H LV Switch Gear Functions and Selection
H LV Switch Gear Functions and Selection
2 3 4
Contents
The basic functions of LV switchgear
1.1 Electrical protection 1.2 Isolation 1.3 Switchgear control
H2
H2 H3 H4
The switchgear
2.1 Elementary switching devices 2.2 Combined switchgear elements
H5
H5 H9
Choice of switchgear
3.1 Tabulated functional capabilities 3.2 Switchgear selection
H0
H10 H10
Circuit-breaker
4.1 4.2 4.3 4.4 4.5 4.6 Standards and description Fundamental characteristics of a circuit-breaker Other characteristics of a circuit-breaker Selection of a circuit-breaker Coordination between circuit-breakers Discrimination MV/LV in a consumers substation
H
H11 H13 H15 H18 H H22 H28
EIG_chap_H-2010.indb 1
04/12/2009 17:51:09
The role of switchgear is: b Electrical protection b Safe isolation from live parts b Local or remote switching
National and international standards define the manner in which electric circuits of LV installations must be realized, and the capabilities and limitations of the various switching devices which are collectively referred to as switchgear. The main functions of switchgear are: b Electrical protection b Electrical isolation of sections of an installation b Local or remote switching These functions are summarized below in Figure H. Electrical protection at low voltage is (apart from fuses) normally incorporated in circuit-breakers, in the form of thermal-magnetic devices and/or residual-currentoperated tripping devices (less-commonly, residual voltage- operated devices - acceptable to, but not recommended by IEC). In addition to those functions shown in Figure H1, other functions, namely: b Over-voltage protection b Under-voltage protection are provided by specific devices (lightning and various other types of voltage-surge arrester, relays associated with contactors, remotely controlled circuit-breakers, and with combined circuit-breaker/isolators and so on)
H2
Isolation b Isolation clearly indicated by an authorized fail-proof mechanical indicator b A gap or interposed insulating barrier between the open contacts, clearly visible
Control b Functional switching b Emergency switching b Emergency stopping b Switching off for mechanical maintenance
Electrical protection assures: b Protection of circuit elements against the thermal and mechanical stresses of short-circuit currents b Protection of persons in the event of insulation failure b Protection of appliances and apparatus being supplied (e.g. motors, etc.)
EIG_chap_H-2010.indb 2
04/12/2009 17:51:09
A state of isolation clearly indicated by an approved fail-proof indicator, or the visible separation of contacts, are both deemed to satisfy the national standards of many countries
.2 Isolation
The aim of isolation is to separate a circuit or apparatus (such as a motor, etc.) from the remainder of a system which is energized, in order that personnel may carry out work on the isolated part in perfect safety. In principle, all circuits of an LV installation shall have means to be isolated. In practice, in order to maintain an optimum continuity of service, it is preferred to provide a means of isolation at the origin of each circuit. An isolating device must fulfil the following requirements: b All poles of a circuit, including the neutral (except where the neutral is a PEN conductor) must open(1) b It must be provided with a locking system in open position with a key (e.g. by means of a padlock) in order to avoid an unauthorized reclosure by inadvertence b It must comply with a recognized national or international standard (e.g. IEC 60947-3) concerning clearance between contacts, creepage distances, overvoltage withstand capability, etc.: Other requirements apply: v Verification that the contacts of the isolating device are, in fact, open. The verification may be: - Either visual, where the device is suitably designed to allow the contacts to be seen (some national standards impose this condition for an isolating device located at the origin of a LV installation supplied directly from a MV/LV transformer) - Or mechanical, by means of an indicator solidly welded to the operating shaft of the device. In this case the construction of the device must be such that, in the eventuality that the contacts become welded together in the closed position, the indicator cannot possibly indicate that it is in the open position v Leakage currents. With the isolating device open, leakage currents between the open contacts of each phase must not exceed: - 0.5 mA for a new device - 6.0 mA at the end of its useful life v Voltage-surge withstand capability, across open contacts. The isolating device, when open must withstand a 1.2/50 s impulse, having a peak value of 6, 8 or 12 kV according to its service voltage, as shown in Figure H2. The device must satisfy these conditions for altitudes up to 2,000 metres. Correction factors are given in IEC 60664-1 for altitudes greater than 2,000 metres. Consequently, if tests are carried out at sea level, the test values must be increased by 23% to take into account the effect of altitude. See standard IEC 60947.
H3
Impulse withstand peak voltage category (for 2,000 metres) (kV) III IV 4 6 6 8 8 12
Fig. H2 : Peak value of impulse voltage according to normal service voltage of test specimen. The degrees III and IV are degrees of pollution defined in IEC 60664-1
(1) the concurrent opening of all live conductors, while not always obligatory, is however, strongly recommended (for reasons of greater safety and facility of operation). The neutral contact opens after the phase contacts, and closes before them (IEC 60947-1).
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 3
04/12/2009 17:51:09
Switchgear-control functions allow system operating personnel to modify a loaded system at any moment, according to requirements, and include: b Functional control (routine switching, etc.) b Emergency switching b Maintenance operations on the power system
Functional control
This control relates to all switching operations in normal service conditions for energizing or de-energizing a part of a system or installation, or an individual piece of equipment, item of plant, etc. Switchgear intended for such duty must be installed at least: b At the origin of any installation b At the final load circuit or circuits (one switch may control several loads) Marking (of the circuits being controlled) must be clear and unambiguous. In order to provide the maximum flexibility and continuity of operation, particularly where the switching device also constitutes the protection (e.g. a circuit-breaker or switch-fuse) it is preferable to include a switch at each level of distribution, i.e. on each outgoing way of all distribution and subdistribution boards. The manuvre may be: b Either manual (by means of an operating lever on the switch) or b Electric, by push-button on the switch or at a remote location (load-shedding and reconnection, for example)
H4
These switches operate instantaneously (i.e. with no deliberate delay), and those that provide protection are invariably omni-polar(1). The main circuit-breaker for the entire installation, as well as any circuit-breakers used for change-over (from one source to another) must be omni-polar units.
