Time Domain Reflectometry Theory: Application Note 1304-2
Time Domain Reflectometry Theory: Application Note 1304-2
Reflectometry Theory
Application Note 1304-2
The most common method for evaluating a transmission line and its
load has traditionally involved applying a sine wave to a system and
measuring waves resulting from discontinuities on the line. From
these measurements, the standing wave ratio (σ) is calculated and
used as a figure of merit for the transmission system. When the
system includes several discontinuities, however, the standing wave
ratio (SWR) measurement fails to isolate them. In addition, when
the broadband quality of a transmission system is to be determined,
SWR measurements must be made at many frequencies. This method
soon becomes very time consuming and tedious.
2
This echo technique (see Figure 1) reveals at a glance the
characteristic impedance of the line, and it shows both the
position and the nature (resistive, inductive, or capacitive) of
each discontinuity along the line. TDR also demonstrates whether
losses in a transmission system are series losses or shunt losses.
All of this information is immediately available from the
oscilloscope’s display. TDR also gives more meaningful information
concerning the broadband response of a transmission system than
any other measuring technique.
X
e x(t)
Ei ex Zo ZL
Ei +Er
Ei
Zo ≠ Z L
t
Transmission Line Load
3
Propagation on a The classical transmission line is assumed to consist of a continuous
structure of R’s, L’s and C’s, as shown in Figure 2. By studying this
Transmission Line equivalent circuit, several characteristics of the transmission line
can be determined.
If the line is infinitely long and R, L, G, and C are defined per unit
length, then
√
R + j ωL
Zin = Zo —————
G + jωC
γ = α + jβ =√ (R + jωL) (G + jωC)
ZS L R L R
ES C G C G ZL
The velocity at which the voltage travels down the line can be defined
in terms of β:
ω
Where νρ = — Unit Length per Second
β
4
The propagation constant γ can be used to define the voltage and the
current at any distance x down an infinitely long line by the relations
Since the voltage and the current are related at any point by the
characteristic impedance of the line
Eine–γ x Ein
Zo = ———— = —— = Zin
Iine–γ x Iin
If the load is different from Zo, these equations are not satisfied
unless a second wave is considered to originate at the load and to
propagate back up the line toward the source. This reflected wave is
energy that is not delivered to the load. Therefore, the quality of the
transmission system is indicated by the ratio of this reflected wave
to the incident wave originating at the source. This ratio is called the
voltage reflection coefficient, ρ, and is related to the transmission
line impedance by the equation:
Er ZL – Zo
ρ = —— = ————
Ei ZL + Zo
1 + ⎥ ρ⎥
σ = ————
1 – ⎥ ρ⏐
5
TDR Step Reflection A time domain reflectometer setup is shown in Figure 3.
Testing The step generator produces a positive-going incident wave that is
applied to the transmission system under test. The step travels down
the transmission line at the velocity of propagation of the line. If the
load impedance is equal to the characteristic impedance of the line,
no wave is reflected and all that will be seen on the oscilloscope is
the incident voltage step recorded as the wave passes the point on
the line monitored by the oscilloscope. Refer to Figure 4.
Ei Er
Sampler ZL
Circuit
Step
Generator
Ei
Er
Ei
6
Locating The reflected wave is readily identified since it is separated in time
Mismatches from the incident wave. This time is also valuable in determining
the length of the transmission system from the monitoring point to
the mismatch. Letting D denote this length:
T νρΤ
D = νρ • —— = ———
2 2
Analyzing The shape of the reflected wave is also valuable since it reveals both
Reflections the nature and magnitude of the mismatch. Figure 6 shows four typical
oscilloscope displays and the load impedance responsible for each.
Figures 7a and 7b show actual screen captures from the 86100A.
