Abb CCM
Abb CCM
ABB LV Systems
MNS
For detailed information Air circuit-breaker Sace Megamax F (ACB) .......................... 1TSCB TC/CO/AA/10
regarding apparatus and FRCTL 0058 95 GB
Moulded-case circuit-breaker Sace Isomax (MCCB) .............. 1TSCB 6490797003
Moulded-case circuit-breaker Sace Limitor (MCCB) ........................ Cat 2-9 6-1992
Miniature circuit-breaker (MCB) ............................................ G STO 3113 94 50002
ABB Fuseline ..................................................................................... OF1-EN 95-94
Switch-disconnector, earthing switch ABB Control Oy, OETL ................ 1 EN 95-01
Fuse-switch ABB Control Oy, OESA ................................................... 1 A SE 94-11
MNS
2 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS General
MNS systems are suitable for applications in all fields concerning the generation,
distribution and use of electrical energy, e. g., they can be used as:
Main and sub-distribution boards for energy and
Motor current supply of Motor Control Centres
• in utility companies
• in power plants
• in oil refineries
• on off-shore drilling platforms
• on ships
• in production facilities
• in sewage management
• in buildings for other than dwelling purposes.
System features
The Modular Low-Voltage Switchgear System has proven its worth for many years
worldwide. At the same time, it constitutes a safe investment for the future due to its
continuous further development. The high flexibility of the MNS system results from
a framework construction with maintenance-free bolted connections which can be
equipped as required with standardized components and can be perfectly adapted
to each application. The consistent application of the modular principle both in
electrical and mechanical design permits optional selection of the structural design,
interior arrangement and degree of protection according to the operating and
environmental conditions.
The design and material used for the MNS system largely prevent the occurrence of
electric arcs, or provide for arc quenching within a short time. The MNS-System
complies with the requirements laid down in IEC 1641, and was furthermore
subjected to extensive accidental arc tests by an independent institute. Type test
certificates are available.
The MNS system offers the user many alternative solutions and notable advantages
in comparison with conventional-type installations:
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 3
MNS System overview – Product structure
System overview
The basic design:
– Standard IEC 439-1
– For applications with more demanding
requirements
– Re-building whilst in operation
– Personal safety
– Operational reliability
– Easy to install
– Maintenance and service friendly
– Planning aid in form of PC program
Product structure
MODULAR SYSTEM (cubicles) FUNCTION UNITS (apparatus)
MNS
MNS
4 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Product description
Modular system (cubicles)
Standards
MNS is designed to comply to the requirements of the
international standard IEC 439-1 and any other referenced
IEC publication.
IEC 439-1 contains a number of sections which state that
the design is to be ”as agreed between the user and the
manufacturer”. If no other agreement is made the
ABB Installation standard is delivered.
Operating conditions
MNS switchgear is suitable for installation in closed locations
for electrical equipment and other operating facilities in
compliance with the switchgear degree of protection.
IP31-cubicles have ventilation grill in the rear panel and in roof
panels. IP31 is only used for the cubicle while all individual
distribution units are at least IP41.
IP41-cubicles are protected from contact by means of a fine
mesh grill fitted to the ventilation openings.
IP54-cubicle is without any ventilation openings and with all
doors and top plates sealed.
Corrosion resistance
The corrosion protection is obtained by using corrosion
resistant materials.
All visible panels such as doors, end panels, rear panels, etc.,
are painted only to enhance the appearance of the switchgear.
All painted panels are protected by a 20 µm thick layer of zinc.
Cubicle design.
Non-painted panels and basic elements are manufactured
from 1.5 mm Aluzink® which is a corrosion resistant sheet
steel, plated with a 25 µm thick coating.
Anchor rails and hinges are made from zinc plated steel
(12 µm) which is then either bright or yellow chromium plated.
Mechanical design
The cubicles are made up of mechanical parts joined together by screws.
The switchgear W-cubicle has a modular hole system for the installation of
withdrawable units and cover plates. Module division: 50 mm = 1 M module.
Only the sides at the left and right ends of a row of cubicles, or the side panels on
each side of a single cubicle, need to be fitted with end panels.
The MNS-cubicles are delivered complete with engraved legend plate for cubicle
identification at the cubicle top, designation plates on the withdrawable units, and
identification plate on the cubicle bottom in accordance with IEC 439-1.
Measuring instruments
ABB CEWE Instruments are used as measuring instruments. Sizes are 96 x 96,
72 x 72 or 48 x 48 mm depending on the height of the distribution unit.
The voltmeters are of the type IQ with selector switch for measuring between
phases and between phases and neutral. A 3-pole MCB is included. The voltmeter
is delivered for ranges 0–250 V, 0–500 V and 0–600 V. V A A A
The A-meters are fed by current transformers and are available in two versions:
• with only instantaneous display (IQ)
IQ IQB
• with combined instantaneous display and bi-metal system (15 minutes thermal Instrument types.
lag) with slave pointer for maximum display (IQB).
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 5
MNS Product description
Modular system (cubicles)
Busbar system
The busbar system is installed in the cubicle before delivery and includes horizontal
main busbar system including neutral and protective busbars; vertical busbars.
The horizontal busbars are situated, either at the top or at the bottom, in a
segregated area at the rear of the cubicle to prevent accidental contact.The busbars
in adjacent cubicles are interconnected at site after the cubicles have been fixed to
the foundation. This arrangement facilitates easy extension of an already existing
switchgear.