(1) One break in each phase and (where appropriate) one break in the neutral. (2) Taking into account stalled motors. (3) In a TN schema the PEN conductor must never be opened, since it functions as a protective earthing wire as well as the system neutral conductor.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 4
04/12/2009 17:51:09
2 The switchgear
H5
Category AC-23 includes occasional switching of individual motors. The switching of capacitors or of tungsten filament lamps shall be subject to agreement between manufacturer and user. The utilization categories referred to in Figure H7 do not apply to an equipment normally used to start, accelerate and/or stop individual motors. Example A 100 A load-break switch of category AC-23 (inductive load) must be able: b To make a current of 10 In (= 1,000 A) at a power factor of 0.35 lagging b To break a current of 8 In (= 800 A) at a power factor of 0.45 lagging b To withstand short duration short-circuit currents when closed
Utilization category Frequent Infrequent operations operations AC-20A AC-20B AC-21A AC-22A AC-21B AC-22B
Typical applications
Cos
Connecting and disconnecting under no-load conditions Switching of resistive loads including moderate overloads Switching of mixed resistive and inductive loads, including moderate overloads Switching of motor loads or other highly inductive loads
0.95 0.65
AC-23A
AC-23B
(1) i.e. a LV disconnector is essentially a dead system switching device to be operated with no voltage on either side of it, particularly when closing, because of the possibility of an unsuspected short-circuit on the downstream side. Interlocking with an upstream switch or circuit-breaker is frequently used.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 5
04/12/2009 17:51:10
H6
Example: A 150 A contactor of category AC3 must have a minimum current-breaking capability of 8 In (= 1,200 A) and a minimum current-making rating of 10 In (= 1,500 A) at a power factor (lagging) of 0.35.
Discontactor()
A contactor equipped with a thermal-type relay for protection against overloading defines a discontactor. Discontactors are used extensively for remote push-button control of lighting circuits, etc., and may also be considered as an essential element in a motor controller, as noted in sub-clause 2.2. combined switchgear elements. The discontactor is not the equivalent of a circuit-breaker, since its short-circuit current breaking capability is limited to 8 or 10 In. For short-circuit protection therefore, it is necessary to include either fuses or a circuit-breaker in series with, and upstream of, the discontactor contacts.
Control circuit
Fig. H9 : Symbol for a contactor
Power circuit
Two classes of LV cartridge fuse are very widely used: b For domestic and similar installations type gG b For industrial installations type gG, gM or aM
Fuses exist with and without fuse-blown mechanical indicators. Fuses break a circuit by controlled melting of the fuse element when a current exceeds a given value for a corresponding period of time; the current/time relationship being presented in the form of a performance curve for each type of fuse. Standards define two classes of fuse: b Those intended for domestic installations, manufactured in the form of a cartridge for rated currents up to 100 A and designated type gG in IEC 60269-1 and 3 b Those for industrial use, with cartridge types designated gG (general use); and gM and aM (for motor-circuits) in IEC 60269-1 and 2
(1) This term is not defined in IEC publications but is commonly used in some countries.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 6
04/12/2009 17:51:10
2 The switchgear
The main differences between domestic and industrial fuses are the nominal voltage and current levels (which require much larger physical dimensions) and their fault-current breaking capabilities. Type gG fuse-links are often used for the protection of motor circuits, which is possible when their characteristics are capable of withstanding the motor-starting current without deterioration. A more recent development has been the adoption by the IEC of a fuse-type gM for motor protection, designed to cover starting, and short-circuit conditions. This type of fuse is more popular in some countries than in others, but at the present time the aM fuse in combination with a thermal overload relay is more-widely used. A gM fuse-link, which has a dual rating is characterized by two current values. The first value In denotes both the rated current of the fuse-link and the rated current of the fuseholder; the second value Ich denotes the time-current characteristic of the fuse-link as defined by the gates in Tables II, III and VI of IEC 60269-1. These two ratings are separated by a letter which defines the applications. For example: In M Ich denotes a fuse intended to be used for protection of motor circuits and having the characteristic G. The first value In corresponds to the maximum continuous current for the whole fuse and the second value Ich corresponds to the G characteristic of the fuse link. For further details see note at the end of sub-clause 2.1. An aM fuse-link is characterized by one current value In and time-current characteristic as shown in Figure H14 next page. Important: Some national standards use a gI (industrial) type fuse, similar in all main essentails to type gG fuses. Type gI fuses should never be used, however, in domestic and similar installations.
gM fuses require a separate overload relay, as described in the note at the end of sub-clause 2.1.