These displays are easily interpreted by recalling:
Er ZL – Zo
ρ = ——— = ——————
Ei ZL + Zo
7
Z L– Z o
(A) E r = E i Therefore –––––––– = +1
Ei Z L+Zo
Which is true as ZL –– ∞
Ei ZL •
• • Z = Open Circuit
Z L– Z o
ZL (B) E r = E i Therefore –––––––– = –1
Ei –E i Z L+Zo
Which is only true for finite Z
(B) Short Circuit Termination (Z L = 0) When ZL = 0
•
• • Z = Short Circuit
1 Z L– Z o
–– E i 1 1
3 (C) E r = + –– Ei Therefore –––––––– = + ––
3 Z L+Zo 3
ZL 2Z o and Z L = 2Zo
Ei
1
– –– E i Z L– Z o
3 1 1
ZL 1 (D) E r = – –– Ei Therefore –––––––– = – ––
Ei –– Z o 3 Z L+Zo 3
2
1
1 and Z L = –– Z o
(D) Line Terminated in Z L = –– Z o 2
2
R
( i.e., ZL = R + sL , ———— , etc. ) ,
1 + RCs
Ei
multiplying ρ (s) by —— the transform of a step function of Ei,
s
8
and then transforming this product back into the time domain to
find an expression for er(t). This procedure is useful, but a simpler
analysis is possible without resorting to Laplace transforms. The
more direct analysis involves evaluating the reflected voltage at t = 0
and at t = ∞ and assuming any transition between these two values
to be exponential. (For simplicity, time is chosen to be zero when the
reflected wave arrives back at the monitoring point.) In the case of
the series R-L combination, for example, at t = 0 the reflected voltage
is +Ei. This is because the inductor will not accept a sudden change
in current; it initially looks like an infinite impedance, and ρ = +1 at t
= 0. Then current in L builds up exponentially and its impedance
drops toward zero. At t = ∞, therefore er(t) is determined only by the
value of R.
R – Zo
( ρ = ———— When τ = ∞ )
R + Zo
L
γ = ————
R + Zo
Figure 7a. Screen capture of open Figure 7b. Screen capture of short
circuit termination from the 86100 circuit termination from the 86100
9
R–Z R–Z o –t
A E i (1+ ––––o )+(1– –––– )e /τ
R+Z o R+Z o
Series
R–L Ei L R
Where τ = –––––
R+Z o
ZL
L
Ei
t R–Z
0 (1+ ––––o )Ei
R+Zo
B
Shunt
R–C R–Z
(1+ ––––o )Ei ZL R C
Ei –E i R+Zo
R–Z –t
E i (1+ ––––o ) (1–e /τ )
t R+Z o
Zo R
0 Where τ = ––––– C
Z o+R
R–Z –t
C E i (1+ ––––o )e /τ
R–Z R+Z o
Shunt ( ––––o )E i
R+Zo
R–L ZL L R
Ei R+Z o
Where τ = ––––– L
t RZ o
0
D R–Z
( ––––o )E i
Series R+Zo
R–C R
R–Z –t
E i (2–(1 ––––o )e /τ 2E i ZL
R+Z o
C
Ei
t
0
Where τ = (R+Zo) C
10
A similar analysis is possible for the case of the parallel R-C
termination. At time zero, the load appears as a short circuit since
the capacitor will not accept a sudden change in voltage. Therefore,
ρ = –1 when t = 0. After some time, however, voltage builds up on
C and its impedance rises. At t = ∞, the capacitor is effectively an
open circuit:
R – Zo
ZL = R and = ————
R + Zo
Zo R
———— C
Zo + R
The two remaining cases can be treated in exactly the same way.
The results of this analysis are summarized in Figure 8.
Discontinuities So far, mention has been made only about the effect of a mismatched
on the Line load at the end of a transmission line. Often, however, one is not
only concerned with what is happening at the load, but also at
intermediate positions along the line. Consider the transmission
system in Figure 9.
Zo Zo ZL
Assume ZL = Zo
11
M
L
Zo Zo
L
Ei τ = –––
2Z o
Ei
Assuming that the lossy line is infinitely long, the input impedance is
given by:
Zin = Zo = √ R + jωL
—————
G + jωC
Zin = √ R + jωL
————— =
jωC
√ L R
—— ( 1 + —— )
C jωL
1/
2
Zin ≈ √ L R
—— ( 1 + ——— ) When R < ωL
C j2ωL
Since the leading edge of the incident step is made up almost entirely
of high frequency components, R is certainly less than ωL for t = 0+.
Therefore the above approximation for the lossy line, which looks
like a simple series R-C network, is valid for a short time after t = 0.
It turns out that this model is all that is necessary to determine the
transmission line’s loss.
