Guide To Forms of Separation Final
Guide To Forms of Separation Final
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
July 2011
Contents
Preface Introduction Useful definitions What are forms of separation Fundamental objectives of separation Legal obligations Basics of separation Main considerations Detailed selection Decision tree Other considerations Illustrations Frequently asked questions 4 5 5 7 7 8 9 9 10 13 14 16 30
Acknowledgements BEAMA would like to thank IEC and BSI for allowing references to their standards; Health and Safety Executive (HSE) for reference to their documents.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Introduction
For specifiers, one of the most significant choices they face when specifying a low-voltage assembly, is the form of separation. Selection of an inappropriate form of separation will at the very least cause disappointment. As a consequence the assembly may either be much more expensive than necessary or it may be unsuitable for the application.
Useful Definitions
The Standard includes definitions relating to Assemblies.Those particularly relevant to the forms of separation of Assemblies include the following.
Assembly
Power switchgear and controlgear assembly (PSC-ASSEMBLY) Low-voltage switchgear and controlgear ASSEMBLY used to distribute and control energy for all types of loads, intended for industrial, commercial and similar applications where operation by ordinary persons is not intended. This includes floor standing or wall mounting distribution switchboards, panel boards, and motor control centres using electromechanical and/or electronic components. It does however specifically exclude individual devices and self-contained components which control a single circuit i.e. wall mounted starters and fuse switches.
Functional Unit
Part of an ASSEMBLY comprising all the electrical and mechanical elements including switching devices that contribute to the fulfilment of the same function. NOTE Conductors which are connected to a functional unit but which are external to its compartment or enclosed protected space (e.g. auxiliary cables connected to a common compartment) are not considered to form part of the functional unit Comprises all parts necessary to form a complete incoming or outgoing circuit. It includes the load current carrying device(s) and associated equipment, cable terminals, and control devices within the assembly, that are necessary to form the complete circuit. It excludes the connections from the unit to the busbars (busbar connections) and any insulation or shrouding with which they may be provided. It may consist of more than one compartment or enclosed protected space.
Section
Constructional unit of an ASSEMBLY between two successive vertical delineations. Usually considered to be a single full height column containing one or more functional units. One or more columns are required to complete an assembly.
Sub-Section
Constructional unit of an ASSEMBLY between two successive horizontal or vertical delineations within a section. The area or space within a column identified and bounded by two adjacent and horizontal constructional members e.g. cross members or shelves.
Compartment
Section or sub-section enclosed except for openings necessary for interconnection, control or ventilation
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
[Return to FAQs]
Enclosure
Housing affording the type and degree of protection suitable for the intended application. Provides protection for equipment against certain external influences from any accessible direction and against direct contact to a degree of protection of at least IP2X.
Partition
Part of the enclosure of a compartment separating it from other compartments. A component used to form the top, bottom, sides, front or back of a compartment or enclosure and which can be manufactured from metal or an appropriate synthetic material. A devices integral housing may also satisfy this requirement.
Barrier
Part providing protection against direct contact from any usual direction of access. Used to achieve a form of separation, it must meet the requirement of at least IP2X. It can also take the form of insulating material in direct contact with the live part, e.g. heat shrink sleeving on a busbar. Alternatively it can be rigid insulation, e.g. terminal shields or an earthed metal screen appropriately positioned relative to the live part(s).
Duty Holder
The term used within the Electricity At Work Regulations to refer to the person appointed to be responsible for the electrical equipment, systems and conductors and any work or activities being carried out on or near the electrical equipment.The Duty Holder must be competent and may be the employer, an employee, or a self-employed person.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
NOTE The degree of protection IP2X covers the degree of protection IPXXB.
These are much less precise requirements than normally expected in a standard.The forms of separation given are only typical and the means by which separation is achieved is subject to agreement between the user and the manufacturer. More fundamentally, no indication is given as to the objectives of separating an assembly. The benefits a particular form of separation may bring are not defined, conversely, nor are the disadvantages if an inappropriate selection is made.
