Flash Mixer and Flocculation
Flash Mixer and Flocculation
This page is concerned with the design of flash mix and flocculation chambers. Both devices
operate in much the same way - the water flows through the tank and is mixed in the process.
The primary differences between a flash mix chamber and a flocculation chamber include the
detention time and the velocity gradient.
The detention time is the time required for a small amount of water to pass through a tank at a
given flow rate. Mathematically, detention time is given by the following formula:
Where:
In the case of the flash mix chamber we will consider, the optimal detention time is 30 seconds.
The detention time of a flocculator is much greater, around 30 minutes.
The second factor, the velocity gradient, is a measurement of the intensity of mixing in the
chamber. The velocity gradient determines how much the water is agitated in the tank, and also
determines how much energy is used to operate the flash mixer or flocculator.
Although the detention time and velocity gradient are the most important factors influencing the
performance of a flash mixer and flocculator, the physical features of each chamber can differ
greatly. The shape of both types of mixers can vary from cylindrical to rectangular or cubical.
The water can be mixed simply by water flowing around baffles, or it can be mixed with a
variety of types of paddles, turbines, and propellers.
This page is primarily concerned with determining the volume and dimensions of the tanks. The
volume depends on the amount of water being treated, and is generally much greater for a
flocculator than for a flash mix chamber. The dimensions, in turn, depend on the volume of the
tank.
Power Consumption
In addition to calculating the volume and dimensions of various flash mixers and flocculators,
we will be determining the amount of power which the devices require to operate. You can use
the power requirements to optimize the efficiency of the flocculators and flash mixers, or merely
to predict how much operation of the devices will cost.
Specifications
Each set of calculations can only be used on a certain type of device. This set of calculations is
appropriate for a mechanical rapid mixer, a type of flash mix chamber. A diagram of the flash
mixer is shown below.
Specifications:
Cylindrical tank.
Diameter: 3-10 ft.
Depth: Less than 10 ft.
Four vertical baffles.
Mixing by vertical-shaft, turbine-type impeller.
Flow from bottom to top.
Detention time: 30 sec.
Velocity gradient: 500-1000 sec.-1
A few of these specifications require explanation. The first few specifications merely limit the
physical shape and size of the mixer. The rest are briefly explained below.
The baffles are flat boards or plates, deflectors, guides, or similar devices placed in flowing
water to cause more uniform flow, to absorb energy, and to divert, guide, or agitate liquids. You
can see the baffles as four yellow rectangular shapes around the sides of the flash mixer.
The impeller is shown in white at the center of the chamber. A motor makes the impeller spin,
which in turn agitates the water. The arrows show the mixing action of the water.
The inlet and outlet devices are not shown in the diagram, but flow should enter from the bottom
of the chamber and leave through the top of the chamber.
Summary of Calculations
We will use the following steps to determine the flash mixer's dimensions:
Tank Volume
V=Qt
Where:
V = volume, ft3
Q = flow, cfs
t = detention time, sec
You should recognize this formula as a version of the formula we introduced for detention time
in a previous section.
The flow for our plant is 2 cfs and the detention time for the mechanical rapid mixer has been
specified to be 30 seconds. So the volume of the tank can be calculated as follows:
V = 60 ft3
Tank Dimensions
In order to determine the dimensions of the tank, we first assume a depth, then we calculate a
diameter. The depth can be anything within the specified range of 10 feet or less. Here, we will
assume a depth of 5 feet.
Where:
D = diameter, ft
V = volume, ft3
d = depth, ft
Since we know that the volume of our tank is 60 ft3 from the last section and since we've
assumed a depth of 5 feet, the diameter of the tank is calculated as follows:
Power Requirements
The power requirement is the amount of energy which is needed to operate the device. By
calculating the power requirements of the flash mixer, we can determine how much it will cost to
run the device. Calculating the power requirements is done in three steps, as shown below:
1. Calculate water horsepower. First, we calculate the amount of water horsepower used to
operate the flash mixer. To do so, we use the following formula:
P = VG2 / 550
Where:
In this page, we will assume that the water temperature is 60°F, with the corresponding
viscosity of 0.0000233 lb-sec/ft.2 You may choose to use other water temperatures in your
calculations, especially if your source water temperature varies greatly between summer
and winter.