The vertical busbars are protected to degree of protection IP20. The apparatus
units are connected to the busbars with plug-in contacts. The vertical busbar system
are available with 3 or 4 poles and in two versions:
● metal enclosed
● insulated enclosed
Protective earth and neutral busbars can be arranged according to following
Insulated enclosed vertical busbar system.
alternatives:
● 3 pole + PEN
● 3 pole + N + PE
● 4 pole + PE.
Barriers
The switchgear cubicles is fitted with barriers:
● in front of horizontal busbar system
● between units
● between units and cable compartment
● in front of vertical busbars
● between apparatus and busbars.
The material in the barriers will not produce poisonous gases if affected by arcing.
MNS
6 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Product description
Function units (apparatus)
Withdrawable units
The W/R-cubicle can accomodate two different types of
withdrawable units; Normal units with full cubicle width and
Compact units with 1/4 cubicle width. The compact units are
available as DOL-starters in current sizes up to 15 kW at
400 V.
The main circuit power lines are connected to the cable
connection device of the withdrawable units. The auxiliary
circuit line is connected to a slide connector with screw
terminals. Connections
for main and auxiliary
circuits.
Compact units
The units have a 16-pole auxiliary circuit connector, a front
panel and side panels made of isulating material. The ope-
rating handle is also used for the electrical as well as the
mechanical interlocking function.
The handle can be set in five positions:
On-position Compact units.
All circuits connected. Unit locked in service position.
Off-position
Main circuit disconnected, auxiliary circuit discon-
nected. Unit locked in service position.
Test position
Main circuit disconnected, auxiliary circuit connected.
Unit locked in position.
Move position
All circuits disconnected. Unit can be moved.
Disconnected position
All circuits disconnected. Unit is locked in position.
The switch handle can be moved from position O to I only
after the handle has been depressed (push-to-turn feature).
Compact motor starter unit with MCB. Normal motor starter unit with MCCB.
The switch handle can be locked in off, test and disconnected
position with up to 3 padlocks.
Normal units
The units have multi-pole contacts for connection of the
auxiliary circuit. The operatin handle is also used for the
electrical as well as the mechanical interlocking function.
The handle can be set in four positions:
On-position
All circuits connected. Unit locked in service position.
Cable connection
Off-position
device for main
Main circuit disconnected, auxiliary circuit circuits.
disconnected. Unit locked in service position or
disconnected (isolated) position.
TEST Test position Slide connectors for
Main circuit disconnected, auxiliary circuit connected. auxiliary circuits.
Unit locked in position.
Move position
All circuits disconnected. Unit can be moved.
The switch handle can be locked in off, test and disconnected Normal unit.
position with up to 3 padlocks.
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 7
MNS Product description
Function units (apparatus)
Removable units
The W/R-cubicle can accomodate removable units (R-units).
These units have the main circuit directly connected to the
Main circuits directly
apparatus terminals and the auxiliary circuit connected to connected to the
plug-in terminal blocks. apparatus terminals.
The units are screw-fixed to the cubicle. The outgoing cables
must therefore first be removed before the unit itself can be
removed.
The handle can be set in two positions:
On-position
All circuits connected. Unit locked in service position.
Off-position Flat-pin multi-pole
terminals for auxiliary
Main circuit disconnected. Unit can be removed after circuits.
the outgoing cables have been disconnected.
The handle can be locked in off-position with up to 3 pad-
locks. Removable unit.
MNS
8 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS CenterPro
PC-designed switchgear
General
Low Voltage Switchgear
Center Pro is Projecting and quotation 3/PEN, 400V 50Hz In=1250A, Ik=35kA, IP31
aid for Center switchgear. It is a PC-
based program which minimizes the
manual work of planning a switchgear.
The user has to answer questions
regarding switchgear data and distri-
bution objects. The program then
dimensions and selects suitable switch-
gear modules such as breakers, star-
ters, distribution units, busbar systems,
etc., and organizes them in an optimal
switchgear layout.
Computer-generated data
The program will automatically Computer requirements
generate: Computer IBM PC or compatible using an
Technical specification INTEL 386/486 processor.
Block diagrams, front layouts and Primary
memory Min. 580 kbytes available.
single-line drawings.
Hard disk Min 2.5 Mbytes available.
Circuit diagrams.
Operating
Spread worldwide system MS-DOS 3.3 or later.
Graphics EGA
CenterPro is used by electrical
Printer IBM compatible graphics printer.
consultants, in large industry and utility HPGL compatible printer or
companies as well as within the ABB plotter HP 7550 is required for
Group. single-line drawing and circuit
diagram.
CenterPro is delivered on diskettes
together with a Users Manual.
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 9
MNS
MNS
10 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Technical data
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 11
MNS Overveiw
Transformer cubicle
800 – 2500 kVA 2327 mm
50 – 75 kA
Disconnector cubicle
Incoming, sectioning, distribution
2263 mm
Disconnector size 2263 mm
1250 A
1600 A
2500 A
3150 A
652 mm
600 – 800 mm
Horisontal busbar system, IP 31
1500 A
2100 A
3000 A
Apparatus cubicle W/R
3400 A
For withdrawable and removable units
Metal enclosed vertical busbars
1175 A 2263 mm
1700 A
Isolated vertical busbars
750 A
1000 – 1200 mm
2263 mm
Non-equipped cubicle
400 – 800 mm
MNS
12 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Transformer cubicle
Construction
The fronts of the cubicle are made up of dors with hinges
screwed to the cubicle frames on the "lock side". Cubicles are
normally placed min. 40 mm from surrounding walls.
