Contactors For Capacitor Switching: Application Guide
Contactors For Capacitor Switching: Application Guide
Capacitor Switching
Contents
General
Reminder of capacitor transient conditions .......................................................................................................... 2
Installation studies
Three-phase capacitor bank with a single step ............................................................................................... 16
Three-phase capacitor bank with several steps of identical power ....................................................... 17
Three-phase capacitor bank with several steps of different powers ..................................................... 18
ABB Control 1
1SBC 0064 99 R1002
Capacitor Bank Switching
General
Fixed power factor correction consists of inserting, in parallel on the An automatic power factor correction system, on the other hand,
network, a capacitor bank whose total power is provided by the assembly consists of several capacitor banks of identical or different powers (several
of capacitors of identical or different unit powers. steps), energized separately according to the value of the power factor
The bank is energized by a contactor that simultaneously supplies all to be corrected.
the capacitors (a single step). An electronic device automatically determines the power of the steps to
The inrush current peak, in the case of fixed correction, can reach 30 be energized and activates the relevant contactors.
times the nominal current of the capacitor bank. The inrush current peak, in the case of automatic correction, depends
on the power of the steps already on duty, and can reach 180 times the
nominal current of the step to be energized.
E1178D
E1179D
2 ABB Control
1SBC 0064 99 R1002
Contactors for Capacitor Switching
The ABB Solutions
ABB offers 3 contactor versions according to the value of the inrush current peak and the power of the capacitor bank.
SB8171S2
SB8075S3
SB7324S2
A.. and AF.. standard contactors (A 12 ... A 300 and AF 400 ... AF 750)
Maximum permissible peak current Î < 30 times the nominal rms current of the switched capacitor.
Refer to the table on page 4 for the operational values.
SB8010S3
SB8009S3
SB8078S3
SB7820S2
SB7821S2
● In a given application, if the user does not know the value of the inrush current peak, this value
can be approximately calculated using the formulas given on pages 8 and 9.
ABB Control 3
1SBC 0064 99 R1002
Contactors for Capacitor Switching
Selection Table
If, in an application, the current peak is greater than the maximum peak current Î specified in the last column in the table, select a higher rating, refer
to the UA contactors (see page 5) or add inductances (see page 12).
The capacitor bank will be protected by gG type fuses whose rating is equal to 1.5 ... 1.8 times nominal current.
4 ABB Control
1SBC 0064 99 R1002
Contactors for Capacitor Switching
Selection Table
UA.. contactors
The UA.. contactors have been specially developed for the switching of capacitor banks whose inrush current peaks are less than or equal to
100 times nominal rms current. The table below gives the permissible powers according to operational voltage and temperature close to the
contactor. It also specifies the maximum peak current Î values accepted by the contactor.
The kvar ratings acc. to the table below are applicable to "star" connected capacitors (less current, cable savings).
The capacitors must be discharged (maximum residual voltage at terminals < 50 V) before being re-energized when the contactors are making.
In these conditions, electrical durability of contactors is equal to 100 000 operating cycles.
For 220 V and 380 V, multiply by 0.9 the rated values at 230 V and 400 V respectively.
Example: 50 kvar/400 V corresponding to 0.9 x 50 = 45 kvar/380 V.
If, in an application, the current peak is greater than the maximum peak current Î specified in the table above, select a higher rating, refer to the
UA...-R contactors (see page 6) or add inductances (see page12).
The capacitor bank will be protected by gG type fuses whose rating is equal to 1.5 ... 1.8 times nominal current.
ABB Control 5
1SBC 0064 99 R1002
Contactors for Capacitor Switching
Selection Table
Operating principle
The front-mounted block mechanism of the UA…-R contactors alternately ensures early making and breaking of the auxiliary "PA" poles with
respect to the main "PP" poles of the contactor.
When the coil is energized, the early making auxiliary poles connect When the coil is de-energized, early breaking of the auxiliary poles
the capacitor to the network via the set of resistors, thus attenuating the ensures that the capacitor is disconnected via the main poles.
current peak. A few milliseconds later, the contactor main poles short-
circuit the resistors with a new reduced inrush current.
The insertion contacts remain closed, ready to operate as early-breaking
contacts for the next breaking sequence.
R R
PA PP A1 PA PP A1
A2 A2
R R
E1181D
E1180D
C C
These contactors can be used in installations in which peak current far exceeds 100 times nominal rms current. The contactors are delivered
complete with their damping resistors and must be used without additional inductances (see table below).
The kvar ratings acc. to the table below are applicable to "star" connected capacitors (less current, cable savings).
The capacitors must be discharged (maximum residual voltage at terminals < 50 V) before being re-energized when the contactors are making.
