How many DALI ECGs can be controlled individually in OSRAM DALI PROFESSIONAL?
DALI PROFESSIONAL provides in total 256 DALI ECG addresses divided into 4 DALI lines. To control these individually you need 256 buttons or 64 pushbutton couplers which exceeds the maximum DALI current. With this you can only control 220 ECGs individually. To achieve a full individual control of all 256 ECGs, we recommend to use 22 Glasstouches (12 buttons each) combined with the according e:bus gateways / power supplies.
Page 2 of 11
For what reason we recommend to use 230V buttons / switches for OSRAM DALI Pushbutton Coupler input contacts?
There is no technical reason for that, also a 12 V bell button would work, but there are regulations. DALI wiring needs only basic insulation, therefore it has to be handled like mains voltage. The wallbox geometry of the pushbutton coupler does not allow to design the necessary safety distances. For this reason also the connected buttons have to be handled like mains voltage devices.
How can I integrate a remote control into OSRAM DALI PROFESSIONAL system?
Use the OSRAM TOUCH DIM RC device as receiver and connect the output contacts to a OSRAM DALI Pushbutton Coupler. The RF signal can be generated from any Enocean button signal source. One OSRAM TOUCH DIM RC can handle two Enocean channels.
Page 3 of 11
DALI PROFESSIONAL Controller CONT-4 incl. all DALI supplied couplers consumes 10..25 W depending on the usage. The controller shows no real standby status because there are many processes in the background even if all ECGs are switched off by DALI.
230V AC
B) Software Solution in DALIpro GUI Put all switches into one function and define 'switch linkage' = parallel in Properties / General.
Can OSRAM DALI SWITCH SO be used with other systems than DALI PROFESSIONAL?
OSRAM DALI SWITCH SO is not only made for use in DALI PROFESSIONAL. It is working similar to an ECG, means if a DALI controller sends a DALI command with dimmlevel > 1 all 3 relais switch ON, with dimmlevel = 0 they switch OFF.
Usually a PC / notebook provides type A socket (rectangular connector, see left side of picture). The DALI controller USB input is type B (square connector, see right side of picture).
Page 4 of 11
Do I need always a pushbutton controller to create a light regulation? If you start and stop the regulation with the PIR you need no pushbutton coupler. Here a configuration example where
the light is on during occupancy and switches off after 20 minutes with non-occupancy :
For practical reasons it is always an advantage if there are some additional pushbuttons to have a chance for manual control e.g. if PIR sensor gets defect / dirty / shielded ...
Page 5 of 11
Check DALI line connection press once -> LED ON press again -> LED OFF DALI wire 1 here or here DALI wire 2 here or here
DALI wire 1 here or here DALI wire 2 here or here internal shortcut for throughwiring option max. 5 m cable to Sensor LED Check DALI line connection press once -> LED ON press again -> LED OFF
Page 6 of 11
Page 7 of 11
Mounting of Sensor LS/PD outside of Luminaire Ceiling Integration LS/PD MULTI3 CI EAN 4008321916648
EAN 4008321916662
Page 8 of 11
Plug&Play mode Toggle function for each button to all ECGs in the same DALI line (ON/OFF/DIM; TouchDIM functionality)
Automatic occupancy detection with PIR of LS/PD Sensor / Sensorcoupler Switches On all ECGs in the same DALI line 5 minute off-delay when no more occupancy detected
5 minutes
ZPE 2771864 000 00 EN Page 9 of 11
Real Time Clock Applications : Install external timer (clock) + pushbutton coupler to get time synchronized sequences started
DLINK DAP-1160
Wireless G Open Source Repeater Gateway LAN -> WLAN
Page 10 of 11
DALI Professional System features with DALIpro Software Limits, maximum values per DALI PROFESSIONAL Controller CONT-4 4x maximum 64 ECG addresses 4x maximum 64 input device addresses (sensors / pushbuttons) Current limitation 200 mA per DALI port -> total limit of number of ECGs + input devices depending on mix 4x max. 300 m DALI line length, wires 1.5 mm2 max. 5 m Sensor to Sensorcoupler max. 5 m Lightsensor distance to measurement area (depending on reflection characteristic) max. 2 m Pushbutton to Pushbutton Coupler 4x 16+ Groups, line overlapping allowed '+' means additional 'virtual' groups possible by software, but uses addressed commands Maximum number of groups only limited by controller memory 4x 16 Scenes, line overlapping allowed, but then one scene used for each line 4x 8 active light regulation loops more possible when noticeable delay accepted, limited by reaction times 4x switch-over relais maximum 5 A ohmic load each System Features out-of-the-box plug & play functionality if no configuration loaded full- and semi-automatic energy saver function with occupancy- and light-sensor up to 10 lightsensors / sensorcouplers per regulation corridor function with unlimited steps PIR disable / enable function sequences consisting of scenes, fade control, loops scene stepping visible ressource status message switch function e.g. for Highbay Sensor integration serial / parallel configuration of grouped switches programmable internal relay to be used in action list testfunction for all DALI devices configuration check against physical available devices simple 'failed ECG' replacement retrieve configuration by download from controller full project documentation in HTML file Perfect for industry hall warehouse classrooms single office large office meeting room corridor