Cubicles are supplied as kits with assembly instructions. Self-
tapping screws are used for assembly which require either
electric or air driven screwdrivers.
Degree of protection IP31 (cubicles suitable for location in
switchgear rooms).
Installation configurations
Transformer cubicles fitted with busbar systems can be
directly connected to MNS switchgear with depth 652 mm.
Cubicle rows may be placed either left or right of the
transformer cubicle.
The transformer cubicles may also be mounted as stand-
alones without connection to a switchgear.
PE and N conductors
Horizontal protective earth and neutral conductors (PEN) are
located at the bottom rear of the cubicle. Connection between
conductor and transformer N connectors is made by RK type 650
cables or site-assembled busbars.
1452 500–2500 kVA
Transformer connection bars The extension unit is included
to allow doors with operating
Down lead conductors are designed for direct connection of handles or such to be opened
ABB Transformers Lepper Resiblock type DYHK10 and ABB 90° or more.
Transformers type TFTTK-F for 10/0.4 kV. 2000
2200
2400
2600
2800
Rear in line with the switchgear cubicles.
650
2000
2200
2400
2600
2800
Front in line with the switchgear cubicles.
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 13
MNS Transformer cubicle
Width Depth Type name For trafo type For trafo type
DYHK 10/0,4 kV TFTTK-F 10/0,4 kV
mm mm kVA kVA
Options
Connection to isolated neutral in
feeded switchgears ................................ +N
Bracket for contact thermometer ..... +P12
Earthing coupler, high voltage side ... +E1
Busbars tinned .................................... +SN
Switchgear colour, Standard .......... + Grey
Switchgear colour, ASEA H .......... + Beige
MNS
14 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Air circuit-breaker cubicle
General
The circuit-breaker cubicles are designed for ACB-type withdrawable air circuit-breakers.
The circuit-breaker can be switched to the disconnected position with the cubicle door
closed. The cubicle is available in ratings 1250 to 3900 A, 3- and 4-pole versions.
Incoming supply
Different incoming supplies are available:
Cable from below is used when incoming cable is available. The cubicle is equipped
with cable conductor and anchor rail.
Cable from above is used when incoming cable is available. The cubicle is equipped
with terminals for cable connection above the roof panel.
Busbars from above are used when connection is available (not trunking system). The
cubicle has terminals for busbar connections above the roof panel.
Sectioning is used for sectioning of main busbars in the switchgear. Available for both
right and left hand supplies. Sectioning version fits to transformer cubicles.
Circuit-breaker
The circuit-breaker is an ACB of type ABB SACE Megamax.
The breaker is equipped with an solid-state, microprocessor based protection unit with
the following protective functions:
● Protection against overload (L)
● Selective protection against short-circuit (S)
● Instantaneous protection against short-circuit (I)
● Protection against earth fault (G).
The breaker is also equipped with auxiliary contacts, shunt opening release and
shutters for auxiliary and main circuits.
Dimensions
A A A
V
9M
14 M
2263
7M 120.5
9M
3.5 M
B 652
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 15
MNS Air circuit-breaker cubicle
3-pole 4-pole
Circuit-breaker Cubicle width, Type Cubicle width, Type
size mm name mm name
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity Horizontal busbar system
A A A kAeff mm
MNS
16 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Air circuit-breaker cubicle
Options
VOLTAGE MEASURING
for 4-wire and 3-wire system with
neutral bar
3 fuses ............................................. +P5AN
3 fuses, V-meter and phase to phase
selector switch above breaker 1) .... +P5DN
3 fuses, V-meter and phase to phase
selector switch below breaker 1) .... +P6DN
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 17
MNS Disconnector cubicle
General
The disconnector cubicle is designed for fixed disconnectors. The cubicle is
available in sizes 1250, 2000, 2500 and 3150 A in 3- and 4-pole versions.
The cubicle has interlocking to prevent the door being opened when the switch-
disconnector is in the on-position.
Incoming supply
Different incoming supplies are available:
Cable from below is used when incoming cable is available. The cubicle is equipped
with cable conductor and anchor rail.
Cable from above is used when incoming cable is available. The cubicle is equipped
with terminals for cable connection above the roof panel.
Busbars from above are used when connection is available (not trunking system).
The cubicle has terminals for busbar connections above the roof panel.
Sectioning is used for sectioning of main busbars in the switchgear. Available for
both right and left hand supplies.
Switch-disconnector
The switch-disconnector is a fixed mounted type, ABB Control Oy, OETL with one
opening and one closing auxiliary contact.
The cubicle has interlocking so that the door cannot be opened when the switch-
disconnector is in on-position. The door must be closed to operate the switch-
disconnector.
Dimensions
A A A
V
9M
14 M
2263
7M
9M
3.5 M
B 652
MNS
18 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Disconnector cubicle
3-pole 4-pole
Disconnector Cubicle width, Type Cubicle width, Type
size mm name mm name
PEN PEN
C. Sectioning, C. Sectioning,
supply from supply from
right left
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity Horizontal busbar system
A A A kAeff mm
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 19
MNS Disconnector cubicle
Options
VOLTAGE MEASURING
for 3-wire system without neutral bar
3 fuses ................................................ +P5A
3 fuses, V-meter and phase to phase
selector switch above breaker 1) ...... +P5D
3 fuses, V-meter and phase to phase
selector switch below breaker 1) ...... +P6D
3-pole MCB ......................................... +P5E
Specify voltage 400/500 V.
