Mikro Din300
Mikro Din300
Features
25 selectable sensitivity settings: 30 mA to 30 A 9 selectable time delays: 0ms to 3s Earth leakage level indicators Detection of no connection to ZCT Relay tripped indicator Trip starting indicator Protected against nuisance tripping
S1 S2
TRIP CONTACT
SHUNT TRIP
10
11
12
13
NO
14
NC
LOAD
COM
REMOTE RESET
REMOTE TEST
AUX
S1 S2
L1 L2 L3 N
DIN300E
TRIP CONTACT
SHUNT TRIP
9
COM
10
NO
11
12
13
NO
14
NC
LOAD
NC COM
DIN300 / 300E
DIN300
L1 L2 L3 N
Technical Data
AUXILIARY SUPPLY
Model DIN300 / 300E -240A Model DIN300 / 300E -110A Rated frequency VA rating : : : : 198 ~ 265 V AC 94 ~ 127 V AC 50 / 60 Hz 3 VA typical
CASE DIMENSIONS
71mm
20mm
45mm
SETTINGS RANGES
Sensitivity setting : 30 mA, 50 mA, 75 mA, 100 mA, 125 mA, 150 mA, 200 mA, 250 mA, 300 mA, 500 mA, 750 mA, 1A, 1.25A, 1.5A, 2A, 2.5A, 3A, 5A, 7.5A, 10A, 12.5 A, 15A, 20A, 25A, 30A. : Instantaneous, 50 ms, 100 ms, 150 ms, 250 ms, 350 ms, 500 ms, 1s, 3 s.
20mm
Front view
PERFORMANCE
Setting accuracy Timing accuracy : -15% to +0% : 5%
71mm
CONTACTS
Contacts ( Trip / 50% pre-fault* ) Contact arrangement : Contact rating : Contact material : Expected electrical life : Expected mechanical life : Change over 5 A, 250 V AC ( cos = 1 ) Silver alloy 100,000 operations at rated current 5 x 106 operations
Side view
85mm
30mm
20mm 20mm
INPUTS
Remote test* / Reset inputs* : N.O. dry contacts
Ordering Information
MODEL DESCRIPTION
For 50 / 60 Hz system, auxiliary voltage 240 V AC For 50 / 60 Hz system, auxiliary voltage 110 V AC For 50 / 60 Hz system, auxiliary voltage 240 V AC For 50 / 60 Hz system, auxiliary voltage 110 V AC DIN300 - 240 A DIN300 - 110 A DIN300E - 240 A
DIN300 / 300E
INDICATORS
Auxiliary supply Time delay Trip Leakage current* : : : : Green indicator Red indicator Red indicator 5 red indicators for leakage levels
MECHANICAL
Mounting method Approximate weight : Din rail mounted : 0.3 kg
DIN300E - 110 A
ENVIRONMENTAL CONDITIONS
Temperature Humidity
* Applicable to DIN300E model only