H7
1 hour
Fuse-blow curve
Inf I2
In y 4 A 4 < In < 16 A 16 < In y 63 A 63 < In y 160 A 160 < In y 400 A 400 < In
Fig. H13 : Zones of fusing and non-fusing for LV types gG and gM class fuses (IEC 60269-1 and 60269-2-1)
EIG_chap_H-2010.indb 7
04/12/2009 17:51:10
b The two examples given above for a 32 A fuse, together with the foregoing notes on standard test requirements, explain why these fuses have a poor performance in the low overload range b It is therefore necessary to install a cable larger in ampacity than that normally required for a circuit, in order to avoid the consequences of possible long term overloading (60% overload for up to one hour in the worst case) By way of comparison, a circuit-breaker of similar current rating: b Which passes 1.05 In must not trip in less than one hour; and b When passing 1.25 In it must trip in one hour, or less (25% overload for up to one hour in the worst case)
Class aM fuses protect against short-circuit currents only, and must always be associated with another device which protects against overload
Class aM (motor) fuses These fuses afford protection against short-circuit currents only and must necessarily be associated with other switchgear (such as discontactors or circuit-breakers) in order to ensure overload protection < 4 In. They are not therefore autonomous. Since aM fuses are not intended to protect against low values of overload current, no levels of conventional non-fusing and fusing currents are fixed. The characteristic curves for testing these fuses are given for values of fault current exceeding approximately 4 In (see Fig. H4), and fuses tested to IEC 60269 must give operating curves which fall within the shaded area. Note: the small arrowheads in the diagram indicate the current/time gate values for the different fuses to be tested (IEC 60269).
No short-circuit current-making rating is assigned to fuses. Reminder Short-circuit currents initially contain DC components, the magnitude and duration of which depend on the XL/R ratio of the fault current loop. Close to the source (MV/LV transformer) the relationship Ipeak / Irms (of AC component) immediately following the instant of fault, can be as high as 2.5 (standardized by IEC, and shown in Figure H6 next page).
4 In
x In
Fig. H14 : Standardized zones of fusing for type aM fuses (all current ratings)
At lower levels of distribution in an installation, as previously noted, XL is small compared with R and so for final circuits Ipeak / Irms ~ 1.41, a condition which corresponds with Figure H15. The peak-current-limitation effect occurs only when the prospective rms AC component of fault current attains a certain level. For example, in the Figure H16 graph, the 100 A fuse will begin to cut off the peak at a prospective fault current (rms) of 2 kA (a). The same fuse for a condition of 20 kA rms prospective current will limit the peak current to 10 kA (b). Without a current-limiting fuse the peak current could attain 50 kA (c) in this particular case. As already mentioned, at lower distribution levels in an installation, R greatly predominates XL, and fault levels are generally low. This means that the level of fault current may not attain values high enough to cause peak current limitation. On the other hand, the DC transients (in this case) have an insignificant effect on the magnitude of the current peak, as previously mentioned. Note: On gM fuse ratings A gM type fuse is essentially a gG fuse, the fusible element of which corresponds to the current value Ich (ch = characteristic) which may be, for example, 63 A. This is the IEC testing value, so that its time/ current characteristic is identical to that of a 63 A gG fuse. This value (63 A) is selected to withstand the high starting currents of a motor, the steady state operating current (In) of which may be in the 10-20 A range. This means that a physically smaller fuse barrel and metallic parts can be used, since the heat dissipation required in normal service is related to the lower figures (10-20 A). A standard gM fuse, suitable for this situation would be designated 32M63 (i.e. In M Ich). The first current rating In concerns the steady-load thermal performance of the fuselink, while the second current rating (Ich) relates to its (short-time) startingcurrent performance. It is evident that, although suitable for short-circuit protection,
I
Prospective fault-current peak rms value of the AC component of the prospective fault curent Current peak limited by the fuse 0.01 s 0.005 s t
Tf Ta Ttc
Schneider Electric - all rights reserved
0.02 s Tf: Fuse pre-arc fusing time Ta: Arcing time Ttc: Total fault-clearance time
Fig. H15 : Current limitation by a fuse
(1) For currents exceeding a certain level, depending on the fuse nominal current rating, as shown below in Figure H16.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 8
04/12/2009 17:51:11
2 The switchgear
Maximum possible current peak characteristic i.e. 2.5 Irms (IEC) (c) 160A Nominal 100A fuse 50A ratings Peak current cut-off characteristic curves 10 20 50 100
overload protection for the motor is not provided by the fuse, and so a separate thermal-type relay is always necessary when using gM fuses. The only advantage offered by gM fuses, therefore, when compared with aM fuses, are reduced physical dimensions and slightly lower cost.
(b)
Fig. H16 : Limited peak current versus prospective rms values of the AC component of fault current for LV fuses
H9
Fig. H18 : Symbol for a non-automatic fuse-switch Fig. H19 : Symbol for a non-automatic switch-fuse
The current range for these devices is limited to 100 A maximum at 400 V 3-phase, while their principal use is in domestic and similar installations. To avoid confusion between the first group (i.e. automatic tripping) and the second group, the term switch-fuse should be qualified by the adjectives automatic or non-automatic. Fuse disconnector + discontactor Fuse - switch-disconnector + discontactor As previously mentioned, a discontactor does not provide protection against shortcircuit faults. It is necessary, therefore, to add fuses (generally of type aM) to perform this function. The combination is used mainly for motor control circuits, where the disconnector or switch-disconnector allows safe operations such as: b The changing of fuse links (with the circuit isolated) b Work on the circuit downstream of the discontactor (risk of remote closure of the discontactor)
Schneider Electric - all rights reserved
The fuse-disconnector must be interlocked with the discontactor such that no opening or closing manuvre of the fuse disconnector is possible unless the discontactor is open ( Figure H20), since the fuse disconnector has no load-switching capability. A fuse-switch-disconnector (evidently) requires no interlocking (Figure H2). The switch must be of class AC22 or AC23 if the circuit supplies a motor. Circuit-breaker + contactor Circuit-breaker + discontactor These combinations are used in remotely controlled distribution systems in which the rate of switching is high, or for control and protection of a circuit supplying motors.
