Manual Ups
Manual Ups
01-2001
General Catalog
summary su m m ar y
po we r , i lexible innf fle xible p r o t e c t i o n
p 04 p 06 p p p p p p 08 08 10 12 14 18
THE RIELLO ELETTRONICA GROUP PRODUCT RANGE (fast selection table) IT RANGE Win Dialog Personal Dialog Pro Net Dialog Dialog Active Dialog Plus NETWORK RANGE Power Dialog Plus Multi Dialog INDUSTRY RANGE Master Dialog Dialog Power Centre NET-TEL RANGE (19" rack solutions) Dialog Active rack Dialog Plus Rack Dial Inverter Multiswitch Multi shelter cabinets DIALOG SEC [security] RANGE for security DIALOG E-BUSINESS RANGE FOR THE INTERNET STABILIZER RANGE Stabilog-EL1 static Stabilog-EM1-EMT3-EMY3 dinamici COMMUNICATION SOFTWARE PowerShield2 Kit Software per AS/400 Netman USB Converter Multiplexer UPSERVICE POWER SUPPLY PROBLEMS and UPS selection
p 22 p 22 p 26 p 32 p 32 p 42 p p p p p p 44 44 48 50 52 54
p 56 p 57 p 58 p 59 p 60 p p p p p p 64 64 66 66 66 66
p 67 p 68
F L E X I B L E
P O W E R ,
70
the years that have passed since power business was launched for the first time (with 30 years specific experience in Uninterruptible Power Supplies - UPS)
20
the lines of the RIELLO UPS range
2 years
the average age of the products, maintained in a primary position with far-reaching R&D investments
3
the independent enterprises dedicated to developing new technologies and products
9001
the ISO certification awarded to RIELLO UPS
70,000
the number of appliances produced each year by RIELLO UPS
4
INFLEXIBLE
The range comprises 300VA to 6400k VA UPS Stabilizers Communication software Multi switches Inver ters (DC input /AC output) Modular rack-mount cabinets
PROTECTION
Turin), continuously develops solutions to improve product characteristics and provide users with exceptional reliability at reduced use and operating costs (consider for example the reduction in space/consumption/impact on the mains power supply/communication options).
All thesecomponents allow users set to up the most suitable availability solution according to their specific requirements.
[QUALITY POLICY]
RIELLO UPS is ISO9001 certified. Over the years, quality has become engrained in the culture of RIELLO UPS personnel and plays an active role in determining product quality and in particular in providing a faster, more effective, CUSTOMER SERVICE that is oriented at problem-solving. The test procedure includes no less than 6 fully automatic tests, from the electronic cards to the finished product, which is tested on a bed that reproduces actual operation at the installation site (Active Run In). Also very important in relation to quality is the TUV certification, awarded for some lines, and integrated production of the entire UPS range which is developed and produced at the Legnago (VR), Milan and Turin facilities.
[ THE
"DIALOG" RANGE]
DIALOG = Communication! RIELLO has given top priority to communication with large-scale investments in communication software that makes it possible to integrate the UPS in any type of environment, in particular in the IT sector where communication between machines is vital. The software solutions, often included in the Dialog line, are developed by the Riello UPS research centers and are entitled to be considered avant-garde in relation to the existing market solutions.
[APPLIED RESEARCH]
The RIELLO UPS research center, at 3 different sites (Vallese, Milan and
/
5
U P S
IT RANGE
P R O D U C T
Personal computers Small computer networks Local Area Networks (LAN) Work stations
R A N G E
Servers Point of Sale Systems (POS)
For less complex IT applications (home PC or SOHO (Small Office/Home Office), where the main requirements are lower costs, unfailing availability and excellent communication capabilities.
WIN DIALOG 320-620VA page 08 PERSONAL DIALOG PRO 300-650VA page 10 NET DIALOG page 12 DIALOG ACTIVE 500-2000VA sinewave output page 14 DIALOG PLUS 700-5000VA page 18
NETWORK RANGE
Personal computers POWER DIALOG PLUS 6-10kVA page 22 MULTI DIALOG 10-20kVA singlephase and three-phase page 26
For corporate computer networks, up to internet server providers and telecommunications, wherever top flight reliability and modularity (possibility of upgrading system power and reliability at any time) are required. Small computer networks Local Area Networks (LAN) Work stations Servers Point of Sale Systems (POS)
INDUSTRY RANGE
Personal computers MASTER DIALOG RM 8-20kVA single-phase page 32 MASTER DIALOG RT 10-160kVA three-phase page 36 DIALOG POWER CENTRE2 200-800kVA three-phase page 42
For industrial processes, security (emergency lights, fire alarms) and hospital applications, wherever maximum electrical and mechanical performance is required in addition to long back-up. Small computer networks Local Area Networks (LAN) Work stations Servers Point Of Sale Systems (POS)
NET-TEL RANGE
For IT and telecommunications applications, in 19 rack-mount cabinets, wherever high level reliability, modularity and compactness are essential. Work stations Servers Point Of Sale Systems (POS)
page 58
page 64
RIELLO UPS also proposes a range of DC/DC converters, inverters and custom solutions: contact us for further information.
Daata centers
Industrial PLCs
Cash registers
Electro-medical devices
Industrial processes
Data centers
Industrial PLCs
Cash registers
Electro-medical devices
Industrial processes
Data centers
Industrial PLCs
Cash registers
Electro-medical devices
Industrial processes
Data centers
Industrial PLCs
Cash registers
Electro-medical devices
Industrial processes
/
7
WIN DIALOG
APPLICATIONS
personal computers small computer networks
[320-620VA single-phase]
CHARACTERISTICS
mains power supply stabilization and filtering (Line Interactive (VI) technology with AVR and filters for suppression of atmospheric disturbances) low consumption (sleep mode: the inverter is switched off under no-load conditions) integrated protection for PC networks and telephone line/modem (07/09 models) possibility of switching on the UPS without the mains supply present (Cold Start capability) high level reliability of the batteries (battery test)
The WIN DIALOG series comprises the 320-420620VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages by the EMI filters. In the case of a mains failure, the load will be powered by the inverter with pseudo sinewave for brief periods, long enough to permit shut-down of the computer systems by the UPS MON software which is standard.
ADVANCED COMMUNICATION
UPS MON supervision and shut-down software for Windows 95, 98, Me, NT 4.0 Workstation operating systems included (on CD ROM) (07/09 models) advanced communication (standard RS232 interface) (07/09 models)
2-YEAR WARRANTY
; ; ; ;
1 2 3 4
UPS on mains UPS on batteries Battery replacement ON/OFF - test - alarm reset
; ; ; ;
1 2 3 4
/
8
POWER INPUT
MODELS
WD 05 320VA/190W
WD 07 420VA/250W 220 240 Vac 230 Vac (+/-25%) 50/60 Hz with autorange 230 Vac (-14%, +9%) 230 Vac (+/-5%) 50 o 60 Hz (+/- 0.5%) Typical 2 ms, maximum 4 ms Pseudo sinewave Maintenance-free sealed lead-acid 4-6 h Battery low overcurrent short-circuit
WD 09 620VA/370W
Rated voltage Voltage range Frequency OUTPUT Voltage in battery operation Frequency in battery operations Transfer time Waveform from battery BATTERIES Type Recharge time OTHER DATA Protection Tel./Net. protection Communication Safety compliance EMC conformance Noise Operating temperature Storage temperature Color Elevation and relative humidity Voltage in mains operation
RJ45 connectors RS232 serial EN 50091-1-1 and Directives 73/23 EEC, 93/68 EEC
EN 50091-2 cl. B and Directives 89/336 EEC, 92/31 EEC, 93/68 EEC < 40 dBA at 1 mt. 0 C / +40 C -15 C / +45 C Light gray RAL 7035 6000 meters max. elevation, 0 95 % non condensing
Back-up graph
WD 09 3 PC
WD 07
2 PC
WD 05
1 PC
10
15 (MIN)
20
25
30
35
Description
Power
Win Dialog WD05 320VA/190W Win Dialog WD07 420VA/250W Win Dialog WD09 620VA/370W communication software
Back-up Dimensions (min) (HLP) mm 5-15* 152x110x325 9-20* 152x110x325 7-30* 152x110x325 See software section page 66
Technical
data /
9
CHARACTERISTICS
2 outlets: one for critical loads (computers), one for non-critical loads (printers), with the possibility, in the case of a blackout, of software-programmable disconnection of one output before the other ("Power Share" function ) after 1 min. of back-up or in battery low conditions mains supply stabilization and filtering - Line Interactive (VI) technology - with AVR and filters for suppression of atmospheric disturbances Pininfarina design low consumption (efficiency 97%) possibility of switching on the UPS without the mains supply present (Cold Start capability) Auto restart at power-up high level reliability of the batteries (automatic battery test)
The PERSONAL DIALOG PRO series comprises the 300-450-650VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages by the EMI filters. In the case of a mains failure, the load will be powered by the inverter with pseudo sinewave long enough to permit shut-down of the computer systems by the PowerShield software which is standard. For advanced communication, performance (standard power share function) and design (Pininfarina) PERSONAL DIALOG PRO is the solution for more demanding users who require fully automatic control of their power system.
ADVANCED COMMUNICATION
high level multi-platform communication for all operating 2 systems and network environments: PowerShield supervision and shut-down software included, with standard integrated SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is furnished with a cable for direct connection to the PC (Plug and Play)
2-YEAR WARRANTY
; ; ; ;
1 2 3 4
Mains supply present UPS on batteries Battery efficiency test (intermittent with low charge) Overload and stand-by
; ;
5 6
; ; ; ; ;
1 2 3 4 5
;
5
;
1
;
4
;
3
;
2
/
10
POWER INPUT
MODELS
PD 30 300VA/195W
PDP 65 650VA/410W
Rated voltage Voltage range Frequency OUTPUT Voltage in battery operation Frequency in battery operation Transfer time Waveform from battery BATTERIES Type Recharge time OTHER DATA Protection Safety compliance EMC conformance Surge capability Noise Color Operating temperature Storage temperature Relative humidity Voltage in mains operation 230 Vac (-18%, +15%)
230 Vac 5% 50 or 60 Hz 0.1% typical 2 ms, maximum 4 ms Pseudo sinewave Maintenance-free sealed lead-acid 4-6 h Battery low overcurrent short-circuit EN 50091-1-1 and Council Directive 73 / 23 EEC EN 50091 - 2 cl. B and Council Directive 89 / 336 EEC IEC 801-5 < 40 dBA at 1 mt. Base gray, shell blue 0 C / +40 C -15 C / +45 C < 90 % non condensing
Back-up graph
PDP65 3 PC
PDP45
2 PC
PD30
1 PC
10
15 (MIN)
20
25
30
35
Description Personal Dialog PD30 Personal Dialog Pro PDP45 Personal Dialog Pro PDP65 communication software
Back-up Dimensions Weights (min) (HLP) mm (Kg) 7-18* 137x201x374 6 10-24* 137x201x374 6,5 8-34* 137x201x374 9,5 See software section page 66
Technical
data /
11
NET DIALOG
APPLICATIONS
personal computers
[1000-1500VA single-phase]
CHARACTERISTICS
4 outlets: three for critical loads (computers),one for non-critical loads (printers) with the possibility, in the case of a blackout, of software-programmable disconnection of the "non-critical" loads before the others ("Power Share" function) after 1 minute of back-up or in battery low conditions mains supply stabilization and filtering (Line Interactive VI technology) with AVR and filters for suppression of atmospheric disturbances possibility of switching on the UPS without the mains supply present (Cold Start capability) automatic restart at power-up integrated protection for PC networks and telephone line/modem high level reliability of the batteries (automatic battery test)
The NET DIALOG series comprises the 1000-1500VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages by the EMI filters. In the case of a mains failure, the load will be powered by the inverter with pseudo sinewave long enough to permit shut-down of the computer 2 systems by the PowerShield software which is standard. The UPS also integrates an outlet for PC networks and telephone line, for filtering and complete protection of the installation. For advanced communication and top flight performance (standard power share function), NET DIALOG is the solution for more demanding users who require fully automatic control of their power system.