12
In terms of an equivalent circuit valid at t = 0+, the transmission line
with series losses is shown in Figure 12.
Zs
R'
E Z in e in
C'
1
Z in= R' + ––––
jωC'
Figure 12. A simple model valid at t = 0+ for a line with series losses
The series resistance of the lossy line (R) is a function of the skin
depth of the conductor and therefore is not constant with frequency.
As a result, it is difficult to relate the initial slope with an actual
value of R. However, the magnitude of the slope is useful in
comparing conductors of different loss.
1
Yin = —— =
Zin
√ G + jωC
————— =
R + jωL
√ G + jωC
—————
jωL
Yin =√ C
L
G
— ( 1 + ——— )
jωC
1/
2
Yin ≈√ C
L
G
— ( 1 + ——— ) When G <ωC
j2ωC
13
Going to an equivalent circuit (Figure 13) valid at t = 0+,
Zs
E Y in e in G' L'
1
Y in= G' + ––––
jωL'
Figure 13. A simple model valid at t = 0+ for a line with shunt losses
Multiple One of the advantages of TDR is its ability to handle cases involving
Discontinuities more than one discontinuity. An example of this is Figure 14.
ρ
1 ρ
2
Zo Z' o ZL
Z L – Z'o
ρ = –––––––
2 Z L + Z'o
Er
E r1 2
Ei
Z o>Z'o <ZL
Figure 15. Accuracy decreases as you look further down a line with multiple
discontinuities
14
It is seen that the two mismatches produce reflections that can be
analyzed separately. The mismatch at the junction of the two
transmission lines generates a reflected wave, Er , where
Z′o – Zo
Er = ρ1 Ei = ( ———— ) Ei
Z′o + Zo
ZL – Z′o
ρ2 = ————
ZL + Z′o
Two things must be considered before the apparent reflection from
ZL, as shown on the oscilloscope, is used to determine ρ2. First,
the voltage step incident on ZL is (1 + ρ1) Ei, not merely Ei. Second,
the reflection from the load is
[ ρ2 (1 + ρ1) Ei ] = ErL
is again reflected off the load and heads back to the monitoring
point only to be partially reflected at the junction of Zo′ and Zo.
This continues indefinitely, but after some time the magnitude of
the reflections approaches zero.
15
Agilent Email Updates
www.agilent.com
www.agilent.com/find/dcaj
www.agilent.com/find/emailupdates
Get the latest information on the products and Agilent Technologies’ Test and Measurement
Support, Services, and Assistance
applications you select.
Agilent Technologies aims to maximize the value you
receive, while minimizing your risk and problems. We
strive to ensure that you get the test and measurement
capabilities you paid for and obtain the support you
Agilent Direct need. Our extensive support resources and services
www.agilent.com/find/agilentdirect can help you choose the right Agilent products for
your applications and apply them successfully. Every
Quickly choose and use your test equipment
instrument and system we sell has a global warranty.
solutions with confidence. Two concepts underlie Agilent’s overall support policy:
“Our Promise” and “Your Advantage.”
Agilent
Our Promise
Open Our Promise means your Agilent test and measurement
www.agilent.com/find/open equipment will meet its advertised performance
Agilent Open simplifies the process of connecting and functionality. When you are choosing new
and programming test systems to help engineers equipment, we will help you with product information,
design, validate and manufacture electronic including realistic performance specifications and
products. Agilent offers open connectivity for a practical recommendations from experienced test
broad range of system-ready instruments, open engineers. When you receive your new Agilent
industry software, PC-standard I/O and global equipment, we can help verify that it works properly
support, which are combined to more easily and help with initial product operation.
integrate test system development.
Your Advantage
Your Advantage means that Agilent offers a wide range
of additional expert test and measurement services,
which you can purchase according to your unique
technical and business needs. Solve problems
efficiently and gain a competitive edge by contracting
with us for calibration, extra-cost upgrades, out-of-
warranty repairs, and onsite education and training,
as well as design, system integration, project
management, and other professional engineering
services. Experienced Agilent engineers and
technicians worldwide can help you maximize your
productivity, optimize the return on investment of your
Agilent instruments and systems, and obtain dependable
measurement accuracy for the life of those products.
Phone or Fax