3-pole MCB, V-meter and phase to phase
selector switch above breaker 1) ....... +P5F
Specify voltage 400/500 V.
3-pole MCB, V-meter and phase to phase
selector switch below breaker 1) ....... +P6F
Specify voltage 400/500 V.
3 fuses, 2-pole V-meter without selector
switch ............................................... +P6G
3 pole MCCB, 2-pole V-meter without
selector switch ................................. +P6H
Specify voltage 400/500 V.
3 extra fuses ....................................... +P6A
Extra 3-pole MCB ............................... +P6E
Specify voltage 400/500 V.
VOLTAGE MEASURING
for 4-wire and 3-wire system with
neutral bar
3 fuses ............................................. +P5AN
3 fuses, V-meter and phase to phase
selector switch above breaker 1) .... +P5DN
3 fuses, V-meter and phase to phase
selector switch below breaker 1) .... +P6DN
MNS
20 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Apparatus cubicle for W and R-units
General
The switchgear W-cubicle can be equipped with withdrawable W-units and
removable R-units.
The cubicle consists of a 600 mm compartment for fitting of W and R-units and a
400 mm or 600 mm cable compartment on the right for outgoing (and incoming, if
used) cables.
Cable compartment
The cable compartment is provided with fixing points for both the main circuit and
the auxiliary circuit cables.
Four mounting bars for power cables are positioned on the right hand side of cable
compartment.
Horizontal cable channels for connection between cubicles are positioned at the
very top (included).
Module space
The cubicle has space for 36 modules (36M). 1M = 50 mm.
Dimensions
2263
36 M
400/600 652
1000/1200
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 21
MNS Apparatus cubicle for W and R-units
Cubicle
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity
A A A kAeff mm
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity
A A A kAeff mm
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity Horizontal busbar system
A A A kAeff mm
At top At bottom
1500 1450 1250 50 2//30x10 Cu –H4 –H04
2100 2050 1600 75 2//60x10 Cu –H6 –H06
3000 2950 2100 100 4//60x10 Cu –H8 –H08
N
3400 3350 2450 100 4//60x10 Cu –H8A –H08A
PE / PEN
MNS
22 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Apparatus cubicle for W and R-units
Options
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 23
MNS Non-equipped cubicle
General
The non-equipped F-cubicle is 400 mm or 600 mm wide and can be equipped with
an assembly plate for fixed mounting of apparatus.
The cubicle front is covered by a full height door with standard locks.
Dimensions
2263 2093
373.5
400/600/800 652
MNS
24 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Non-equipped cubicle
Cubicle
400 VMM203-D4
600 VMM203-D6
800 VMM203-D8
Short-circuit Busbar
Rated current at 35 °C ambient withstand size Type name
IP31 IP41 IP54 capacity Horizontal busbar system
A A A kAeff mm
At top At bottom
1500 1450 1250 50 2//30x10 Cu –H4 –H04
2100 2050 1600 75 2//60x10 Cu –H6 –H06
3000 2950 2100 100 4//60x10 Cu –H8 –H08
N
3400 3350 2450 100 4//60x10 Cu –H8A –H08A
PEN / PE
Options
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 25
MNS
MNS
26 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Overview
Switch-fuse MCCB
DOL-starter
normal start
type 2, 50 kA
≤315 kW ≤280 kW
DOL-starter
Motor heavy duty start
starters type 2, 50 kA
≤315 kW ≤280 kW
W-units
Two-direction starter
type 2, 50 kA
≤315 kW ≤280 kW
Star-delta starer
type 2, 50 kA
MCCB
16–800 A
MCCB R-unit
MCCB
Function units 3, 4-pole
W and R-units 30–200 kA W-unit Plug-in MCCB
Distri- 16–800 A
IP31 IP41 bution
R-unit
units
IP43
IP54 MCB + PROLIM
10–25 A
3-, 4-pole, 50 kA
W-unit R-unit
Switch-fuse
160–800 A
3-, 4-pole
W-unit R-unit
MCB-board with
backup
Backup 100–125 A
1, 2, 3, 4-pole MCB 6–63 A
170 kA
Group
board R-unit, fixed MCCB R-unit, plug-in MCCB
MCB-board without
backup
MCB 6–63 A
1, 2, 3, 4-pole,
10 kA
R-unit
1, 3-pole
Diazed fuse
board
Thread II 25 A
Thread III 63 A
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 27
MNS Incoming units, W
General
For a simple incoming supply the incoming line can be con- The incoming units consists of a MCCB of type SACE Isomax
nected in a switchgear W-cubicle to an incoming unit of the or switch-fuse of type ABB Control Oy, OESA.
same type as the distribution units.
MCCB-units
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Switch-fuse units
3-pole 4-pole
Rated Mo- Type Mo- Type
current dule designation dule designation
size size
4-pole
Switch-fuse: ABB Control Oy, type OESA
Options
MNS
28 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Main cubicle switch and
sectioning circuit-breaker, R
General
The main cubicle switch sectionalises the vertical busbar The switch is a switch-fuse of type ABB Control Oy, OESA.
system in the apparatus cubicles (W and R cubicles). For
this purpose an additional vertical busbar system is needed
placed to the right in the cubicle.