Using a velocity gradient of 750 sec-1, we can calculate the water horsepower used to run
our flash mixer as follows:
2. Calculate electrical horsepower. Since motors are not 100% efficient, the amount of
electricity used to power the flash mixer is greater than the water horsepower used to mix the
water. We assume a "wire to water" efficiency of 80% and use the following formula to
calculate the electrical horsepower:
Where:
So, in the case of our example, the electric horsepower would be:
E = 1.79 eHp
3. Estimate power costs. The final step is to estimate the daily cost of the electricity used to run
the mechanical rapid mixer. We will assume that the unit runs 24 hours per day and that the
electricity cost is $0.05 per kilowatt-hour. The following formula can be used to calculate the
power cost for the mixer.
Where:
In our example, the cost of running the unit for a day would be:
Cost = $1.60
Conclusions
Our calculations show that our plant can be served by a mechanical rapid mixer with a volume of
60 cubic feet. With a depth of 5 feet, the mixer's diameter should be 3.9 feet.
It will take a water horsepower of 1.43 to run the device, which translates to an electric
horsepower of 1.79. The flash mixer will cost about $1.60 per day to run.
Flocculation - Page 2
Specifications
Flocculators work much like flash mix chambers, though the water is agitated at a slower rate (a
lower velocity gradient) and the detention time is greater. Here, we will calculate the tank
volume, tank dimensions, and power requirements for a horizontal-shaft paddle flocculator like
the one shown below.
Specifications:
Rectangular tank
Depth: 7-16 ft
Width: 10-50 ft.
Length: 2 x width
Minimum number of stages: 2
Minimum number of channels: 2
Mixing by horizontal shaft paddles
Variable speed motors for tapering mixing
Shaft rotational speed: 60-100 rev/hr
Paddle area: <10-20% of tank cross section
Peripheral paddle speed: 0.5-2 ft/sec
Detention time: 30-60 min
Flow through velocity: 0.5-1.5 ft/min
Velocity gradient: 30-60 sec-1
Mixing opportunity parameter: 104-105
Summary of Calculations
Tank Volume
The tank volume is calculated just as it was for the flash mix chamber. However, the
flocculation basin is typically divided into two or more channels, as shown below.
Since the water must be divided between the various channels in the flocculator, the flow is
similarly divided. To find the flow in one channel, we use the following formula:
Qc = Q/n
Where:
In our example calculations, we will use the same treatment plant which we used for the flash
mix chamber calculations. The flow of this plant, as you will remember, is 2 cfs.
Qc = 2 cfs/2
Qc = 1 cfs
V = 1,800 ft.3
When calculating the volume, we used the same formula used for the flash mix chamber, but
added in a conversion since detention time was given in minutes rather than seconds.
Tank Dimensions
The tank dimensions of the flocculator channel are calculated in the same manner that was used
for the flash mix chamber. However, since the flocculator is a rectangle rather than a cylinder,
the formulas used are different.
First we choose a depth within the specified range. We will use a depth of 10 feet here.
The flocculator specifications note that the length should be equal to twice the width. So we can
find the width using the following formula:
Where:
W = width, ft
V = volume, ft3
d = depth, ft
L=2W
Where:
L = length, ft
W = width, ft
L = 2 (9.5 ft)
L = 19 ft
Check Velocity
The velocity of water flowing through the flocculation basin must be within a very specific
range, designed to gently mix the water without breaking apart the floc. In the case of our basin,
the specifications list the flow through velocity as between 0.5 and 1.5 ft/min.
To check whether the flow through velocity of the basin we've designed is within these limits,
we used the following formula:
v = 60 Qc/Ax
Where:
In our example, first we calculate the cross-sectional area of one of our channels:
Ax = 95 ft2
v = 60 (1 cfs)/(95 ft2)
v = 0.63 ft/min
This velocity is within the acceptable range, so we can use the tank dimensions calculated above
to design our flocculation basin. If the velocity had been too high, we would have assumed a
greater number of channels and then chosen new dimensions. If the velocity was too low, we
would have repeated the calculations using a smaller depth or only one channel.
Power Requirements
The power requirements are calculated just as they were for the flash mix chamber, except that
you must be sure to calculate the power requirements for the entire flocculator rather than for just
one channel. We will assume a water temperature of 60°F and a velocity gradient of 45 sec.-1
Our calculations are shown below:
Cost = $0.34
Notice that the cost to run the flocculator is much less than the cost to run the flash mix
chamber. This smaller cost is due to the much less vigorous mixing occurring in the flocculator.
Conclusions
Our plant requires a two channel, horizontal-shaft paddle flocculator with a total volume of 3,600
ft.3 Each channel will have a volume of 1,800 ft3, a depth of 10 ft, a width of 9.5 ft, and a length
of 19 ft.
The flow through velocity in each channel will be 0.63 ft/sec. The power cost for the entire
flocculator will be $0.34 per day.