0% found this document useful (0 votes)
111 views

TQ - ABB-LV SWGR

The document contains a technical query list regarding a 400V switchgear package for a gas compression station project. It includes 15 queries around specifications, ratings, dimensions, and other technical details. Key points include confirming ratings for breakers and busbars at an ambient temperature of 40 degrees Celsius, providing CT/VT sizing calculations, complying with applicable local laws and standards, and revising the offer to include 4000A ratings for incomers and bus coupler, 4000A bus rating, drawout feeders over 185kW, REF protection relay details, and 20% spare feeders. Dimensional restrictions and degree of protection are also noted. The vendor is asked to respond to the queries and submit a revised offer.

Uploaded by

malli55
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
111 views

TQ - ABB-LV SWGR

The document contains a technical query list regarding a 400V switchgear package for a gas compression station project. It includes 15 queries around specifications, ratings, dimensions, and other technical details. Key points include confirming ratings for breakers and busbars at an ambient temperature of 40 degrees Celsius, providing CT/VT sizing calculations, complying with applicable local laws and standards, and revising the offer to include 4000A ratings for incomers and bus coupler, 4000A bus rating, drawout feeders over 185kW, REF protection relay details, and 20% spare feeders. Dimensional restrictions and degree of protection are also noted. The vendor is asked to respond to the queries and submit a revised offer.

Uploaded by

malli55
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 4

Project :

318337OM01 (Ajeel Gas Compression Station)

Offer receipt Date :

TECHNICAL QUERY LIST


Package/equipment

400V switchgear

Vendor

Offer Reference

P-13-0196Rev.0

Query Date :

SN

Clause/Page Ref

Query description

Horizon Microtech Pvt Ltd , Replies

Table of compliance Please include the compliance for Appendices.

General

Bidder to confirm that current ratings selected for breaker


and busbars shall be at ambient temperature. Bidder shall
consider ambient temperature 40degC.

General technical
comments

Bidder shall submit CT/VT sizing calculation post order


during engineering to check adequacy of selected CT/VTs.

General

Bidder shall confirm applicable laws and decree as


mentioned in technical specification. Deviation of local laws
is not acceptable.

General

Vendor to provide 110V DC & 230V AC load requirement for


LV switchgear.

General

Please provide heat dissipation details of LV switchgear.

Data Sheet

All outgoing feeder shall be drawout type.In the data sheet


>185kW rated feeder as fixed type.Please revise the offer.

1 0f 4

SN

Clause/Page Ref

Query description

Horizon Microtech Pvt Ltd , Replies

Data Sheet

Vendor to consider LV switchgear Incomer 1, Incomer 2


breaker & Bus coupler rating as 4000A,65kA for 1 sec.Pl.
submit the revised offer for the same.

Data Sheet

Vendor shall consider 400V switchgear bus rating as


4000A.Pl submit the revised offer.

10

Data Sheet

Feeders connected sub distribution board shall be provided


with 4 pole MCCB instead of SFU.Revised offer shall be
submitted for the same.

11

Data Sheet

As per project SLD, LV side REF protection relay & CTs shall
be included.Please indicate details in the data sheet.

12

Data Sheet

As per Electrical equipment layout,LV switchgear dimension


is restricted to Length X Width - 20000 X 1000mm.Please
ensure the same.

13

General

Please indicate all around clerance requirement for


panel(Front/Back/Top/side).

14

Scope of work

20% spare feeders shall be considered for each rating/type


of feeder or atleast one spare feeder shall be provided.Pl
submit the revised offer for the same.

15

Technical description Degree of protection shall be IP42.Please confirm.