identifier, cable type, termination details for all panels and components that
make up the system. Electronic format shall be .dwg.
Installation Schedule This schedule shall show critical activities that blend with the projects construction
schedule by phase and area. Minimum activities shown shall be cable rough-in, component installation,
FVT testing, PVT testing and project close-out training & submittals. The schedule shall be created in
Microsoft Project or Primavera and submitted in Adobe Acrobat .pdf format.
Red-Line Construction Drawings During installation, the contractor is required to maintain this set of
drawings on the job updated daily. This drawing set should show all field change notes that include and
not limited to cable routing, equipment placement, additions, changes and deletions
ESS Testing & Quality Control
Field Verification Testing (FVT)
FVT is the quality control process that accounts for and verifies the quality workmanship for each
cable and component that makes up the ESS. The contractor must submit for Emory approval
the complete FVT plan prior to use.
Performance Verification Testing (PVT)
PVT a comprehensive process of assuring a complete working and campus integrated ESS as
specified in this RFP. It shall include properly working access control points, camera locations,
monitoring stations, headed, etc. This testing process will serve as the owners acceptance of the
ESS and its components. The contractor must submit for Emory approval the complete FVT plan
prior to use.
ESS Project Close-Out Training & Submittals
Training
Provide training documentation and up to 4 hours user training for each system provided. Include
an additional 4 hours of maintenance of troubleshooting training for each system provided.
FVT Manuals
Submit two (2) hard copy sets and two (2) electronic copies on CD. Hard copies shall be in hard
shell 3 ring binders.
PVT Manuals
Submit two (2) hard copy sets and two (2) electronic copies on CD. Hard copies shall be in hard
shell 3 ring binders with each form showing accepted signatures from Emory.
Progress Drawings - (As-Built Drawings)
Submit two (2) hard copy sets and two (2) electronic copies on CD that shows all changes made
from final version of Red-Line Construction Drawings. Hard copy shall be bounded set using 48
paper. Electronic copies of as built drawings are also to be provided in accordance with Campus
Services Document Delivery Standards, which is included as a contract attachment.
Warranty
Submit warranty documentation detailing full systems parts and labor including a schedule of
components and dates the warranty is due.
Revision Date April, 2015
Section Page 8 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Section Page 9 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Section Page 10 of 12
Section 28 10 00
Electronic Security Systems (ESS)
One duplex, network data outlet must be installed on each of two walls of the security room. See typical
room layout for locations.
One duplex electrical outlet must be installed on each of two walls of the security room. Each outlet must
be on a separate 120V/20A, dedicated circuit and must be connected to emergency power. See typical
room layout for locations.
One Fire Alarm interface mounted on backboard to be provided by Fire Alarm Vendor, for interface to
security panel for fire/life safety.
The room (including the ceiling) must be painted and the floor must be tiled to help reduce atmospheric
dust.
Section Page 11 of 12
Section 28 10 00
Electronic Security Systems (ESS)
Section Page 12 of 12
Section 28 31 00
Fire Detection and Alarm
References
1.1.1.
1.2.
Plans are subject to review and approval by the authority having jurisdiction and to FM
Global review. Installation is subject to FM Global acceptance. In the event it is
discovered that the work, or any portion of the work, has not used the necessary
approved materials, equipment, or services, or has otherwise not been performed in
accordance with FM Global standards, or for any reason does not meet with FM Global
acceptance, the Contractor responsible for the work shall, at its own expense and without
any cost to Emory University, within forty-five (45) days of notice in writing of any
deficiency (or within such times as the parties to this contract have agreed in writing),
perform such work and replace such materials as is necessary to bring the work and
materials into compliance with relevant FM Global standards and secure FM Global
acceptance.
General
1.2.1. A completely new system shall be intelligent and addressable and fully microprocessorbased with the capability of two-way communication over signaling line circuits between
addressable initiating devices or addressable interfacing/control modules and the fire
alarm control panel.
1.2.2. The new system shall utilize all new and unused equipment and materials, which are free
from contamination and corrosion.
1.2.3. In research, clinic, academic buildings, and residence halls, new fire alarm panels shall
be networkable, and voice evacuation systems shall be used. In other buildings, voice
evacuation is preferred and may be used, or the system shall be arranged to provide
distinct evacuation signals using electronic horns and strobe lights.
1.2.4. In residence halls, all resident rooms shall have a smoke detector supervised by the fire
alarm control panel. Detectors shall be powered by the buildings electrical system and
shall have an integral sounder base. Tampering with or removal of the sensor head shall
send a trouble signal to the panel and activate the sounder alarm.
1.2.5. All wire shall be clearly labeled at accessible points, and consistency in color coding of
wiring shall be maintained.
1.2.6. In an existing occupied building, all existing fire alarm equipment shall be left untouched
and in service until it is to be removed to facilitate the installation of the new system,
except where subject to damage and false alarms through construction activities. No part
of an existing system can be disabled or covered without the permission of the Emory
Project Manager who will seek guidance from the Emory Fire Safety Director. In an
occupied existing building with no sprinkler system, if construction activities become a
source of false alarms, Smoke detectors may be replaced during the construction period
with heat detectors, if coordinated with the Emory University Project Manager and the
approval of the Emory University Fire Safety Director. It is the responsibility of the
contractor to remove, store in a safe location, and reinstall devices upon the completion
of the construction work.
1.2.7.
New fire alarm panels for large additions to existing buildings shall be networked with the
existing building, including voice evacuation system. With fire alarm upgrades and new
installations, fire alarm systems for connected buildings should be networked.
1.2.8.
In existing buildings with voice evacuation systems, new fire alarm speakers shall be
voice speakers.
Section Page 1 of 7
1.2.9.
1.2.10.
1.2.11.
1.2.12.
1.2.13.
1.2.14.
1.3.
Section 28 31 00
Fire Detection and Alarm
All panels and peripheral devices shall be the standard product of a single manufacturer
and shall display the manufacturer's name on each component. Notifier Fire Systems
shall be manufacturer of main Fire Alarm panel and the voice evacuation system. See
Part 2- Products
The fire alarm control panel shall allow for loading or editing special instructions and
operating sequences as required. The system is to be capable of on-site programming to
accommodate facility expansion, building parameter changes, or changes as required by
local codes. All software operations are to be stored in a non-volatile programmable
memory within the fire alarm control panel. Loss of primary and secondary power shall
not erase the instructions stored in memory.
Fire Alarm panel shall be programmed by the installer to show distinct, specific, and clear
locations of sensing devices.
Fire Alarm systems shall be enclosed in conduit from the fire alarm panel, for multifloor
risers, where exposed or subject to damage, inside of walls, above hard ceilings, and in
mechanical spaces. Generally, fire alarm systems shall be completely enclosed in
conduit.
All circuits of the fire alarm control panel shall be designed for future expansion. In no
case shall circuit capacities exceed 80 percent of the design capacity as specified by the
manufacturer.
Equipment locations are shown on the drawings. These drawings form a part of this
specification and as such, the equipment locations shall be strictly adhered to, except the
notification device locations, which are intended to be approximate. Locations shall
comply with applicable Codes and be coordinated with other trades/building features in
the field.
Submittals
1.3.1. General: Written approval shall be obtained from the approval authorities prior to the
beginning of any site installation work.
1.3.2. Submittal Package after award: A complete information package concerning the fire
alarm system shall be developed and submitted to the approval authorities. The purpose
of this package is to allow thorough review of the proposed system design and
arrangement in order to determine compliance with the specification and design
drawings. The contractor is required to submit a complete package within 30 days of
contract award for review and approval. The contractor is also responsible for submitting
these documents to the AHJ for approval within this 30-day period.
1.3.3. All drawing submittals shall be submitted on the same size sheets. The drawings shall be
sequentially numbered throughout the entire set.
1.3.4. The submittal package and shop drawings shall be prepared under the direct supervision
of a NICET Level III Certified Technician or a registered Professional Engineer
appropriate for the design. The technician or engineer shall be employed by the installing
contractor or the fire alarm equipment distributor.
1.3.5. At the time of completion of the submittal package, the contractor shall independently
perform a quality assurance review of the entire submittal package internally to assure
completeness and conformance with the specification and design drawings. Written
confirmation of this review, which certifies compliance with the specification and design
drawings, is required. All employees involved in 1) development of the submittal package
and 2) quality assurance review of the submittal package shall be identified.
1.3.6. Submittal Review and Approval
1.3.7. Copies of the submittal package shall be distributed as follows:
Submit the number of copies that the contractor requires for distribution, plus one copy
for the Architect, plus one copy for each consultant discipline required to review the
submittal.
One (1) copy shall be sent to: FM Global, 3460 Preston Ridge Road, Suite 400,
Alpharetta GA 30005
Section Page 2 of 7
Section 28 31 00
Fire Detection and Alarm
1.4.
1.5.
1.6.
Qualifications
1.6.1. All work performed to comply with this specification shall be carried out by and/or
managed by a competent firm regularly engaged in the installation and testing of fire
alarm systems for commercial buildings. Contractor shall be licensed and insured per
Emory University requirements. Vender must have references for satisfactory
performance of similar projects of similar size and has been in business with the same
business name for at least five years.
1.6.2. A fire alarm contractor working under an electrical contractor as a subcontractor shall not
use subcontractors for installation and certification without written permission of the
Emory University Project Manager.
1.7.
Regulatory Requirements
1.7.1. Equipment and materials shall be approved for their designed use and performance. The
term "approved" shall mean Underwriters Laboratories (UL) listed and FM Global
approved.
1.7.2. Approval Authorities: Approval authorities shall include Emory University (Owner); their
authorized representative, Factory Mutual Engineering Association; and the
Governmental Authority Having Jurisdiction.
Section Page 3 of 7
Section 28 31 00
Fire Detection and Alarm
1.8.
1.9.
Section Page 4 of 7
1.9.4.
1.9.5.
2.
Section 28 31 00
Fire Detection and Alarm
Permanently mount two plan tubes near the fire alarm panel and place a copy of the asbuilt-fire alarm system plans in the tube. The second tube is for sprinkler system plans.
Printer, if required, includes printer table and box of spare paper in addition to initial box
of paper.
2.1.
Section Page 5 of 7
Section 28 31 00
Fire Detection and Alarm
Training Of Employees
2.3.1. An employee of the installing contractor or the fire alarm equipment distributor who has
NICET Level III certification shall provide instruction to key employees of Emory
University on the operation and maintenance of the complete system. The contractor
shall contemplate a minimum of three training sessions of one to two hours in length.
These training sessions may need to be conducted after normal working hours in order to
accommodate all working shifts. At least one of these training sessions shall be carried
out for key personnel prior to the system being initially placed on-line for the beginning of
the burn-in period.
2.3.2. Three bound copies, which summarize the training instruction, shall be submitted to the
Owner for future reference.
Section Page 6 of 7
3.
Section 28 31 00
Fire Detection and Alarm
Commissioning
3.1.1. At the completion of project, before Owner Acceptance, the installing fire alarm
Contractor shall verify monitoring of the fire alarm system. Installing Contractor shall
verify new fire alarm system has two telephone lines at the dialer (DACT) (unless other
non-telephone transmitting technologies are utilized in lieu of phone lines) and shall be
verified as monitored by the Emory Police Department. The DACT shall be programmed
to separately indicate to the Emory Police Department three conditions: general system
alarm, general system supervisory condition, and general system trouble. These signals
shall be consistent with signals from existing systems monitored by the Police Receiver.
