This document provides instructions for installing and setting an EOCR-E Series electronic over current relay that can use external current transformers. It describes the external CT option, available current ratings, mounting options for rack, flush window and terminal types, and settings for configuring the CT ratio. Diagrams show examples of units with external CTs installed. Settings include selecting the CT ratio that matches the primary current rating of the external CT, with limitations on ratios over 75:5 and setting values over 6 amps.

Uploaded by

Naveen Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views

External CT Usage-EOCR

This document provides instructions for installing and setting an EOCR-E Series electronic over current relay that can use external current transformers. It describes the external CT option, available current ratings, mounting options for rack, flush window and terminal types, and settings for configuring the CT ratio. Diagrams show examples of units with external CTs installed. Settings include selecting the CT ratio that matches the primary current rating of the external CT, with limitations on ratios over 75:5 and setting values over 6 amps.

Uploaded by

Naveen Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

Instruction : External Product Name: EOCR-E Series

Current Transformer
Installation of Ext CT Electronic Over Current Relay
Multi-function digital Relay

 External CT Option
The current higher than 60Amps can be applied with the External CT Option.
The Ext CTs should be selected in 5A of the secondary current rating of a External CT .

 Rating Current

Reference Current Setting Range(A) Current Ratio of Ext. CT

H1 10 ~ 120 100 : 5
HH 15 ~ 180 150 : 5
H2 20 ~ 240 200 : 5
H3 30 ~ 360 300 : 5
H4 40 ~ 480 400 : 5
▼ ▼ ▼

 Figures

Rack mounting type

- This model is provided with assembled one in


the factory.
- with 3 CT.

- This model is provided with assembled one in


the factory.
- with 3 SR-CT

SWP-040-02, Form 13, rev. 0, 1999.5.17


Instruction : External Product Name: EOCR-E Series
Current Transformer
Installation of Ext CT Electronic Over Current Relay
Multi-function digital Relay

Flush mounting window type

- This model is provided with assembled one in


the factory.

- D–Sub connector is assembled.

Flush mounting terminal type

- This picture shows an example of the


assembled EOCR with a External CT.

- This picture shows an example of the


assembled EOCR with a External CT.
This terminal type without terminals can
be provided by a special order.

SWP-040-02, Form 13, rev. 0, 1999.5.17


Instruction : External Product Name: EOCR-E Series
Current Transformer
Installation of Ext CT Electronic Over Current Relay
Multi-function digital Relay

 Setting

- CT ratio should be set in a primary current rating of the External CT.


- It’s not possible to set the CT ratio in case “oc” setting value is over 6.0A .
- It’s not possible to adjust or change the value during operation.
- In case CT ratio is over 75:5, the indication on the screen shows c100, c200...c400..c800.

- Setting mode.

- Setting value.
Off(--), 5t, 2t, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 120, 150, 200, 250, 300, 400, 500,
600, 750, 800.