Electrical Formulae Used in Calculations
Electrical Formulae Used in Calculations
USED IN CALCULATIONS
OBJECTIVE
LV CABLES
VOLTAGE DROP (RUN/START) IS THE MAIN CRITERIA
(R cosfi + X sinfi) 100 · L · I
DV = ---------------------------------------- (%)
V1
where:
V1 = V / √3 for 3-ph system
V1 = V / 2 for 1-ph system.
V = line to line voltage of the system (V)
R = cable electrical resistance at rated operating
temperature (ohm/km)
X = cable reactance (ohm/km)
Cosfi = power factor of the line current
Sinfi = corresponding sinus
L = line length (km)
I = line current (A)
CABLE SIZING CALCULATION
• MV CABLES
• SHORT CIRCUIT WITHSTAND ALSO NEEDS TO BE
VERIFIED
S2 = I2 · t / k2
Where :
t = fault duration (s)
S = cross-sectional area (mm2)
I = effective short circuit current (A)
k = 115 for copper conductor insulated with PVC
143 for copper conductor insulated with EPR or XLPE
94 for AL conductor insulated with XLPE
CABLE SIZING CALCULATION
Iz = k1 · k2 · k3 · In (A)
where:
k1 = correction factor for ambient temperature
k2 = correction factor for grouped cables, according to typical
arrangement of cables
k3 = additional derating factor, when applicable; otherwise:
k3=1.
CABLE SIZING CALCULATION
where:
P= electrical input power (peak) from user list
n= number of distribution transformers installed –1,
except single feeds where n=1
cosfi = load power factor or improved value, in case
capacitor bank is installed.
1.2 = Spare Capacity
POWER FACTOR CORRECTION
Pcc = An / ucc
Where
Pcc is the Short Circuit Power at the Trafo.
Secondary side in MVA
An is the Rating of the Transformer in MVA.
ucc is the Per unit impedance of the Trafo.
EARTHING CONDUCTOR SIZING
SOURCE
REQUIRED TO
110kV CHECK THE
• VOLTAGE LEVELS
TRANSFORMER
• CURRENT FLOW