In addition, dialer shall be verified to indicate phone line outage. See Emory Standards
Section 019113- General Commissioning Requirements
3.1.2. Commissioning shall verify that the installing contractor performed initial inspection on
completion under the supervision of a fully qualified fire alarm inspector minimum NICET
Level II. The initial testing on completion of installation shall include cleaning of all
detectors and equipment. Installing contractor shall provide an initial signed and dated
inspection report of the complete fire alarm system including list of all initiating devices
and notification appliances (in addition to the official Record of Completion).
Section Page 7 of 7
Section 31 00 00
Earthwork
Section 31 00 00 Earthwork
Scope of Work
The work specified shall include all labor, equipment and incidentals necessary to perform all excavation,
backfill, new fill, grading and finish grading in preparation for building construction, utilities, landscaping
and grassing, required to complete the work shown and specified on the contract documents. The work
also includes all safety equipment necessary to perform these operations (sheeting, bracing, and
supports in accordance with OSHA regulations) and removal of all materials from the excavation which
are deemed unsuitable for backfilling.
Design Specification
The Architect/Engineer shall define the types of earthwork being specified, including earth excavation,
rock excavation, mass excavation, and confined excavation, and shall specify the format for the
Contractor's payment schedule associated with these different scopes. The Architect/Engineer must
specify the compaction to be achieved in the field based on the required soils dry density and moisture
content and the associated quality assurance testing to be done to verify compaction. The Contractor
shall provide the Testing Agency with a continuously updated and accurate schedule of the construction
activities that require sampling, observation, or verification by the Testing Agency. The Contractor shall
also establish benchmarks for reference on the site.
Quality Assurance
Emory University or the Project Team, as defined by contract, will arrange for the services of an
independent Testing Agency to perform required field and laboratory testing. The Testing Agency will
submit the following reports to Emory's Project Manager and copy the Contractor:
1.
Analysis of all soil materials tested, including fill, backfill, and borrow
2.
Verification of each footing sub grade
3.
In-place density test reports
4.
Moisture-density relationship test reports
5.
Compressive strength or bearing test reports
6.
Soil test for nutrient content, composition, and acidity
7.
All other reports requested by the Architect/Engineer or Emory University
Site Conditions
The Architect/Engineer must extensively inventory the existing site conditions including vehicle and
pedestrian traffic, site utilities, subsurface conditions, ground water, and site limitations, prior to
commencing construction activities. Emory University assumes no responsibility for the completeness or
accuracy of the data contained in any reports supplied in reference to the site conditions. Items of historic
or archeological value discovered during earthwork operations shall remain the property of Emory
University. The Contractor is responsible for notifying the appropriate utility locators before any work
begins. To locate non- Emory underground utilities, the Contractor must call the Georgia Utility Protection
Center at 1-800-282-7411. The Contractor is responsible for hiring a private utility locator to locate utilities
owned by Emory University. It is the responsibility of the contractor to insure that all utilities within the
project limits are marked and documented. The contractor shall repair all damaged utilities at no cost to
Emory University. The contractor must maintain an as-built document that indicates the exact location of
all utilities within the project limits and shall issue the document to Emory University at the completion of
the project.
Execution
The Architect/Engineer shall specify and define the products involved in the earthwork operation. This
specification shall also address the parameters of unsatisfactory products and materials. The Architect/
Engineer shall also address the site preparation, including the stripping of topsoil, protection and
barricades, the Contractor's responsibilities and liabilities, weather limitations, tree and root protection,
dewatering, all excavating, backfilling, filling, fill placement, compacting, grading, proof-rolling, and field
quality control. Generally, backfill shall be compacted in 6" lifts and compacted to a 98% dry density
Revision Date June, 2013
Section Page 1 of 2
Section 31 00 00
Earthwork
under roads and structures and 95% dry density elsewhere. The use of excavating equipment and trucks
to perform compaction in trenches is not allowed. The earthwork execution must also specify the
maintenance of completed areas, the repair of damaged areas, and the correction of areas where
settlement has occurred. The storage and disposal of topsoil, excess material, and waste material shall
be specifically described in the specification. All underground utilities must be located by hand digging
before the grading or excavation operation begins.
Planting Soils
Prior to placing top soil or amending existing soil, the Landscape Architect, University Landscape
Architect, and Director of Exterior Services shall inspect and approve the prepared subsoil. Subsoil shall
be free of all debris, non-organic material, roots, sticks, and rock or stone larger than in any
dimension. After placement of topsoil or amendment of existing soil and prior to installation of plant
material, soil test shall be completed. Soil shall have the following characteristics;
pH range: 5.5-7.0
Soil Texture:
Stone Content:
Nutrient Status:
Section Page 2 of 2
Section 31 10 00
Tree Protection and Selective Clearing
Planning:
Root space is the most critical factor in tree protection through the construction process. The
root system can easily extend beyond the drip line of the tree canopy. Within the drip line this
root system is denoted as the Critical Root Zone (CRZ). Disturbance within the CRZ can
directly affect the trees chances for survival. To protect these CRZs the following standards
shall apply:
a. The Tree Protection Zone of specimen trees or stands of trees or otherwise designated
tree save areas shall include no less that the total area beneath the tree(s) canopy as
defined by the farthest canopy drip line of the tree(s). In some circumstances the Emory
Landscape Architect and/or Campus Arborist may require a Tree Protection Zone in
excess of the area defined by the drip line.
b. The use of tree save islands and stands of trees is encouraged rather than individual
trees scattered throughout a site wherever possible.
c. All construction activities such as material storage, parking, concrete washout, and
vehicle access shall be conducted as to prevent disturbances within Tree Protection
Zones.
d. Contractor shall be required to submit a logistics plan which indicates the location of all
tree protection fencing and the locations of all construction activities such as vehicle
access, construction trailers, parking, material storage, etc.
Section Page 1 of 3
Section 31 10 00
Tree Protection and Selective Clearing
e. No entry or disturbance shall occur within the Tree Protection Zone of specimen trees or
tree islands without prior approval by the Emory Landscape Architect or Campus
Arborist.
2.
Protective Barriers:
a. Active protective tree fencing shall be installed along the outer edge of and completely
surrounding the CRZ of all specimen trees, tree islands, or otherwise designated Tree
Protective Zones, prior to any land disturbance and shall remain until final landscaping is
complete.
b. These protective fences shall be 6 chain link fence with in-ground posts. Polyvinyl
construction fence may be used only with written approval from the Emory Project
Manager and the Emory Campus Arborist. All Tree Protection Zones should be
designated as such with TREE SAVE AREA signs posted visibility on all sides of the
fenced area at 50 foot intervals. Signs requiring subcontractor cooperation and
compliance of tree protection standards shall also be placed at all site entrances.
c. All exposed roots 1 inch or greater at the edge of the Tree Protection Zone shall be
pruned with a clean cut to the soil edge.
d. Pruning of tree limbs to accommodate clearance for construction activities shall be
reviewed and approved by Emory University Arborist. All work shall be performed by an
Emory University approved tree contractor in accordance to standard arboricultural
practices approved by the Emory Campus Arborist
e. Any invasive species shall be removed from within the Tree Protection Zone.
f. Tree Protection Zones shall be mulched, minimum of 3 with either recycled wood chips
from onsite removals or a shredded pine or hardwood mulch.
Clearing
No damage shall be done to property, trees, or shrubbery to be retained in, or outside, the Limits Of
Construction. The contractor at no cost to Emory University shall repair damage that occurs. Prior to
starting work, all retained trees and shrubs shall have protective barriers in place. Disposal of all
objectionable matter is the responsibility of the contractor and shall be addressed in the contract
documents.
Grubbing
Grubbing consists of the complete removal of objectionable matter that is embedded in the underlying soil
including tree roots, foreign materials, and any object protruding from the earth. Objectionable matter
shall include all roots more than 3/4" in diameter for a minimum depth of 12" below subgrade in open
areas and 36" below subgrade in areas that will be under the foundations of the proposed structure or the
finished subgrade of paved areas. The roots of protected trees and shrubs must be protected during this
operation.
Stripping
Topsoil shall be stockpiled in a designated area within the limits of the site if there is sufficient area to do
so. Appropriate erosion controls shall be employed around the stockpiles. The disposal of the topsoil not
required for the project shall be addressed in the contract documents.
Preservation of Adjacent Property and Existing Structures
Exercise extreme care to avoid causing unnecessary disturbance to private property bordering the
construction site. Existing Site Improvements that must be removed shall be replaced with equal or better
quality materials and workmanship.
Modification of Existing Utilities
If an underground or overhead utility must be disconnected, removed or modified in any way, the
Engineering Consultant must review the proposed work with Emorys Project Manager and Engineering
Section Page 2 of 3
Section 31 10 00
Tree Protection and Selective Clearing
Services to determine the full scope of Work required. Active utilities traversing the site shall be preserved
in operating condition.
1.
Disconnection of existing utility service shall be arranged in accordance with regulations and/or
requirements governing the utility concerned.
2.
If the utility is to be abandoned and it does not serve any other University facilities, the utility
should be fully removed to the edge of the Limits of Construction.
3.
Encroachment:
a. Clearing activities: root systems often intermingle and fuse among trees. The removal of
trees adjacent to Tree Protection Zones can cause inadvertent damage to the protected
root systems. Wherever possible it is advisable to cut minimum 24 deep trenches (with a
Ditchwitch) along the limits of land disturbance prior to clearing so as to cut rather than
tear roots. This encroachment line will be determined by the Campus Arborist.
b. Where compaction may occur on roots outside the Tree Protection Zone the area must
be maintained with a minimum 4 inch layer of wood chips ( preferably recycled from
onsite removals) or pine bark when possible.
c. Utility trenching: The installation of utilities through a Tree Protection Zone should occur
by way of tunneling or boring rather than trenching.
d. In the event of any encroachment within Tree Save Areas, corrective pruning, soil
therapy or other recommended arboriculture procedures shall be performed by a tree
contractor using standard arboriculture practices and approved by the Emory Campus
Arborist.
Tree Destruction Penalties
All trees must be maintained in an undamaged condition. Damage is defined as the act of scarring,
cutting, nailing, breaking, etc., any portion of a tree or its root system. The penalty assessed to the
contractor for damaging a tree is as shown in the schedule of values below. This schedule of values
applies to all Emory University projects, unless the Emorys Project Manager approves another valuing
system in writing:
Shrub Height Cost
6' - 8'
$200.00
8' - 10'
$250.00
10' 12
$300.00
12' - 14'
$375.00
14' - 16'
$450.00
16' - 18'
$600.00
18' - 20'
$800.00
Tree Size/Caliper Height Cost
1.5" - 2.0" 14'
$400.00
2.0" - 2.5" 16'
$450.00
2.5" - 3.0" 16'
$500.00
3.0" - 3.5" 16'
$575.00
3.5" - 4.0" 8'
$600.00
4.0" - 5.0" 20'
$800.00
5.0" - 6.0" 22'
$1000.00
6.0" - 7.0" Any
$1200.00
7.0" - 8.0" Any
$1400.00
8.0" - 11.0" Any
$1800.00
12.0" - 20.0" Any
$2,500.00
21.0" and greater Any $3,500.00
Section Page 3 of 3
Section 31 25 00
Construction Storm Water and Erosion Control
Section Page 1 of 1
Section 32 00 00
Exterior Improvements
Section Page 1 of 2
Section 32 00 00
Exterior Improvements
hardscapes do not interfere with fire and emergency apparatus or vehicle or personnel access and
egress, utilities, or telecommunications lines.
