Abb Tzidc Calib Procedure

The document provides steps to auto calibrate an ABB TZIDC positioner: 1) Press specific keys to navigate menus until "1.2" is displayed, indicating auto calibration mode is enabled. 2) Press additional keys to start the auto calibration, which will countdown and display messages over 5 minutes as it completes the calibration process. 3) Once complete, the display will show the current valve position feedback in percentage and the valve will be ready for operation commands from the DCS control system.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
2K views

Abb Tzidc Calib Procedure

The document provides steps to auto calibrate an ABB TZIDC positioner: 1) Press specific keys to navigate menus until "1.2" is displayed, indicating auto calibration mode is enabled. 2) Press additional keys to start the auto calibration, which will countdown and display messages over 5 minutes as it completes the calibration process. 3) Once complete, the display will show the current valve position feedback in percentage and the valve will be ready for operation commands from the DCS control system.
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 3

ABB TZIDC POSITIONER AUTO CALIBRATION PROCEDURE

press MODE key

hold mode key & press key simultaneously untill

display shows “1.2” comes in display

display shows “1.2” MANUAL

release mode & key

Hold the & simultaneously

press ENTER key once

Release ENTER key

Display shows the countdown from ”3 to 0”

Release & simultaneously

Display shows parameter “P 1.0” (LINEAR)


Press MODE & KEY simultaneously

Display shows “P 1.1” AUTO ADJUSTING START

Release MODE & KEY

Display shows “P1.1” AUTO ADJUST

Press ENTER key & Hold it

Display shows countdown from “3 TO O”

Release ENTER key

Display shows “10-RUN MODE”

Simultaneously AUTO CALIBRATION started

Calibration completed(with in 5 minutes)

Display shows v 122, “STROKE COMPLETED”

Hold MODE key & Press untill display shows “P 1.5”

Display shows “P 1.5” , “EXIT”


Release MODE key

Display shows “P 1.5 NV” (non-volatile memory save)

Hold ENTER key

Display shows countdown from “3 to 0”

Release ENTER key

Display shows “CHECK & VERIFY”

“AUTO SAVE” occurs but not shown in display

Display shows the current position of the value in %

Hold MODE key and press key

untill display shows “P 1.1””CONTROL FIX”

Release MODE & key

Display shows calibration completed & shows the current position feedback of the valve

valve is now ready for operation command from DCS