EIG_chap_H-2010.indb 9
04/12/2009 17:51:11
3 Choice of switchgear
Isolation Switchgear item Isolator (or disconnector)(4) Switch(5) Residual device (RCCB)(5) Switch- disconnector Contactor Remote control switch Fuse Circuit breaker Circuit-breaker disconnector(5) Residual and overcurrent circuit-breaker (RCBO)(5) Point of installation (general principle) b b b
Control Functional
Emergency switching
Electric shock
b b
b (1) b (1)
b b
b b b b
b b b b b b
b (1) (2) b (1) (2) b (1) (2) b (1) (2) b (1) (2)
b b b b b b b (3)
H0
b b b b
b b b b b
All points where, for operational reasons it may be necessary to stop the process
(1) Where cut-off of all active conductors is provided (2) It may be necessary to maintain supply to a braking system (3) If it is associated with a thermal relay (the combination is commonly referred to as a discontactor) (4) In certain countries a disconnector with visible contacts is mandatory at the origin of a LV installation supplied directly from a MV/LV transformer (5) Certain items of switchgear are suitable for isolation duties (e.g. RCCBs according to IEC 61008) without being explicitly marked as such Fig. H22 : Functions fulfilled by different items of switchgear
EIG_chap_H-2010.indb 10
04/12/2009 17:51:11
4 Circuit-breaker
The circuit-breaker/disconnector fulfills all of the basic switchgear functions, while, by means of accessories, numerous other possibilities exist
As shown in Figure H23 the circuit-breaker/ disconnector is the only item of switchgear capable of simultaneously satisfying all the basic functions necessary in an electrical installation. Moreover, it can, by means of auxiliary units, provide a wide range of other functions, for example: indication (on-off - tripped on fault); undervoltage tripping; remote control etc. These features make a circuit-breaker/ disconnector the basic unit of switchgear for any electrical installation.
Functional Emergency switching Switching-off for mechanical maintenance Overload Short-circuit Insulation fault Undervoltage
Possible conditions b b b (With the possibility of a tripping coil for remote control) b b b b (With differential-current relay) b (With undervoltage-trip coil) b Added or incorporated b (Generally optional with an electronic tripping device)
Protection
H
Fig. H23 : Functions performed by a circuit-breaker/disconnector
Industrial circuit-breakers must comply with IEC 60947-1 and 60947-2 or other equivalent standards. Domestic-type circuit-breakers must comply with IEC standard 60898, or an equivalent national standard
Description
Figure H24 shows schematically the main parts of a LV circuit-breaker and its four essential functions: b The circuit-breaking components, comprising the fixed and moving contacts and the arc-dividing chamber b The latching mechanism which becomes unlatched by the tripping device on detection of abnormal current conditions This mechanism is also linked to the operation handle of the breaker. b A trip-mechanism actuating device: v Either: a thermal-magnetic device, in which a thermally-operated bi-metal strip detects an overload condition, while an electromagnetic striker pin operates at current levels reached in short-circuit conditions, or v An electronic relay operated from current transformers, one of which is installed on each phase b A space allocated to the several types of terminal currently used for the main power circuit conductors Domestic circuit-breakers (see Fig. H25 next page) complying with IEC 60898 and similar national standards perform the basic functions of: b Isolation b Protection against overcurrent
EIG_chap_H-2010.indb 11
04/12/2009 17:51:12
Some models can be adapted to provide sensitive detection (30 mA) of earthleakage current with CB tripping, by the addition of a modular block, while other models (RCBOs, complying with IEC 61009 and CBRs complying with IEC 60947-2 Annex B) have this residual current feature incorporated as shown in Figure H26. Apart from the above-mentioned functions further features can be associated with the basic circuit-breaker by means of additional modules, as shown in Figure H27; notably remote control and indication (on-off-fault).
Fig. H25 : Domestic-type circuit-breaker providing overcurrent protection and circuit isolation features
O-OFF
-O O- FF
-O O- FF
H2
Moulded-case circuit-breakers complying with IEC 60947-2 are available from 100 to 630 A and provide a similar range of auxiliary functions to those described above (see Figure H28). Air circuit-breakers of large current ratings, complying with IEC 60947-2, are generally used in the main switch board and provide protector for currents from 630 A to 6300 A, typically.(see Figure H29). In addition to the protection functions, the Micrologic unit provides optimized functions such as measurement (including power quality functions), diagnosis, communication, control and monitoring.
Fig. H26 : Domestic-type circuit-breaker as above (Fig. H25) with incorparated protection against electric shocks
Fig. H28 : Example of a Compact NSX industrial type of circuitbreaker capable of numerous auxiliary functions
Fig. H29 : Example of air circuit-breakers. Masterpact provides many control features in its Micrologic tripping unit
EIG_chap_H-2010.indb 12
04/12/2009 17:51:12
4 Circuit-breaker
H3
Frame-size rating
A circuit-breaker which can be fitted with overcurrent tripping units of different current level-setting ranges, is assigned a rating which corresponds to the highest currentlevel-setting tripping unit that can be fitted. Example A Compact NSX630N circuit-breaker can be equipped with 11 electronic trip units from 150 A to 630 A. The size of the circuit-breaker is 630 A.