Execution
Installation shall be in accordance with manufacturer's instructions and approved submittals. The
specifications shall further address the specifics of each installation and application.
Section Page 2 of 2
Section 32 12 00
Flexible Paving
Section Page 1 of 1
Section 32 12 16
Asphalt Paving
Testing Agency: The contractor shall be responsible for coordinating paving activities with
the owners testing agency to allow field inspection and testing in conformance with these
specifications.
1.
The testing agency shall prepare daily test reports, and state in each report whether
the tested work complies with the specified requirements. Any additional testing
required to verify compliance of corrected work shall be at the contractors expense.
B.
C.
Surface Smoothness: Finished surface of each hot-mix asphalt course shall be tested for
compliance with smoothness tolerances, and shall include a visual inspection of the
asphalt pavement surface by the Owner or the Owners representative.
Section Page 1 of 2
D.
Quality Assurance Testing: For the purpose of Quality Assurance Testing and Acceptance
Evaluation, the HMA paving work shall be divided into lots and sublots. A lot will be equal to
the quantity of paving completed in one working day.
1.
For each lot, a sample of HMA will be obtained in accordance with ASTM D 3665
random sampling procedure by the Owners testing agency and following mix
properties determined:
a.
b.
c.
2.
3.
One location within each sublot shall be randomly selected using ASTM D 3665
procedures for density testing. Two cores shall be obtained at each location and
their density determined in accordance with ASTM D 3665a dn their thicknesses
determined in accordance with ASTM D 3549. The density and thickness for each
location shall be the average of the two core samples. The compaction of each
sublot shall be the percentage of the average density for the sublot compared to the
maximum density of the sample lot determined in accordance with ASTM D 2041.
Acceptance Evaluation:
1.
F.
For the first lot of the project and every third lot thereafter, the following additional
properties shall be determined:
a.
b.
c.
d.
e.
E.
Section 32 12 16
Asphalt Paving
The HMA paving for a lot is acceptable if the asphalt cement content is within 0.3
percent of the JMF recommended asphalt content, the aggregate gradation and mix
properties meet the requirements of these specifications (or agency requirements for
off-site paving), the average compaction for all sublots is 94 percent, with no sublot
compaction less than 92 percent or greater than 98 percent (or agency compaction
requirements for off-site paving).
Remove and replace, or install additional hot-mix asphalt where test results or
measurements indicate that it does not comply with specified requirements, at no additional
cost to the Owner.
G. Quality Control Testing and Inspection: The Contractor shall at their own expense perform
quality control testing and inspection as necessary for the Contractor to control operations to
provide HMA paving meeting the requirements of these specifications. Testing and
inspection by the Owner shall not relieve the Contractor of responsibility to control the work
quality and performance.
Sustainability
Emory University prefers the use of demolished materials in the base and subbase work associated with
paving and other site work. The use of metals in the demolished materials is not acceptable due to these
metals inhibiting pipe and utility location activities.
Section Page 2 of 2
Section 32 12 43
Porous Flexible Paving
Section Page 1 of 1
Section 32 13 13
Concrete Paving
Section Page 1 of 1
Section 32 16 13
Concrete Curbs and Gutters
Section Page 1 of 1
Section 32 17 13
Car Stops
Section Page 1 of 1
Section 32 17 23
Pavement Markings
Section Page 1 of 2
b.
c.
d.
e.
f.
Section 32 17 23
Pavement Markings
Apparent reflectivity.
Washability.
Accelerated weathering.
Dry opacity.
Color retention.
2. If test results show material being used does not comply with specified requirements, the
Contractor may be directed to stop painting, remove noncomplying paint, pay for testing, repaint
surfaces coated with rejected paint, and remove rejected paint from previously painted surfaces
if, upon repainting with specified paint, the two coatings are incompatible.
Protection
A. Provide "Wet Paint" signs to protect newly painted finishes.
Section Page 2 of 2
Section 32 80 00
Irrigation Systems
Section 32 80 00 Irrigation
Irrigation Back Flow Preventers
Irrigation back flow preventers shall be either Watts 009 or Watts 909. Irrigation back flow preventers
may be located aboveground with an insulated protection box in certain situations where the box can be
located in a concealed location. In all other cases, the irrigation back flow preventer shall be located in
the building. Adequate drains shall be located underneath the back flow preventer assembly and the air
vent drain shall be piped to this drain. Back flow preventers for irrigation service shall include a strainer
upstream of the back flow preventer assembly and shall include a valve upstream of the strainer.
Irrigation back flow preventers shall be sized as one full size unit. The irrigation water line from the water
main to the back flow preventer assembly shall be Type K copper. The discharge of the back flow
preventer shall be Type K copper from the assembly into the ground where a transition to PVC shall be
made.
Automatic / Reclaim Control Systems
Automatic controls for reclaim water systems and its integration to other systems shall be commissioned.
Refer to Section 01 91 13 General Commissioning Requirements.
Section Page 1 of 1
Section 32 90 00
Planting
Section 32 90 00 Planting
Scope of Work
The Landscape Architect shall specify for the provision and installation of all landscaping and grassing
required to complete the work indicated and specified on the contract documents. The work shall include
installation of trees, shrubs, groundcovers, plants, and all related works including but not limited to staking
and guying, mulching, soil amendments, and fertilizing.
Quality Assurance
The contract documents shall indicate that all work shall comply with the following standards:
1. National List of Scientific Plant Names, 1982
2. American National Standards Institute, Inc. (ANSI); ANSI Z60.1 96 American Standard for
Nursery Stock by the American Association of Nurserymen.
3. American Society for Testing and Materials (ASTM);
a. F 405-89 Specifications for Corrugated Polyethylene Piping and Fittings,
b. D1140-92 Test Method for Amount of Materials in Soil Finer Than the No. 200 Sieve,
c. D1248-84 Specification for Polyethylene Plastics Molding and Extrusion Materials,
d. D4549-85 Specification for Polyethylene Molding and Extrusion Materials,
e. D2487-92 Test Method for Classification of Soils for Engineering Purposes,
f. D2940-74(85) Specification for Aggregate Material for Bases and Sub-bases for
Highways and Airports,
g. D2974-87 Test Method for Moisture, Ash, and Organic Matter of Peat and Other Organic
Soils,
h. D4491-92 Test Method for Water Permeability of Geotextiles by Permitivity,
i. D5268-92 Specification for Topsoil Used for Landscaping Purposes,
j. D4972-89 Test Method for pH of Soils.
Site Conditions
The Landscape Architect/Architect shall inventory the existing site conditions including traffic, vehicular
and pedestrian, site utilities, sub-surface investigation, ground water, and site limitations. Extra care
needs to be employed with regards to existing and proposed paths of sub surface utilities due to the
number of high pressure services on campus. Emory University assumes no responsibility for the
completeness or accuracy of the data contained in any reports supplied in reference to the site
conditions.
Submittals
Contractor shall provide certification that all plant materials are neonicotinoid free. Certification shall
include a list of the original source for all plant material.
Warranty Requirements
Provide a minimum one (1) year warranty for all plant material.
Products
The Landscape Architect/Architect shall specify and define the products involved in the landscape
installation. All plant material shall comply with the Landscape Master Plan Palette included in the Emory
University Campus Design Guidelines. Plant material not included in the Landscape Master Plan Palette,
shall be approved by the Emory University Exterior and Auxiliary Services Director and the Emory
University Landscape Architect.
The use of neonicotinoids and plant material (trees, shrubs, groundcovers, plants and seed) treated with
neonicotinoids will not be acceptable. All plant material shall be certified to have been produced or grown
without the use of neonicotinoids.
Section Page 1 of 2
Section 32 90 00
Planting
Execution
The design for all landscape shall specify and detail the type, location, and installation methods of all
trees, shrubs, plants, and groundcovers. Irrigation systems shall be designed to provide appropriate
amounts of water for each plant type. The installation of plant material shall take place during appropriate
seasons to avoid plant loss.
Sustainability
Emory supports the reduced use of potable water for landscape irrigation purposes. The design team
should evaluate strategies such as specifying indigenous plant species requiring little or no irrigation, the
use of high efficiency micro-irrigation, storm-water and/or HVAC condensate harvesting. Following this
guidance may enable the project to achieve the Water Efficiency Credit 1 Water Efficient Landscaping
under the current LEED rating system.
Storm-water harvesting via the use of cisterns is referenced more in Section 33 40 00 - Storm Drainage
Utilities.
Section Page 2 of 2
Section 32 92 00
Turf and Grasses
Section Page 1 of 4
Section 32 92 00
Turf and Grasses
finished grades are not completed in time to permit planting and establishment of the permanent grass
during the favorable season between the dates specified above, the Contractor shall apply a 3" cover of
pine straw to protect the new graded areas from erosion and to keep windborne dust to a minimum.
Wheat straw shall not be used in any instance. In the event that a permanent lawn is not established by
the deadline for grassing, then the requirement is to have a pine straw cover until that season when
Fescue can be established is required.
Seed
The Architect and the Owner shall be furnished with copies of a statement from the vendor certifying that
each container of seed delivered is fully labeled in accordance with the Federal Seed Act and is at least
equal to the requirements for seed in the materials paragraph of these specifications (the Grassing
Specification). This certification shall appear on or with all copies of invoices for the seed. Each lot of
seed shall be subject to sampling and testing at the discretion of the Architect. Sampling and testing shall
be in accordance with the Georgia Department of Transportation Specifications.
Fertilizer and Lime
The Architect and Owner shall be furnished with copies of all invoices for all fertilizer and lime used on the
project. Invoices for fertilizer shall show the grade furnished. Invoices for lime shall show total minimum
carbonates and minimum percentages of the material furnished that pass the 100, 20, and 10 mesh
sieves. Each lot of fertilizer and lime shall be subject to sampling
and testing at the discretion of the Architect. Sampling and testing will be in accordance with the official
methods of the Association of Official Agricultural Chemists. Upon completion of the project, a final check
of the total area treated, and if the minimum rates of application have not been met, the Architect or
Owner may require the distribution of additional quantities of fertilizer and lime to make up the minimum
rates of application specified by the Architect.
Preparation of Planting Beds
1. Grades on the areas to be seeded, which have been established to facilitate drainage and
maintenance shall be maintained in a true and even condition. Where plant bed grades are
not smooth and even, the areas shall be leveled and left in an even, compacted condition
prior to seeding in order to prevent the formation of low places and pockets where water will
stand.