ADVANCED COMMUNICATION
advanced, multi-platform communication for all operating systems and network environments: PowerShield2 supervision and shut-down software included, with integrated SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play)
2-YEAR WARRANTY
; ; ; ; ; ;
1 2 3 4 5 6
Mains supply present Overload / Standby Battery replacement On batteries ON button OFF button
;
3
; ;
1 2
; ;
5 6
;
4
; ; ; ; ; ;
1 2 3 4 5 6
Input fuse RS232 serial Inlet Outlets Power share outlet PC/telephone line/modem protection
/
12
POWER INPUT
MODELS
ND 100 1000VA/600W 220 240 Vac 230 Vac (-22%, +15%) 50/60 Hz with autorange 230 Vac (-13%, +11%) 230 Vac (+/- 5%) 50 o 60 Hz (+/- 0.5%)
ND 150 1500VA/900W
Rated voltage Voltage range Frequency OUTPUT Voltage in mains operation Voltage in battery operation Frequency in battery operation Transfer time Waveform from battery BATTERIES Type Back-up at typical load (min Recharge time OTHER DATA Protection PC NET/Tel/Modem protection Communications Safety compliance EMC conformance Surge capability Noise Color Operating temperature Storage temperature Relative humidity
Maintenance-free sealed lead-acid 99 4-6 h Battery low overcurrent short-circuit RJ45 connectors Porta RS232 EN 50091 - 1 - 1 and Council Directive 73 / 23 EEC EN 50091 - 2 cl. B and Council Directive 89 / 336 EEC IEC 801-5 < 40 dBA at 1 mt. Light gray RAL 7035 0 C / +40 C -15 C / +45 C < 90 % non condensing
Back-up graph
60
50
ND 100
BACK-UP (MIN)
40
ND 150
30
20
LOAD
(VA)
Back-up (min) 9* 9*
Weights (Kg) 16 21
10
1000
1100
1200
1300
1400
1500
100
200
300
400
500
600
700
800
900
Technical
data /
13
Pseudo sinewave
DIALOG ACTIVE
[500-2000VA single-phase]
The DIALOG ACTIVE series comprises the 500-10001500-1600-2000VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages and surges. In the case of a mains failure, the load will be powered by the inverter with pure SINEWAVE long enough to permit shut-down of the computer systems by the PowerShield software which is standard. The UPS also integrates an outlet for PC networks and telephone line, for filtering and complete protection of the installation. For advanced communication and top flight performance (standard power share function), DIALOG ACTIVE is the solution for more demanding users who require complete protection and fully automatic control of the power system.
2
; ; ; ; ; ; ;
1 2 3 4 5 6 7
Load AVR on UPS on batteries Batteries/stand-by status UPS on mains Battery test ON/OFF button
; ;
2 4
;
6 5 3
DA 160-200
DA 50-150
;
2
; ;
8 4
; ;
7
;
1
;
5
; ;
6
;
1
; ;
3 7
; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8
Outlets PC/telephone line/modem protection Inlet USB connector Selector switch (RS232/USB) serial RS232 Input fuse Slot for network card (DA 160 - DA 200)
/
14
CHARACTERISTICS
APPLICATIONS:
mains supply stabilization and filtering Line Interactive (VI) technology with AVR and
Small/medium computer networks Local Area Networks (LAN) Workstations Servers POS (Point of Sale) systems
possibility of switching on the UPS without the mains power present (Cold Start capability)
ADVANCED COMMUNICATION
high level reliability of the batteries (automatic battery test)
advanced, multi-platform communication for all operating systems and network environments: PowerShield 2 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems.
equipped with slot for integration of the SNMP agent (DA160/DA200 models) on the UPS
2-YEAR WARRANTY
15
D
POWER INPUT Rated voltage
L
DA 50 500VA/335W
G
DA 75 DA 100
A
230 VAC 230V (-25 / + 21)%
C
DA 150
T
DA 160
V
DA 200
MODELS
750VA/500W
Voltage range with mains supply present Frequency Frequency range OUTPUT Rated voltage Voltage in mains operation Frequency Voltage in battery operation Waveform Distortion BATTERIES Type Recharge time OTHER DATA Operating temperature Humidity Protection Safety compliance EMC conformance Surge capability Color Noise
50 60 Hz with autorange
230 VAC 230 V (-15 / +11)% 50 60 Hz with autorange 230V (+/- 5%) Sinewave <2% Maintenance-free sealed lead-acid 8h 0 40 C <90% Overload short-circuit overvoltage undervoltage temperature low battery EN 50091-1-1 and Council Directive 73 / 23 EEC, Council Directive 93 / 68 EEC EN 50091 2 cl. B and Council Directive 89 / 336 EEC IEC 801-5 6 KV 1.2 / 50 s; 3 KA 8 / 20 s differential Light gray RAL 7035 < 40 dBA a 1 m.
Back-up graph
60 60 50 50
DA 50
40
DA 150
40
BACK-UP (MIN)
DA 100
30
BACK-UP (MIN)
DA 75
DA 160 DA 200
30
20
20
10
10
1000
100
150
200
250
300
350
400
450
500
550
600
650
700
750
800
850
900
950
50
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
LOAD (VA)
LOAD (VA)
/
16
2000
100
200
300
400
500
600
700
800
900
Technical
data
+/- 5 Hz
Description Dialog Active DA50 Dialog Active DA75 Dialog Active DA100 Dialog Active DA150 Dialog Active DA160 Dialog Active DA200 Network card (DA 160 - DA 200) Communication software * According to load applied
Power 500VA/335W 750VA/500W 1000VA/670W 1500VA/1000W 1600VA/1070W 2000VA/1340W / (see back-up graph)
Weights (Kg) 13 14 14 20 25 25 /
(*) Version with battery charger for faster recharging of the batteries
/
17
DIALOG PLUS
[700-5000VA single-phase]
The DIALOG PLUS series comprises the 700-10001500-2000-3000-4000-5000VA models with double on-line conversion technology (VFI). The load is always powered by the inverter which provides a sinusoidal output, with filtered and stabilized voltage, waveform and frequency. The input and output filters also considerably increase the immunity of the load to mains supply disturbances and to surges. The UPS can power the load for long periods (using the optional battery modules) or long enough to permit shut-down of the computer 2 systems by the PowerShield software, which is standard, for Windows 95, 98, 2000, Me, NT 4.0 operating systems. For technology and top flight performance, DIALOG PLUS is the best solution for the supply of sensitive and vital mission-critical applications.
; ; ; ; ; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8 9 10 11 12
Load applied Battery charger Timer on Mains supply present Inverter on UPS on batteries UPS on bypass Batteries discharged/Battery replacement Stand-by Buzzer on/reset button OFF button Normal functioning
/
18
CHARACTERISTICS
APPLICATIONS:
reliable, stabilized, filtered voltage (double online conversion technology (VFI according to EN50091-3 specifications) with filters for the suppression of atmospheric disturbances
Local Area Networks (LAN) Servers Data centers Industrial PLCs Cash registers Emergency devices (lights/alarms) Electro-medical devices Telecommunications devices
power factor correction of the load (UPS input power factor, close to 1)
low consumption (programmable Auto Power Off function for automatic shut-down of the UPS under no-load conditions)
simplified maintenance
battery optimization: through the power share function (for automatic, software-programmable disconnection of non-critical loads during backup (DLP70 and DLP100 models), after 1 minute of back-up or in battery low conditions
ADVANCED COMMUNICATION
advanced, multi-platform communication, for all operating systems and network environments: PowerShield 2 supervision and shut-down software included, with SNMP agent for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play)
2-YEAR WARRANTY
19
D
POWER INPUT
L
DLP70
G
DLP100 DLP150 DLP200
P
DLP300
L
DLP400
U
DLP500
MODELS
Rated voltage 220 - 230 - 240 Vac Voltage range 170276 Vac 176-276 Vac 170-276 Vac Rated frequency 50 - 60 Hz 5 Hz Power factor > 0.93 > 0.99 > 0.98 Input current Sinewave BY- PASS Voltage range 180 - 264 Vac Frequency range Selected frequency 5 Hz BATTERY Recharge time 5-7h 4-6h 5-7h 6-8h OUTPUT Rated voltage 230 Vac 1.5% 220 or 230 or 240 Vac selectable 1.5% Waveform Sinewave Voltage distortion < 2% Frequency 50 or 60 Hz autorange 50 or 60 Hz selectable Crest factor of the current 3:1 3.5 : 1 3:1 INSTALLATION INFORMATION AC/AC efficiency 89 % 89 % 89 % 90 % 90 % 90 % 90 % Operating temperature 0 - 40 C Humidity < 90 % non condensing Protection Low battery - overcurrent - short-circuit - overvoltage - undervoltage - temperature Compliance EN 50091-1-1 specifications and Council Directive 73 / 23 EEC EN 50091 - 2 cl. B and Council Directive 89 / 336 EEC Surge capability IEC 801-5 6KV 1.2/50 sec; 3KA 8/20 sec Color Light gray RAL 7035 Noise < 40 dBA at 1 m < 45 dBA at 1 m Maximum input current 3.5 A 5A 7.4 A 10 A 14.4 A 16 A 24 A Diff. input current* 1 mA 1 mA 1 mA 1 mA 1 mA 1 mA 6 mA * This value must be added to the differential current of the equipment.
Back-up graph
60 60
50
50
DLP 70
AUTONOMIA (MIN)
40
AUTONOMIA (MIN)
40
30
30
20
20
10
10
2250
1000
1250
1500
1750
2000
2500
2750
3000
3250
3500
3750
4000
4250
4500
4750
1000
1100
1200
1300
1400
CARICO (VA)
1500
CARICO (VA)
20
5000
250
500
100
200
300
400
500
600
700
800
900
750
Technical data
Description Dialog Dialog Dialog Dialog Dialog Dialog Dialog Plus Plus Plus Plus Plus Plus Plus DLP70 DLP100 DLP150 DLP200 DLP300 DLP400 DLP500
Weights (Kg) 7 10 23 27 43 44 65
25 45 25 30 30 60 60 20 25 45 45 25 30 30 60 60 90 90 20 26 26 35 45 50 70 20 30 50 105
Options
Description Isolation transformer module for DLP100/DLP150 Isolation transformer module for DLP200/DLP300 Isolation transformer module for DLP500 Communication software LED-based remote control panel Dimensions (HWD) mm 340x158x480 340x158x480 265x400x500 Weights (Kg) 22 30 60 Type MMDLP150 MMDLP300 MMDLP500 Code ACCHX115RU-05 ACCHX230RU-02 ACCMO650NP
ESD input, slot for the network interface), POWER DIALOG PLUS is the best solution for the supply of sensitive and vital mission-critical equipment and security devices (electromedical) guaranteeing maximum reliability. Note the simple installation: the UPS can be connected both to single-phase and three-phase mains.
DIGITAL DISPLAY The multi-language display provides detailed status, measurement and alarm information
;
12
; ; ; ; ; ;
1 2 3 4 5 6
UPS on mains UPS on battery Battery replacement alarm Load on bypass UPS shutdown (steady light) or stand-by (flashing light) SMART ACTIVE functioning
; ; ; ; ;
7 8 9 10 11
/
22
CHARACTERISTICS
Reliable, stabilized, filtered voltage (double online conversion technology (VFI according to EN50091-3 specifications) with filters for suppression of atmospheric disturbances High level reliability of the UPS: full microprocessor control static or manual bypass without interruption High level diagnostics: states, measurements, alarms available on standard LCD display! Power factor correction of the load (input power factor of the UPS, close to 1) Very low noise level <40dB(A) Low consumption (Economy Mode function and Smart Active Mode to increase efficiency up to 98%). - Economy Mode: makes it possible to select Line Interactive (VI) technology for mains powering of not very sensitive loads for certain periods. The function is software programmable or can be set manually from the UPS. - Smart Active: if the mains supply is out of range, the UPS will power the load from the inverter. When the mains supply is within range again, the UPS will monitor this for a certain period before switching the load again.
APPLICATIONS:
Local Area Networks (LAN) Servers Data centers Industrial PLCs Cash registers Emergency devices (lights/alarms) Electro-medical devices Telecommunications devices
Simple to install: - possibility of connecting the UPS both to single-phase and three-phase mains supply (PWP 650-800-1000 models) - output terminal block + 2 IEC outlets for powering of local equipment (computers, modems, etc.)
ADVANCED COMMUNICATION
high level reliability of the batteries (automatic and manual battery test)
advanced, multi-platform communication, for all operating systems and network environments: PowerShield2 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operatisng systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play) RS232 serial port slot for installation of the mains adapter
low impact on the mains supply (sinusoidal absorption of the input current on singlephase/single-phase series)
Emergency operation: the UPS can be set for operating only with mains absent (for emergency lights)
ESD (Emergency Switching Device) contact for UPS shut-down using remote emergency button 23
P O W E R
MODELS
INPUT Rated voltage Minimum voltage for non intervention of the battery Rated frequency Power factor
D I A L O G
PWP 600 PWP 650 PWP800 230Vac single-phase 170Vac @ 100% load 140Vac @ 50 load% 50 - 60 Hz 5 Hz
P L U S
PWP1000
Single-phase Three-phase Single-phase Three-phase Single-phase Three-phase 0.99 0.99 7% 0,95 27% 0,99 7% 0,95 27% 0,99 7% 0,95 27% Single-phase Three-phase 7% Single-phase Three-phase Single-phase Three-phase
Current distortion with distorting load BY PASS Voltage range Frequency range BATTERY Typical back-up Recharge time OUTPUT Rated voltage Static variation Dynamic variation Waveform Voltage distortion with linear load Voltage distortion with distorting load Frequency Crest factor Rated power in VA/W OVERLOAD TIMES 100% < Load < 125% 125% < Load < 150% Load 150% INSTALLATION INFORMATION 6000/4200 12
180 264 Vac (selectable in Economy Mode and SMART ACTIVE MODE) Selected frequency 5 Hz 20 68h 220 / 230 / 240 Vac selectable 1% 1% 5% in 20ms Sinewave < 2% < 5% 50 / 60 Hz selectable or with autorange 3:1 6500 / 4600 2 30 s 0.5 s Input Input 92% 98% 0 40 C < 90 % non condensing Low battery overcurrent short-circuit - overvoltage - undervoltage temperature EN 5009111, Directives 73 / 23 EEC and 93/68 /EEC EN 50091-2 cl. A, Council Directive 89/336 EEC Light gray RAL 7035 < 40 dBA at 1 mt.