0.4 In
Rated current of the tripping unit In Adjustment range Overload trip current setting Ir Circuit breaker frame-size rating
160 A
360 A
400 A
630 A
Example (see Fig. H30) A NSX630N circuit-breaker equipped with a 400 A Micrologic 6.3E overcurrent trip relay, set at 0.9, will have a trip-current setting:
Fig. H30 : Example of a NSX630N circuit-breaker equipped with a Micrologic 6.3E trip unit adjusted to 0.9, to give Ir = 360 A
(1) Current-level setting values which refer to the currentoperated thermal and instantaneous magnetic tripping devices for over-load and short-circuit protection.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 13
04/12/2009 17:51:13
Type of protective relay Domestic breakers IEC 60898 Modular industrial(2) circuit-breakers Thermalmagnetic Thermalmagnetic Thermalmagnetic
Overload protection
Short-circuit protection
Ir = In
H4
Electronic
Fixed: Im = 7 to 10 In Adjustable: - Low setting : 2 to 5 In - Standard setting: 5 to 10 In Short-delay, adjustable 1.5 Ir y Im y 10 Ir Instantaneous (I) fixed I = 12 to 15 In
(1) 50 In in IEC 60898, which is considered to be unrealistically high by most European manufacturers (Merlin Gerin = 10 to 14 In). (2) For industrial use, IEC standards do not specify values. The above values are given only as being those in common use. Fig. H31 : Tripping-current ranges of overload and short-circuit protective devices for LV circuit-breakers
t (s )
t (s )
Ir
Im
Ii
Icu
I(A
Ir
Im
Icu
EIG_chap_H-2010.indb 14
04/12/2009 17:51:13
4 Circuit-breaker
Isolating feature
A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard (see sub-clause 1.2). In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol All Multi 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category.
The short-circuit current-breaking performance of a LV circuit-breaker is related (approximately) to the cos of the fault-current loop. Standard values for this relationship have been established in some standards
Icu (rated ultimate s.c. breaking capacity) and Ics (rated service s.c. breaking capacity) are defined in IEC 60947-2 together with a table relating Ics with Icu for different categories of utilization A (instantaneous tripping) and B (time-delayed tripping) as discussed in subclause 4.3.
Tests for proving the rated s.c. breaking capacities of CBs are governed by standards, and include: b Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit b Current and voltage phase displacement. When the current is in phase with the supply voltage (cos for the circuit = 1), interruption of the current is easier than that at any other power factor. Breaking a current at low lagging values of cos is considerably more difficult to achieve; a zero power-factor circuit being (theoretically) the most onerous case. In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers. Figure H34 below extracted from IEC 60947-2 relates standardized values of cos to industrial circuit-breakers according to their rated Icu. b Following an open - time delay - close/open sequence to test the Icu capacity of a CB, further tests are made to ensure that: v The dielectric withstand capability v The disconnection (isolation) performance and v The correct operation of the overload protection have not been impaired by the test.
H5
Icu
6 kA < Icu y 10 kA 10 kA < Icu y 20 kA 20 kA < Icu y 50 kA 50 kA < Icu
Fig. H34 : Icu related to power factor (cos ) of fault-current circuit (IEC 60947-2)
This is the value of voltage to which the dielectric tests voltage (generally greater than 2 Ui) and creepage distances are referred to. The maximum value of rated operational voltage must never exceed that of the rated insulation voltage, i.e. Ue y Ui.
EIG_chap_H-2010.indb 15
04/12/2009 17:51:13
Familiarity with the following characteristics of LV circuit-breakers is often necessary when making a final choice.
Generally, for industrial circuit-breakers, Uimp = 8 kV and for domestic types, Uimp = 6 kV.
Im
Fig. H35 : Category A circuit-breaker
I(A)
H6
t (s )
Icu
6 kA < Icu y 10 kA 10 kA < Icu y 20 kA 20 kA < Icu y 50 kA 50 kA y Icu
Fig. H37 : Relation between rated breaking capacity Icu and rated making capacity Icm at different power-factor values of short-circuit current, as standardized in IEC 60947-2
I(A ) Im
Fig. H36 : Category B circuit-breaker
Icw
Icu
Icu of 100 kA. The peak value of its rated making capacity Icm will be
100 x 2.2 = 220 kA.
In a correctly designed installation, a circuitbreaker is never required to operate at its maximum breaking current Icu. For this reason a new characteristic Ics has been introduced. It is expressed in IEC 60947-2 as a percentage of Icu (25, 50, 75, 100%)
(1) O represents an opening operation. CO represents a closing operation followed by an opening operation.
Schneider Electric - Electrical installation guide 2010
EIG_chap_H-2010.indb 16
04/12/2009 17:51:14
4 Circuit-breaker
Many designs of LV circuit-breakers feature a short-circuit current limitation capability, whereby the current is reduced and prevented from reaching its (otherwise) maximum peak value (see Fig. H38). The current-limitation performance of these CBs is presented in the form of graphs, typified by that shown in Figure H39, diagram (a)
Fault-current limitation
The fault-current limitation capacity of a CB concerns its ability, more or less effective, in preventing the passage of the maximum prospective fault-current, permitting only a limited amount of current to flow, as shown in Figure H38. The current-limitation performance is given by the CB manufacturer in the form of curves (see Fig. H39). b Diagram (a) shows the limited peak value of current plotted against the rms value of the AC component of the prospective fault current (prospective faultcurrent refers to the fault-current which would flow if the CB had no current-limiting capability) b Limitation of the current greatly reduces the thermal stresses (proportional I2t) and this is shown by the curve of diagram (b) of Figure H39, again, versus the rms value of the AC component of the prospective fault current. LV circuit-breakers for domestic and similar installations are classified in certain standards (notably European Standard EN 60 898). CBs belonging to one class (of current limiters) have standardized limiting I2t let-through characteristics defined by that class. In these cases, manufacturers do not normally provide characteristic performance curves.
a)
b)
22
H7
4,5.105 2.105
Current limitation reduces both thermal and electrodynamic stresses on all circuit elements through which the current passes, thereby prolonging the useful life of these elements. Furthermore, the limitation feature allows cascading techniques to be used (see 4.5) thereby significantly reducing design and installation costs
Icc
Prospectice fault-current
EIG_chap_H-2010.indb 17
04/12/2009 17:51:14
The choice of a range of circuit-breakers is determined by: the electrical characteristics of the installation, the environment, the loads and a need for remote control, together with the type of telecommunications system envisaged
Ambient temperature
Ambient temperature
The rated current of a circuit-breaker is defined for operation at a given ambient temperature, in general: b 30 C for domestic-type CBs b 40 C for industrial-type CBs Performance of these CBs in a different ambient temperature depends mainly on the technology of their tripping units (see Fig. H40).