Their electrical durability is 250 000 operating cycles for Ue < 500 V and100 000 operating cycles for Ue > 500 V.
Powers in kvar
6 ABB Control
1SBC 0064 99 R1002
Contactors for Capacitor Switching
Selection examples
The information given on pages 8 and 9 will enable the user to calculate current peaks and to limit them to a value acceptable for the contactor.
Since this calculation is never exact, capacitor bank manufacturers optimise their products by tests.
ABB Control 7
1SBC 0064 99 R1002
Calculation of Inrush Current Peak and Frequency
If the inrush current peak on energizing of a capacitor bank is greater than that acceptable for the switching contactor, there is a risk that power
factor correction will no longer be ensured.
This is because, in this case, the contactor may remain permanently closed due to welding of its main poles.
The formulas given below are used to estimate inrush current peak as well as current frequency during the transient period. The values of the
inductances used in the formulas can be determined by the methods described on pages 10 and 11.
Caution:
These formulas are applicable only if the capacitor bank is completely discharged at the time of energizing (maximum voltage at terminals < 50 V).
U
10 9 Q Q
Line Î= x Î = k1
L: Line inductance Transformer 3πf L + Lt L + Lt
by phase S: Power in kVA
χ: Short-circuit voltage as a %
Lt: Transformer inductance by phase
U: Phase-to-phase voltage in V Inrush current frequency f0:
1
Contactor f0 = k2 U
Q (L + Lt)
Î: in Amperes
f: mains current frequency in Hz
E1182D
Q: in kvar
L, Lt in µH
Capacitor with a single step k1 = 1457 (50 Hz) or 1330 (60 Hz)
Q: Power in kvar (star or delta connection)
k2 = 89.2 (50 Hz) or 97.2 (60 Hz)
U
n-1 Qn
Î = k1 x
n Ln
1
f0 = k2 U
L n x Qn
Î: in Amperes
L1 = L2 = L... = Ln: inductance by phase of a step in µH
Ln L2 L1
Q1 = Q2 = Q... = Qn: power of a step in kvar
n: number of capacitor steps
U: phase-to-phase voltage in V
E1183D
8 ABB Control
1SBC 0064 99 R1002
Calculation of Inrush Current Peak and Frequency
Kn K2 K1
Inrush peak current Î:
(Q 1 + Q 2 + … + … + Q n - 1) Q n 1
Î = k1 x
Q1 + Q2 + … + … + Qn 1
Ln +
1 1 … 1
+ + +
Ln L2 L1 L1 L2 Ln - 1
E1183D
Qn Q2 Q1
Energizing of Q n
Q1 = a Qn L1 = Ln / a
Q2 = b Qn L2 = Ln / b
Q .. = .. Q n L .. = L n / ..
➟
➟
Qn - 1 = z Qn L n - 1 = Ln / z
ABB Control 9
1SBC 0064 99 R1002
Determining the Transformer Inductance
The value of the inductance (Lt) of the transformer used in the various formulas above can be determined by following the method described below.
S: Power in kVA
χ: Short-circuit voltage as a % . χU χ U2
2
1
U Lt = . 10 3 Lt =
U: Phase-to-phase operating voltage in Volts 200 π f S k3 S
f: Current frequency in Hertz
E1184D
k 3 = 31.4 (50 Hz) or 37.68 (60 Hz)
E1184D
Use
400
300
200
100
80 Example:
60
Transformer:
40 S = 1000 kVA
30 χ=5%
20
U = 380 V
f = 50 Hz
L t = 23 µH by phase
10
8
6
660/690 V
4
3 500 V
415/440 V
2
380/400 V
χ (%) S
220 V (kVA)
1 4
10 20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
4,5
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
5
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
5,5
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
6
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
7
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
8
20 30 40 60 100 200 300 400 600 1000 2000 5000 10000
9
30 40 60 100 200 300 400 600 1000 2000 5000 10000
10
E1187D
10 ABB Control
1SBC 0064 99 R1002
Determining the Electrical Connection Inductances
For a symmetrical connection formed by non-magnetic conductors, the linear coefficient of apparent self-inductance is the same for all the
conductors and is given by:
2 am
L = [ 0.05 + 0.46 log10 ] µH/m µH/m This chart lets you determine the
d linear coefficient of apparent self-inductance
0,6
d = diameter of the conductive core (mm)
a m = geometric average of distances between the
conductor axes (mm)
E1196D
am = a
0,4
am = a
0,3
E1195D
E1188D
am = a 3 2 d
E1194D
a m = 1.26 a
Guideline values
ABB Control 11
1SBC 0064 99 R1002
Attenuation of the Inrush Peak
If the electrical connection inductances are very low, the inrush current peak of the capacitor bank may not be sufficiently attenuated and thus cause
welding of the main poles of the contactor.