Single-phase Three-phase* Single-phase Three-phase* Single-phase Three-phase*
16
12
8000 / 5600
10000 / 7000
Input 91%
Input 92%
Input 91%
Input 92%
Efficiency 91% Efficiency Line-interactive/Smart Active Operating temperature Humidity Protection Compliance Color Noise Maximum input current* Differential input current** VALUE OF THE OUTPUT PROTECTIONS FOR SELECTIVITY*** Normal fuses (GI) Normal switches Extra Fast fuses (EF)
29A
31 A
11A 10 mA
41 A
15 A
50 A
18 A
* In the case of UPS with three-phase input and single-phase output, the cables and input protections must be calculated according to the value of the single-phase current in the case in which the UPS switches the load (single-phase) to input (three-phase). In this case, the single-phase load will be supported entirely on one of the three input phases. ** This value must be added to the differential current of the equipment. *** Complying with these values, the UPS will be able to provide the power required to interrupt the output protection in the case of a short-circuit without switching the load to the mains supply.
/
24
Technical
data
Description Power Power Power Power Power Power Power Power Dialog Dialog Dialog Dialog Dialog Dialog Dialog Dialog Plus Plus Plus Plus Plus Plus Plus Plus PWP600 PWP600 PWP650 PWP650 PWP800 PWP800 PWP1000 PWP1000
Dimensions (HWD) mm 585x283x805 585x283x805 735x283x805 735x283x805 735x283x805 735x283x805 735x283x805 735x283x805
Back-up graph
60 50
AUTONOMIA (MIN)
40
30
20
10
0 10000 1000 1500 2000 2500 3000 3500 4000 4500 5000 5500 6000 6500 7000 7500 8000 8500 9000 9500 500 0
CARICO (VA)
Options
Description Isolation transformer module for PWP600 Isolation transformer module for PWP650 Network adapter module on slot Communication software LED-based remote control panel Dimensions (HWD) mm 500x400x265 500x400x265 Weights (Kg) 80 80 Code ACCTM265NP ACCTM265NP
ACCSA2XXRU-01 See software section page 64 (PowerShield2 standard version included) ACCMRT20NP
software included, ESD input, slot for the network interface), MULTI DIALOG is the best solution for the supply of sensitive and vital mission-critical equipment and security devices (electromedical). Note the simply installation: the UPS can be connected both to single-phase and three-phase mains.
; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8
Language selection Input/output measurements Controls/settings/ customizations Event log Buzzer reset Time/date Scroll back Scroll forward
Buttons 7 and 8 are used to display detailed information about system control. disponibili sul controllo del sistema
; ;
/
26
CHARACTERISTICS
reliable, stabilized, filtered voltage (double online conversion technology (VFI according to EN50091-3 specifications) with filters for suppression of atmospheric disturbances
APPLICATIONS
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs Cash registers Emergency devices (lights/alarms) Electro-medical devices Telecommunications devices
high level reliability of the UPS assured by: - full microprocessor control - IGBT technology
its 0.8 power factor makes it suitable for powering IT and industrial loads
high level diagnostics: event log with 128 messages, states, measurements, alarms available on standard multi-language LCD display
low consumption - high efficiency (92% thanks to the digital control and the IGBT technology) - standard Economy Mode function to increase efficiency (up to 98%): makes it possible to select Line Interactive (VI) technology for mains powering of not very sensitive loads for certain periods. The function is software programmable or can be set manually from the UPS.
simple to install: - possibility of connecting the UPS both to single-phase and three-phase mains - possibility of calibrating the output voltage from the control panel (to offset voltage drops on the cables)
maximum reliability and availability of power (modular parallel up to 4 units for redundant parallel (N+1) or power parallel)
ADVANCED COMMUNICATION
advanced, multi-platform communication, for all operating systems and network environments: PowerShield 2 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play) double RS232 serial port slot for installation of mains adapter ESD (Emergency Switching Device) contact for UPS shut-down using remote emergency button remote control panel 27
power factor correction of the load (input power factor of the UPS, close to 1)
high level reliability of the batteries - automatic battery test - recharge compensated with temperature
Emergency operation: the UPS can be set for operating only with mains absent (for emergency lights)
M U L T I
SINGLE-PHASE MODELS
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Frequency range Power factor BATTERIES Type Recharge time [h] INVERTER OUTPUT Rated power [kVA] Active power [kW]* Number of phases Rated voltage [V] Voltage regulation range Crest factor (Ipeak/Irms) Waveform Distortion with linear load Static stability Dynamic stability Frequency Overload BYPASS Rated voltage Number of phases Permitted voltage range Rated frequency Permitted frequency range INSTALLATION INFORMATION Input Remote signaling Remote controls Communication Operating temperature Relative humidity Color Audible noise Protection rating Efficiency Compliance Air flow (m3/h)
D I A L O G
MDM1000 MDM1500 10 15 230V single-phase or 400V three-phase + N 20 % 45 65 Hz 0.95 Sealed lead-acid 8 10 8 15 12/10.5* 1 230 200 243 V 3:1 Sinewave 2% 1% 5 % in 10 ms 50 / 60 Hz selectable 125/150% of the rated current for 10/ 1 230V 1 15 % ( selectable from 5 % to 25 %) 50 / 60 Hz 2 % (selectable from 1 % to 5 %) Single-phase and three-phase zero-potential contacts ESD and bypass Double RS232/C 0 + 40 C 95 % (non condensing) Light gray RAL 7035 < 56 dBA IP20 > 92% 20 16/12*
M D M
MDM2000 20
Safety EN 50091-1 EMC EN 50091-2 Lev. A Directives 73/23-93/68-89/336 EEC 320 68A 27A 100mA In (Rated current)/7 In (Rated current)/7 In (Rated current)/2 480 91A 36A
320 (for installations in a closed environment) Bypass input current 45A Maximum rectifier input current Differential input current VALUE OF THE OUTPUT PROTECTIONS FOR SELECTIVITY** Normal fuses (GI) Normal switches (Curve C) Extra Fast fuses * With single-phase input. 18A
** Complying with these values, the UPS will be able to provide the power required to interrupt the output protection in the case of a short-circuit without switching the load to the mains supply.
28
Technical data
UTMM100035RU UTMM100735RU UTMM101135RU UTMM101535RU UTMM150035RU UTMM150735RU UTMM151135RU UTMM151535RU UTMM200035RU UTMM200635RU UTMM201035RU
* For parallel UPS (with parallel kit included), add -02 to the UPS code (ex. MDM 1000 0 parallelable = UTMM100035RU-02
Dimensions (HWD) Weights Battery Module Battery Module 1200x450x750 160 1200x450x750 1200x555x720 1200x450x750 1200x450x750 1200x450x750 1200x860x720 1200x450x750 1200x450x750 1200x860x720 1200x860x720 160 563 240 240 240 845 240 240 845 845
Type MDM1000-08+ BB384-12M MDM1000-15+ BB384-12M MDM1000-00+ BB384-38M MDM1500-08+ BB576-12M MDM1500-10+ BB576-12M MDM1500-15+ BB576-12M MDM1500-00+ BB576-38M MDM2000-07+ BB576-12M MDM2000-10+ BB576-12M MDM2000-00+ BB576-38M MDM2000-07+ BB576-38M
30 35 40 65
30 40 45 60
Code Battery Module (UPS+batteries) UTMM100735RU + ACCMDM20NP-24 UTMM101535RU + ACCMDM20NP-24 UTMM100035RU + ACCMDM38RU-01 UTMM150735RU + ACCMDM20NP-25 UTMM151135RU + ACCMDM20NP-25 UTMM151535RU + ACCMDM20NP-25 UTMM150035RU + ACCMDM38RU-02 UTMM200635RU + ACCMDM20NP-25 UTMM201035RU + ACCMDM20NP-25 UTMM200035RU + ACCMDM38RU-01 UTMM200635RU + ACCMDM38RU-02
Options
Description Dimensions (HWD) mm Weights (Kg) 140 160 188 Code ACCMRM10RU ACCMRM15RU ACCMRM20RU Isolation transformer module 1200x450x750 400V three-phase 230V single-phase 10kVA Isolation transformer module 1200x450x750 400V three-phase 230V single-phase 15kVA Isolation transformer module 1200x450x750 400V three-phase 230V single-phase 20kVA Communication software See Software section page 64 LED-based remote control panel (see picture page22) battery trays + cables (for MDM 10 kVA - 0) battery trays + cables (for MDM 15/20 kVA 0)
Description
Power
Dimensions Power factor 0.7 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750 1200x450x750
Weights (HWD) mm 90 180 200 218 95 230 275 285 110 245 300
Type (Kg) MDM1000-00 MDM1000-08 MDM1000-10 MDM1000-15 MDM1500-00 MDM1500-08 MDM1500-10 MDM1500-15 MDM2000-00 MDM2000-07 MDM2000-10
Code
M U L T I
THREE-PHASE MODELS
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Frequency range Power factor BATTERIES Type Recharge time [h] INVERTER OUTPUT Rated power [kVA] Active power [kW] Number of phases Rated voltage [V] Voltage regulation Crest factor (Ipeak/Irms) Waveform Distortion with linear load Static stability Dynamic stability Frequency Overload BYPASS Rated voltage Number of phases Permitted voltage range Rated frequency Permitted frequency range INSTALLATION INFORMATION Input Remote signaling Remote controls Communication Operating temperature Relative humidity Color Noise Protection rating Efficiency Compliance Air flow (m3/h) 10 8 10
D I A L O G
MDT1000 MDT1500 15 400V three-phase + N 45 65 Hz 0.95 Sealed lead-acid 8 15 12 3 400 Adjustable from 346 422 V 3:1 Sinewave 2% 1% 5 % in 10 ms 50 / 60 Hz selectable 125/150% of the rated current for 10/ 1 400V 3 15 % ( selectable from 5 % to 25 %) 50 / 60 Hz 2 % (selectable from 1 % to 5 %) Three-phase + N zero-potential contacts ESD and bypass Double RS232/C 0 + 40 C 95 % (non condensing) Light gray RAL 7035 < 56 dBA IP20 > 92% 20 %
M D T
MDT2000 20
20 16
Safety EN 50091-1 EMC EN 50091-2 Lev. A Directives 73/23-93/68-89/336 EEC 320 15A 18A 320 23A 27A 100mA In (Rated current)/7 In (Rated current)/7 In (Rated current)/2 480 30A 360
(for installations in a closed environment) Bypass input current Maximum rectifier input current Differential input current
VALUE OF THE OUTPUT PROTECTIONS FOR SELECTIVITY* Normal fuses (GI) Normal switches (Curve C) Extra Fast fuses (EF)
* Complying with these values, the UPS will be able to provide the power required to interrupt the output Protection in the case of a short-circuit without switching the load to the mains supply.