Verification of separation is by application of the appropriate IP test to BS EN 60529 (IPXXB and/or IP2X).
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
[Return to FAQs]
Legal Obligations
As most National Standards, including the BS EN 61439 series, are derived from International Standards, they reflect good practice but they do not fully encompass the requirements of local legislation. Indeed, the standards may not be legally binding. In the United Kingdom legal obligations take precedence over standards. For low-voltage assemblies the Low Voltage Directive (LVD) and the Electricity at Work Act are relevant and in particular, Regulation 14 of the latter must be respected.
The Law
Regulation 14
No person shall be engaged in any work activity on or near any live conductor (other than one suitably covered with insulating material so as to prevent danger) that danger may arise unless:(a) it is unreasonable in all the circumstances for it to be dead; and (b) it is reasonable in all the circumstances for him to be at work on or near it while it is live; and (c) suitable precautions (including where necessary the provision of suitable protective equipment) are taken to prevent injury
Clearly this regulation is pertinent and onerous when contemplating working within a partially energised assembly. There is no allowance for tolerable risk. If an assembly can reasonably be isolated prior to any covers being removed, it must be isolated. Where it is impractical to totally isolate an assembly prior to carrying out work within an assembly, the degree of separation, and the way in which the separation is achieved within the assembly should be considered in a risk assessment to be undertaken by the Duty Holder (see definitions).This risk assessment will consider all relevant factors including: (i) (ii) (iii) (iv) Work to be carried out, Mechanical protection afforded by any insulation and separation, Possibility of initiating a flashover, Likelihood of an electric shock.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Basics of Separation
Specifying the most appropriate form of separation for an assembly is not an easy matter. In specifying a form of separation the following should be considered: The consequences of isolating the assembly or part of, Nature of task to be performed, Competence of person undertaking work whilst the remainder of the assembly is energised.
[Return to FAQs]
Users and specifiers of assemblies are encouraged to consider in detail the application and then to follow the process outlined in the main considerations section, in order to determine the most appropriate form of separation required.
Main considerations
BS EN 61439-2 identifies four main categories of separation; Forms 1, 2, 3 and 4. As a first step users should consider what operations they need to carry out without fully isolating the assembly.Then using a process generally as outlined in the chart below, identify the main category of separation they require for their application.
Application Needs
Isolation available for all internal operations (except changing fuse links)
Adjust setting and carry out limited maintenance in functional units, as applicable whilst adjacent circuits are live.
Connect and disconnect cables. Adjust setting and carry out limited maintenance in functional units, as applicable whilst adjacent circuits are live.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Having established the fundamental form for separation needed for an application, specific details must be considered. The IEC and EN versions of 61439-2 divide Forms 2, 3 and 4 into two sub categories. However, within the requirements defined in the standards there are three fundamental ways of providing separation: Insulation of live parts, Partitions or barriers (metallic or non-metallic), Integral housing of a device.
Each has different attributes; clearly much depends on the agreement between user and manufacturer. In order to aid the agreement between user and manufacturer, BS EN 61439-2 includes a National Annex which further details the sub categories by type of construction such as describing the location of terminals for external conductors and in some instances, the location of cable glands relative to the associated cable terminals. In making the appropriate choice the user needs to consider: The tasks to be carried out with the assembly partially energised adjusting relay setting, terminating large power cables, replacing components, etc. What tools may be used. Is there a risk of tools slipping and damaging insulation. Possibility of mechanical impact causing damage to the integrity of the separation. Is there a danger of small components falling from one compartment to another causing a hazard. Can temporary barriers be effectively used to supplement the protection provided by separation whilst work is being carried out. The additional safety that can be provided by the use of Personal Protective Equipment. The anticipated level of skill of those carrying out any work within the assembly.
Detailed selection
Using the considerations listed above and any other relevant application specific needs the user should then refine their separation needs and select the appropriate sub category of the basic form selected.
Forms 1 and 2
Form 2b
Type 1
Busbar separation is achieved by insulated covering, e.g. sleeving, wrapping or coatings. Busbar separation is by metallic or non-metallic rigid barriers or partitions.