2. After the areas have been brought to an even and smooth grade, they shall be loosened to a
depth of at least 4 inches by plowing, disking, or harrowing. During tillage operation, the
surface shall be cleared of roots, cable, wire, or waste material, which might hinder final
grading, planting, or subsequent maintenance operations. Irregularities in the surface
resulting from tillage shall be smoothed out before sprigging or seeding operations are
begun.
Application of Fertilizer
Fertilizer shall be distributed uniformly at a rate of 1,000 pounds per acre and shall be incorporated into
the soil to a depth of approximately three inches by disking, or harrowing. The incorporation of fertilizer
may be a part of the tillage operation. If it is determined in the final checking that the minimum rates of
application or fertilizer have not been met, the Contractor shall distribute additional fertilizer to meet the
specified quantity.
Application of Lime
Following, or simultaneously with the incorporation of fertilizer, lime shall be distributed at the rate of
1,200 pounds per acre and shall be incorporated into the soil to a depth of at least three inches by
disking, or harrowing. The incorporation of lime, along with the fertilizer, may form a part of the tillage
operation specified above.
Sowing Seed for Permanent Grasses
Sow seed by mechanical power-drawn drills, seeders, or mechanical hand-seeders. When drills are used,
provision shall be made by markers or other means to assure that the successive seeded strips overlap
Revision Date November, 2014
Section Page 2 of 4
Section 32 92 00
Turf and Grasses
or are separated by a space no greater than the space left between rows planted by the equipment being
used. When delays in operations carry the work beyond the most favorable planting season for the
species designated, or when conditions are such, by reason of drought, high winds, or excessive
moisture, that satisfactory results cannot be obtained, the work shall be stopped and resumed only when
conditions are satisfactory. If inspection, during seeding operations or after there is a show of green,
indicated that strips are wider than the space between rows planted have been left unplanted, or areas
have been skipped, sow additional seed on these areas. Kentucky 31 seed shall be sown at the rate of 4
lbs. Per 1000 sq. ft.
1. Broadcast Seeding: Seed shall be broadcast either by hand or approved sowing equipment
at the rate specified above. The seed shall be uniformly distributed over the designated
areas. Half the seed shall be sown with the sower moving in one direction and the remainder
shall be sown with the sown moving at right angles to the first sowing. The seed shall be
covered to an average depth of 1/4 inch by means of a brush harrow, spike-tooth harrow,
chain harrow, or cultipacker. Broadcast seeding shall not be done during windy weather.
2. Hydroseeding: Prepare homogeneous slurry of the recommended quantities of seed and
fertilizer, adding wood cellulose fiber (conweb) and water to produce a distribution rate of 90
gal./1000 sq. ft. Distribute slurry uniformly and within one hour after mixing.
3. Mulching - All seed areas seeded with permanent grasses and areas on slopes 4:1 or
steeper shall be uniformly mulched in a continuous blanket immediately following seeding
and compacting operations. Mulch shall be spread at a rate of 1 1/2 tons to the acre. It is
intended that mulch shall allow some sunlight to penetrate and air to circulate, at the same
time shading the ground, reducing erosion, and conserving soil moisture. The thickness of
the covering shall hold the soil but be loose and open to favor the development of grass.
Following the spreading of mulch, the material shall be anchored to the soil by means of a
seed drill, culitpacker or disk harrow which will secure the mulch and prevent loss or
bunching by wind or rain, or mulch may be anchored with string lines placed at sufficient
intervals. On slopes where machinery cannot be used, mulch may be retained in place by
hand spading or string lines which will not be detrimental to subsequent maintenance. Upon
completion, the surface of the mulched areas shall be smooth and free from clods of earth,
bumps, or water-holding pockets.
4. Compacting - After seeding operations have been completed, the entire area shall be
compacted by means of a cultipacker or roller weighing 60 to 90 pounds per linear foot of
roller. If the soil is such that a smooth or corrugated roller cannot be operated, a pneumatic
roller, not a wobble-wheel, shall be used. The pneumatic roller shall have tires sized so that
coverage of the soil surface is obtained. When a cultipacker is used, the final rolling shall be
at right angles to the existing slopes to prevent water erosion or at right angles to the
prevailing wind to prevent dust. Seeded areas inaccessible to roller equipment shall be firmed
by hand methods.
5. Watering - Water will be required within 12 hours following planting and mulching operations
unless the ground is moist or rain is imminent. Watering shall soak the ground six inches
below the surface of the ground. Additional applications shall be made at intervals when the
grass begins to suffer from drought, soaking the ground as specified. During the summer
months, watering shall be done in the cool of the day. During the fall months, no watering
shall be done where there is danger of freezing. Water shall be delivered in containers, which
are equipped with means for even distribution of water at the indicated rate. Watering shall be
done in a manner, which will prevent erosion from the application at excessive rates and
prevent damage to the finished surface by wheel scars. Adequate watering shall be
continued until an acceptable stand of grass is established.
Maintenance
The Contractor shall maintain seeded, and mulched areas until date of Final Inspection. Lawns should be
cut at least twice before acceptance. Maintenance shall consist of providing protection against traffic by
warning signs and barricades, repairing any areas damaged as a result of the Contractor's own
operations, and erosion, and mowing to a height of three inches when weeds or other vegetation tend to
Revision Date November, 2014
Section Page 3 of 4
Section 32 92 00
Turf and Grasses
shade or smother the new plantings. Seeded areas will be considered established and satisfactory when
new growing sprouts are not less than 9 seedlings at least 2 inches long in each square foot of area.
1. Application of Nitrogenous Fertilizer: During the maintenance period, the Contractor shall
furnish and apply nitrate of soda or ammonium nitrate to the planted areas. The nitrogen
fertilizer shall be uniformly spread and distributed with equipment at the rate that will give not
less than 75 pounds of available nitrogen per acre. Other commercial types of nitrogenous
material may be substituted at the option of the Contractor. The time of applications shall be
limited to the following unless the Architect approves time extension. Applications will be
required so that a total of 5 pounds of nitrogen per 1000 sq. ft. will have been applied under
this contract. Applications should be made in September and May.
2. Establishment: The Contractor shall care for seeded and mulched areas until a cover of
growing spouts is visible as specified. During this establishment period, the Contractor shall
reseed and remulch unsatisfactory areas. Contractor shall keep mowed weeds and
vegetation that might tend to smother out the permanent grass. All costs and charges in
connection with work and materials for maintenance and establishment of the permanent
grass, including soil repairs, shall be borne by the Contractor at no additional expense to
Emory University. The establishment period shall extend until the date of Final Inspection.
Seeded areas not showing satisfactory growth at the surface, sixty days after planting shall
be reseeded.
3. Cleanup - Remove all paper bags, excess material and debris from the project site. At the
completion of the establishment period all stakes, tools, equipment, and debris shall be
removed and the site shall be left in a neat condition.
Sustainability
Emory supports the reduced use of potable water for landscape irrigation purposes. The design team
should evaluate strategies such as specifying indigenous plant species requiring little or no irrigation, the
use of high efficiency micro-irrigation, stormwater and/or HVAC condensate harvesting. Following this
guidance may enable the project to achieve the Water Efficiency Credit 1 Water Efficient Landscaping
under the current LEED rating system..
Stormwater harvesting via the use of cisterns is discussed more in Section 33 40 00 - Storm Drainage
Utilities.
Section Page 4 of 4
Section 33 10 00
Water Utilities
Gate valves shall employ mechanical joints. Acceptable manufacturers are as follows:
o Mueller
o M&H
o Kennedy
All buried valves shall have cast iron three-piece valve boxes. Water system valve boxes shall
have a minimum of a 12 x 12 cast in place concrete pad poured around the valve box. This is
for landscaped areas. The valve boxes shall have water cast in their tops.
Pressure testing with air is prohibited.
Piping 4 and greater shall be ductile iron. Piping scheduled to be 3 and smaller shall be Type K
copper. The Engineer may elect to upsize this piping to 4 ductile iron if there are cost savings.
Do not locate piped utilities under any building or structure. Warning tape shall be buried over all
piped utilities. Fire hydrants acceptable fire hydrants are as follows:
o Mueller
o M&H
o Clow
Types
o Double Check Valve Back Flow Preventers:
Acceptable Products:
Watts 007
Watts 709
Watts 757
Acceptable Location: Domestic back flow preventers may be located
underground in a vault if a double check valve back flow preventer type is
acceptable. Double check valve back flow preventers may be acceptable in
buildings such as office or classroom buildings. Research, laboratory or clinical
buildings require the use of a reduced pressure zone back flow preventer. .
o Reduced Pressure Zone Back Flow Preventers:
Acceptable Products:
Watts 909
Acceptable Location: If a reduced pressure zone back flow preventer is used, it
shall be located in a building.
Section Page 1 of 2
Section 33 10 00
Water Utilities
Section Page 2 of 2
Section 33 30 00
Sanitary Sewerage Utilities
Products
A. Sanitary sewer piping shall be ductile iron piping.
B. All sanitary sewer manholes shall include accessible steps.
C. The tops of all sanitary sewer lids used as manhole or structure covers shall have the word
Sewer integrally cast into the lid.
D. Sanitary sewer cleanouts shall have a minimum of a 12 x 12 concrete pad poured around the
cleanout frame to secure the frame and to make the cleanout easier to locate. Note that details
on the project drawings will need to add the words cast in place when referring to the concrete
pad.
E. Locate a manhole at every lateral sanitary sewer connection into a main line. Locate a manhole
at every turn in the line greater than 45 degrees.
F. The Contractor shall be required to video the sanitary sewer mains under the building structure
out to the first cleanout or sanitary sewer structure. This shall be done after the sewers are
cleaned and the building is in use. We have had problems with settlement of these sewer mains.
Quality Control
A.
Video Inspection of major trunk lines all the way to the last sanitary sewer manhole required
after substantial completion. Quality review of sewer piping to ensure there is no lateral
settling.
Sustainability
A. Emory supports the reduced use of potable water for building sewer conveyance. The design
team should evaluate strategies that may allow the project to achieve Water Efficiency Credit 2
Innovative Wastewater Technologies under the current LEED rating system and should review
options with the Emory Project Manager. Recent designs have used graywater and stormwater
to help attain this goal, and a water reclamation facility that is currently under construction to
supply quality water for non-potable uses to the north side of campus will likely be operational in
2015. Projects in this north sector are encouraged to consider using the reclaimed water as
project logistics allow.
B. Graywater reuse systems may collect waste discharge from the following sources: bathtubs,
showers, lavatories, clothes washers, and laundry trays. Water from other approved nonpotable
sources including swimming pool backwash operations, air conditioner condensate, rainwater,
cooling tower blow-down water, foundation drain water, steam system condensate, fluid cooler
discharge water, food steamer discharge water, combination oven discharge water, industrial
process water, and fire pump test water may also be permitted to be collected for reuse by
graywater systems, as approved by the code official and as appropriate for the intended
application. Options should be discussed with the Emory Project Manager during Schematic
Design.
C. Stormwater harvesting via the use of cisterns is discussed more in Section 33 40 00 - Storm
Drainage Utilities.