30
Technical data
For parallel UPS (with parallel kit included), add -02 to the UPS code (ex.: MDT 1000 0 parallelable = UTMT100045RU-02)
USP MODEL
Back-up Power fact. 0.8Power fact. 0.7 Multi Dialog 30 35 MDT 10 kVA 40 46 65 Multi Dialog MDT 15 kVA 30 35 40 65 Multi Dialog MDT 20 kVA 30 40 45 60 75 35 40 46 75 35 46 55 70
Dimensions (WHD) Battery Module 1200x450x750 1200x450x750 1200x555x720 1200x450x750 1200x450x750 1200x450x750 1200x860x720 1200x450x750 1200x450x750 1200x860x720 1200x860x720
Weights (Kg) Type Battery Module 160 MDT1000-08+ BB384-12M 160 MDT1000-15+ BB384-12M 563 MDT1000-00+ BB384-38M 240 MDT1500-08+ BB576-12M 240 MDT1500-10+ BB576-12M 240 MDT1500-15+ BB576-12M 845 MDT1500-00+ BB576-38M 240 MDT2000-07+ BB576-12M 240 MDT2000-10+ BB576-12M 845 MDT2000-00+ BB576-38M 845 MDT2000-07+ BB576-38M
Code Battery Module (UPS+batteries) UTMT100745RU + ACCMDM20NP-24 UTMT101545RU + ACCMDM20NP-24 UTMT100045RU + ACCMDM38RU-01 UTMT150745RU + ACCMDM20NP-25 UTMT151145RU + ACCMDM20NP-25 UTMT151545RU + ACCMDM20NP-25 UTMT150045RU + ACCMDM38RU-02 UTMT200645RU + ACCMDM20NP-25 UTMT201045RU + ACCMDM20NP-25 UTMT200045RU + ACCMDM38RU-02 UTMT200645RU + ACCMDM38RU-02
Options
Description Dimensions (HWD) mm Weights (Kg) 145 165 190 Code ACCMRT10NP-01 ACCMRT15NP-01 ACCMRT20NP-01 Isolation transformer module 1200x450x750 400V/400V three-phase 10kVA Isolation transformer module 1200x450x750 400V/400V three-phase 15kVA Isolation transformer module 1200x450x750 400V/400V three-phase 20kVA communication software See Software section page 64 LED-based remote control panel Battery trays + cables (for MDT 10 kVA - 0) Battery trays + cables (for MDT 15/20 kVA - 0)
Description
Power
Back-up Dimensions Power fact. 0.8 Power fact. 0.7 10kVA/8kW 0 0 1200x450x750 8 10 1200x450x750 15 17 1200x450x750 15kVA/12kW 0 0 1200x450x750 8 10 1200x450x750 11 13 1200x450x750 15 17 1200x450x750 20kVA/16W 0 0 1200x450x750 7 9 1200x450x750 10 12 1200x450x750
Weights Type (HWD) mm 95 MDT1000-00 185 MDT1000-08 223 MDT1000-15 100 MDT1500-00 235 MDT1500-08 280 MDT1500-10 290 MDT1500-15 115 MDT2000-00 250 MDT2000-07 305 MDT2000-10
Code (Kg) UTMT100045RU UTMT100745RU UTMT101545RU UTMT150045RU UTMT150745RU UTMT151145RU UTMT151545RU UTMT200045RU UTMT200645RU UTMT201045RU
MASTER
DIALOG
HWD 1400x800x740 mm
HWD 1400x1070x740 mm
9 10 11 12 13
Digital display Bypass ON / Manual Bypass Inverter ON / overload Mains supply present Functioning from batteries / end of discharge pre-alarm
32
CHARACTERISTICS
reliable, stabilized, filtered voltage (double on-line conversion technology (VFI according to EN50091-3 specifications) with filters for suppression of atmospheric disturbances high level reliability of the UPS assured by: - extremely high short-circuit current (2.8In); this makes the UPS compatible with even the most difficult applications: transformers, lighting, drives, industrial processes) - full microprocessor redundant control (2 microprocessors) - isolation transformer on inverter output - IGBT technology its 0.8 power factor makes it suitable for powering of IT and industrial loads high level diagnostics: event log, states, measurements, alarms available on standard multi-language LCD display maximum care of the batteries temperature-dependent recharge protection against deep battery discharge simple to install: - possibility of inserting the UPS on any distribution system (neutral not required on rectifier input). Possibility of separating the rectifier/bypass power networks and of powering these with 2 even separate sources, without the need for galvanic isolation (necessary on certain UPS without output transformer). - possibility of regulating the output voltage (to offset voltage drops on the cables) maximum reliability and availability of power (parallel distributed up to 6 units for redundant (N+1) or power parallel) standard BACK FEED protection, against power return on the mains in the case of fault low consumption: assured by the selectable ECO-MODE function that makes it possible to power from the mains, when this is stable, guaranteeing very high efficiency (98%, RT10000/RT16000 models)
ESD (Emergency Switching Device) input for UPS shut-down using remote emergency button input for switching to bypass by remote signal digital or LED-based remote control panel
APPLICATIONS
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs Electro-medical devices Telecommunications devices Emergency devices (lights/alarms) Industrial processes
ADVANCED COMMUNICATION
advanced, multi-platform communication, for all operating systems and network environments: PowerShield 2 supervision and shut-down software included, with SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play)
33
M A S T E R
RM
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Frequency range Soft start RECTIFIER OUTPUT Rated battery voltage Maintenance voltage Ripple INVERTER OUTPUT Rated power [kVA/KW] Rated voltage [V] Rated current [A] Regulation of the output voltage Crest factor Waveform Static stability Dynamic stability Rated frequency Frequency stability (mains supply failure ) Frequency stability (mains supply present) Overload Inverter efficiency at rated load Maximum recharge current [A] BYPASS LINE Rated current [A] Rated voltage [V] Permitted voltage range Rated frequency Permitted frequency range Overload capacity In x 10ms Standard capabilities INSTALLATION INFORMATION Efficiency Compliance Air flow (m3/h) (for installations in a closed environment) Remote signaling Remote controls Computer interface Operating temperature Maximum relative humidity non condensing Noise (dBA) Protection rating Color of the cabinet Rectifier maximum input current [A] Bypass input current [A] Differential input current* VALUE OF THE OUTPUT PROTECTION (FOR SELECTIVITY)** Normal fuses (GI) Normal switches (Curve C) Extra fast fuses Cable infeed 15 36 48 54 91 18 35 92 BATTERY (Maintenance-free sealed lead-acid) 35 8/6.4 8 RM 800
D I A L O G
RM1000 RM1500 RM2000 10 400V three-phase 45 65 Hz 0 100% in 10sec 384V Variable acc. to temperature [-0.5V x C] < 1% 10/8 43 3:1 Sinewave 1% 5 % in 5 ms Same as the input (autorange) 0.05 % 2 % (adjustable 1% / 5% from control panel) 125/150/200 % of the rated current for 10/1/7 s 93 0,2 x C10 43 230 single-phase 15 % (adjustable 10 % , 25 % from front panel) 50 / 60 Hz (autorange) 2 % (adjustable 1% , 5% from front panel) 14 12 14 BackFeed protection; separable bypass line 92 92 92 65 87 93 93 15/12 65 20/16 87 20 % 15 20
R M
EN50091-1-1, EMC EN50091-2 Lev. A EC Directives 73/23-93/68-89/336 310 372 558 744
zero-potential contacts (mains power failure, UPS on bypass, end of discharge pre-alarm... output 12Vdc 80mA) ESD and bypass RS232/C 0 + 40 C 95 % 48 54 IP20 Light gray RAL 7035 18 45 100mA In (Rated current) / 5.5 In (Rated current) / 5.5 In (Rated current) / 1.6 Bottom/rear 27 68 36 91 53 60 53 60
* This value must be added to the differential current of the equipment. ** Complying with these values, the UPS will be able to provide the power required to interrupt the output Protection in the case of a short-circuit without switching the load to the mains supply.
34
Technical
data
8kVA/6.4kW
10kVA/8kW
15kVA/12kW
20kVA/16kW
For parallel UPS (with parallel kit included), add -02 to the UPS code (ex.: RM800 0 parallelable = UMRM080035RU-02)
* Back-up data referred to combination with UPS with back-up 0 Different back-up values from those indicated are available on request. Other types of batteries are also available (long-life; open vent; Nickel Cadmium)
Options
Description Isolation transformer three/single-phase module for RM800 Isolation transformer three/single-phase module for RM1000 Isolation transformer three/single-phase module for RM1500 Isolation transformer three/single-phase module for RM2000 RM800 CLEAN (THDi<8%) RM1000 CLEAN (THDi<8%) RM1500 CLEAN (THDi<8%) RM2000 CLEAN (THDi<8%) Kit for connection in parallel Remote control panel with LCD LED-based remote control panel Empty cabinet for 38Ah battery including connection cable kit Empty cabinet for 65Ah battery including connection cable kit Communication software (full version) Dimensions (HWD) mm 1200x555x720 1200x555x720 1200x555x720 1200x555x720 Weights (Kg) 140 140 160 188 Code ACCMRM08RU ACCMRM10RU ACCMRM15RU ACCMRM20RU
80 80 95 95 / / / 105 135
Description
Power
Dimensions Power factor 0.7 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720
Weights Code (HWD) mm (Kg) 190 UMRM080035RU 287 UMRM081035RU 325 UMRM082035RU 422 UMRM083535RU 460 UMRM085035RU 200 UMRM100035RU 297 UMRM100635RU 335 UMRM101535RU 432 UMRM103035RU 470 UMRM104035RU 220 UMRM150035RU 335 UMRM151035RU 425 UMRM151535RU 490 UMRM152035RU 230 UMRM200035RU-03 462 UMRM201035RU-03 500 UMRM201535RU-03
M A S T E R
RT
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Rated frequency Soft start RECTIFIER OUTPUT Ripple INVERTER OUTPUT Rated power [kVA/KW] Number of phases Rated voltage [V] Rated current [A] Regulation of the output voltage Crest factor Waveform Static stability Dynamic stability Rated frequency Frequency stability (no mains) Frequency stability (Mains supply present) Overload Efficiency of the inverter at rated load BATTERY (Maintenance-free sealed lead-acid) Maximum recharge current [A] BYPASS LINE Rated current [A] Rated voltage [V] Voltage range Rated frequency Permitted frequency range Overload capacity In x 10ms Standard capabilities INSTALLATION INFORMATION Efficiency Compliance Remote signaling Remote controls Standard interface Operating temperature Maximum relative humidity non condensing Noise (dBA) Protection rating Color of the cabinet Air flow (m3/h) 496 (for installations in a closed environment) Maximum input current rectifier [A] Bypass input current [A] Differential input current* VALUE OF THE OUTPUT PROTECTION (FOR SELECTIVITY)** Normal fuses (GI) Normal switches (Curve C) Fast-blow fuses Cable infeed 18 15 48 54 90 14 14 91 14 10/8 10 RT1000
D I A L O G
RT1500 RT2000 RT3000 15 20 400V three-phase 20 % 50 / 60 Hz autorange 0 100% in 10sec < 1% 15/12 20/16 3+N 400 22 29 3:1 Sinewave 1% 5 % in 5 ms Same as the input (autorange) 0,05 % 2 % (adjustable 1% / 5% from control panel) 125/150/200 % of the rated current per 10/1/7 s 91 92 0,2 x C10 22 29 400V three-phase 15 % (adjustable 10 % , 25 % from control panel) 50 / 60 Hz (autorange) 2 % (adjustable 1% , 5% from control panel) 15 14 15 14 BackFeed protection; separable bypass line 90 91 91 92 43 58 92 93 43 58 Adjustable from 348V to 424V (from control panel) 30/24 40/32 30 40
R T
RT4000
EN50091-1-1, EMC EN50091-2 Lev. A Directives 73/23-93/68-89/336 EEC zero-potential contacts (mains power failure, UPS on bypass, end of discharge pre-alarm... - output 12Vdc 80mA) ESD and remote bypass RS232/C 0 + 40 C 95 % 48 54 53 60 IP20 Light gray RAL 7035 682 28 23 868 37 30 100mA In (Rated current) / 5.5 In (Rated current) / 5.5 In (Rated current) / 1.6 bottom / rear 1240 55 45 1488 72 61 53 60 53 60
* This value must be added to the differential current of the equipment. ** Complying with these values, the UPS will be able to provide the power required to interrupt the output Protection in the case of a short-circuit without switching the load to the mains supply.