To avoid this risk, the user must select a contactor that can withstand a higher current peak (UA or UA...-R range) or may serial-connect "additional"
inductances in the circuit.
( )
2
Q k1
Î = k1 thus Lmin = Q – Lt
L + Lt Î2
Lmin: minimum inductance of the electrical connection in µH.
Î: maximum peak, acceptable for the contactor in A (see tables on pages 4 and 5).
● Capacitor bank with several identical steps Q: power of the capacitor bank in kvar.
Qn: power of the nth step in kvar.
Î = k1
n–1
n
Qn
L n + Lt
thus Lmin = ( k12
Î2
(n – 1) 2
n2 )
Q n – Lt Lt: inductance by phase of the transformer in µH.
k1=1457 (if f = 50 Hz) or = 1330 (if f = 60 Hz)
The chart on page 13 allows, by direct reading, identification of the minimum value of the inductance according to:
– the type of contactor,
– the power of the capacitor bank in kvar,
– the number of steps.
4 π2 . a2 . N2
L = 10 -7 .F .F 1 2
b+c+r
c
10 b + 12 c + 2 r
a
F1 =
10 b + 10 c + 1,4 r
d
L: self-inductance in H
N: number of circular turns
a, b, c, d, r: dimensions in m
● Charts
The charts on pages 14 and15 allow, by direct reading, identification of the number of turns to be made according to:
– the cable cross-sectional area that will be used to connect the capacitor bank,
– the diameter of the cylinder used to make the inductance coil,
– the necessary inductance value.
12 ABB Control
1SBC 0064 99 R1002
Attenuation of the Inrush Peak
12 16 26 30 40 50 63 75 26 30 10
Lm /1 5
A A A A A A A A UA UA 95 5 18 0
A A 14 A 5 63 75
(µH) Contactor type UA UA UA 0
21
100 A 0
30
6 0/
80 A
2
95
60 UA 0
46
0/
40
40 A F
0
11
30 UA 0
75
0/
58
20 A F
10
8
Example:
6
4 UA 30 27.5 kvar
3
n = 3 x 400 V steps
f = 50 Hz
2
L m = 2.2 µH
1,0
0,8
0,6
0,4
0,3
0,2
Number of steps
0,1 1
1 2 3 4 6 10 20 30 40 60 100 200 500 1000 2000 Q (kvar)
2
4 6 10 20 30 40 60 100 200 500 1000 2000 3000
3
3 4 6 10 20 30 40 60 100 200 500 1000 2000 3000
4
2 3 4 6 10 20 30 40 60 100 200 500 1000 2000 3000
5
2 3 4 6 10 20 30 40 60 100 200 500 1000 2000 3000
6
2 3 4 6 10 20 30 40 60 100 200 500 1000 2000 3000
7
E1190DG1
8
2 3 4 6 10 20 30 40 60 100 200 500 1000 2000 3000 or more
ABB Control 13
1SBC 0064 99 R1002
14
Inductance value according to the number of turns made on a cylinder of a ø equal to 10 times the diameter "c" of the insulated cable.
L Note: For a given number of turns, the inductance value obtained with ø = 15 x c is half the sum of those obtained with 10 x c and 20 x c
(µH)
mm2
120
95
70
50
35
25
16
10
6
10
alue of the
V apparatus
self-inductance:
If the exact values are not
1 known, the following ones can
be used:
Attenuation of the Inrush Peak
Contactor:
0,3 µH
Fuses:
0,4 µH by phase
Circuit-breaker:
Additional inductances (Ø = 10 x cable diameter)
0,5 µH
}
0,1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 N turns
E1191DG
Number of turns to be made on a cylinder of a diameter equal to 10 times that of the cable (including the cable insulation material)
ABB Control
Inductance value according to the number of turns made on a cylinder of a ø equal to 20 times the diameter "c" of the insulated cable.