Section Page 1 of 1
Section 33 40 00
Storm Drainage Utilities
Products
A. For storm piping sized at 10 in diameter and less, use Schedule 40 PVC piping.
B. For storm sewer piping sized greater than 10 in diameter, use Reinforced Concrete piping.
C. For piping located under structures, use ductile iron piping in lieu of PVC.
D. All storm sewer manholes shall include accessible steps.
E. The tops of all storm sewer lids used as manhole or structure covers shall have the word Storm
integrally cast into the lid.
F. Storm sewer cleanouts shall have a minimum of a 12 x 12 concrete pad poured around the
cleanout frame to secure the cleanout frame and to make the cleanout easier to locate. Note that
details on the project drawings will need to add the words cast in place when referring to the
concrete pad.
Sustainability
A. All Emory projects shall attempt to meet and exceed the requirements of Sustainable Sites
Credits 6.1 and 6.2 Stormwater Management: Quantity and Quality Control under the current
LEED rating system. Following this guidance may also enable the project to achieve the Water
Efficiency Credit 1 Water Efficient Landscaping. If these requirements are not possible or place
an undue cost on the project, this should be outlined during Schematic Design. At the minimum,
however, local, state and federal regulations regarding stormwater control must be followed.
B. Generally, emphasis shall be placed on reducing impervious cover, increasing on-site infiltration,
reducing or eliminating contaminants from runoff, and stormwater harvesting. The use of cisterns
to store recovered stormwater for irrigation purposes is the most common method of stormwater
harvesting at Emory. Specific requirements for these systems regarding capacity, pumping and
filtration should be determined with the assistance of Emorys Energy and Utilities department
and Exterior Services and Sustainability departments.
C. Additionally, it is critical to review approaching this credit from a campus-wide, holistic
perspective. Emory Universitys Stormwater Master Plan shall be reviewed prior to design
activities, and all drainage concepts for the project shall be consistent with the Master Plan. Both
project sub-basin and regional drainage conditions shall be assessed during design; sometimes
the most prudent manner to improve the stormwater rate and quantity comes from a larger site
than the current project alone.
Section Page 1 of 1
Section 33 60 00
Steam & Chilled Water Distribution Systems
1.02
GENERAL
SCOPE OF WORK
A.
The Contractor shall supply all labor, equipment, materials and incidentals necessary to
install the underground steam, condensate, and chilled water distribution system. These
systems include but are not limited to: field fabricated conduit piping, equipment room
entry, manhole construction, utility trench construction, equipment, valves, piping, thermal
expansion devices, thermal insulation, piping supports, fittings and accessories. The above
systems shall be installed and tested as shown on the Contract Drawings and/or as
specified herein.
B.
This specification section is included for general use for steam, condensate, and chilled
water underground distribution piping systems. This specification section covers items that
may or may not be a part of this particular project. Refer to the drawings for actual scope
of work including quantities and types of piping.
RELATED WORK
(Note to Engineer: Your project manual may or may not have the following sections depending upon
whether this project is a stand-alone project or combined with a major building construction project.
Please revise accordingly.)
1.03
A.
B.
Section 02220: Excavation, Backfill, Fill, and Grading for Structures and Pavement (Site
Mechanical)
C.
Section 02221: Excavation, Backfill, and Grading for Underground Steam and Chilled Water
Distribution Systems (Site Mechanical)
D.
E.
APPLICABLE PUBLICATIONS
The publications listed below form a part of this specification to the extent referenced. The publications
are referred to in the text by the basic designation only. The latest revision to that particular standard or
code is intended to be used.
A.
Section Page 1 of 21
B.
C.
API 601-88
Bolted Bonnet Steel Gate Valves for Petroleum and Natural Gas
Industries
Metallic Gaskets for Raised-Face Pipe Flanges & Flanged
Connections (Double-Jacketed Corrugated and Spiral-Wound)
E.
D.
Section 33 60 00
Steam & Chilled Water Distribution Systems
F.
G.
H.
Section 33 60 00
Steam & Chilled Water Distribution Systems
1.04
DEFINITIONS
A.
1.05
In ANSI B31.1, the advisory provisions shall be considered mandatory, as though the word
shall had been substituted for should wherever it appears.
SUBMITTALS
A.
The following items shall be submitted to and reviewed by the Architect/Engineer prior to
commencing work.
1. Shop Drawing Submittals, Approval of Materials and Proposed Schedule of Activities:
Submit shop drawings, material certification, and schedule of work activities.
2. Underground Steam, Condensate and Chilled Water Piping Systems. Submit shop
drawings stress analysis and material certifications on the accepted materials.
3. Pipe, Pipe Fittings, and Piping Accessories: Submit manufacturers material brochures
showing conformance to the requirement of ANSI B31.1 or a letter from the
manufacturer certifying conformance to ANSI requirements.
4. Gaskets: Submit gasket manufacturers brochure.
5. Studs and Nuts: Submit manufacturers material brochure showing conformance to the
requirements of ASTM A-193 and ASTM A-194 or a letter from the manufacturer
certifying conformance to ASTM requirements.
6. Welding Fittings: Submit manufacturers material brochures showing conformance to
the requirements of ASTM A-234, ANSI B16.5, ANSI B16.9, and ANSI B16.11 or a
letter from the manufacturer certifying conformance to ASTM and ANSI requirements.
7. Welding Procedures Specification (WPS), Procedure Qualification Record (PQR) and
Individual Welder Certifications shall be submitted in accordance with paragraph
QUALIFICATIONS OF WELDERS.
8. Test Gauges: Submit manufacturers material brochure on dial type pressure gauges
to be used during the test procedure on the steam, condensate return and chilled water
distribution piping.
9. Qualifications of Independent Testing Firm or Firms: Submit the name, address, and
telephone number of any firm or firms selected to conduct test.
10. Pipe Supports and Hangers: Submit manufacturers material brochures, all conforming
to MSS SP-58 and SP-69. Submit shop drawings of pipe supports in manholes
(locating by type and size of pipe supports in manholes).
11. Valves: Submit manufacturers material brochures.
12. Strainers: Submit manufacturers material brochures.
Section Page 3 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
13. Thermal Pipe Insulation: Submit manufacturers material brochures and a letter from
manufacturer certifying conformance to ASTM requirements. Include aluminum jacket
lagging, coatings, mastics, sealant and adhesives as necessary.
14. Pipe Sleeves: Submit shop drawing and/or manufacturers material brochure indicating
dimensions and certifying conformance to contract drawing details.
15. Expansion Joint: Submit shop drawing and manufacturers material brochure.
16. Sump Pump: Submit manufacturers material brochure.
17. Sump Pump Screen: Submit shop drawings.
18. Steam Traps: Submit manufacturers material brochures.
19. Buried Warning Tape: Submit manufacturers material brochure.
1.06
Steam System:
1. The existing steam system is designed for an operating pressure of 150 psig at 366
degrees F. The existing condensate system is designed for an operating pressure up
to 50 psig and an operating temperature of 190 degrees F. Expansion for new
underground condensate systems shall be calculated at a minimum temperature
differential of 300 degrees F. New steam and condensate system components
including piping, equipment, valves, and accessories shall be suitable for minimum
steam working pressure of ANSI Class 150 (150 psig steam working pressure).
B.
1.07
REGULATORY REQUIREMENTS
A.
Conform to the safety and fire regulations of State Fire Marshall and DeKalb County Fire
Department when work is in progress.
PART 2 - PRODUCTS
2.01
2.
3.
4.
Unless otherwise specified, all carrier pipe, fittings, and piping accessories shall
conform to the requirements of ANSI B31.1, and shall be of the proper type for
pressure and temperature of the heating medium. Joints for ferrous piping shall
be butt welded for piping 2-1/2 and above. Joints for ferrous piping 2 and below
shall be socket welded.
Steam Piping: Pipe shall be black steel plain end beveled and shall be Schedule
40 conforming to ASTM A 106, Grade B seamless.
Condensate Return Piping: Pipe shall be black steel plain end beveled and shall
be Schedule 80 conforming to ASTM A-106, Grade B seamless.
Fittings: Provide fittings compatible with pipe being used. Fittings shall be used in
conformance with ANSI B31.1. Fittings in size 2-1/2 and larger: Steel butt
welding type conforming to ANSI B16.9. Fittings in size 2 and smaller: Socket
weld fittings conforming to ANSI B 16.11.
Section Page 4 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
5.
Insulation shall be mineral fiber, 8-pound density. Insulation shall have been
tested and certified in compliance with the Department of Navy 96-hour Conduit
Boiling Test. Pipe insulation shall be Rockwool, Delta, Owens Corning HT1200
BWT or approved equal. Insulation thickness shall be as follows: 6 inch steam
piping and greater 2-1/2 inches thick; 4 inch steam piping 1-1/2 inches thick; 3
inch steam piping 1 inch thick; 2-1/2 inch steam piping 1 inch thick; 2 inch steam
piping 1inch thick; 1-1/2 inch steam piping 1 inch thick; 1 inch steam piping 1 inch
thick; 4 inch and greater condensate piping 1-1/2 inch thick; 3 inch and below
condensate piping 1 inch thick.
6. Air Space: A minimum air space of 3/4 inch between the insulation outside
diameter and the underground conduit inside diameter shall be provided for
conduit venting and draining.
7. Underground Conduit for Carrier Piping: All piping conduit shall be smooth wall,
constructed of 10-gauge steel.
8. External conduit coating shall be fusion bond epoxy (3M Scotchkote 206N or
226N with a top coat of 3M Scotchkote 6251 or Lilly Pipe Clad 2040) applied onto
a shot blasted steel conduit with a minimum thickness of 20 mils. The base
specification shall be fusion bond epoxy. The Vendor may provide an alternate for
evaluation of a urethane coating (Isotech Isocoat) applied onto a shot blasted
steel conduit with a minimum thickness of 30 mils. The interior conduit coating
shall be epoxy with a minimum thickness of 6 mils.
9. The external conduit shall be repaired in the field using epoxy (3M Scotch Kote
312) or urethane (Isotech Patchcoat) as appropriate.
10. Field closures: All field closures shall be installed in strict accordance with the
manufacturers recommendations. Shrink sleeves shall be provided by Raychem
or Canusa.
B.
Holiday Inspection:
1.
2.
C.
All underground buried conduit coatings shall be suitable to withstand multiple holiday
sparking while maintaining its dielectric strength. Holiday testing shall be performed at
2500 volts or 5000 volts as recommended by the manufacturer.
Two separate holiday tests shall be performed on all coated conduits during the
following periods of construction: 1) prior to placing in the trench; 2) prior to backfill
operations. The Contractor shall be responsible for performing the holiday tests and
providing the Owner with a certified test report prior to backfilling operations. Any
discrepancies found during the tests shall be repaired by the Contractor, and
supervised by a factory representative of the prefabricated pipe manufacturer and
retested.
Air tests:
1. The outer casing of the steam and condensate piping shall be tested with compressed
air at a pressure of 15 psig. All joints shall be soap mixture tested for leaks. All leaks
shall be repaired and re-tested to 100% no leak compliance.
D.
Section Page 5 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
testing of the conduit; 5) the initial backfilling operation. The manufacturer shall
provide a minimum of two (2) days (16 FTE-hours) of supervision on the jobsite
supervision.
2. The piping shall be installed in strict accordance with the manufacturers published
standard installation guide.