36
Technical data
Power 10kVA/8kW
15kVA/12kW
20kVA/16kW
30kVA/24kW 40kVA/32kW
*For parallel UPS (with parallel kit included), add -02 to the UPS code (ex. RT 1000 0 parallelable = UMRT100045-02) UPS MODEL Back-up* Back-up* Dimensions (HWD) Weights (Kg) Type Power fact. 0.8Power fact. 0.7 Battery Module Batt. Mod. Master Dialog RT 1000 63 72 1200x555x720 563 BB384-38A 130 150 1200x860x720 875 BB384-65B Master Dialog RT 1500 40 46 1200x555x720 563 BB384-38A 80 92 1200x860x720 875 BB384-65B 95 110 2x(1200x555x720) 1126 2X(BB384-38A) Master Dialog RT 2000 30 35 1200x555x720 563 BB384-38A 55 63 1200x860x720 875 BB384-65B 65 75 2x(1200x555x720) 1126 2X(BB384-38A) 95 110 1400x860x720 1180 BB384-100D Master Dialog RT 3000 15 17 1200x555x720 563 BB384-38A 35 40 1200x860x720 875 BB384-65B 45 51 1400x860x720 920 BB384-80D 60 69 1400x860x720 1180 BB384-100D 100 114 2x(1400x860x720) 1840 2X(BB384-80D) Master Dialog RT 4000 10 12 1200x555x720 563 BB384-38A 21 24 1200x860x720 875 BB384-65B 30 35 1400x860x720 920 BB384-80D 45 51 1400x860x720 1180 BB384-100D 55 63 2x(1200x860x720) 1750 2X(BB384-65B) * Back-up data referred to combination with UPS with back-up 0 Different back-up values from those indicated are available on request. Other types of batteries are also available (long-life; open vent; Nickel Cadmium) Dimensions (HWD) mm 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x270x720 1200x270x720 1200x270x720 1200x270x720 1200x270x720 Weights (Kg) 145 165 190 215 260 290 315 335 387 435 Code to be combined with that of the UPS with Back-up 0) ACCMRM20NP-01 ACCMRM20NP-02 ACCMRM20NP-01 ACCMRM20NP-02 (2x) ACCMRM20NP-01 ACCMRM20NP-01 ACCMRM20NP-02 (2x) ACCMRM20NP-01 ACCMRM20NP-16 ACCMRM20NP-01 ACCMRM20NP-02 ACCMRM20RU-24 ACCMRM20NP-16 (2x) ACCMRM20NP-24 ACCMRM20NP-01 ACCMRM20NP-02 ACCMRM20RU-24 ACCMRM20NP-16 (2x) ACCMRM20NP-02
Description Isolation transformer module for RT1000 Isolation transformer module for RT1500 Isolation transformer module for RT2000 Isolation transformer module for RT3000 Isolation transformer module for RT4000 RT1000 CLEAN (THDi<8%) RT1500 CLEAN (THDi<8%) RT2000 CLEAN (THDi<8%) RT3000 CLEAN (THDi<8%) RT4000 CLEAN (THDi<8%) Kit for connection in parallel Remote control panel with LCD LED-based remote control panel 38Ah empty cabinet with cable kit 65Ah empty cabinet with cable kit Communication software (full version)
Code ACCMRT10NP-01 ACCMRT15NP-01 ACCMRT20NP-01 ACCMRT30NP-01 ACCMRT40NP-01 ACCMRM10NP-01 ACCMRM15NP-01 ACCMRM20NP-21 ACCMRM20NP-22 ACCMRM20NP-23 ACCMRM20NP-11 ACCMRM20NP-05 ACCMRT20NP ACCMRM20NP-03 ACCMRM20NP-04
1200x555x720 1200x860x720
105 135
Options
37
Dimensions Power factor 0.7 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x555x720 1200x825x720 1200x555x720
Weights Code (HWD) mm (Kg) 210 UMRT100045RU 307 UMRT100645RU 345 UMRT101545RU 442 UMRT103045RU 480 UMRT104045RU 220 UMRT150045RU 335 UMRT151045RU 452 UMRT151545RU 490 UMRT152045RU 230 UMRT200045RU-03 462 UMRT201045RU-03 500 UMRT201545RU-03 282 UMRT300045RU 552 UMRT300845RU 330 UMRT400045RU
M A S T E R
RT
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Rated frequency Frequency range Soft start RECTIFIER OUTPUT Ripple INVERTER OUTPUT Rated power [kVA/KW] Number of phases Rated voltage [V] Rated current [A] Regulation of the output voltage Crest factor Waveform Static stability Dynamic stability Rated frequency Frequency stability (mains supply not present) Frequency stability (mains supply present) Overload Efficiency of the inverter at rated load BATTERY (Maintenance-free sealed lead-acid) Maximum recharge current [A] BYPASS LINE Rated current [A] Rated voltage [V] Permitted voltage range Rated frequency Permitted frequency range Overload capacity In x 10ms Standard capabilities INSTALLATION INFORMATION Efficiency Compliance Remote signaling Remote controls Standard interface Operating temperature Maximum relative humidity non condensing Noise (dBA) Protection rating Color of the cabinet Air flow (m3/h) (for installations in a closed environment) Maximum input current rectifier [A] Bypass input current [A] Differential input current* VALUE OF THE OUTPUT PROTECTION (FOR SELECTIVITY)** Normal fuses (GI) Normal switches (Curve C) Fast-blow fuses Cable infeed
D I A L O G
RT6000 RT8000 60 400V three-phase 20 % 50 / 60 Hz autorange 45 65 Hz 0 100% in 10sec < 1% 60/48 3+N 400 87 3:1 Sinewave 1% 5 % in 5 ms Same as the input (autorange) 0,05 % 2 % (adjustable 1% / 5% from control panel) 125/150/200 % of the rated current per 10/1/7 s 93 0.2 x C10 87 400V three-phase 15 % (adjustable 10 %, 25 % from control panel) 50 / 60 Hz (autorange) 2 % (adjustable 1%, 5% from control panel) 12 11 BackFeed protection; separable bypass line 92 92 115 93 115 Adjustable from 348V to 424V (from control panel) 80/64 80
R T
EN50091-1-1, EMC EN50091-2 Lev. A Directives 73/23-93/68-89/336 EEC zero-potential contacts (mains supply failure, UPS on bypass, end of discharge pre-alarm... - output 12Vdc 80mA) ESD and remote bypass RS232/C 0 + 40 C 95 % 53 62 IP20 Light gray RAL 7035 2232 100 91 100mA In (Rated current) / 5.5 In (Rated current) / 5.5 In (Rated current) / 1.6 bottom/rear 2960 125 121
* This value must be added to the differential current of the equipment. ** Complying with these values, the UPS will be able to provide the power required to interrupt the output protection in the case of a short-circuit without switching the load to the mains supply.
38
Technical
data
*For parallel UPS (with parallel kit included), add -02 to the UPS code (ex. RT6000 parallelable = UMRT600045RU-02)
* Different back-up values are available on request. Other types of batteries are also available. (long life; open pot; Nickel Cadmium)
Options
Description Isolation transformer module for RT6000 Isolation transformer module for RT8000 RT6000 CLEAN (THDi<8%) RT8000 CLEAN (THDi<8%) Kit for connection in parallel Remote control panel with LCD LED-based remote control panel 38Ah empty cabinet with cable kit 65Ah empty cabinet with cable kit 100Ah empty cabinet with cable kit Dimensions (HWD) mm 1400x640x720 1400x640x720 1400x270x740 1400x270x740 / / / 1400x555x740 1400x860x740 1400x860x740 Weights (Kg) 380 430 145 145 / / / 120 150 150 Code ACCMRT60NP-01 ACCMRT80NP-01 ACCMRM60NP-01 ACCMRM20NP-20 ACCMRM20NP-11 ACCMRM20NP-05 ACCMRT20NP ACCMRM20NP-06 ACCMRM20NP-07 ACCMRM20NP-12
M A S T E R
RT
RECTIFIER INPUT Rated power [kVA] Rated voltage Voltage range Rated frequency Frequency range Soft start RECTIFIER OUTPUT Ripple INVERTER OUTPUT Rated power [kVA/KW] Number of phases Rated voltage [V] Rated current [A] Regulation of the output voltage Crest factor Waveform Static stability Dynamic stability Rated frequency Frequency stability (mains supply not present) Frequency stability (mains supply present) Overload Efficiency of the inverter at rated load Maximum recharge current [A] BYPASS LINE Rated current [A] Rated voltage [V] Permitted voltage range Rated frequency Permitted frequency range Overload capacity In x 10ms Standard capabilities INSTALLATION INFORMATION Efficiency Compliance Remote signaling Remote controls Standard interface Operating temperature Maximum relative humidity non condensing Noise (dBA) Protection rating Color of the cabinet Air flow (m3/h) (for installations in a closed environment) Maximum input current rectifier [A] Bypass input current [A] Differential input current* VALUE OF THE OUTPUT PROTECTION (FOR SELECTIVITY)** Normal fuses (GI) Normal switches (Curve C) Fast-blow fuses Cable infeed 3700 160 152 93 12 145 94 BATTERY (Maintenance-free sealed lead-acid) 145 100/80 100 RT10000
D I A L O G
RT12000 RT16000 120 400V three-phase 20 % 50 / 60 Hz autorange 45 65 Hz 0 100% in 10sec < 1% 120/96 3+N 400 174 Adjustable from 348V to 424V (from control panel) 3:1 Sinewave 1% 5 % in 5 ms Same as the input (autorange) 0,05 % 2 % (adjustable 1% / 5% from control panel) 125/150/200 % rated current for 10/1/7 s 94 0,2 x C10 174 400V three-phase 15 % (adjustable 10 %, 25 % from control panel) 50 / 60 Hz (autorange) 2 % (adjustable 1%, 5% from control panel) 10 BackFeed protection; separable bypass line 93 93 10 232 95 232 160/128 160
R T
EN50091-1-1, EMC EN50091-2 Lev. A Directives 73/23-93/68-89/336 EEC zero-potential contacts (mains power failure, UPS on bypass, end of discharge pre-alarm... - output 12Vdc 80mA) ESD and remote bypass RS232/C 0 + 40 C 95 % 54 62 IP20 Light gray RAL 7035 4400 190 182 100mA In (Rated current) / 5.5 In (Rated current) / 5.5 In (Rated current) / 1.6 bottom / rear 5800 250 243
* This value must be added to the differential current of the equipment. ** Complying with these values, the UPS will be able to provide the power required to interrupt the output protection in the case of a short-circuit without switching the load to the mains supply.
40
Technical data
Description Master Dialog RT10000 Master Dialog RT12000 Master Dialog RT16000
For parallel UPS (with parallel kit included) add -02 to the UPS code (ex. RT10000 parallelable = UMRT1K0045RU-02)
Cabinets/batteries
Description Empty cabinet for 36/40 batt. max 100Ah, including connection cable kit Battery type 1265 Battery type 1280 Battery type 12100 Dimensions (HWD) mm 1800x860x740 190x350x166 183x355x167 227x330x171 Weight (Kg) 190 23,5 24 32 Code
Options
Description Dimensions (HWD) mm Weights (Kg) Code Isolation transformer 1400x640x720 480 ACCMRT100NP-01 module for RT10000 Isolation transformer 1400x640x720 500 ACCMRT120NP-01 module for RT12000 Isolation transformer 1400x640x720 550 ACCMRT160NP-01 module for RT16000 RT10000 CLEAN (THDi<8%) 1400x270x740 180 ACCMRM100NP-01 RT12000 CLEAN (THDi<8%) 1400x270x740 180 ACCMRM120NP-01 RT16000 CLEAN (THDi<8%) 1400X270X740 200 ACCMRM160NP-01 Kit for connection in parallel / / ACCMRM20NP-11 Remote control panel with LCD / / ACCMRM20NP-05 LED-based remote control panel (see picture page 20) / ACCMRT20NP Communication software (full version) see software section page 64 (PowerShield2 standard version included)
The DIALOG POWER CENTRE2 range comprises the 200250-300-400-500-600-800kVA three-phase models with double on-line conversion technology (VFI) with transformer in output at the inverter. The load is always powered by the inverter which provides a sinusoidal output voltage, with filtered and stabilized voltage, waveform and frequency. The input and output filters also considerably increase the immunity of the load to mains supply disturbances and to surges. DIALOG POWER CENTRE2 is compatible with the most critical industrial installations thanks to its
minimum impact on the mains supply: distortion of the input current up to 5% which guarantees sinusoidal absorption without creating resonance phenomena with other line equipment (power factor correction capacitors). In addition, distortion does not depend on line parameters such as impedance and frequency. DIALOG POWER CENTRE2 makes it possible to economize when scaling the power source (isolation transformer or generator). high level diagnostics: event log, states, measurements, alarms available on standard multilanguage LCD display maximum reliability and availability of power (parallel distributed or centralized for redundant (N+1) or power parallel) ESD (Emergency Switching Device) input for UPS shutdown using remote emergency button
mechanical and electrical robustness assured by: isolation transformer on the inverter extremely high short-circuit current sinusoidal absorption (THDi up to 5%)
OPTIONS
Various options are available to configure a back-up system tailored to your requirements; some of these are given in the list below: isolation transformers phase shift transformers various types of batteries (Normal Life - long Life) and technology (sealed - open pot - NiCd) with various hours of back-up communication software rephasing blocks back feed protection automatic battery circuit breaker (for remote control)
SPECIFIC SOLUTIONS
The UPS can be adapted to your requirements. Consult RIELLO UPS for offers and feasability about specific solutions and options not listed in this catalog.
CHARACTERISTICS
reliable, stabilized, filtered voltage (double online conversion technology (VFI according to EN50091-3 specifications) with filters for suppression of atmospheric disturbances high level reliability of the UPS assured by: - extremely high short-circuit current (this makes the UPS compatible with even the most difficult applications: transformers, lighting, drives, industrial processes) -isolation transformer on inverter output -IGBT technology
42
MODELS
RECTIFIER INPUT Rated power Rated voltage Voltage range Frequency range (kVA)
DPC 200
DPC 250
DPC 300
DPC 400
DPC 500
DPC 600
DPC 800
200
250
300
500
600
800
Distortion of the current absorbed RECTIFIER OUTPUT Ripple INVERTER OUTPUT Rated power (kVA) cos
0.8
200 160
250 200
300 240
500 400
600 480
800 640
380-400-415V three phase +N 3:1 Sinewave 1% 5 % in 5 ms 50 Hz 0,05 % 2 % 125/150% of the rated current for 10/1 Maintenance-free sealed lead-acid 0,2 x C10 362 435 580 400V three-phase 50 / 60 Hz 6 pulses 1800x 2160x 900 2500 92 1800x 2360x 900 2800 93 1800x 2920x 900 3800 93 0 + 40 C 95 % 65 65 65 IP20 Light gray RAL 7035 EN50091-1-1, EMC EN50091-2 Lev. A Directives 73/23-93/68-89/336 EEC 78 78 78 65 1800x 3880x 900 4200 94 12 pulses 1800x 4780x 900 4800 94 1800x 4780x 900 6000 94 1800x 725 870 1160
Crest factor at rated power (Ipeak/Irms) Waveform Static stability Dynamic stability Rated frequency Frequency stability - Without synchronism - With synchronism on mains Overload BATTERY Type Maximum recharge current [A] BYPASS LINE Rated current [A] Rated voltage [V] Rated frequency INFORMATION ABOUT THE SYSTEM Dimensions (HWD) Weights (Kg) VERSION DIALOG POWER CENTRE CLEAN (TDHi<6%) Efficiency Standard interface Operating temperature Relative humidity non condensing Noise (dBA) Protection rating Color of the cabinet Compliance 92 2100 1500x 900 290
SYSTEM CONFIGURATION The Power Centre2 range features a wide range of options able to solve all your system engineering problems. These are not single products but real UPS that must be engineered after a careful analysis of your problems, with particular attention also being paid to standards and system configuration. This is why we ask you to contact our experts.
