0% found this document useful (0 votes)
108 views

Pressure Loss & Performance Fan Calculation: Input Data Edit Comp & Fitg View Graph View Chart & DRWG

The document provides calculations for pressure loss and performance of a fan system. It includes input data on duct geometries and flow rates. Pressure loss is calculated for each component using friction loss and minor loss coefficients. Total pressure loss of 217.1 Pa is calculated over the 46.1 m length. A graph shows the variation in static, velocity and total pressure over the length.

Uploaded by

Herawan Heri
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
108 views

Pressure Loss & Performance Fan Calculation: Input Data Edit Comp & Fitg View Graph View Chart & DRWG

The document provides calculations for pressure loss and performance of a fan system. It includes input data on duct geometries and flow rates. Pressure loss is calculated for each component using friction loss and minor loss coefficients. Total pressure loss of 217.1 Pa is calculated over the 46.1 m length. A graph shows the variation in static, velocity and total pressure over the length.

Uploaded by

Herawan Heri
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 11

PRESSURE LOSS & PERFORMANCE

FAN CALCULATION

EDIT VIEW CHART


INPUT DATA VIEW GRAPH
COMP & FITG & DRWG
NCE
Pressure Loss Calculation
BACK
Total supply flow rate (m3/s): 4 m3/s

System Details
Description
Spec and Duct Geometrical Data
No
Shape EQ Rectangular Flowrate
Segmen Name Code
(circ or rect) Dia. (mm) height (m) width (m) m3/s
1 A-E-F Grille G cir 500 1
2 Damper < 1m VD1 cir 500 1
3 Straight Duct SD cir 500 1
4 SQ Elbow 90o , sharp ES1 cir 500 1
5 Straight Duct SD cir 500 1
6 F-G T, flow to Thru Te2 cir 600 2
7 Straight Duct SD cir 600 2
8 G-H T, flow to Thru Te2 cir 700 3
9 Straight Duct SD cir 700 3
10 H-I-J T, flow to Thru Te2 cir 850 4
11 Straight Duct SD cir 850 4
12 SQ Elbow 90o , sharp ES1 cir 850 4
13 Straight Duct SD cir 850 4
14 J-K Fan FAN cir 850 4
15 FanSysLoss > 5D Floss1 cir 850 4
16 Straight Duct SD cir 850 4
17 Louver L cir 850 4

Note: insert rows to add extra system data


Fill Cell with This colour only

Data Data Element Loss & Calculated


Length Fric Loss MinorLoss Componen Velocity c/s/ area Pressure Loss Head Loss Length
(m) Pa/m C Loss (Pa) (m/s) (m2) Total (Pa) (m) (m)
0 0.00 0.00 30.00 5.09 0.20 30.00 2.55 0
0 0.00 0.00 15.00 5.09 0.20 15.00 1.27 0
5 0.76 0.00 0.00 5.09 0.20 3.80 0.32 5
0 0.00 1.30 0.00 5.09 0.20 20.23 1.72 5
5 0.76 0.00 0.00 5.09 0.20 3.80 0.32 10
0 0.00 0.50 0.00 7.07 0.28 15.01 1.28 10
5 0.76 0.00 0.00 7.07 0.28 3.80 0.32 15
0 0.00 0.50 0.00 7.80 0.38 18.23 1.55 15
5 0.76 0.00 0.00 7.80 0.38 3.80 0.32 20
0 0.00 0.50 0.00 7.05 0.57 14.91 1.27 20
5 0.76 0.00 0.00 7.05 0.57 3.80 0.32 25
0 0.00 1.30 0.00 7.05 0.57 38.76 3.29 25
15 0.76 0.00 0.00 7.05 0.57 11.40 0.97 40
0 0.00 0.00 0.00 7.05 0.57 0.00 0.00 40
0 0.00 0.00 0.00 7.05 0.57 0.00 0.00 40
6 0.76 0.00 0.00 7.05 0.57 4.56 0.39 46
0.1 0.00 0.00 30.00 7.05 0.57 30.00 2.55 46.1

total: 217.10 18.44


System Pressures
Pt (Fan) Static Pres Velocity Pres Total Pres
dP (Pa) (Pa) (Pa) (Pa)
0.00 -30.00 15.56 -14.44
0.00 -45.00 15.56 -29.44
0.00 -48.80 15.56 -33.24
0.00 -69.03 15.56 -53.47
0.00 -72.83 15.56 -57.27
0.00 -87.84 30.02 -57.82
0.00 -91.64 30.02 -61.62
0.00 -109.87 36.46 -73.41
0.00 -113.67 36.46 -77.21
0.00 -128.58 29.81 -98.77
0.00 -132.38 29.81 -102.57
0.00 -171.14 29.81 -141.32
0.00 -182.54 29.81 -152.72
217.10 34.56 29.81 64.37
0.00 34.56 29.81 64.37
0.00 30.00 29.81 59.81
0.00 0.00 29.81 29.81
System Pressure Variation
Static Pres (Pa)
Pressure (Pa)

Velocity Pres (Pa)

Total Pres (Pa)

90.00

60.00

30.00

0.00
0 5 10 15 20 25 30 35 40 45 50
-30.00

-60.00

-90.00

-120.00

-150.00

-180.00

-210.00
Length (m)
BACK

SAMPLE DRAWING (A

Table Velocity Range Criteria

Type of Duct Comfort Systems


Industrial Systems
High Speed Systems
Main ducts 4 - 7 m/s 8 - 12 m/s 10 - 18 m/s

Main branch
ducts 3 - 5 m/s 5 - 8 m/s 6 - 12 m/s

Branch ducts 1 - 3 m/s 3 - 5 m/s 5 - 8 m/s


SAMPLE DRAWING (ATTACHED HERE)
BACK

Minor Loss Friction


Fiiting-Component Code Coefficient Pa Pa/m
Straight Duct SD 0 0 0.76
SQ Elbow 90 , sharp
o
ES1 1.3 0 0
SQ Elbow 90o , with vanes ES2 0.7 0 0
SQ Elbow 45o bend, sharp ES3 0.5 0 0

Cir Elbow 90oradiusR/D <1 EC1 0.5 0 0


Cir Elbow 90oradiusR/D >1 EC2 0.25 0 0
Cir Elbow 45oradiusR/D <1 EC3 0.2 0 0
Cir Elbow 45oradiusR/D >1 EC4 0.05 0 0
T, flow to branch Te1 0.7 0 0
T, flow to Thru Te2 0.5 0 0

Reducer w/ angle < 8o Red1 0.5 0 0


Reducer w/ angle > 8o Red2 0.3 0 0
Fan FAN 0 0 0
FanSysLoss > 5D Floss1 0 0 0
FanSys Loss Sharp Floss1 50 0
FanSys Loss Very Sharp Floss1 100 0
Grille G 0 30 0
Louver L 0 30 0
Diffuser D 0 25 0
Damper < 1m VD1 0 15 0
Damper >1 m VD2 0 25 0
Chamber-Plenum CBR 0 85 0
Filter Medium F1 0 100 0
Fiter High F2 0 150 0
Coil Cooler CH 0 70 0
Heater H 0 50 0
BACK

System Pressure Variation

Pressure (Pa)
90.00

60.00

30.00

0.00
0 5 10 15 20 25 30
-30.00

-60.00

-90.00

-120.00

-150.00

-180.00

-210.00
Length (m)
Static Pres
(Pa)
Velocity Pres
ariation (Pa)
Total Pres
(Pa)

25 30 35 40 45 50

Length (m)