Type 2
10
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
With Form 1 all components including busbars and cable termination can, and usually are, in the same compartment. In order to safely work within the assembly it must be isolated upstream. Form 2 has the busbars separated from the functional units and, depending on whether 2a or 2b is selected the cable terminals may be separated from the busbars. However, as functional units are not separated from each other, Form 2 has little practical advantage over Form 1. In reality a Form 2 assembly without any additional barriers or screens must be isolated prior to the interior of the assembly being accessed.
Form 3
Form 3b
Type 1
Busbar separation is achieved by insulated covering, e.g. sleeving, wrapping or coatings. Busbar separation is by metallic or non-metallic rigid barriers or partitions.
Type 2
Form 3 may permit work to be carried out within the functional unit, for example; routine maintenance, fault finding, replacement of fuse links. In selecting the constructional type the specifier must, bearing in mind there is no requirement for the terminals of one circuit to be separated from adjacent circuits, determine if there is benefit to be gained from separating the busbars from cable terminals. If there is advantage in having the busbars separated, the means of separation, sleeving or similar or rigid barriers must be determined based on the likely mechanical needs of the separation.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
11
Form 4
Type 2
Type 3
Terminals for external conductors not in the same compartment as the associated functional unit, but in individual, separate, enclosed protected spaces or compartments.
Form 4b
Type 4
Type 5
Type 6
Type 7
Form 4 provides many variants which offer different opportunities in use. Selecting the most appropriate needs a very detailed understanding of the application and a logical thought process to arrive at the most suitable solution.The following flow chart may assist in this exercise.
12
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
[Return to FAQs]
Form 4
No
Is there a need for clear demarcation between the functional unit and the associated cable terminals
Yes
Yes Type 1
Light physical work only to be undertaken in the functional unit and cabling areas, e.g. adjustment of settings, fault finding, replacement of fuse links. The termination of power cables without isolation of the assembly or the use of supplementary protection is not required.
Yes
?
No
Type 4
No
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. The termination of power cables without isolation of the assembly or the use of supplementary protection is not required.
Yes
?
No
Type 5
Yes Type 2
?
No Yes
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. Cables may need to be terminated adjacent to live cable cores insulation on the cable core is considered to provide adequate mechanical protection.
Yes
?
No
Type 6
Type 3
Work may need to be carried out within the functional unit, e.g. routine maintenance, fault finding, replacement of fuse links. Heavy cables may need to be terminated adjacent to live cables added mechanical protection of cable armour up to cable box/area considered necessary. Supplementary protection is not required.
Yes
Type 7
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
13
[Return to FAQs]
Other considerations
In applications where an extremely high continuity of supply is required there may be an advantage in being able to replace or add a functional unit while the busbars and adjacent circuits remain energised and in service. For these applications an assembly with withdrawable or removable functional units should be specified. The level of protection provided to operators while the functional unit is being removed and when it is removed needs to be agreed with the manufacturer. BS EN 61439-2 is not definitive in what separation will offer or how it will be achieved. Much is left to agreement between the user and manufacturer.This is intentional as it allows manufacturers to use their initiative, whilst meeting the basic requirements set out in the standard. It also enables the most appropriate assembly to be provided for the particular application, but in so doing, it does make selecting the right assembly all the more difficult. In addition to the process outlined above the following should be taken into account before reaching a final decision on the form of separation to be specified for a particular application.
4. Size
As a general rule the higher the degree of separation then the larger the assembly. Barriers and partitions take up space and may restrict air flow necessitating the use of larger components to achieve the required rating of a circuit within the assembly.Almost certainly a Form 4 Type 3 or 7 specification will increase the size of the assembly compared with a lower form of separation.