Switch-fuse unit
3-pole 4-pole
Rated Mo- Type Mo- Type
current dule designation dule designation
size size
Options
Current meter
One A-meter 72×72 mm fitted in the front for
indication of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 29
MNS Motor starter units W
● Two-direction starters (the motor must be stopped before ● Dimensioned for thermal/mechanical short-circuit resistance
reversing) only for unit (external cable and motor are not included)
● Star-delta starters ● Heavy duty start acc. to 947-4-1, class 20 (= starting time
max. 20 s), ≥ 75 kW class 30 (= starting time max. 30 s).
Design The correct selection of starter for a specific motor may be
The starters are available with switch-fuse or in fuse-less obtained using CenterPro.
version.
Starters with switch-fuse Operating supply
The switch-fuse is of the type ABB Control Oy, OESA. Type The starter operating voltage is 220 and 230 V, 50 Hz
of fuse is aM-type of gG-type. or 110 V, 50 Hz.
Fuse-less starters
Circuit diagrams
The short-circuit protection is an MCCB of type SACE Modul LN
series or MCB and PROLIM for small starters. Each starter is supplied with a circuit diagram detailing the
functions of the starter. Position designations Q, K, F, etc., are
as per IEC 750 ”Item designation in electrotechnology”.
Overview
400 V, ≤250 kW
Normal start
500 V, ≤280 kW
400 V, ≤250 kW
Heavy duty start
starting time max. 20 s at ≤7,5 kW 500 V, ≤280 kW
starting time max. 30 s at >7,5 kW
With MCCB
400 V, ≤250 kW
Two-direction
500 V, ≤280 kW
400 V, ≤160 kW
Star-delta
500 V, ≤200 kW Direct-on-line starter with MCCB, normal start,
4M.
Motor starter
type 2, 50 kA
IP41 (std.)
IP43 400 V, ≤315 kW
IP54
Normal start
500 V, ≤315 kW
400 V, ≤315 kW
Heavy duty start
starting time max. 20 s at ≤7,5 kW 500 V, ≤315 kW
starting time max. 30 s at >7,5 kW
With switch-fuse
400 V, ≤315 kW
Two-direction
500 V, ≤315 kW
400 V, ≤315 kW
Star-delta
Direct-on-line starter with MCB + Prolim,
500 V, ≤315 kW
normal start, 2M.
MNS
30 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Motor starter units W
400 V 500 V
Max. mo- Fuse type gG Fuse type aM Mo- Type designation Max. mo- Fuse type gG Fuse type aM Mo- Type designation
tor output Max. current for the unit dule tor output Max. current for the unit dule
AC3 Imax Imax size AC3 Imax Imax size
kW A A kW A A
Normal units
3 8,3 8,3 2M VMLD9-L80-W2 4 7 7 2M VMLD9-L80-W2
4 11 11 2M VMLD12-L80-W2 5,5 11 11 2M VMLD16-L80-W2
7,5 16 16 2M VMLD16-L80-W2 7,5 14 14 2M VMLD25-L80-W2
11 – 25 2M VMLD25-L80-W2 11 19 19 2M VMLD50-L80-W2
22 50 50 2M VMLD50B-L80-W2 22 42 42 2M VMLD50B-L80-W2
30 59 59 2M VMLD63-L80-W2 30 45 45 2M VMLD63-L80-W2
37 75 75 4M VMLD75-L160-W4 37 63 63 4M VMLD75-L160-W4
45 96 96 4M VMLD90B-L160-W4 45 80 80 4M VMLD90-L160-W4
55 – 110 4M VMLD100-L160-W4 75 – 125 4M VMLD100-L160-W4
55 110 – 6M VMLD100-L250-W6 75 125 – 6M VMLD100-L250-W6
Compact units
3 8,3 8,3 4 M/4 VMLD9-L63-W4/4 4 7 7 4 M/4 VMLD9-L63-W4/4
4 11 11 4 M/4 VMLD12-L63-W4/4 5,5 11 11 4 M/4 VMLD16-L63-W4/4
7,5 16 16 4 M/4 VMLD16-L63-W4/4 7,5 14 14 4 M/4 VMLD25-L63-W4/4
11 – 25 4 M/4 VMLD25-L63-W4/4 15 25 25 4 M/4 VMLD30-L63-W4/4
15 30 30 4 M/4 VMLD30-L63-W4/4 18,5 32 32 4 M/4 VMLD50-L63-W4/4
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 31
MNS Motor starter units W
400 V 500 V
Max. mo- Max. Module Type designation Max. mo- Max. Module Type designation
tor output current for size tor output current for size
AC3 the unit AC3 the unit
kW A kW A
Normal units
0,37 1,4 2M VMLD9-M25S1-W2 1,1 2,4 2M VMLD9-M25S4-W2
0,75 2,4 2M VMLD9-M25S2-W2 1,5 3,1 2M VMLD16-M25S4-W2
1,1 3,1 2M VMLD25-M25S4-W2 2,2 4,8 2M VMLD25-M25S9L5-W2
2,2 6,5 2M VMLD25-M25S6-W2 4 8,5 2M VMLD50-M25S9L5-W2
3 8,3 2M VMLD50-M25S9-W2 11 19 2M VMLD50-M2S20L5-W2