Technical
data
43
[500VA-2000VA single-phase]
APPLICATIONS:
Small/medium computer networks Local Area Networks (LAN) Workstations Servers POS (Point of Sale) systems
The DIALOG ACTIVE RACK series comprises the 500-1000-1500-1600-2000VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages and surges. In the case of a mains failure, the load will be powered by the inverter with pure sinewave long enough to permit shut-down of the computer systems by 2 the PowerShield software which is standard. The UPS also integrates an outlet for PC networks and telephone line, for filtering and complete protection of the installation. For advanced communication, top flight performance (standard power share function), DIALOG ACTIVE is the solution for more demanding users who require protection and fully automatic control of the power system.
CHARACTERISTICS
mains supply stabilization and filtering Line Interactive (VI) technology with AVR and filters for the suppression of atmospheric disturbances) high quality output voltage pure sinewave voltage (distortion <2%) high level immunity to surges (6kV according to IEC801-5) possibility of switching on the UPS without the mains supply present (Cold Start capability) integrated protection for PC networks and telephone line/modem high level reliability of the batteries (automatic battery test)
; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8
Battery efficiency Load applied Mains-powered functioning Back-up Stand-by/Battery to be replaced Stabilizer AVR UPS ON control Battery test control
2-YEAR WARRANTY
/
44
POWER INPUT
MODELS
DAR 50 500VA/335W
DAR 75 750VA/500W
DAR 150
DAR 200
1500VA/1000W 2000VA/1340W
Rated voltage Range with mains supply present Frequency Frequency range OUTPUT Rated voltage Voltage in mains operation Frequency Voltage in battery operation Waveform Distortion BATTERY Type Recharge time OTHER DATA Operating temperature Humidity Protection Safety compliance EMC conformance Surge capability Color Noise 230 V
230 VAC 230V (-25 / + 21)% 50 60 Hz with autorange 5 Hz CITA 230 VAC (-15 / +11%) 230V + 5% Sinewave <2% Maintenance-free sealed lead-acid 8h 0 40 C <90% Overload short-circuit overvoltage undervoltage temperature low battery EN 50091-1-1 and Directives 73 / 23 EEC and 93 / 68 EEC EN 50091 2 cl. B and Council Directive 89 / 336 EEC IEC 801-5 6 KV 1.2 / 50 sec ; 3 KA 8 / 20 sec differential dark gray RAL 5004 < 40 dBA at 1 m. 50 60 Hz with autorange
Description Dialog Active Rack DAR50 Dialog Active Rack DAR75 Dialog Active Rack DAR100 Dialog Active Rack DAR150 Dialog Active Rack DAR200 By-pass manuale Communication software
Back-up (min) 13 8 8 10 10
Dimensions (HWD) mm 89x483x450 89x483x450 89x483x450 133x483x450 133x483x450 89x483x380 See software section page 64
Weights (Kg) 19 20 21 26 34 2
Technical
data /
45
[2200VA-5000VA single-phase]
APPLICATIONS:
Small/medium computer networks Local Area Networks (LAN) Workstations Servers POS (Point of Sale) systems
The DIALOG ACTIVE RACK series comprises the 22003000-4000-5000VA models with digital Line Interactive (VI) technology. The load is powered by the mains which, when present, has amplitude stabilized by the AVR and is filtered of overvoltages and surges. In the case of a mains failure, the load will be powered by the inverter with a pure sinewave long enough to permit shut-down of the computer systems by the PowerShield2 software which is standard. The UPS also integrates an outlet for PC networks and telephone line, for filtering and complete protection of the installation. For advanced communication, top flight performance (standard power share function), DIALOG ACTIVE RACK is the solution for more demanding users who require complete protection and fully automatic control of the power system.
CHARACTERISTICS
mains supply stabilization and filtering line Interactive (VI) technology with AVR and filters for suppression of atmospheric disturbances high quality output voltage (pure sinewave voltage (distortion <2%) high level immunity to line overvoltages (480joules/6.5kA) high level reliability of the batteries (recharge according to temperature and automatic battery test) possibility of swapping the batteries fast battery recharge (<2h) possibility of increasing back-up to several hours
1 2 3 4 5 6 7 8 9 10 Battery efficiency Load applied Input voltage / Battery charge Mains out of range
ADVANCED COMMUNICATION
advanced, multi-platform communication for all operating systems and network environments: PowerShield2 supervision and shut-down software included, with SNMP agent. USB or RS232 serial port (selectable) equipped with slot for integration of the SNMP agent on the UPS
2-YEAR WARRANTY
46
MODELS
POWER INPUT Rated voltage Voltage range Frequency OUTPUT Rated voltage Voltage in mains operation Frequency Voltage in battery operation Waveform Peak factor Distortion BATTERIES recharge Type Recharge time OTHER DATA Operating temperature Humidity EMC conformance
220-230-240 VAC 175 283 VAC 50 Hz 220-230-240 VAC 230 V (-12 / +12%) 50 Hz 230V 2% Sinewave 4:1 <2% 8h Maintenance-free sealed lead-acid 2h 0 40 C <90% EN 50091 2 cl. A and Directive 89 / 336 EEC IP21 dark gray RAL 5004 < 35 dBA at 1 m
Safety complianceEN 50091-1-1 and Directive 73 / 23 EEC, Directive 93 / 68 EEC Line overvoltage suppression capacity480joules/6.5kA Protection rating of the enclosure Color Noise
Description Dialog Active Rack DAR220 Dialog Active Rack DAR300 Dialog Active Rack DAR400 Dialog Active Rack DAR500
Back-up (min) 12 12 12 12
Weights (Kg) 44 54 62 75
Options
Description Dry contacts card DAR 220-500 EPO DAR 220-500 input Manual external bypass 3000VA Module slot SNMP DAR 220-500 Communication software (full version) Dimensions (HWD) mm / / 190x235x70 / see software section page 64 Weights (Kg) / / 2 /
Technical data
[700-3000VA single-phase]
The DIALOG PLUS RACK series comprises the 7001000-1500-2000-3000VA models with double online conversion technology (VFI). The load is always powered by the inverter which provides a sinusoidal output voltage, with filtered and stabilized voltage, waveform and frequency. The input and output filters also considerably increase the immunity of the load to mains supply disturbances and to surges. The UPS can power the load for long periods (using the optional battery modules) or long enough to permit shut-down of the computer systems by the PowerShield 2000, Me, NT 4.0 operating systems. For technology and performance, DIALOG PLUS RACK is the best solution for the supply of sensitive and vital mission-critical equipment.
2
CHARACTERISTICS
reliable, stabilized, filtered voltage (double on-line conversion technology (VFI according to EN50091-3 specifications) with filters for the suppression of atmospheric disturbances high level immunity to surges (6kV according to IEC801-5) autorestart at power-up (programmable) power factor correction of the load (input power factor of the UPS, close to 1) low consumption ("Auto Power Off" function for automatic shut-down of the UPS under no-load conditions) simplified maintenance (manual bypass available on rack module) high level reliability of the batteries (automatic battery test) high level reliability of the UPS (full microprocessor control) low impact on the mains supply (sinusoidal absorption)
;
1
ADVANCED COMMUNICATION
;
5
advanced, multi-platform communication for all operating 2 systems and network environments: PowerShield supervision and shut-down software included, with SNMP agent, for Windows 95, 98, 2000, Me, NT 4.0, Novell operating systems. The UPS is equipped with a cable for direct connection to the PC (Plug and Play) RS232 serial port
;
6
;; ;
2 3 4
2-YEAR WARRANTY
; ; ; ; ; ;
1 2 3 4 5 6
Battery efficiency Load applied Input voltage / Battery charge Back-up Stand-by UPS ON
/
48
POWER INPUT
MODELS
DLPR70 700VA/450W
DLPR100 1000VA/700W
DLPR150
DLPR200
DLPR300
Rated voltage Voltage range for non intervention of the battery Rated frequency Frequency Maximum current Rated current Power factor BY PASS Voltage range for switching Frequency range for switching BATTERY Transfer time (mains power failure) Recharge time OUTPUT Rated voltage Waveform Voltage distortion Frequency Crest factor of the current Rated power in VA Rated power in W OTHER DATA AC/AC efficiency Operating temperature Humidity Protection Safety compliance EMC conformance Surge capability Color Noise 89 % 89 % 700 450 1000 700 50 o 60 Hz con autom. 5-7h 5-7h 3.5 A 2.5 A 0.93 5A 3.5 A 0.93
50 o 60 Hz con autom.
< 90 % non condensing Low battery overcurrent - short-circuit overvoltage undervoltage - temperature EN 50091 - 1 - 1 and Directive 73 / 23 / EEC IEC 801-5 6KV 1.2/50usec; 3KA 8/20usec dark gray RAL 5004 < 40 dBA at 1 mt.
Description Dialog Dialog Dialog Dialog Dialog Plus Plus Plus Plus Plus Rack Rack Rack Rack Rack DLPR70 DLPR100 DLPR150 DLPR200 DLPR300
Back-up (min) 8 10 11 11 13
Weights (Kg) 7 10 24 27 43
Back-up 30 22 35 55 25 26 35
Weights (Kg) Type Battery Module 15 18 30 57 35 40 52 BBR 36-14 BBR 60-7 BCR 60-12* BCR 60-24* BCR 72-12* BBR 120-7 BCR 120-12*
Code Battery Module to be combined with that of the UPS with standard back-up) ACCRC110RU-01 ACCH1R15RU-07 ACCH1R15RU-01 ACCH1R15RU-02 ACCK1R20RU-01 ACCH2R30RU-05 ACCH2R30RU-01
* Includes auxiliary battery charger for faster recharging Description External manual bypass Dimensions (HWD) mm 89x483x380 Weight (Kg) 2 Code ACCBYPXXNP-01
Technical
data /
49
50 - 60 Hz 5 Hz
DIAL INVERTER
[300-3000VA]
The DIAL INVERTER is available for various power ratings, from 300VA up to 3000VA, dc voltage input at 24/48 or
I O
ON/0FF LINE BATTERY BATTERY PRESENT WORKING LOW BATTERY START OVERLOAD
110Vdc and ac single-phase output (230V). DIAL INVERTER can be installed in 19 rack-mount cabinets for integration in any computer, telephone (exchanges) or industrial (process control) applications
I O
1 = BY - PASS 0 = UPS
BY-PASS FUSE
LINE PRESENT BATTERY WORKING BATTERY LOW
telephone exchanges ventilation systems telecommunications automation control circuits for industrial systems
APPLICATIONS
OVERLOAD
BY PASS ON NO ALARM
LOAD
AUTONOMY
I O
ON/OFF BATTERY START
II
HT 3000 R
Input 24, 48 or 110Vdc high quality voltage: output 230Vac sinewave massima protezione del carico tramite lIsolamento isolation and input and output anti-disturbance filters simple maintenance using manual bypass switch protection against short-circuit and overload in output limiting of inrush current at start-up zero-potential contact interface for remote signaling
CHARACTERISTICS
COMMUNICATION
L N
DIAL 110
+
DIAL 24 - DIAL 48
; ; ; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8 9 10
ON-OFF Start from battery Bypass switch Bypass fuse Outlets Inlet Signal connector Input dc voltage Ground outlet Battery fuse
; ; ; ; ; ; ; ; ;
1 2 3 4 5 6 7 8 9 9
ON-OFF Start from battery Battery isolator Bypass switch (option) Output connector (or input for manual bypass) Output connector Signal connector Input dc voltage Ground outlet Leds: - Stand by - inverter on - batteries almost discharged - overload - battery charge - bypass on
/
50
MODELS
Rated power (VA) Rated power (W) INPUT Rated voltage (Vdc) Operating voltage (Vdc) Maximum current (A) OUTPUT Voltage (V) Frequency (Hz) Waveform Harmonic distortion PROTECTION Overheating Short-circuit Current inrush at power-on OTHER DATA Containers Color Depth (mm)
DiAl24-03
DiAl24-05
DiAl24-10
DiAl48-05
DiAl 48-10
300 240 24 20 30 15 230 +/-2% 50 +/-0,01% Sinewave 2% Yes Yes Yes 19Rack 3U
500 400 24 20 30 25 230 +/-2% 50 +/-0,01% Sinewave 2% Yes Yes Yes 19Rack 3U
1000 800 24 20 30 50 230 +/-2% 50 +/-0,01% Sinewave 2% Yes Yes Yes 19Rack 3U 420
500 400 48 40 - 58 12 230 +/-2% 50 +/-0,01% Sinewave 2% Yes Yes Yes 19Rack 3U
1000 800 48 24 230 +/-2% 50 +/-0,01% Sinewave 2% Yes Yes Yes 19Rack 3U
DiAl48-20
DiAl110-10
DiAl110-20
DiAl110-30
MODELS
Rated power (VA) Rated power (W) INPUT Rated voltage (Vdc) Operating voltage (Vdc) Maximum current (A) OUTPUT Voltage (V) Frequency (Hz) Waveform Harmonic distortion PROTECTION Overheating Short-circuit Current inrush at power-on OTHER DATA Containers Color Depth (mm) 490 460 19Rack 5U 19Rack 7U 19Rack 7U 460 19Rack 7U 460 dark gray RAL 5004 Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes 230 +/-2% 50 +/-0,01% Sinewave 2% 230 +/-2% 50 +/-0,01% Sinewave 2% 230 +/-2% 50 +/-0,01% Sinewave 2% 230 +/-2% 50 +/-0,01% Sinewave 2% 48 40 - 58 53 110 92 - 140 11 110 92 - 140 22 110 92 - 140 33 2000 1600 1000 800 2000 1600 3000 2400
Description DiAl 24-03 DiAl 24-05 DiAl 24-10 DiAl 48-05 DiAl 48-10 DiAl 48-20 DiAl 110-10 DiAl 110-20 DiAl 110-30 Automatic bypass Automatic bypass
Power 300VA/240W 500VA/400W 1000VA/800W 500VA/400W 1000VA/800W 2000VA/1600W 1000VA/800W 2000VA/1600W 3000VA/2400W 1000VA 3000VA
Dimensions (HWD) mm 133x483x420 133x483x420 133x483x420 133x483x420 133x483x420 222x483x490 311x483x460 311x483x460 311x483x460
Weights Code (Kg) 18 IINV02430035RUA 20 IINV02450035RUA 25 IINV0241K035RUA 20 IINV04850035RUA 25 IINV0481K035RUA 30 IINV0482K035RUA 35 IINV1101K035RUA 40 IINV1102K035RUA 45 IINV1103K035RUA add-01 to the code of the inverter add -01 to the code of the inverter
Technical
data /
51
40 - 58
MULTI-SWITCH
[100% reliability]
The MULTI SWITCH promotes a high level continuous service on the installation. Its principle of operation guarantees a higher level of reliability than that of a single UPS, with bypass, or of an installation with several UPS in parallel.