3. Manufacturer Certification: The prefabricated pipe manufacturer shall provide a
certificate stating that the direct buried piping system was installed in accordance with
the manufacturers recommendations.
4. The underground steam and condensate return conduit system shall be shipped with
covers installed on the piping prior to shipment from the factory.
E.
Acceptable Manufacturers:
1. Pre-fabricated/Pre-insulated: The underground steam and condensate piping system
shall be manufactured by one of the following manufacturers: Perma-pipe, Rovanco or
Thermacor.
2.02
2.03
BACKING RINGS
A.
2.04
Section Page 6 of 21
1.
2.05
Section 33 60 00
Steam & Chilled Water Distribution Systems
Provide full-face gaskets for flat-face flanged joints, and ring gaskets for raised-face
flanged joints.
B.
Bolts: ASTM A193, Grade B7. Bolts shall be zinc plated in accordance with ASTM B-633.
Extend bolts no less than two full threads beyond the nut with the bolts tightened to the
required torque.
C.
Nuts: ASTM A194, Grade 2H. Nuts shall be zinc plated in accordance with ASTM B-633.
D.
Washers: ASTM F436, flat circular hardened steel washers. Washers shall be zinc plated
in accordance with ASTM B-633. Provide washers under bolt heads and nuts.
E.
Studs: ASTM A-193, Grade B7, alloy steel and shall be threaded full length and shall
extend completely through the nuts. Furnish two (2) hex nuts each per stud. Stud nuts
shall conform to A194.
Upper Attachments:
1.
2.
B.
Wall Supports: Where piping is run adjacent to walls, welded steel brackets Grinnell FIG.
195 and 199 may be used. The bracket shall be bolted to the wall with a back plate of such
size and thickness as to properly distribute the weight.
C.
Pipe Insulation Protective Shields and Saddles for Horizontal Piping in Manholes and
Tunnels:
1.
Provide galvanized sheet metal pipe insulating protection shields at each pipe hanger
for all horizontal insulated steam and condensation return pipes. Shield sizes shall be:
Pipes 2 inches and smaller:
Pipes 2-1/2 inches and larger:
2.
D.
Shields shall be 180 degree type at all pipe hangers; except that on trapeze hangers,
pipe rack and on floor supported, horizontal pipes shields shall be 360 degree type.
Use calcium silicate inserts at all shields, hangers, sleeves, etc.
Section Page 7 of 21
2.
3.
4.
E.
Framing channels and fittings shall be provided with factory applied galvanized finish.
Galvanized pipe clamps, including bolts and nuts and washers, shall be provided with
the framing channels and shall be used for securing pipes to channels. Pipe clamps on
insulated pipes shall fit around pipe insulation protection shield.
Framing channels and fittings shall be F&S Mfg. Co. Series F Metal Framing, Fee and
Mason FAMET Channel and Fitting, Carpenter & Patterson Channel Strut, B-Line or
approved equal.
Intermediate Attachments: Supports for horizontal piping shall be all threaded carbon steel,
Grinnell Fig. 146., of the following sizes:
Pipe Size
2-inch and smaller
2 -inch and 3-inch
4-inch
6-inch
8-inch
10-inch
F.
Section 33 60 00
Steam & Chilled Water Distribution Systems
Pipe Attachments:
1. Hangers for insulated pipe shall be sized to bear on the outside of the insulation.
2 Hangers for steel horizontal piping where provisions for expansion are not required
shall be Grinnell Fig. 160, clevis type with vertical adjustment.
3. Hangers for steel piping where provisions for expansion are required shall be Grinnell
Fig. 171 or Fig. 181, adjustable roller hanger with Grinell Fig. 160, pipe covering
protection saddles.
2.06
VALVES
A.
Globe Valves:
1. Globe valves 1 1/2 inches and smaller in size shall be ANSI 150 pound class, bronze,
with union bonnets and threaded ends. Globe valves shall conform to ANSI B16.34,
and MSS SP-61. Valve packing and trim shall be suitable for high-pressure steam
service. Globe valves shall be Crane, Stockham, Nibco, Milwaukee or Hammond.
2. Globe valves 2 inches and larger in size shall be ANSI 150 pound class, steel, with
flanged ends. Globe valves shall be plug-type disc type, conforming to ANSI B16.34.
Value packing and trim shall be suitable for high-pressure steam service. Globe valves
shall be Crane, Stockham, Milwaukee, Hammond or Powell.
B.
Gate Valves:
1. Gate valves 2 inches and larger in size shall be ANSI 150 pound class, cast carbon
steel, stainless steel trim, wedge gate type and suitable for the operating temperature
and pressure. They shall have outside screw and yoke. Valve body shall have straightthrough ports without recesses except between seats to ensure minimum turbulence,
erosion, and resistance to flow. The bonnet shall be bolted-type and equipped with a
bonnet bushing. Design and dimensions shall conform to API Standard 600. Pressure
temperature rating shall be in accordance with ANSI B16.34. Face-to-face dimensions
shall conform to ANSI B16.5. Flanges shall conform to ANSI B16.5. Valve body
markings shall conform to MSS SP-25.
2. Gate valves 1 1/2 inches and smaller in size shall be ANSI 150 pound class, bronze with
union bonnet and threaded ends. Renewable seat rings and valve trim shall be made of
bronze.
Section Page 8 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
3. Gate valves shall conform to ANSI B16.34. Valve packing shall be non-asbestos type,
suitable for the system temperature.
4. Gate valves 6 inches and larger shall be provided with an integral bypass valve.
5. Gate valves shall be Crane, Stockham, Nibco, Milwaukee, Hammond or Powell...
2.07
C.
Check Valves: Check valves 1 1/2 inches and smaller shall be bronze, threaded ends.
Valves 2 inches and larger shall have cast steel or forged steel bodies and shall have
flanged ends. All valves shall be of the swing check type with renewable seats and disc.
Valves shall be designed so that the disc and seat can be renewed without removing the
valve from the pipe line. Steel valves shall conform to ASTM A216.
D.
Ball Valves: ANSI Class 150. Provide non-lubricated double seated ball valve type capable
of handling two-way shut-off lever operated. Minimum bore size shall be 90 percent of the
internal cross sectional area of a pipe with the same nominal diameter. Valves in carbon
steel piping shall have steel bodies with chromium-plated or nickel-plated steel balls.
Valves shall have stainless steel stems and trim, and Viton seats, body seals, and stem
seals. Ball valves shall be manufactured by Neles-Jamesbury Corporation, Apollo, or
approved equal.
PIPING ACCESSORIES
A.
Strainers: All strainers shall be the Y type unless indicated otherwise and shall have a
steam working pressure of 150 psi at 366 F. ANSI Class 150 strainers shall be steel, with
screwed ends (1/1/2 inch and smaller), with flanged ends (2 inch and larger), perforated 20
mesh stainless steel screen, machined screen seat and blow off outlet. Strainers shall be
installed at the inlet of all steam traps and at other locations as shown on the drawings.
Provide piping full size of the flow off connection, with a gate valve. Subject to compliance
with requirements, provide strainers of one of the following: SARCO, Armstrong or
approved equal.
B.
Pipe sleeves: Provide where piping passes through manhole structures and equipment
room walls. Grout sleeves in position and location during construction. Provide sleeves of
sufficient length to pass through entire thickness of structure with a minimum one inch
clearance between exterior of piping or pipe insulation and interior of sleeve conduit or core
drilled hole. Seal space with waterproof link seal closure.
C.
Flanges:
1. In steam and condensate return piping where specified, required or shown on the
drawings, provide flanged connections. Flanges shall have a steam working pressure
suitable for the pressure classification of the piping system in which installed. Where
flanges are used at equipment connections, flanges shall match equipment flanges.
Flanges shall be forged steel, socket weld type (2 inch and smaller pipe size), welding
neck type (2 1/2 inch and larger), raised face, ANSI B16.5.
2. Flange bolting materials shall be carbon steel meeting the specifications of ASTM
Standard A193 and ANSI B16.4, Grade A hexagon head bolts and hexagonal nuts.
Flange bolt threads shall be lubricated with molybdenum disulfide anti-seize
compound. All flange bolting materials within the same piping pressure classification
shall be similar on the entire project.
D.
Section Page 9 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
2. Unless otherwise indicated, the trap capacity shall be based on a condensate handling
capacity of 100% of the maximum load developed by the piping system or apparatus to
which it is connected.
3. Traps shall be manufactured by Sarco or Armstrong.
E.
2.08
Unions: Union joints in pipe 2-1/2 inches and smaller shall be provided in each pipe line
preceding the connections to each piece of equipment and as indicated. Unions shall
match the piping system in which they are installed.
THERMAL PIPE INSULATION FOR STEAM AND CONDENSATE PIPING (IN MANHOLES AND
TUNNELS)
A.
2.09
Insulation Thickness
1 1/2 thick
3 thick
4 thick
2 thick
2 thick
Pipe Markings:
1. Pipe markings shall be applied by using stencils and spray on stencil ink. Band and
letter sizes and identification shall be as indicated in PART 3 EXECUTION. Direction
of flow arrows shall be placed next to color bands. A white background of stencil ink
shall be provided where black letters are used on pipe or pipe covering material that is
already black.
2. In lieu of painting markings, manufactured, preprinted markings may be used in
accordance with the following:
a.
b.
c.
d.
B.
Band and Letter Size: Band and letter sizes shall conform to the following ASHRAE
standards:
Section Page 10 of 21
O.D. of Piping
of Covering
C.
D.
2.10
B.
1/2
1-1/2 to 2
3/4
2-1/2 to 6
12
1-1/4
8 to 10
24
2-1/2
Identification: Band legend and color and letter color shall conform to the following table:
Piping Band
Legend
Letters
Band Color
HPS
Black
Yellow
Condensate Return
CR
Black Yellow
Sand backfill shall be used as a backfill material for a minimum of 6 inch on all sides of
underground steam and, condensate piping. Only washed river sand shall be used. The
sand shall meet the gradation requirements of the Georgia State Department of
Transportation Specifications. Sand shall be subject to testing for suitability.
Sand shall be compacted to 90% minimum of its maximum dry density.
Provide plastic tape for warning and identification of buried steam, condensate and chilled
water/hot water piping. Provide tape in minimum 4-inch width rolls, color coded for the
utility involved, with warning and identification imprinted in bold black letters continuously
and repeatedly over entire tape length. Use permanent code and letter coloring unaffected
by moisture and other substances contained in trench backfill material. Install continuously
along length of piping, 18 inches above the piping along with final backfilling.
CURB MARKERS
A.
2.13
2.12
Size of
Ltr./No.
SAND BACKFILL
A.
2.11
Width
Color Band
Section 33 60 00
Steam & Chilled Water Distribution Systems
Provide Curb Markers by Rhino Marketing & Protection Systems to indicate underground
utilities where they cross streets and other surfaces designated for vehicle traffic.
PIPE SLEEVES
A.
Fit all pipes passing through concrete manholes, building walls and floors, with shop
fabricated pipe sleeves or core drill with mechanical link seals. Extend each sleeve through
its respective wall and cut flush on inside and outside surfaces. Provide sleeve size based
on recommended link seal size for pipe or conduit being installed. Pipe sleeves shall be
fabricated from Schedule 40, black steel pipe conforming to ASTM A-53, Grade B.