4 11 2M VMLD50-M25S12-W2 15 25 2M VMLD50-M2S25L5-W2
5,5 14 2M VMLD50-M25S16-W2 22 42 4M VMLD50-M125L-W4
11 25 2M VMLD50-M25S25-W2 30 52 4M VMLD63-M125L-W4
22 52 2M VMLD50-M28K63L-W2 37 63 4M VMLD90-M125L-W4
37 75 4M VMLD75-M125L-W4 45 80 4M VMLD145-M125L-W4
Compact units
0,37 1,4 4 M/4 VMLD9-M25S1-W4/4 1,1 2,4 4 M/4 VMLD9-M25S4-W4/4
0,75 2,4 4 M/4 VMLD9-M25S2-W4/4 1,5 3,1 4 M/4 VMLD16-M25S4-W4/4
1,1 3,1 4 M/4 VMLD25-M25S4-W4/4 2,2 4,8 4 M/4 VMLD25-M25S9L5-W4/4
2,2 6,5 4 M/4 VMLD25-M25S6-W4/4 4 8,5 4 M/4 VMLD30-M25S9L5-W4/4
3 8,3 4 M/4 VMLD30-M25S9-W4/4 11 19 4 M/4 VMLD30-M25S20L5-W4/4
MNS
32 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Motor starter units W
Contactor ≤ 75 A
Contactor > 75 A
400 V 500 V
Max. mo- Fuse type gG Fuse type aM Mo- Type designation Max. mo- Fuse type gG Fuse type aM Mo- Type designation
tor output Max. current for the unit dule tor output Max. current for the unit dule
AC3 Imax Imax size AC3 Imax Imax size
kW A A kW A A
Normal units
3 8,3 8,3 2M VMLDH9-L80-W2 4 7 7 2M VMLDH9-L80-W2
4 11 11 2M VMLDH12-L80-W2 5,5 11 11 2M VMLDH16-L80-W2
5,5 14 14 2M VMLDH16-L80-W2 7,5 14 14 2M VMLDH25-L80-W2
7,5 19 19 2M VMLDH50-L80-W2 11 19 19 2M VMLDH50-L80-W2
18,5 42 42 2M VMLDH50B-L80-W2 22 42 42 2M VMLDH50B-L80-W2
22 52 52 2M VMLDH63-L80-W2 30 – 45 2M VMLDH63-L80-W2
30 – 63 2M VMLDH75-L80-W2 30 45 – 4M VMLDH63-L160-W4
30 63 – 4M VMLDH75-L160-W4 37 63 63 4M VMLDH75-L160-W4
37 – 78 4M VMLDH90-L160-W4 45 – 80 4M VMLDH90-L160-W4
37 78 – 6M VMLDH100-L250-W6 45 80 – 6M VMLDH100-L250-W6
45 – 90 4M VMLDH100-L160-W4 55 – 90 4M VMLDH100-L160-W4
45 96 – 6M VMLDH100B-L250-W6 55 100 – 6M VMLDH100B-L250-W6
55 127 112 6M VMLDH145-L250-W6 75 129 129 6M VMLDH145-L250-W6
75 156 – 6M VMLDH210B-L400-W6 90 – 145 6M VMLDH210-L250-W6
90 – 185 6M VMLDH210B-L250-W6 90 145 – 6M VMLDH210-L400-W6
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 33
MNS Motor starter units W
Contactor ≤ 75 A
Contactor > 75 A
400 V 500 V
Max. mo- Max. Module Type designation Max. mo- Max. Module Type designation
tor output current for size tor output current for size
AC3 the unit AC3the unit
kW A kW A
Normal units
0,55 1,8 2M VMLDH9-M25S2-W2 1,1 2,4 2M VMLDH9-M25S4-W2
0,75 2,4 2M VMLDH25-M25S4-W2 1,5 3,1 2M VMLDH25-M25S6-W2
1,5 4 2M VMLDH25-M25S6-W2 2,2 5 2M VMLDH25-M25S9L5-W2
2,2 6,5 2M VMLDH50-M25S9-W2 3 6,5 2M VMLDH50-M25S9L5-W2
3 8,5 2M VMLDH50-M25S12-W2 4 8,5 2M VMLDH50-M25S12L5-W2
MNS
34 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Motor starter units W
400 V 500 V
Max. mo- Fuse type gG Fuse type aM Mo- Type designation Max. mo- Fuse type gG Fuse type aM Mo- Type designation
tor output Max. current for the unit dule tor output Max. current for the unit dule
AC3 Imax Imax size AC3 Imax Imax size
kW A A kW A A
Normal units
3 8.3 8.3 2M VMLR9-L80-W2 4 7 7 2M VMLR9-L80-W2
4 11 11 2M VMLR12-L80-W2 5,5 11 11 2M VMLR16-L80-W2
7,5 16 16 2M VMLR16-L80-W2 7,5 14 14 2M VMLR25-L80-W2
11 – 25 2M VMLR25-L80-W2 11 19 19 2M VMLR50-L80-W2
22 50 50 2M VMLR50B-L80-W2 22 42 42 2M VMLR50B-L80-W2
30 63 63 2M VMLR63-L80-W2 30 45 45 2M VMLR63-L80-W2
37 75 75 4M VMLR75-L160-W4 37 63 63 4M VMLR75-L160-W4
45 96 96 6M VMLR90B-L160-W6 45 80 80 6M VMLR90-L160-W6
55 – 110 8M VMLR100-L160-W8 75 – 125 8M VMLR100-L160-W8
55 110 – 8M VMLR100-L250-W8 75 125 – 8M VMLR100-L250-W8
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 35
MNS Motor starter units W
400 V 500 V
Max. mo- Max. Module Type designation Max. mo- Max. Module Type designation
tor output current for size tor output current for size
AC3 the unit AC3 the unit
kW A kW A
Normal units
0,37 1,4 2M VMLR9-M25S1-W2 1,1 2,4 2M VMLR9-M25S4-W2
0,75 2,4 2M VMLR9-M25S2-W2 1,5 3,1 2M VMLR16-M25S4-W2