14
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
[Return to FAQs]
6. Neutral
The risks associated with neutral conductors in a present day distribution system have prompted much debate and at times have led to a more cautious approach than is necessary. BS 7671 (UK wiring regulations) prescribes that except for a main switch intended for operation by ordinary persons, in a TN-S or TN-C-S system the neutral conductor need not be isolated or switched where it can be regarded as being reliably connected to earth by a suitably low impedance. The neutral conductor of a circuit may remain connected when the line conductor(s) of that circuit are isolated. This could be a hazard because a voltage difference between a neutral and earth can be present. Prior to undertaking work on the circuit it must be ascertained if the capacity to deliver a harmful electric shock exists. In a TN-S or TN-C-S system, a harmful touch voltage due to load current in the neutral is unlikely, where the circuit conductors have been sized to comply with the voltage drop constraints in Table 12A of BS 7671. Nevertheless, a competent person must complete a risk assessment and appropriate test(s) to confirm that, the exposed neutral connection within the assembly is not a hazardous live part. In particular,The (UK) Electricity at Work Regulations 1989 including any amendments must be complied with.
8. Cost
Higher forms of separation, generally lead to larger and structurally more complex assemblies and therefore higher costs. For the most cost effective solution the lowest level of separation that meets the needs of the application should be specified.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
15
Introduction to Illustrations
The illustrations which follow are interpretations for the various types of construction used to achieve satisfactory forms of separation in accordance with BS EN 61439-2. Specifiers and users should be aware that the different methods that manufacturers use to achieve various forms of separation can often result in two products which both bear the same overall form type but can be physically and financially different. The illustrations are in no way intended to be considered as prescriptive. Although many assemblies are custom built and by nature unique the illustrations represent a general indication of typical product offerings of BEAMA member companies. BS EN 61439-2 also includes panel boards within its scope. This has been reflected in production of these illustrations. All of the following illustrations exclude the external enclosure.
16
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Notes: Forms of Separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device
All diagrams from figures AA 1, 2, & 3 from Annex AA Text from UK National Annex Both from BS EN 61439-2
Form 1
Form 1
Form 2
Form 2a
Form 3
Form 3a
Form 4
Form 4a Type 1
Form 2b Type 1
Form 3b Type 1
Form 2b Type 2
Form 3b Type 2
Form 4b Type 4
Form 2: Functional unit separate from the busbars The a designation denotes terminals are not separate from the busbar The b designation denotes terminals are separate from the busbar Type 1 utilises insulated coverings for busbar separation Type 2 utilises insulated partitions and barriers for busbar separation.
Form 3: As Form 2 plus: Functional units separate from other functional units The a designation denotes terminals are not separate from the busbar The b designation denotes terminals for external conductors are in a separate compartment to the functional unit Type 1 utilises insulated coverings for busbar separation Type 2 utilises insulated partitions and barriers for busbar separation.
Form 4: As Form 3 plus: Terminals for external conductors separate each other The a designation denotes terminals within the functional unit The b designation denotes terminals for external conductors are in a separate compartment to the functional unit Types 1 & 4 utilises insulated coverings for busbar separation Types 2, 3, 5, 6 & 7 utilise partitions and barriers for busbar separation Types 3 & 7 feature integral glanding Type 5 utilises insulated coverings for terminals for external conductors.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
17
Form 1
Form 1 assemblies are closed so as to provide protection against contact with internal live parts, or compartments, but where no internal separation is provided for functional units or terminals. Form 1 requires that; (i) Busbars are not separated from functional units (ii) Busbars are not separated from any incoming or outgoing termination (iii) Functional units are not separated from other functional units (iv) Functional units are not separated from any incoming or outgoing termination.
Form 2a
All Form 2 assemblies are enclosed so as to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units. Form 2a requires that; (i) Busbars are separated from functional units (ii) Busbars are not separated from any incoming or outgoing termination (iii) Functional units are not separated from other functional units (iv) Functional units are separated from any incoming or outgoing termination (v) Terminals are not separate from each other.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The a designation denotes terminals for external conductors are not separate from the busbars. The above illustration uses the Integral Housing of the Device as a means of separation.