APPLICATIONS
e.business Data centers ISP/ASP Local Area Networks (LAN) Server Farms Servers
PRINCIPLE OF OPERATION
The MULTI-SWITCH permits distribution and remote management of eight network users in a system with one or two direct or UPSconnected power lines. The Multi-Switch is able to connect each of the eight users (each with a maximum power absorption of 3A) to either of the two power lines (A and B) while also monitoring power absorption at the same time.
CHARACTERISTICS
Full protection of equipment against power failures and faults with the load Versatility of use: possibility of powering the MULTI SWITCH with 2 different power sources (2 UPS even of different size and type). Wired in 19" cabinet LCD display for monitoring of measurements/alarms/states Possibility of connection to a supervision center on a serial interface No signal connection is required between the multi switch and the power sources or the equipment
/
52
TECHNICAL DATA
Input voltage Maximum load for each output (A) Maximum load for each input (A) Output voltage Operating conditions: maximum elevation maximum humidity (non condensing) operating temperature storage conditions maximum noise level Communication interface Enclosure protection rating Inlets Outlets Rack dimensions Weight (Kg): Laws and standards Color Protection
180-276 Vac single-phase, 50/60Hz 3 10 selection of one of the two input sources 3000mt 0-90% 0-40C maximum elevation 15,000m/0-45C <35dB(A) serial on DB9 connector IP20 2 IEC 320 (10A) C14 8 IEC 320 (3A each) 1U-19 5 CE marking/EN50091-1-1 (safety)/EN50091-2 (EMC) level A/ CEI 74-2/IEC 60950 dark gray RAL 5004 overcurrent overvoltage undervoltage
PRINCIPLE OF OPERATION
SOURCE1
MULTI SWITCH
SOURCE2
Power 8 outlets 3A
Weights (Kg) 5
Code MMSR208M003RU
Options
Software See Software section page 66
Technical
data /
53
APPLICATIONS
MULTI SHELTER is suitable for all applications that require a system for housing 19 rack drawers: Servers Routers Hubs UPS MULTI-SWITCH PLCs for industrial control Telephone systems
CHARACTERISTICS
Easy to assemble Universal solution Flexibility: - reversible door opening to the right or left - possibility of choosing cable infeed position (from bottom, to the side) Wide range of solutions, with variable depth, height and width
A full range of solutions for structured cabling of rack-mount modules (UPS, MULTI-SWITCH, HUBS, SERVERS, etc.). The MULTI SHELTER range is available in various dimensions and with a wide selection of options, for adaptation and which to the installation environment, allow communication
ACCESSORIES:
Electrical accessories Multi-outlet device Distribution panel Concentrator rack
between the MULTI SHELTER and a supervision computer system. These are not just cabinets but real communicating units that can be integrated seamlessly in a BMS (Building Management System or wired building).
Sensors Temperature sensor Vibration sensor Smoke sensor Anti-intrusion sensor Humidity sensor
54
TECHNICAL DATA:
Colour: dark gray RAL 5004 / light gray RAL 7035
COMMON FEATURES: Front door: glass with key Rear panel: closed Side panels Socket: 10 mm Kit 4 setable feets
Wall-mount cabinets
Description Rack 19 wall mounting 6U Rack 19 wall mounting 6U Rack 19 wall mounting 9U Rack 19 wall mounting 15U Dimensions (WD) mm 600x280 600x350 600x350 600x500 light gray RAL 7035 MKS-0662/A MKS-0663/A MKS-0963/A MKS-1565/A Code dark gray RAL 5004 MKS-0662/N MKS-0663/N MKS-0963/N MKS-1565/N
Accessories
Description Module 6 plugs Module 6 differential switches Module 6 magnetic-thermal protections Module 6 power switches Temperature sensor Smoke sensor Humidity sensor Vibration sensor SNMP agent for management (Rack concentrator) light gray RAL 7035 MKS-AM36/A MKS-AM6-D/A MKS-AM6-M/A MKS-AM6-S/A MKS-ST MKS-SF MKS-SU MKS-SV MPU-Rack Code dark gray RAL 5004 MKS-AM36/N MKS-AM6-D/N MKS-AM6-M/N MKS-AM6-S/N MKS-ST MKS-SF MKS-SU MKS-SV MPU-Rack
Vibration sensor
Rack concentrator (for communication of the signals from the sensors to the computer network)
Smoke sensor
* MULTI SHELTER is compatible with all RIELLO UPS solutions of the NET-TEL range (DIALOG ACTIVE RACK, DIALOG PLUS RACK, DiAl inverter, MULTI SWITCH). For configuration of the rack system (cabinet + accessories), please consult the retailer or visit our web site.
55
R A N G E D I A L O G S E C [ S E C URITY]
SECURITY
This sector includes the following applications: Emergency lights Alarms Electromedical devices These applications require a back-up system configured as follows: standard UPS with high capacity battery charger isolation transformer (where required) possibility of communication with remote peripherals the following ranges assure technological and regulatory compliance with these applications: DIALOG PLUS (page 18) POWER DIALOG PLUS (page 22) MULTI DIALOG (page 26) MASTER DIALOG (page 32)
The systems used for these applications have many similarities. In many cases, they must have the following characteristics either because they are indispensable (just think of the enormous importance of a continuous power supply for electro-medical devices) or are required by law (there is a specific standard for the electro-medical sector CEI 64-8 V2 and also a number of guidelines and standards EN 50171 for emergency lights and devices):
Long back-up (60/90') Very short recharge time Input/output galvanic isolation High level diagnostics (display of a large amount of information on the control panel of the appliance) Interface device for remotization of the information (normally using dry relay contacts) Very high short-circuit current (required in particular for emergency lighting)
/
56
Data centers, medium/large Internet Providers (ASP and ISP), Server Farms or hubs for intercontinental Internet communication (Point Of Presence - POP). These are the many applications that always require continuous power supply with the following characteristics: a highly reliable power supply (the Internet must continue to operate round the clock 365 days a year without any interruptions due to power problems) a modular power supply able to keep pace with the growth of network equipment. All Internet-dedicated computer applications
continue to expand both as regards size (new servers are added to those already existing) and power (just think of how information technology requires continuous updates as the market is flooded with more and more powerful software products)
These applications require a back-up power supply that can be paralleled, that is able to guarantee continuous power even if a fault occurs in one of the UPS (parallel redundant) or which permits connection in parallel with similar systems even some time after the first UPS has been installed in order to increase system power (power parallel). The ranges available MULTI DIALOG (page 26) MASTER DIALOG (page 32) DIALOG POWER CENTRE2 (page 42) permit redundant or power The RACK product range is also important for e-business applications, in particular: MULTI SHELTER cabinets (page 54) MULTI SWITCH (page 52) DIALOG PLUS RACK (page 48) DIALOG ACTIVE RACK (page 44)
57
STABILIZERS RANGE
WHY USE STABILIZERS?
Fluctuations (up to 25%) may occur in the amplitude and form of the voltage mainly due to: switching on of high power equipment starting of critical equipment (motors, lifts, lighting devices) short-circuit on secondary equipment and other situations that occur daily on the public mains supply. reduced maintenance availability of a wide power range high level efficiency high level compensation capacity (also for very variable input network (+/-25%)
They are normally used for less sensitive, high power loads (processes, lights) with high absorption at start-up (motors, air conditioners, compressors, pumps). There are two versions of dynamic stabilizers:
a version able to power unbalanced three-phase loads or with a maximum imbalance between the phases of 50% a version able to power even up to 100% unbalanced three-phase loads and to guarantee high level precision both with unbalanced loads and asymmetrical voltages.
These phenomena are further amplified if the power is supplied by independent power systems (generators). These fluctuations may cause serious problems (that are often not obvious) for electrical equipment. Powering a bulb at 10% above its rated value reduces the life of the bulb by half whereas if it is powered 30% below the same value, it loses 30% of its brightness. The more complex the equipment, the greater the damage:
a computer may be damaged or make calculation errors a laboratory appliance may make measurement errors an industrial control may drive the process incorrectly Stabilizers are the solution to voltage fluctuations. There are various types of stabilization devices: 1. Dynamic stabilizers 2. Static stabilizers 3. Stabilizers combined with UPS
2. STATIC STABILIZERS
Maintain voltage stability using an electronically-controlled static device (transistor) which acts on the secondary of a transformer, responding quickly and correcting the voltage fluctuations. Advantages:
high quality voltage improved protection of the load against electromagnetic disturbances They are normally used for sensitive loads (information technology, Industrial PLCs, etc.)