1,1 3,1 2M VMLR25-M25S4-W2 2,2 4,8 2M VMLR25-M25S9L5-W2
2,2 6,5 2M VMLR25-M25S6-W2 4 8,5 2M VMLR50-M25S9L5-W2
3 8,3 2M VMLR50-M25S9-W2 11 19 2M VMLR50-M25S20L5-W2
4 11 2M VMLR50-M25S12-W2 15 25 2M VMLR50-M25S25L5-W2
5,5 14 2M VMLR50-M25S16-W2 22 42 4M VMLR50-M125L-W4
11 25 2M VMLR50-M25S25-W2 30 52 4M VMLR63-M125L-W4
22 52 2M VMLR50-M28K63L-W2 37 63 6M VMLR90-M125L-W6
37 75 4M VMLR75-M125L-W4 45 90 6M VMLR100-M125L-W6
MNS
36 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Motor starter units W
400 V 500 V
Max. mo- Fuse type gG Fuse type aM Mo- Type designation Max. mo- Fuse type gG Fuse type aM Mo- Type designation
tor output Max. current for the unit dule tor output Max. current for the unit dule
AC3 Imax Imax size AC3 Imax Imax size
kW A A kW A A
Normal units
7,5 16 16 4M VMLS9-L160-W4 7,5 14 14 4M VMLS12-L160-W4
11 23 23 4M VMLS12-L160-W4 11 19 19 4M VMLS16-L160-W4
15 30 30 4M VMLS16-L160-W4 15 24 24 4M VMLS25-L160-W4
18,5 42 42 4M VMLS25-L160-W4 22 43 43 4M VMLS50-L160-W4
22 50 50 4M VMLS50-L160-W4 45 72 72 4M VMLS50B-L160-W4
37 78 78 4M VMLS50B-L160-W4 55 90 90 4M VMLS63-L160-W4
45 96 96 4M VMLS63-L160-W4 75 112 112 4M VMLS75-L160-W4
55 127 125 4M VMLS75-L160-W4 90 138 138 6M VMLS90-L160-W6
75 156 156 6M VMLS90B-L160-W6 110 – 160 8M VMLS100-L160-W8
110 210 210 10 M VMLS100-L250-W10 132 207 200 10 M VMLS100-L250-W10
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 37
MNS Motor starter units W
400 V 500 V
Max. mo- Max. Module Type designation Max. mo- Max. Module Type designation
tor output current for size tor output current for size
AC3 the unit AC3 the unit
kW A kW A
Normal units
15 32 4M VMLS75B-M125L-W4 7,5 14 4M VMLS75-M125L-W4
22 55 4M VMLS75C-M125L-W4 18,5 32 4M VMLS75B-M125L-W4
30 69 6M VMLS100B-M160L-W6 22 43 4M VMLS75C-M125L-W4
37 80 6M VMLS100C-M160L-W6 30 46 6M VMLS100-M160L-W6
45 95 6M VMLS210-M200L-W6 45 69 6M VMLS100B-M160L-W6
Options
MNS
38 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units W and R
Overveiw
3-pole
W-units
MCCB type Isomax N 4-pole
Normal breaking capacity
35 kA at 400 V 3-pole
16–800 A
4-pole
R-units
Plug-in
mounted 3-pole
MCCB
4-pole
3-pole
W-units
MCCB type Isomax S/H 4-pole
High breaking capacity
MCCB 50–65 kA at 400 V 3-pole
20–800 A
4-pole
R-units
Plug-in
mounted 3-pole
MCCB
4-pole
3-pole
W-units
4-pole
MCCB type LN
Current limiting breaker
170–200 kA at 400 V 3-pole
Distri-
bution 16–630 A
units 4-pole
R-units
IP31 Plug-in
IP54 mounted 3-pole
MCCB
4-pole
MS 325 + PROLIM
Miniature circuit-breaker + current limiter
50 kA W-units 3-pole
10–25 A
3-pole
W-units
4-pole
Switch–fuse
160–800 A 3-pole
R-units
4-pole
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 39
MNS Distribution units W
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
40 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units W
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 41
MNS Distribution units W
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
42 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units W
W-units, 3-pole
6,3 50 2M VMLM25S–6–W2 2M VMLM25S–6L5–W2
12,5 50 2M VMLM25S–12–W2 2M VMLM25S–12L5–W2
16 50 2M VMLM25S–16–W2 2M VMLM25S–16L5–W2
20 50 2M VMLM25S–20–W2 2M VMLM25S–20L5–W2
25 50 2M VMLM25S–25–W2 2M VMLM25S–25L5–W2
Options
A-meter
A-meter 48 x 48 mm in the front for indication
of the outgoing current.
with instantaneous A-meter .......... +P2B
with maximum A-meter ............... +P2BM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 43
MNS Distribution units W
Switch-fuse
W-units, 3-pole
63 A 1) (63 A/500V) 2 M VMLL63–W2
160 A 4M VMLLH160–W4
250 A 6M VMLLH250–W6
1)
400 A 6M VMLLH400–W6
VMLL 63 only single breaking and 630 A 8M VMLLH630–W8
fuse accessible only when with-
800 A 8M VMLLH800–W8
drawn unit.