18
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Form 2b Type 1
All Form 2 assemblies are enclosed so as to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units. Form 2b Type 1 requires that; (i) Busbars are separated from functional units
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral terminations see Other Considerations item 6. The b designation denotes terminals are separate from the busbars. The Type 1 designation denotes busbar separation is achieved by insulated coverings sleeving, wrapping or coating. The above illustration uses the Integral Housing of the Device as a means of separation. Cable terminations are integral to the device.
Form 2b Type 2
All Form 2 assemblies are enclosed to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units. Form 2b Type 2 requires that; (i) Busbars are separated from functional units.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral terminations see Other Considerations item 6. The b designation denotes terminals are separate from the busbars. The Type 2 designation denotes busbar separation by partitions and barriers.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
19
Form 3a
All Form 3 assemblies are enclosed so as to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units and separation of the functional units from each other. Terminals are separated from functional units but not from each other. Form 3a requires that; (i) Busbars are separated from functional units (ii) Busbars are not separated from any incoming or outgoing termination (iii) Functional units are separated from other functional units (iv) Functional units are separated from any incoming or outgoing termination (v) Terminals are not separate from each other.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The a designation denotes terminals for external conductors are not separate from the busbars.
The illustration above is Form 3a where the Integral Housing of the device is the means of separation and the arrangement is regarded as Group Mounted.
20
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Form 3b Type 1
All Form 3 assemblies are enclosed so as to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units and separation of the functional units from each other.Terminals are separated from functional units but not from each other. Form 3b Type 1 also requires that; (i) Busbars are separated from functional units (ii) Functional units are separated from other functional units (iii) Terminals for external conductors are separated from the respective functional unit and the busbars.Terminals are not separated from other terminals for external conductors.
Compartmentalised
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 1 designation denotes busbar separation is achieved by insulated coverings sleeving, wrapping or coating.
The above illustration uses Partitions and Barriers as a means of separation and is referred to as Compartmentalised.
Note: Insulation around the busbar connection joints has been removed, in both images to assist clarity.
Group Mounted
The above illustration uses the Integral Housing of the Device as a means of separation and is referred to as Group Mounted. Where a devices integral housing is the means of separation, the construction of the device shall be such that it has a barrier which prevents access from the terminals for external conductors, to the internal parts of the device.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
21
Form 3b Type 2
All Form 3 assemblies are enclosed so as to provide protection against contact with internal live parts, or compartments and where there is internal separation of the busbar from the functional units and separation of the functional units from each other.Terminals are separated from functional units but not from each other.
Compartmentalised
Form 3b Type 2 also requires that; (i) Busbars are separated from functional units (ii) Functional units are separated from other functional units (iii) Terminals for external conductors are separated from the respective functional unit and the busbars. Terminals are not separated from other terminals for external conductors.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 2 designation denotes busbar separation by partitions and barriers.
The above illustration uses Partitions and Barriers as a means of separation and is referred to as Compartmentalised.
Group Mounted
The above illustration uses the Integral Housing of the Device as a means of separation and is referred to as Group Mounted. Where a devices integral housing is the means of separation, the construction of the device shall be such that it has a barrier which prevents access from the terminals for external conductors, to the internal parts of the device.
22
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
[Return to FAQs]
Form 4a Type 1
All Form 4a assemblies require the termination of all associated external conductors, both line(s) and neutral within the functional unit. Separate/common neutral bars do not fulfil this requirement.
Compartmentalised
Form 4a Type 1 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from other terminals and from the busbars.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The above illustration uses a combination of clauses covering Partitions and Barriers and Insulated Coverings. Note: Insulation around the busbar connection joints has been removed, in both images to assist clarity. The a designation denotes terminals for external conductors are within the same compartment as the functional unit. The Type 1 designation denotes busbar separation is achieved by insulated coverings sleeving, wrapping or coating.
Group Mounted
The above illustration uses a combination of clauses covering Integral Housing of the Device and Insulated Coverings.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
23
Form 4a Type 2
All Form 4a assemblies require the termination of all associated external conductors, both line(s) and neutral within the functional unit. Separate/common neutral bars do not fulfil this requirement. Form 4a Type 2 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from other terminals and from the busbars.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The a designation denotes terminals for external conductors are within the same compartment to the functional unit. The Type 2 designation denotes busbar separation by partitions and barriers.