H8
Circuit-breakers with uncompensated thermal tripping units have a trip current level that depends on the surrounding temperature
EIG_chap_H-2010.indb 18
04/12/2009 17:51:14
4 Circuit-breaker
C60a, C60H: curve C. C60N: curves B and C (reference temperature: 30 C) Rating (A) 20 C 25 C 30 C 35 C 40 C 45 C 50 C 55 C 1 1.05 1.02 1.00 0.98 0.95 0.93 0.90 0.88 2 2.08 2.04 2.00 1.96 1.92 1.88 1.84 1.80 3 3.18 3.09 3.00 2.91 2.82 2.70 2.61 2.49 4 4.24 4.12 4.00 3.88 3.76 3.64 3.52 3.36 6 6.24 6.12 6.00 5.88 5.76 5.64 5.52 5.40 10 10.6 10.3 10.0 9.70 9.30 9.00 8.60 8.20 16 16.8 16.5 16.0 15.5 15.2 14.7 14.2 13.8 20 21.0 20.6 20.0 19.4 19.0 18.4 17.8 17.4 25 26.2 25.7 25.0 24.2 23.7 23.0 22.2 21.5 32 33.5 32.9 32.0 31.4 30.4 29.8 28.4 28.2 40 42.0 41.2 40.0 38.8 38.0 36.8 35.6 34.4 50 52.5 51.5 50.0 48.5 47.4 45.5 44.0 42.5 63 66.2 64.9 63.0 61.1 58.0 56.7 54.2 51.7 Compact NSX00-250 N/H/L equippment with TM-D or TM-G trip units Rating Temperature (C) (A) 0 5 20 25 30 35 40 45 50 55 16 18.4 18.7 18 18 17 16.6 16 15.6 15.2 14.8 25 28.8 28 27.5 25 26.3 25.6 25 24.5 24 23.5 32 36.8 36 35.2 34.4 33.6 32.8 32 31.3 30.5 30 40 46 45 44 43 42 41 40 39 38 37 50 57.5 56 55 54 52.5 51 50 49 48 47 63 72 71 69 68 66 65 63 61.5 60 58 80 92 90 88 86 84 82 80 78 76 74 100 115 113 110 108 105 103 100 97.5 95 92.5 125 144 141 138 134 131 128 125 122 119 116 160 184 180 176 172 168 164 160 156 152 148 200 230 225 220 215 210 205 200 195 190 185 250 288 281 277 269 263 256 250 244 238 231
60 C 0.85 1.74 2.37 3.24 5.30 7.80 13.5 16.8 20.7 27.5 33.2 40.5 49.2
H9
Fig. H41 : Examples of tables for the determination of derating/uprating factors to apply to CBs with uncompensated thermal tripping units, according to temperature
Masterpact NW20 version H1/H2/H3 Withdrawable with horizontal plugs Withdrawable with on-edge plugs
40C
In (A)
Maximum adjustment Ir
2,000 1 2,000 1
L1
0.95 1,890
0.90 1,800
20
25
30
35
40
45
50
55
60
EIG_chap_H-2010.indb 19
04/12/2009 17:51:14
Type
Applications b Sources producing low short-circuitcurrent levels (standby generators) b Long lengths of line or cable
I
t
Standard setting type C b Protection of circuits: general case
I
t
High setting type D or K b Protection of circuits having high initial transient current levels (e.g. motors, transformers, resistive loads)
H20
t
I
12 In type MA b Protection of motors in association with discontactors (contactors with overload protection)
I
Fig. H43 : Different tripping units, instantaneous or short-time-delayed
The installation of a LV circuit-breaker requires that its short-circuit breaking capacity (or that of the CB together with an associated device) be equal to or exceeds the calculated prospective short-circuit current at its point of installation
The circuit-breaker at the output of the smallest transformer must have a short-circuit capacity adequate for a fault current which is higher than that through any of the other transformer LV circuit-breakers
Schneider Electric - all rights reserved
EIG_chap_H-2010.indb 20
04/12/2009 17:51:15
4 Circuit-breaker
Several transformers in parallel (see Fig. H45) b The circuit-breakers CBP outgoing from the LV distribution board must each be capable of breaking the total fault current from all transformers connected to the busbars, viz: Isc1 + Isc2 + Isc3 b The circuit-breakers CBM, each controlling the output of a transformer, must be capable of dealing with a maximum short-circuit current of (for example) Isc2 + Isc3 only, for a short-circuit located on the upstream side of CBM1. From these considerations, it will be seen that the circuit-breaker of the smallest transformer will be subjected to the highest level of fault current in these circumstances, while the circuit-breaker of the largest transformer will pass the lowest level of short-circuit current b The ratings of CBMs must be chosen according to the kVA ratings of the associated transformers Note: The essential conditions for the successful operation of 3-phase transformers in parallel may be summarized as follows: 1. the phase shift of the voltages, primary to secondary, must be the same in all units to be paralleled. 2. the open-circuit voltage ratios, primary to secondary, must be the same in all units. 3. the short-circuit impedance voltage (Zsc%) must be the same for all units. For example, a 750 kVA transformer with a Zsc = 6% will share the load correctly with a 1,000 kVA transformer having a Zsc of 6%, i.e. the transformers will be loaded automatically in proportion to their kVA ratings. For transformers having a ratio of kVA ratings exceeding 2, parallel operation is not recommended.