L Note: For a given number of turns, the inductance value obtained with ø = 15 x c is half the sum of those obtained with 10 x c and 20 x c
ABB Control
(µH)
100
Conductor core
cross-sectional
area
mm2
50
35
25
16
10
6
4
10
2,5
alue of the
V apparatus
self-inductance:
If the exact values are not
1 known, the following ones can
be used:
Attenuation of the Inrush Peak
Contactor:
0,3 µH
Fuses:
0,4 µH by phase
Circuit-breaker:
Additional inductances (Ø = 20 x cable diameter)
0,5 µH
}
0,1
1 2 3 4 5 6 7 8 9 10 N turns
E1192DG
Number of turns to be made on a cylinder of a diameter equal to 20 times that of the cable (including the cable insulation material)
15
1SBC 0064 99 R1002
Installation Studies
}
L
10 m
L t + L 1 + L 2 + L 3 = 17 µH
If L m ≤ L t + L 1 + L 2 + L 3 + … ⇒ No additional inductance L x
If L m > L t + L 1 + L 2 + L 3 + … ⇒ Add an additional inductance L x such that: L x ≥ L m – (L t + L 1 + L 2 + L 3 + …)
L x ≥ 21 µH – 17 µH thus L x ≥ 4 µH
If you choose an A 16 contactor; the chart (on page 13) gives L m = 10 µH Thus no additional inductance as 10 < 17 µH
16 ABB Control
1SBC 0064 99 R1002
Installation Studies
}
busbar/capacitor, per phase
(chart on page 11)
Ln = L 3 + L 4 + L 5 = 0.94 µH
If L m ≤ L 3 + L 4 + L 5 + … ⇒ No additional inductance L y
If L m > L 3 + L 4 + L 5 + … ⇒ Add an additional inductance L y L y = 3.2 µH – 0.94 µH = 2.26 µH
If you want to eliminate or reduce L y you can choose a contactor with a higher making capacity.
If you choose an UA75 contactor; the chart (page 13) gives L m = 0.85 µH Thus no additional inductances as 0.85 < 0.94 µH
The upstream inductance value L t + L 1 + L 2 = 35.2 µH makes the addition of additional inductances L x pointless.
ABB Control 17
1SBC 0064 99 R1002
Installation Studies
}
capacitor connection
per phase (chart on page 11)
L 1-1 L 1-2 L 1-n
Ln = L 3 + L 4 + L 5 = 1.17 µH
{
Type Smallest step: 20 kvar UA 26
(table on Step with intermediate power: 30 kvar ⇒ UA 50
page 5)
Most powerful step: 50 kvar ⇒ UA 75
18 ABB Control
1SBC 0064 99 R1002
Installation Studies
20 + 30 + 50
Fictitious number of steps: n1 = =5
20
Additional inductance L y 1 = L 1 – L n
L y 1 = 3 – 1.17 = 1.83 ⇒ Additional inductance of 1.83 µH
The inductances of the other connections must have as their minimum value the one satisfying the most restrictive of the 2 requirements below:
Q1
Requirement no. 1: Be at least inversly proportional to the powers of each capacitor step, i.e. Ln mini = L1 .
Qn
Requirement no. 2: Be compatible with the contactor used (chart on page 13).
20 + 30 + 50 20 + 30 + 50
Fictitious number of steps: n2 = #3 Fictitious number of steps: n3 = =2
30 50
Q1 20 Q1 20
Requirement no. 1: L2 min. = L1 =3x = 2 µH. Requirement no. 1: L3 min. = L1 =3x = 1,2 µH.
Q2 30 Q3 50
Requirement no. 2: Preselected UA 50 contactor (table on page 5) Requirement no. 2: Preselected UA 75 contactor (table on page 5)
Minimum inductance for 3 steps of 30 kvar (chart on page 13): 1.1 µH. Minimum inductance for 2 steps of 50 kvar (chart on page 13): 0.7 µH.
The most restrictive requirement is L2 min. = 2 µH. The most restrictive requirement is L3 min. = 1,2 µH.
Thus, an additional inductance is required The value of the connection inductance,1.17 µH, is very close to 1.2 µH,
L y 2 = 2 µH - 1,17 µH = 0,83 µH there is thus no point providing an additional inductance: Ly3 = 0
The upstream inductance value L t + L 1 + L 2 = 50 µH makes the addition of additional inductances L x pointless.
We could choose all contactors of the same size: the largest preselected rating (UA 75 in our example).
The result would be:
20 kvar step: n1 = 5 ⇒ Chart page 13: L1 min. = 0.8 µH ⇒ Ln = 1.17 µH is greater than L1 thus Ly1 = 0
Q1 20
Checking the other requirement: L2 min. = L1 = 0,8 = 0,53 µH
Q2 30
The most restrictive requirement is L2 min. = 0.8 µH ⇒ Ln = 1.17 µH is greater than L2 thus Ly2 = 0
Q1 20
Checking the other requirement: L2 min. = L1 = 0,8 = 0,32 µH
Q3 50
The most restrictive requirement is L2 min. = 0,78 µH ⇒ Ln = 1,17 µH is greater than L3 thus Ly3 = 0
ABB Control 19
1SBC 0064 99 R1002
Printed in France (X+Z 06.2001 R)
No: 1SBC 0064 99 R1002