B.
Attach leak plate around center of pipe sleeve unit prior to delivery. Install a mechanical
type interlock seal, Buna-N links shaped to fill the annular area between the sleeve and
pipe or conduit. Link type seal shall be installed on interior end of pipe sleeve. Link seals
Section Page 11 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
2.14
2.15
SUMP PUMP
A.
Sump pumps shall be submersible steam ejector type and shall be installed as indicated on
the Drawings.
B.
The pump shall have a ductile iron body with stainless steel internal parts. Pump shall be
provided with stainless steel inlet and outlet check valves and stainless steel float, arm,
linkage and mechanism. Minimum discharge rate shall be 20 gpm capacity at 20 feet pf
water TDH (min.). All pressure parts shall be rated for ANSI 150 pound class.
C.
Sump pump shall be Armstrong, Penberthy Model 2R-SL, Sarco, Watson McDaniel or
Owner approved equal.
2.16
Shop fabricate a sump pump screen for each new sump pump. Screen shall be hot-dipped
galvanized welded frame construction consisting of galvanized steel angles and square
mesh stainless steel hardware cloth. Screen top shall be thick steel checked plate
welded to the frame. Design sump pump screen to sustain a live load of 150 pounds per
square foot. Hot dip galvanize entire unit after fabrication.
MANHOLE LADDER
A.
2.17
Core drilling of new or existing concrete walls is acceptable when the exact location of the
opening cannot be determined prior to the construction of the wall.
Provide steel ladders complete with structural members to form side rails, rungs and
mounting brackets. All materials shall be shop welded construction and hot dipped
galvanized after fabrication. All necessary bolts, anchors, washers and other fastenings
shall be stainless steel. Use standard finished structural steel shapes or bar iron in
compliance with AISC Specifications for Design Fabrication and Erection of Structural Steel
for Buildings.
Manhole frames and cover castings shall be high quality, strong, tough, even-grained, cast
iron, smooth, free from scale, lumps, blisters, sand holes and defects of any kind which
render them unfit for the service for which they are intended. Castings shall be thoroughly
cleaned and subject to hammer inspection. Manhole covers and frame seats shall be
machined and/or cast true to a plane surface. Before shipment from the factory, casting
shall be given one coat of coal tar pitch varnish, which shall present a coating, which is
smooth and tough, but not brittle. Sizes shall be as shown on the drawings. Cast iron shall
be gray iron casting conforming to the AASHTO Designation M-105 and shall be Class No.
30.
B.
Frames and covers shall have a minimum total weight of 400 pounds. Covers shall have a
weight not less than 300 pounds.
C.
All covers shall have the word STEAM in raised 2-inch letters cast into the top.
Section Page 12 of 21
D.
2.18
Section 33 60 00
Steam & Chilled Water Distribution Systems
All manhole frames and covers shall have a minimum of 30 inches clear opening between
the innermost ring circumference. The lower flange of the frame shall be at least 6 inches
in width. All covers shall be supplied with pick holes.
B.
C.
0.150
Above 8 to 16
0.175
Greater than 16
0.200
All chilled water system piping shall be insulated with 2-pound density polyurethane foam.
Insulation thickness shall be as listed below:
Pipe Size
1.25
4-12
1.5
14-18
2.0
D.
The foam insulation shall totally fill the space between the carrier pipe outside diameter and
the conduit internal diameter.
E.
Closure sleeves shall be furnished by the manufacturer with insulation kits and installed
watertight by the Contractor.
F.
Terminate outer jackets 4 inches beyond the inside face of manholes or building walls or
floors, and provide mastic sealant to protect the end of the factory installed insulation.
G.
Chilled water carrier piping shall be Schedule 40 black steel (ERW) conforming to ASTM
A53 Grade B. Piping 12 inches and larger shall have a pipe wall thickness of 0.375 inch
(standard weight).
H.
Supports shall be placed inside the conduit so that the carrier pipe is concentric within the
outer conduit.
I.
Field Closures: All field closures shall be installed in strict accordance with the
manufacturers recommendations. Shrink sleeves shall be provided by Raychem or
Canusa.
Section Page 13 of 21
2.19
Section 33 60 00
Steam & Chilled Water Distribution Systems
J.
Factory Trained Supervision: The pre-fabricated pipe manufacturer shall observe enough
of the installation to be able to accurately submit a certification to the Owner that the direct
buried piping system was installed in accordance with the manufacturers
recommendations. A factory-trained technician with a minimum of two years experience
shall perform the supervision. The technician shall observe the following critical periods of
construction: 1) unloading of the piping system; 2) welding of at least one carrier pipe
connection and the associated conduit closure; 3) hydrostatic carrier pipe testing and 4) the
initial backfilling operation. The manufacturer shall provide a minimum of two (2) days (16
person hours) of supervision.
K.
Underground Chilled Water Gate Valves: Valves shall conform to AWWA C509 resilient
seated, ductile iron body and bonnet, non-rising bronze stem, 250 psig working pressure,
with a 2-inch square operating nut which shall turn counter clockwise to open with flanged
ends. Valves shall be designed for buried underground service. Underground chilled water
gate valves shall be manufactured by CLOW, Kennedy, Stockham, M&H, Nibco, or
Engineer approved equal.
B.
Aboveground Chilled Water Valves: Valves located in crawl spaces, areaways, tunnels and
other accessible locations shall be butterfly valves. Valves shall be rated for a minimum
working pressure of 200 psig. Butterfly valves shall comply with MSS SP-67, shall be the
lug type, cast iron or ductile iron body, EPDM seat and a 316 SS stem. Butterfly valves
shall be lever operated through 6 inches sizes and gear operated for 8 inches and above
sizes. Butterfly valves shall be manufactured by Stockham, Nibco, Milwaukee or
Hammond.
C.
Chilled Water Piping Air Vent Valves: Air vent valves on chilled water piping shall be
bronze angle globe type, union bonnet, integral seat, renewable seat and disc, threaded
end connections, rated ANSI Class 150, one inch in size. Valve shall be manufactured by
Stockham, Nibco, Milwaukee or Crane.
PART 3 - EXECUTION
3.01
PREPARATION
A.
3.02
The Contractor shall be responsible for surveying and laying out the new underground utility
distribution route (steam and chilled water). Advanced trench excavation and physical
location of underground utilities as defined on the Contract Drawings is advised to keep
within the project schedule. Discovery of any unforeseen site conditions shall be reported
to the Owner and Architect/Engineer as soon as they are encountered.
INSTALLATION
A.
Provide all work, labor, materials and equipment to construct the underground utility
distribution system in a complete, convenient manner. Install piping straight and true to
bear evenly on supports. Install valves with stems horizontal or above. Install flanges and
unions at valves, connections to equipment, and where indicated. Completely provide each
system to be ready for operation. Equipment, materials, installation, workmanship,
fabrication, assembly, erection, examination, inspection, and testing shall be in accordance
with ANSI B31.3, except as modified herein. Excavation: The Contractor shall excavate a
Section Page 14 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
minimum of 200 linear feet of trench prior to welding piping. This allows the Contractor to
fully assess field conditions prior to beginning joints.
3.03
B.
C.
Connections to Existing Systems: Notify the Owner in writing at least 7 days prior to the
date the connections are required; receive approval before interrupting service. Provide all
materials and labor required to make connections into existing systems and perform
excavating, backfilling, compacting, and installation as required.
D.
Cutting Existing Pipe: Perform the initial cutting of the existing pipe with a multi-wheel pipe
cutter. After cutting, seal the interior of the piping with a barrier plug. The Architect shall
approve the complete method of cutting, sealing, and welding in advance of the actual
work.
E.
Cleaning of Piping: Keep the interior and ends of new piping and existing piping affected by
the Contractors operations thoroughly cleaned of water and foreign matter. Keep piping
systems clean during installation by means of plugs or other approved methods. When
work is not in progress, securely close open ends of pipe and fittings to prevent entry of
water and foreign matter. Inspect piping before placing into position.
3.04
Section Page 15 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
A. Hang pipe from concrete overhead or pipe support brackets. Pipe shall not be hung from
other piping. Install additional hangers and supports for the concentrated loads in piping
between hangers and supports, such as for valves as required. Install ASTM A36
miscellaneous steel shapes as required. Support piping as follows:
Nominal Pipe One and Size (Inches) 1 & under 1.5
Maximum Hanger Spacing (Feet)
10
12
14
17
19
B. Anchors, Bolts, Nuts, Washers, and Screws: Install where required for securing the work.
Sizes, types, and spacing of anchors and bolts not indicated or specified shall be as required.
3.05
VALVES
A. General: Install valves on steam and condensate return piping in conformance with ANSI
B31.1, ASME Boiler and Pressure Vessel Code, Section VIII, and as required herein at the
locations indicated and elsewhere as required for the proper functioning of the system as
directed. Use gate valves unless otherwise directed.
B. Gate Valves: Install valves in positions to provide accessibility for operation and repair.
Provide gate valves 6 inches and larger with an integral 1 inch globe valve bypass.
C. Globe Valves: Install globe valves so that the pressure shall be below the disk. Install globe
valves with the stems horizontal on steam and condensate lines.
3.06
PIPING ACCESSORIES
A. Strainers: Strainers shall be installed so that the filter screen may be easily removed for
inspection. Strainers installed in the vertical position shall have the blowoff outlet correctly
positioned to accomplish cleaning. Provide strainers with meshes suitable for the service
indicated and where dirt might interfere with the proper operation of moving parts of
equipment.
B. Pipe Sleeves: Provide pipe sleeves where pipes and conduits pass through concrete
manhole, building and/or tunnel walls or floors. Sleeves shall be zinc-coated sheet steel
having a weight of not less than 0.907 pound per square foot. Space between pipe, conduit,
or insulation and the sleeve shall be as recommended by mechanical link seal manufacturer.
Hold sleeves securely in proper position and location before and during construction. All
sleeves shall be of sufficient length to pass through entire thickness of walls. Pack space
between the pipe or conduit and the sleeve firmly with non-shrink grout. Provide a
mechanical link seal on inside wall of pipe sleeve.
C. Flanges and Unions:
Place unions and flanges where necessary to permit easy
disconnection of piping and apparatus, and as indicated. Place unions or flanges as
indicated. Use unions on piping smaller than 2 inches in diameter. Joints for connection to
valves in steam and condensate systems shall be faced true, provided with gaskets, and
made perfectly square and tight. Full-faced gaskets shall be used with steel flanges, and all
gaskets shall be thin as the finish of the flange face permits.
D. IMPORTANT: The Contractor shall return to the jobsite within 24 hours of the start-up of all
steam and condensate systems to re-tighten all bolts, nuts and unions.
E. Steam Traps and Connections: Traps shall be of the type and capacity for the service and
shall be properly supported and connected. Install all traps with a dirt pocket and strainer
Section Page 16 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
between it and the piping or apparatus it drains. Provide a three-valve bypass so that the trap
may be removed and repaired and condensate drained through the throttled bypass valve
during maintenance operations. Provide a check valve on the discharge side of the trap
whenever the trap is installed for lift or operating against a back pressure or discharges into
the condensate line. Provide test connections on the discharge side of the traps. The test
connection shall include a 1/2-inch globe valve with uncapped nipple. See typical steam trap
details on the Contract Drawings.