250 kVA 20 kV/400 V Compact NSX400N
Figure H46 indicates, for the most usual arrangement (2 or 3 transformers of equal kVA ratings) the maximum short-circuit currents to which main and principal CBs (CBM and CBP respectively, in Figure H45) are subjected. It is based on the following hypotheses: b The short-circuit 3-phase power on the MV side of the transformer is 500 MVA b The transformers are standard 20/0.4 kV distribution-type units rated as listed b The cables from each transformer to its LV circuit-breaker comprise 5 metres of single core conductors b Between each incoming-circuit CBM and each outgoing-circuit CBP there is 1 metre of busbar b The switchgear is installed in a floormounted enclosed switchboard, in an ambientair temperature of 30 C Moreover, this table shows selected circuit-breakers of M-G manufacture recommended for main and principal circuit-breakers in each case. Example (see Fig. H47 next page) b Circuit-breaker selection for CBM duty: For a 800 kVA transformer In = 1.126 A; Icu (minimum) = 38 kA (from Figure H46), the CBM indicated in the table is a Compact NS1250N (Icu = 50 kA) b Circuit-breaker selection for CBP duty: The s.c. breaking capacity (Icu) required for these circuit-breakers is given in the Figure H46 as 56 kA. A recommended choice for the three outgoing circuits 1, 2 and 3 would be currentlimiting circuit-breakers types NSX400 L, NSX250 L and NSX100 L. The Icu rating in each case = 150 kA.
H2
MV Tr3 LV CBM
Fig. H46 : Maximum values of short-circuit current to be interrupted by main and principal circuit-breakers (CBM and CBP respectively), for several transformers in parallel
EIG_chap_H-2010.indb 21
04/12/2009 17:51:15
Number and kVA ratings Minimum S.C breaking of 20/0.4 kV transformers capacity of main CBs (Icu) kA 2 x 400 14 3 x 400 28 2 x 630 22 3 x 630 44 2 x 800 19 3 x 800 38 2 x 1,000 23 3 x 1,000 47 2 x 1,250 29 3 x 1,250 59 2 x 1,600 38 3 x 1,600 75 2 x 2,000 47 3 x 2,000 94
Main circuit-breakers (CBM) total discrimination with out going circuit-breakers (CBP) NW08N1/NS800N NW08N1/NS800N NW10N1/NS1000N NW10N1/NS1000N NW12N1/NS1250N NW12N1/NS1250N NW16N1/NS1600N NW16N1/NS1600N NW20N1/NS2000N NW20N1/NS2000N NW25N1/NS2500N NW25N1/NS2500N NW32N1/NS3200N NW32N1/NS3200N
Rated current In of principal circuit-breaker (CPB) 250A NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250H NSX250L NSX250L NSX250L NSX250L NSX250L
These circuit-breakers provide the advantages of: v Absolute discrimination with the upstream (CBM) breakers v Exploitation of the cascading technique, with its associated savings for all downstream components
Short-circuit fault-current levels at any point in an installation may be obtained from tables
H22
CBP1 400 A
CBP2 100 A
CBP3 200 A
The technique of cascading uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation
EIG_chap_H-2010.indb 22
04/12/2009 17:51:15
4 Circuit-breaker
In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer
Conditions of implementation
Most national standards admit the cascading technique, on condition that the amount of energy let through by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage. In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, Figure H48 indicates the cascading possibilities of circuit-breaker types C60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.
Short-circuit breaking capacity of the upstream (limiter) CBs Possible short-circuit breaking capacity of the downstream CBs (benefiting from the cascading technique)
kA rms 150 70 50
150 70 36 30 30
25 20
NG125L NG125L NG125N NG125N C60N/H<=32A C60N/H<=32A C60N/H<=32A C60L<=25A C60L<=25A(*) C60L<=25A Quick PRD 40/20/8 C60H>=40A C60H>=40A C60H>=40A C120N/H C120N/H C120N/H C60N>=40A C60N>=40A C60N>=40A
H23
Advantages of cascading
The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned. The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated. The result is: b Simplified short-circuit current calculations b Simplification, i.e. a wider choice of downstream switchgear and appliances b The use of lighter-duty switchgear and appliances, with consequently lower cost b Economy of space requirements, since light-duty equipment have generally a smaller volume
Discrimination may be total or partial, and based on the principles of current levels, or time-delays, or a combination of both. A more recent development is based on the logic techniques. The Schneider Electric system takes advantages of both current-limitation and discrimination
B
Schneider Electric - all rights reserved 04/12/2009 17:51:16
Isc
0 Total discrimination
Ir B
0
Isc B
Isc
Ir B
Is
Isc B
Isc
Is = discrimination limit
Fig. H49 : Total and partial discrimination
EIG_chap_H-2010.indb 23
Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see Fig. H50). Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see Fig. H5). Protection against overload : discrimination based on current levels (see Fig. H52a) This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above. As a rule of thumb, discrimination is achieved when: b IrA/IrB > 2: Protection against low level short-circuit currents : discrimination based on stepped time delays (see Fig. H52b) This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source.
B A
In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit).
