Distance Relay Setting
Distance Relay Setting
The easiest way is to run all 6 (3 phases, 3 neutrals) or 4 (3 phases and neutral)
leads through a large window CT and connect it to a simple overcurrent relay. This is
not always very easy. You can also use individual CT's, wire all the secondaries in
parallel and in parallel with the overcurrent relay. It is very important the CT's are
matched exactly. Thus the percentage comes into play.
Percentage differential is the difference between the operating current and the
restraint current. Think of it this way, operating current (phase current) tries to close
the relay and the restraint current (neutral) tries to hold it open. If it closes, the
breaker trips. So a 10% differential relay setting says that the operating current
needs to be over 10% more than the restraint current.
This gets much more complicated when you have a zone that includes the generator
and the transformer
Or this one?
The procedure for calculating the actual relay operating time is as follows
<!--[if !supportLists]-->(i) <!--[endif]-->Convert the fault current into the relay coil
current by using the current transformer ratio.
Solution
Rated secondary current of CT = 5 A
Actual relay operating time = 3.5 x Time-setting = 3.5 x 0.6 = 2.1 seconds