24
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Form 4a Type 3
All Form 4a assemblies require the termination of all associated external conductors, both line(s) and neutral within the functional unit. Separate/common neutral bars do not fulfil this requirement. Form 4a Type 3 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from other terminals and from the busbars (iv) Individual, integral cable glanding facilities are to be provided for each circuit.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The a designation denotes terminals for external conductors are within the same compartment as the functional unit. The Type 3 designation denotes busbar separation by partitions and barriers.
The above illustration uses Partitions and Barriers as a means of separation. Cable terminations are integral to the device.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2 25
25
Form 4b Type 4
All Form 4b assemblies require the termination of all associated external conductors, both line(s) and neutral within a space separate from but associated with the functional unit. Separate/common neutral bars do not fulfil this requirement. Form 4b Type 4 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from their own functional unit, other sets of terminals and from the busbars.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 4 designation denotes busbar separation is achieved by insulating coverings sleeving, wrapping or coating.
Note: Insulation around the busbar connection joints has been removed, to assist clarity.
The above illustration uses a combination of clauses covering Partitions and Barriers and Insulated Coverings Cable terminations are extended into separate individual compartments.
26
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Form 4b Type 5
All Form 4b assemblies require the termination of all associated external conductors, both line(s) and neutral within a space separate from but associated with the functional unit. Separate/ common neutral bars do not fulfil this requirement. Form 4b Type 5 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from their own functional unit, other sets of terminals and from the busbars (iv) Separation of terminals for external conductors to be achieved by insulated coverings.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 5 designation denotes busbar separation by partitions and barriers with outgoing terminals separated by insulated coverings.
The above illustration uses Partitions and Barriers as a means of separation and insulated coverings for separation of external terminals.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
27
Form 4b Type 6
All Form 4b assemblies require the termination of all associated external conductors, both line(s) and neutral within a space separate from but associated with the functional unit. Separate/common neutral bars do not fulfil this requirement. Form 4b Type 6 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from other terminals and from the busbars.
Compartmentalised
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 6 designation denotes busbars and terminals are separated by partitions and barriers. The above illustration uses Partitions and Barriers as a means of separation and is referred to as Compartmentalised. Cable terminations are extended into separate individual compartments.
Group Mounted
The above illustration uses the Integral Housing of the Device as a means of separation and is referred to as Group Mounted. Cable terminations are separated by terminal shields. Where a devices integral housing is the means of separation, the construction of the device shall be such that it has a barrier which prevents access from the terminals for external conductors, to the internal parts of the device.
28
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
Form 4b Type 7
All Form 4b assemblies require the termination of all associated external conductors, both line(s) and neutral within a space separate from but associated with the functional unit. Separate/common neutral bars do not fulfil this requirement. Form 4b Type 7 also requires the separation of; (i) Busbars from functional units (ii) Functional Units from each other (iii) Terminals for external conductors from other terminals and from the busbars (iv) Individual, integral cable glanding facilities are to be provided for each circuit.
Notes:
Forms of separation can be achieved by using; (i) Partitions/barriers of metallic or non-metallic material (ii) The integral housing of the device (iii) Terminal shrouds, shields and dividers can be used to contribute towards the required degree of separation (IPXXB) (iv) For neutral termination see Other Considerations item 6. The b designation denotes terminals for external conductors are in a separate compartment to the functional unit. The Type 7 designation denotes busbars and extended terminals are separated by partitions and barriers.
The above illustration uses Partitions and Barriers as a means of separation. Cable terminations are extended into separate individual compartments.
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
29
30
Guide to Forms of Separation Low Voltage Switchgear and Controlgear Assemblies to BS EN 61439-2
BEAMA Limited Westminster Tower 3 Albert Embankment London SE1 7SL Telephone: +44 (0)20 7793 3000 Fax: +44 (0)20 7793 3003 Email: [email protected]
www.beama.org.uk
BEAMA Limited is registered in England No. 84313