Instrument Index
Instrument Index
Sr.No Tag No Old Tag No Service Instrument Type Set Point Unit Signal Type IO Type IP Rating Ex Catergory Mounting
Required.
1 567-PDT-001 567-PDT-001 Differential Air Pressure ( Main Filter ) Transmitter 300 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing
2 567-PDT-002 567-PDT-002 Differential Air Pressure ( Pre Filter ) Transmitter 150 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing
3 567-PDT-003 567-PDT-003 Differential Air Pressure ( FA Filter ) Transmitter 100 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing
4 567-PDT-004 567-PDT-004 Differential Air Pressure ( Blower ) Transmitter 450 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing
5 567-PDT-005 567-PDT-005 Differential Air Pressure ( Blower ) Transmitter 450 Pa 4-20 mA AI IP 67 Zone 2 AHU Casing
6 567-PT-001 567-PT-001 Differential Air Pressure ( Exhaust Fan ) Transmitter 100 Pa 4-20 mA AI IP 67 Zone 2 Duct Mounted
7 567-PDT-431 567-PDT-431 Differential Air Pressure ( Room ) Transmitter 35 Pa 4-20 mA AI IP 67 Safe Wall
8 567-PDT-432 567-PDT-432 Differential Air Pressure ( Room ) Transmitter 35 Pa 4-20 mA AI IP 67 Safe Wall
9 567-PDT-433 567-PDT-433 Differential Air Pressure (Battery Room) Transmitter 20 Pa 4-20 mA AI IP 67 Zone 1 Wall
o
10 567-MTT-101 Humidity / Temperature ( Return Air ) Transmitter 24 / 50 C/% 4-20 mA AI IP 65 Safe Duct Mounted
o
11 567-MTT-201 Humidity / Temperature ( Return Air ) Transmitter 24 / 50 C/% 4-20 mA AI IP 65 Safe Duct Mounted
12 567-PT-001A 567-PT-001A Refrigerant Suction Pressure Transmitter 1 bar (g) 4-20 mA AI IP 67 Zone 2 Refrigeration Line
13 567-PSL-001A Refrigerant Suction Pressure Switch 0.6 bar (g) - - IP 65 Zone 2 Refrigeration Line
14 567-PT-002A 567-PT-002A Refrigerant Discharge Pressure Transmitter 10 ~ 12 bar (g) 4-20 mA AI IP 66 Zone 2 Refrigeration Line
15 567-PT-001B 567-PT-001B Refrigerant Suction Pressure Transmitter 1 bar (g) 4-20 mA AI IP 67 Zone 2 Refrigeration Line
16 567-PSL-001B Refrigerant Suction Pressure Switch 0.6 bar (g) - - IP 65 Zone 2 Refrigeration Line
17 567-PT-002B 567-PT-002B Refrigerant Discharge Pressure Transmitter 10 ~ 12 bar (g) 4-20 mA AI IP 66 Zone 2 Refrigeration Line
18 567-XY-021A Shut Off Damper - Unit A Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper
19 567-ZSO-021A Shut Off Damper - Unit A Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper
20 567-ZSC-021A Shut Off Damper - Unit A Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper
21 567-XY-021B Shut Off Damper - Unit B Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper
22 567-ZSO-021B Shut Off Damper - Unit B Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper
23 567-ZSC-021B Shut Off Damper - Unit B Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper
24 557-RY-022 Shut Off Damper - FA Solenoid Valve - - - - IP 67 Eex'd' Shut Off Damper
25 557-ZSO-022 Shut Off Damper - FA Limit Switch Open - - - IP 67 Ex'd' Shut Off Damper
26 557-ZSC-022 Shut Off Damper - FA Limit Switch Close - - - IP 67 Ex'd' Shut Off Damper
Sr.No Tag No Old Tag No Service Instrument Type Set Point Unit Signal Type IO Type IP Rating Ex Catergory Mounting
Required.
42 557-RY-202 F & G Damper - 557-RV-202 Solenoid Valve - - - - IP 67 Eex'd' F & G Damper
43 557-ZSO-202 F & G Damper - 557-RV-202 Limit Switch Open - - - IP 67 Ex'd' F & G Damper
44 557-ZSC-202 F & G Damper - 557-RV-202 Limit Switch Close - - - IP 67 Ex'd' F & G Damper
System - A
60 567-SOV-001A Refrigerant Liquid Line Solenoid Valve - - - - IP 67 Eex nA Refrigeration Line
System - B
69 567-SOV-001B Refrigerant Liquid Line Solenoid Valve - - - - IP 67 Eex nA Refrigeration Line
75 N.A Instrument Air Pressure Reducer c/w gauge Pressure Regulating 8 bar (g) - - - - Instrument Air Line
Note :
1. The item indicated is part of compressor. It is supplied by Bitzer manufacturer and certified the compressor as explosion proof..
2. Ex-proof junction box will be provided as necessary to suite project requirement ( For refrigerant pressure transmitters, etc,. )
3. These items will be supplied as loose and shall be installed by other.( Maximim Inlet Pressure : 17 bar & Regulating Pressure 0.5 ~ 8 bar )