W-units, 4-pole
160 A 4M VMLLH160–4–W4
250 A 8M VMLLH250–4–W8
400 A 8M VMLLH400–4–W8
630 A 12 M VMLLH630–4–W12
800 A 12 M VMLLH800–4–W12
Options
A-meter
A-meter 72 x 72 mm in the front for indication
of outgoing current. 2)
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
Auxiliary contacts
Choice of up to 2 NO/NC.
1 NO + 1 NC ..................................... +HL2
MNS
44 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units R
MCCB R-units with fixed MCCB, normal breaking capacity, 3- and 4-pole
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 45
MNS Distribution units R
MCCB R-units with fixed MCCB, high breaking capacity, 3- and 4-pole
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
46 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units R
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 47
MNS Distribution units R
MCCB R-units with plug-in MCCB, normal breaking capacity, 3- and 4-pole
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
48 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units R
MCCB R-units with plug-in MCCB, high breaking capacity, 3- and 4-pole
3-pole 4-pole
Rated Breaking Mo- Type Mo- Type
current 1) capacity dule designation dule designation
400, 500, 690 V size size
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 49
MNS Distribution units R
Options
Current meter
A-meter 72 x 72 mm in the front for indication
of outgoing current.
with instantaneous A-meter ......... +P2D
with instantaneous and
maximum A-meter ...................... +P2DM
MNS
50 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Distribution units R
Switch-fuse
R-units, 3-pole
160 A 4 M VMLLH160–R4
250 A 4 M VMLLH250–R4
400 A 4 M VMLLH400–R4
630 A 6 M VMLLH630–R6
800 A 6 M VMLLH800–R6
R-units, 4-pole
160 A 4 M VMLLH160–4–R4
250 A 6 M VMLLH250–4–R6
400 A 6 M VMLLH400–4–R6
630 A 8 M VMLLH630–4–R8
800 A 8 M VMLLH800–4–R8
Auxiliary contacts
Choice of up to 2 NO/NC.
1 NO + 1 NC ..................................... +HL2
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 51
MNS Group boards R
General
Group boards are available in two basic designs:
With miniature circuit-breakers MCB and with D-type fuses.
See overview below.
MCB units are designed without separate terminals for the
main circuit. External cables are connected directly to
apparatus and can therefore be used in a terminal row.
D-fuse units are available in three versions: without terminal –
external cables are connected directly to the D-fuse holders,
with terminal and with group switches where the switches are
positioned last and used as terminals.
Overview
3-pole MCCB
4-pole MCCB
3-pole MCCB
4-pole MCCB
Distri- 15 kA
bution
board
MNS
52 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS MCB boards R
2 4M
432
Without backup MCCB
(as independent direct-supply central at low short circuit levels or for optional external supply).
3 and 4-pole are the same. Max. load 180 A.
Limited to 15 kA by the connection and 10 kA if MCB type S270 is used.
1 4 M VMLA180– –R4 –R4C
Options
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 53
MNS MCB boards, R
MCB apparatus with 1) C-characteristics as per IEC 898, for use in MCB units
270 series 10 kA 1-pole 2-pole 3-pole 4-pole
Rated current 18 mm 36 mm 54 mm 72 mm
280 series Earthing fault protection 0,03 A Earthing fault protection 0,3 A
2-pole 4-pole 2-pole 4-pole
Rated current 72 mm 108/144 mm 72 mm 108/144 mm
MNS
54 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Fuse boards, R
No. of groups
Max. 1-pole 3-pole Module Type
fuse size, thread size designation
Option
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 55
MNS Enclosure unit, W
General
Unit enclosure are semi-finished units for customized function. The units have the
same switch-fuse and modular sizes as the motor starter units.
Vertical
A unit consists of: DIN-rails
● Withdrawable enclosure.
● 3-pole switch-fuse with auxiliary contacts.
● Switch interlock device. The switch can only be operated with the withdrawable
unit in service position.
● Plug-in contacts for incoming supply.
● Cable connectors in cable compart-ment for both main circuit and auxiliary circuit.
Size 2 M
DIN-rail
Size 4 – 10 M
Shaded area indicates free space
for mounting of apparatus.
Unit enclosure
with basic apparatus
Rated No. of auxiliary Module
current 1) contacts size
Compact unit
45 A 1) 16 4/4 M VMLX–W4/4
Options
MNS
56 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS Cover panels
General
The cover panels are used for covering non-equipped areas in switchgear
W-cubicles.
Cover panels
Module
size
Options
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 57
MNS
MNS
58 Catalogue 1TSC 221-EN, Edition 4, October 1998
MNS
MNS
Catalogue 1TSC 221-EN, Edition 4, October 1998 59