3.07
3.08
Section Page 17 of 21
3.09
Section 33 60 00
Steam & Chilled Water Distribution Systems
SUMP PUMPS
A. Installation:
1. All pumps shall be installed in accordance with the manufacturers recommendations.
The Contractor shall supply all necessary steam, water, anchor bolts, temporary lifting
equipment, labor and all other items needed for satisfactory installation.
B. Inspection and Testing:
1. After each pump has been completely installed, the Contractor shall perform actual
condition field tests to verify that the pump is working correctly to specifications. If
requested, the Contractor shall conduct in the presence of the Engineer, such tests as
are necessary to indicate that pump efficiency and discharge conform to the
Specifications. The Contractor shall supply all utilities and water required to conduct the
field tests.
2. If the pump performance does not meet the specifications, the pump shall be removed
and replaced with pumps which satisfy the conditions specified with no additional cost to
the owner.
3.10
WELDING
A. Welding Responsibility
1. Responsibility of Contractor for Fusion Welding: The Contractor is entirely responsible for
the quality of the welding required for repairing the heat distribution system.
B. Qualifications of Welders
1. Rules of procedure for qualification of all welders and general requirements for fusion
welding shall conform to ANSI B31.1 for the qualification of procedures, welders and
welding operators. The Contractor shall be required to follow the qualification of
procedures by destructive testing as outlined in paragraph QW302 of Section IX of the
ASME Boiler and Pressure Vessel Code. The welders shall be certified under rules of
the National Certified Pipe Welding Bureau and qualified by either the National Certified
Pipe Welding Bureau or an independent testing laboratory. Copies of the welders
certificates shall be made available to the Owner, Architect or Engineer upon request.
2. Documentation of the welding procedure and the welder qualification shall be presented
in the form of a Welding Procedure Specification (WPS), and Procedure for
Qualification. The welder or welding operator must submit a welder certification
verifying welders qualification to the procedure. The Welding Procedure Specification
(WPS) shall meet the requirements of this specification.
3. Beveling: Field bevels and shop bevels shall be done by mechanical means. All
beveling shall conform to the Welding Procedure Specification (WPS).
4. Welding Rings: Welding rings shall not be used on this project.
5. Erection: Piping shall not be split, bent, flattened, or otherwise altered before, during, or
after installation. During erection, care shall be taken to remove all dirt, scale, and
other foreign matter from inside the piping by use of a pipe swab or pipe pig before
tying in sections, valves, or fittings. Where the pipe temperature falls to 32 degrees F
or lower, the pipe shall be heated to approximately 100 degrees F for a distance of 1
foot on each side of the weld before welding, and the weld shall be finished before the
pipe cools to 32 degrees F.
6. Defective Welds: Defective welds shall be replaced and re-inspected at no additional
cost to the Owner. Repairing defective welds by adding weld material over the defect
or by peening will not be permitted. Welding repairs will be performed in accordance
Section Page 18 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
with an approved welding repair procedure. The repair procedure shall be submitted to
the Engineer for approval before performing repairs. When the quality of a welders
work appears to be below the requirements of the acceptance criteria, the inspector
shall require the welder to demonstrate his/her ability to produce sound welds by means
of complete re-qualification.
7. Electrodes: All low hydrogen electrodes shall be stored in a storage oven that is kept
free of moisture and dampness during fabrication operations. Low hydrogen electrodes
shall not remain out of the storage oven for more than four (4) hours at a single time. If
the electrodes are placed back into the storage oven, they shall remain for a minimum
of 24 hours before being used. Electrodes that demonstrate contamination, loss of
coating or any other form of damage shall be discarded.
8. Quality control: The on-site Mechanical Superintendent shall inspect all field welds for
the underground piping immediately after fit up. The inspection shall be for proper pipe
preparation and appropriate gaps. The Superintendent shall initial and date each field
weld using a paint pen on the outer casing.
9. Weld tests Per ANSI B31.1, field welds shall have a visual inspection by an Inspector
that is certified to inspect welds per the code requirements. Twenty-five percent (25%)
of all field welds shall be inspected using this method.
3.11
PROTECTIVE COATING
A. Damaged Materials: Fittings, couplings, irregular surfaces, damaged areas of pipe coating,
and existing piping affected by the Contractors operations shall be clean, dry, grease free,
and primed before application of tape. Waterproof shrink sleeves may be provided in lieu of
tape and shall overlap the pipe coating not less than 6 inches. Pipe coating and adhesive
undercoat surfaces to be wrapped with tape shall be primed with a compatible primer prior to
application of tape. Primer shall be as recommended by tape manufacturer and approved by
pipe coating manufacturer.
B. Pipe Coating: Residual material from pipe coating shall be pressed into the break or trimmed
off. Apply tape spirally with one-third overlap as tape is applied. A double wrap of one full
width of tape shall be applied at right angles to the axis to seal each end of the spiral
wrapping. All damage to the piping shall be repaired according to the manufacturers
recommendations.
C. The Finishing Coating: Stretch and apply first layer of tape to conform to components
surface. Apply and press a second layer of tape over first layer of tape.
D. Flange, Valve, and Irregular Surface Coating: Apply coal tar base coating to a minimum dry
film thickness of 30 mils.
3.12
FLUSHING STANDARDS AND SPECIFICATIONS FOR STEAM and CHILLED WATER CARRIER
PIPING
A. Contractor shall visually inspect internal portion of each length of pipe during installation.
Remove all dirt and foreign matter prior to installing additional lengths.
B. After each major section of piping has been installed, it shall be cleaned and flushed utilizing
a high pressure water hydro-jet process. The hydro-jet process involves passing a high
pressure, high volume spray type cleaning head through the piping. The head is inserted in
each section of piping and activated with full water pressure and flow. The length of the
piping section shall be determined ahead of time so that the proper amount of travel can be
tracked with calibrated marking on the spray head feed hose or a meter on the hose reel.
While traveling through the piping, the pressurized water spray knocks debris loose and
carries it back to the open end of the piping where it is collected and removed from the
system. For each section of piping the process shall be performed a minimum of two times
Revision Date November, 2014
Section Page 19 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
and shall be repeated until the water exiting the end of the pipe is clear and free of debris as
determined by the Owner/Engineer.
C. The hydro-jet equipment utilized shall be capable of providing a minimum of 50 GPM at 2000
PSI.
D. All cleaning and flushing shall be performed such that all debris will be pulled or flushed
downhill.
E. All cleaning and flushing shall be initiated from all low points in the system and shall
terminate at the nearest adjacent high point in the system.
F. Coordinate the limitations and requirements of the hydro-jet process with the flushing subContractor such that the piping is installed in a sequence and manner that allows every
section of the new pipeline to be cleaned and flushed. Limitations may include maximum
length of the pipe section, maximum number and/or degree of bends in the pipe section,
maximum slope of the pipe section , equipment and excavation access requirements, and the
minimum size of the openings required in the piping to allow for insertion and retraction of the
cleaning head.
G. Contractor shall provide access at all low points through valves, tees, flanges, etc. to facilitate
the cleaning and flushing process. If temporary fittings or piping is required it shall be
provided by the Contractor and removed by the Contractor after successful cleaning.
H. After flushing and cleaning is completed, Contractor shall provide necessary pipe and fittings
required to complete the piping system. Each cleaned section of piping shall be capped and
protected to keep mud, debris, water, etc., from entering the piping. If a piping section is left
open or unprotected, or is found to be contaminated, it shall be re-cleaned prior to being filled
and activated at no cost to the Owner.
I.
Contractor shall provide all water for flushing and testing. Coordinate rental of fire hydrant
meters as needed from DeKalb County or the University if water is used from the University
water main system.
J.
Contractor shall provide all temporary piping from water source to piping system and shall
provide means for conducting cleaning water from underground piping system to the
appropriate sanitary sewer; i.e. pumps, piping, house, tanks, etc. Contractor to remove all
temporary piping, pumps, hoses, etc., from site immediately after flushing has been
completed. Flushing water shall be discharged without causing damage, nuisance, or
interruption of traffic.
K. Do not flush system through valves, trap stations, etc. or any device where trapped debris
can remain. Remove these devices from the system prior to flushing.
L. The Contractor shall remove all flushing water from the steam system prior to startup with
steam.
M. The Contractor shall provide a full flushing procedure at least two weeks prior to the
beginning of flushing operations for approval by the Owner/Engineer.
3.13
Section Page 20 of 21
Section 33 60 00
Steam & Chilled Water Distribution Systems
have dials indicating not less than 1-1/2 times or more than 2 times the test pressure. Any
deficiencies shall be corrected at the Contractors expense. Failures to correct any
deficiencies will be cause for rejection of the system.
B. Field Tests: The following field tests shall be conducted on the steam and condensate piping
system involved. If any failure occurs, the Contractor shall make such adjustments or
replacements as the Architect may direct, and the tests shall be repeated until satisfactory
installation and operation are achieved.
1. Conduit Coating Tests: Perform tests as noted in Section 2.01.A.2.
2. Air Test: The outer casing of steam and condensate piping shall be tested as noted in
Section 2.01.A.3.
3. Hydrostatic Tests: Hydrostatically test carrier piping system using water not exceeding
100 degrees F. Conduct tests in accordance with the requirements of ANSI B31.1. Test
pressure shall be 200 psig. Test the piping system after the lines have been cleaned and
before any insulation covering has been applied in areas of field welds and the
underground conduit system. Before making tests, remove or valve off from the system,
gages, traps, and other apparatus that may be damaged by the test pressure. Install
calibrated test pressure gages in the system to observe any loss in pressure. Maintain
the required test pressure for a minimum of two (2) hours. Inspect all joints and
connections for leaks. Perform tests after installation and prior to acceptance. AIR
TESTING OF CARRIER PIPING IS NOT PERMITTED.
4. Operational Tests: After completion of the system, or testable portions thereof,
operational tests shall be conducted in service to demonstrate satisfactory function and
operating effectiveness. The tests on each system, or portion thereof, shall last not less
than six (6) hours. The re-torqueing of all bolts and nuts shall occur within 24 hours of
startup.
3.14
AS-BUILT CONDITIONS
A.
B.
C.
D.
E.
Prior to covering the piping with backfill material, the Contractor shall measure and record
the elevations of the tops of the outer jacket of the piping installed at each elbow or
change of direction. This shall also include each building entrance and manhole
entrance. Elevations may be taken in reference to an adjacent manhole cover that is
shown on the survey drawing.
The Contractor shall measure and record physical dimensions of the piping to a known
and durable surface such as a building wall or corner so that the piping can be located in
the future. These dimensions will be done in several places so as to adequately identify
the piping routing.
The Contractor shall measure and record the tops of any piping or ductbank that
intersects the underground chilled water, steam or condensate piping route.
All elevations shall be taken using a surveyors level and survey rod.
The Contractor shall develop a drawing that shows these as-built conditions above.
END OF SECTION
Section Page 21 of 21