I
H24
Ir B
Ir A Isc B Im A
Discrimination based on a combination of the two previous methods (see Fig. H52c) A time-delay added to a current level scheme can improve the overall discrimination performance. The upstream CB has two high-speed magnetic tripping thresholds: b Im A: delayed magnetic trip or short-delay electronic trip b Ii: instantaneous strip Discrimination is total if Isc B < Ii (instantaneous). Protection against high level short-circuit currents: discrimination based on arc-energy levels This technology implemented in the Compact NSX range (current limiting circuitbreaker) is extremely effective for achievement of total discrimination.
Ir B
Ir A
Im A Is cB
A and B open
Is c A
Principle: When a very high level short-circuit current is detected by the two circuitsbreaker A and B, their contacts open simultaneously. As a result, the current is highly limited. b The very high arc-energy at level B induces the tripping of circuit-breaker B b Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5.
B only opens
a) t
b)
t
c) t
B A
Isc B
t
Ir B
Ir A
Isc B
Im A
delayed
Ii A
instantaneous
EIG_chap_H-2010.indb 24
04/12/2009 17:51:16
4 Circuit-breaker
Current-level discrimination
This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers.
D2
D1 D1
D2
The discrimination limit ls is: b Is = Isd2 if the thresholds lsd1 and lsd2 are too close or merge, b Is = Isd1 if the thresholds lsd1 and lsd2 are sufficiently far apart. As a rule, current discrimination is achieved when: b Ir1 / Ir2 < 2, b Isd1 / Isd2 > 2. The discrimination limit is: b Is = Isd1.
H25
Discrimination quality Discrimination is total if Is > Isc(D2), i.e. Isd1 > Isc(D2). This normally implies: b a relatively low level Isc(D2), b a large difference between the ratings of circuit-breakers D1 and D2. Current discrimination is normally used in final distribution. Discrimination based on time-delayed tripping uses CBs referred to as selective (in some countries). Implementation of these CBs is relatively simple and consists in delaying the instant of tripping of the several series-connected circuit-breakers in a stepped time sequence
Time discrimination
This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1.
D2 t
D1
D1
D2
EIG_chap_H-2010.indb 25
04/12/2009 17:51:17
The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination. The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1.
Discrimination quality There are two possible applications: b on final and/or intermediate feeders A category circuit-breakers can be used with time-delayed tripping of the upstream circuit-breaker. This allows extension of current discrimination up to the instantaneous threshold li1 of the upstream circuit-breaker: Is = li1. If Isc(D2) is not too high - case of a final feeder - total discrimination can be obtained. b on the incomers and feeders of the MSB At this level, as continuity of supply takes priority, the installation characteristics allow use of B category circuit-breakers designed for time-delayed tripping. These circuit-breakers have a high thermal withstand (Icw u 50% Icn for t = 1s): Is = Icw1. Even for high lsc(D2), time discrimination normally provides total discrimination: Icw1 > Icc(D2).
Note: Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses. Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary. Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units) "Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuitbreakers Multi9 further downstream (see Fig. H55).
H26
Compact NSX 100 A
Multi 9 C60
Only B opens
I Icc B Icc
Ir B
Fig. H55 : 4 level discrimination with Schneider Electric circuit breakers : Masterpact NT Compact NSX and Multi 9
EIG_chap_H-2010.indb 26
04/12/2009 17:51:17
4 Circuit-breaker
Discrimination schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires
H27
Principles
Activation of the Logic Discrimination function is via transmission of information on the pilot wire: b ZSI input:
D1 pilot wire
v low level (no downstream faults): the Protection function is on standby with a reduced time delay (y 0,1 s), v high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device.
D2
interlocking order
b ZSI output: v low level: the trip unit detects no faults and sends no orders, v high level: the trip unit detects a fault and sends an order.
D3
interlocking order
Operation
A pilot wire connects in cascading form the protection devices of an installation (see Fig. H56). When a fault occurs, each circuit-breaker upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuitbreaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.
EIG_chap_H-2010.indb 27
04/12/2009 17:51:17
4 Circuit-breaker
Discrimination quality This technique enables: b easy achievement as standard of discrimination on 3 levels or more, b elimination of important stresses on the installation, relating to timedelayed tripping of the protection device, in event of a fault directly on the upstream busbars. All the protection devices are thus virtually instantaneous, b easy achievement of downstream discrimination with non-controlled circuit-breakers.
The basic requirement is that a MV fuse will not operate for LV faults occurring downstream of the transformer LV circuit-breaker, so that the tripping characteristic curve of the latter must be to the left of that of the MV fuse pre-arcing curve. This requirement generally fixes the maximum settings for the LV circuit-breaker protection: b Maximum short-circuit current-level setting of the magnetic tripping element b Maximum time-delay allowable for the short-circuit current tripping element (see Fig. H57) Example: b Short-circuit level at MV terminals of transformer: 250 MVA b Transformer MV/LV: 1,250 kVA 20/0.4 kV b MV fuses: 63 A b Cabling, transformer - LV circuit-breaker: 10 metres single-core cables b LV circuit-breaker: Compact NSX 2000 set at 1,800 A (Ir) What is the maximum short-circuit trip current setting and its maximum time delay allowable? The curves of Figure H58 show that discrimination is assured if the short-time delay tripping unit of the CB is set at: b A level y 6 Ir = 10.8 kA b A time-delay setting of step 1 or 2
H28
t (s)
NS 2000 set at 1,800 A Minimum pre-arcing curve for 63 A HV fuses (current referred to the secondary side of the transformer)
1 4 6 8 Step 4 Step 3 Step 2 Step 1
10
1,800 A Ir
10 kA
Isc maxi
31.4 kA
EIG_chap_H-2010.indb 28
04/12/2009 17:51:17