1. DYNAMIC STABILIZERS
Maintain voltage stability using a dynamic device (variable with brushes) that adds or subtracts voltage to/from the input network compensating for any deformations or fluctuations Advantages: reduced weight and dimensions reduced cost
/
58
S T A T I C
STABILOG-EL1 RANGE
APPLICATIONS
information technology control electronics (Industrial PLCs)
S T A B I L I Z E R S
CHARACTERISTICS
extremely high reliability (electronic control) high level quality of the voltage (+/-3% with response speed to fluctuations of 2 ms/V) high level stability of the voltage: insensitive to load, frequency, power factor variations low consumption (efficiency=98%) extra high protection of the load (EMI/RFI filters for protection of the load against conducted radio-disturbances; overcurrent protection) low impact on the mains supply: induced harmonic distortion <0.2% maximum flexibility: possibility of connecting 3 single-phase stabilizers to power even an unbalanced three-phase load (independent phase regulation)
MODELS
Rated input voltage Input Voltage range Output voltage Rated power Rated current Regulation speed Possible variation of the load Power factor of the load Harmonic distortion introduced Efficiency Operating temperature Indications Equipment Connections
EL05
EL10
EL20
EL40
500VA 2.2A
2000VA 8.7A
4000VA 17.4A
From 0 to 100% Any <0,5% 98% -10/+40C Mains supply present/absent in input Switch, fuse 1 Shuko outlet, cord Switch, fuse 1 Shuko outlet, cord Switch fuse Two Shuko outlets, terminal block Switch fuse Two Shuko outlets, terminal block
Technical
data /
59
D Y N A M I C
S T A B I L I Z E R S
STABILOG RANGE STABILOG RANGE-EM1 SINGLE-PHASE STABILOG RANGE-EMT3 THREE-PHASE STABILOG RANGE-EMY3 THREE-PHASE
[for 50%-balanced three-phase or single-phase loads] [for unbalanced three-phase loads orthree-phase asymmetrical voltages]
APPLICATIONS
industrial processes lighting equipment with high start-up absorption (motors, conditioners, compressors, pumps)
CHARACTERISTICS
low impact on the mains supply: no distortion or own disturbances (induced distortion < 0.2%), very low series impedance (from 0.52 to 0.0015 ohm) low consumption: (efficiency up to 98%) voltage quality (regulation and stabilization made on the effective value of the voltage and therefore unaffected by harmonic distortions of the mains supply) easy to install: close to the equipment, inside this flexibility: assured by the wide range of options available very precise stabilization (+/-1%) high level reliability (natural cooling guarantees a very high MTBF very high overload (up to 10 times the rated power)
60
MODELS
Power (kVA) Input/output voltage(V) Input voltage range (+/-%) Input frequency Regulation speed (ms/Volt) Precision +/-%
Equipment
selector
Power factor of the load Possible variation in the load Rated output current Efficiency Harmonic distortion introduced Protection rating Operating temperature Cooling
Description STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG EM110 EM125 EM150 EM170 EM1100 EM1150 EM1300
Technical
data /
61
Clean-contact
S T A B I L I Z Z A T O R I
MODELS
Power (kVA) Input voltage range (+/-%) Regulation speed (ms/Volt) Precision +/-% Equipment EMT350 8/5/4/3 10/15/20/25 25/20/16/12 1 EMT3100 15/10/8/5 10/15/20/25 27/20/15/10 1 EMT3200 EMT3150 20/15 15/20 20/15 1 Voltmeter Indicator light Rated output current Efficiency (%) Protection rating 11.6A 98 IP20 21.7A 98 IP20 29A 98 IP21
D I N A M I C I
EMT3350 EMT3250 35/25 15/20 33/25 1 Voltmeter Indicator light 50.7A 98 IP21 EMT3750 EMT3500 75/50 15/20 18/13 1 Voltmeter Indicator light clean-contact int. 109A 98 IP21
Range selector switch Range selector switch Discharger Settings Discharger Settings Discharger Settings
MODELS
Power (kVA) Input voltage range (+/-%) Regulation speed (ms/Volt) Precision +/-%
EMT3500P 50 25 11 1 Discharger Settings Voltmeter Indicator light clean-contact int. 72.5A 98 IP21
EMT3750P 75 20 13 1 Discharger Settings Voltmeter Indicator light clean-contact int. 109A 98 IP21
EMT31000 100 15 18 1 Discharger Settings Voltmeter Indicator light clean-contact int. 145A 98 IP21
EMT31500 150 15 33 1 Discharger Settings Voltmeter Indicator light clean-contact int. 217A 98 IP21
Description STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG EMT350 EMT3100 EMT3150 EMT3200 EMT3250 EMT3350 EMT3500 EMT3750 EMT3500P EMT3750P EMT31000 EMT31500
Power 8/5/4/3kVA 15/10/8/5kVA 15kVA 20kVA 25kVA 35kVA 50kVA 75kVA 50kVA 75kVA 100kVA 150kVA
Weights (Kg) 45 66 122 122 247 247 269 269 380 380 380 460
Dimensions (HWD) mm 260x600x300 480x270x445 952x483x337 952X483X337 1492x587x337 1492x587x337 1492x650x395 1492x650x395 1492x650x395 1492x650x395 1600x650x600 1600x650x600
Code S1TT008U020RU S1TT015U020RU S1TT015U040RU S1TT020U030RU S1TT025U040RU S1TT035U030RU S1TT050U040RU S1TT075U030RU S1TT050U050RU S1TT075U040RU S1TT100U030RU S1TT150U030RU
/
62
Technical
data
MODELS
Power (kVA) Input voltage range (+/-%) Regulation speed (ms/Volt) Precision +/-% Equipment Rated output current Efficiency (%) Protection rating
EMY370 7/6 15/20 12/10 1 Discharger Settings Voltmeter Indicator light 10A 98 21
EMY3150 EMY3120 15/12 15/20 19/15 1 Discharger Settings Voltmeter Indicator light 21.7A 98 21
EMY3210 EMY3180 21/18 15/20 19/15 1 Discharger Settings Voltmeter Indicator light 30.4A 98 21
EMY3450 EMY3300 45/30 15/20 19/15 1 Discharger Settings Voltmeter Indicator light 65.2A 98 21
MODELS
Power (kVA) Input voltage range (+/-%) Regulation speed (ms/Volt) Precision +/-%
EMY31000 100 20 13 1 Discharger Settings Voltmeter Indicator light clean-contact int. 145A 98 21
EMY31500 150 15 17 1 Discharger Settings Voltmeter Indicator light clean-contact int. 217A 98 21
Description STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG STABILOG EMY370 EMY3120 EMY3150 EMY3180 EMY3210 EMY3300 EMY3450 EMY3600 EMY3900 EMY31000 EMY31500
Power 7/6kVA 12kVA 15kVA 18kVA 21kVA 30kVA 45kVA 60kVA 90kVA 100kVA 150kVA
Weights (Kg) 115 117 117 144 144 192 192 350 350 550 550
Dimensions (HWD) mm 1105x535x410 1105x535x410 1105x535x410 1105x535x410 1105x535x410 1105x535x410 1105x535x410 1600x650x600 1600x650x600 1600x1100x600 1600x1100x600
Code S1TY007U030RU S1TY012U040RU S1TY015U030RU S1TY018U040RU S1TY021U030RU S1TY030U040RU S1TY045U030RU S1TY060U040RU S1TY090U030RU S1TY100U040RU S1TY150U030RU
/
63
COMMUNICATION
SOFTWARE
MAIN CHARACTERISTICS
1) sequential and priority-based shutdown: PowerShield2 permits unattended shut-down of all the PCs of the network, saving any active work and the most widely used applications. Users can define their own shutdown procedures also establishing the order in which critical computers (such as servers) are to be shut down. 2) Multi-platform compatibility : PowerShield2 assures standard management and monitoring capabilities using the TCP/IP communication protocol. This makes it possible to monitor computers with different operating systems from a single console, for example monitoring a UNIX server from a PC with Windows 98 and also connecting to UPS located in different geographical areas using dedicated networks (intranets) or the Internet. 3) Event scheduling: With PowerShield2, users can program their own procedures to shutdown, power-off and power-up their powered systems, considerably increasing system safety and, equally important, power economy. 4) Messages management: PowerShield2 keeps users constantly informed of the status of the UPS both locally and also by sending messages to network users. It is also possible to define a mailing list of users who will receive e-mail messages, faxes and SMS in the case of faults or sudden blackouts. 5) Integrated SNMP agent: PowerShield2 features an integrated SNMP agent for management of the UPS via SNMP. This agent is able to send all the information about the UPS and to generate traps using the RFC 1628 MIB standard. This makes it possible to manage the UPS in compatible SNMP management stations such as HP Open View, Novell Managewise and IBM NetView.
PowerShield 2promotes efficient, user-friendly management of the UPS through display of bar charts containing all the major information such as input voltage, load applied, capacity of the batteries etc.. It is able to provide detailed information in cases of faults and also about the characteristics of the It has been UPS developed with a connected. client/server
architecture that makes it flexible and easy to use, with multi-language support and on-line help.
Windows 95,98, Me, NT 4.0 and 2000. Novell Netware 3.x, 4.x, 5.x, IntraNetWare IBM OS/2 Warp and Server, Mac OS 8.6, 9.x, 10.x The most widely used UNIX operating systems such as: IBM AIX, HP UNIX, SUN OS SPARC, SUN Solaris INTEL and SPARC, SCO Unix and UnixWare, Siemens SINIX, Silicon Graphic IRIX, Compaq True64 UNIX and DEC UNIX, Linux, BSD UNIX and FreeBSD UNIX
64
SAVING OF THE EVENTS LOG AND GRAPHIC DISPLAY OF THE MAIN VALUES
All events relating to UPS operating status are logged so that the user can also check the trend of the input voltage, of the load applied to the UPS and battery back-up.
Codes
65
COMMUNICATION SOFTWARE
Codes
KITSW058-001 KITSW063-001
NETMAN
Riello NetMan network agents are able to monitor and control the UPS via a network. Ideal for UPS integration in medium/large size networks. High level reliability and flexibility for management of multi-server shut-down. Management of UPS information and sending of multi-standard commands: SNMP with RFC1628 and proprietary Mib for management with NMS type HP OpenView or CA Unicenter TNG HTTP TELNET
Compatible with PowerShield2 software for complete multi-standard flexibility. Supports all the Riello UPS lines.
Description External network agent Ethernet NetMan 101 (box version) Network agent with Ethernet NetMan 102 card (slot version) External network agent Token ring NetMan 203 (box version)
Codes
ACCSA1XXRU-01 ACCSA2XXRU-01 ACCSA3XXRU-01
USB CONVERTER
Permits connection of the UPS to Macintosh computers or PCs with Windows 98 and 2000.
Description USB Converter
Codes
ACCUSBXXRU-01
MULTIPLEXER
Riello multiplexers are multiplexers for communication between UPS and PC, compatible with PowerShield2 software and controlling several PCs not connected to the same LAN or for reasons of security on PCs used as proxy server. Compatible with all Riello UPS equipment with RS232 serial port.
Codes
KITSW070-001 KITSW071-001 KITSW072-001
Description 4 serial output Multiplexer for Master Dialog RM RT line 5 serial output Multiplexer for all UPS lines excluding Master Dialog RM RT 10 serial output Multiplexer for all UPS series excluding Master Dialog RM RT
/
66
PRODUCT START-UP providing assistance during initial start-up and also instructing UPService, our Technical Assistance organization, comprises highly specialized technicians able to provide valid, reliable and competent technical support and an efficient after-sales service. UPService provides Customers with the following services:
a CALL CENTER with toll-free number for direct contact with the UPService organization. CALL CENTER personnel are always ready to provide customers with advice regarding the most suitable product for their applications and also to provide consultancy regarding equipment installation and maintenance . UPService offers Customers the possibility
personnel. The Technical Assistance service can also make preliminary surveys to verify suitability of the installation site, analyze possible problems with the site, disconnect or relocate equipment. It is specifically recommended that all UPS with panel type installation be put into service by the technical assistance service.
of stipulating MAINTENANCE CONTRACTS in order to minimize the risks and costs of UPS faults. The various types of contract comprise formulas that range from a simple periodic inspection up to total solutions including repairs, replacement of spare parts and periodic visits.
the new TELEGUARD TELEASSISTANCE service
FAST & NEW the new, free and immediate UPS assistance service. The FAST & NEW service is provided for UPS with a maximum power of up to 4000VA and within the 24-month warranty period. In the case of faults or failures, UPService restores a UPS to operation, for which the remaining warranty period will continue. The only charge for the Customer is that of forwarding the correctly packaged faulty UPS. FAST & READY is a service offered at the customers site, and is for large-size UPS that cannot be transported, both under warranty or after the end of the warranty period. Fast repairs are also guaranteed by the stateof-the-art technology of the equipment and high level professional standards of the UPService personnel and in the Authorized Assistance Centers located all over Italy. UPService guarantees that spare parts will be replaced with only original products that have been tested and updated in order to preserve the original safety, reliability and quality characteristics of the UPS in time.
permits round-the-clock remote supervision of equipment. The intelligence of products (digital control) and their ability to communicate via modem means that UPService can interrogate the UPS under contract periodically and check all their past and present functioning data, sending a report to the customer, fully automatically. The UPS can also call UPService and report alarms or faults. This means that the user does not have to supervise the equipment and also promotes prompt action on the part of the assistance service according to the maintenance contract. UPService organizes regular TECHNICAL TRAINING COURSES for technical operators. For further information about the services, contact:
/
67
2.1.2 CONFIGURATIONS
Many different types of UPS have been developed in response to specific customer requirements for availability and quality of power supply intended for different types of loads, from a few Watts to many Megawatts. The current classification according to performance is indicated in the ENV 50091-3 preliminary specifications which identify three types of UPS: VFI (Voltage and Frequency Independent): more generally known as ON LINE or DOUBLE CONVERSION where the output of the UPS is independent of any fluctuations in the power voltage (mains) and frequency variations are maintained within the limits prescribed by the ENV 61000-2-2 (CEI 110-10) specifications. This type of UPS can operate as a frequency converter (see fig. A). VFD (Voltage and Frequency Dependent): more commonly known as OFF LINE where the output of the UPS depends on fluctuations of the power supply (mains) voltage and frequency variations
static static switch
converter convertor inverter inverter
BATTERY
mains
AC DC
DC AC
AC AC
output
bypass bypass
manual bypass manual bypass
VI (Voltage Independent): usually known as LINE INTERACTIVE where voltage fluctuations are stabilized with normal operating limits by passive/electronic regulation devices (see fig. B).
DC AC
BATTERY
DC AC
inverter
output
EMI FILTER
mains disturbances
AC AC
mains Conditioner Line conditioner
BATTERY
AC DC
DC AC
inverter
AC AC
bypass
static switch convertor
output
BATTERY
AC DC
DC AC
inverter
AC AC
bypass
mains
manual bypass
/
69
P O W E R
S U P P L Y
P R O B L E M S
transmission of the information via a simple twin pair connection. In some cases, it may be advisable to connect a UPS to the supervision system using existing computer networks (SNMP-Simple Network Management Protocol)
fication of the method by which the neutral (isolated neutral) is connected to ground. Application of the provisions of Articles 413.1.5.1 and 413.1.5.4 of the above-mentioned CEI 64-8 specification is not necessary as it is unlikely that a second fault will occur after the first fault during the time the back-up power supply is operating. However, in the case of a mains failure not caused by the opening of a protection ahead of the UPS, this will not function in a cell as there are no changes to the neutral arrangements. In this case, operation is battery-powered. As a result, when the UPS operates temporarily in a cell, the protections established for the IT system need not be provided.
3.1.1 SAFETY
- The EN 50091-1-1 (CEI 22-13) standard prescribes the basic safety requirements for UPS accessible to the operator; - The EN50091-1-2 (CEI 22-16) standard regulates UPS with limited accessibility (inside cabinets, etc.).
3.1.4 PERFORMANCE
The ENV50091-3 (CEI 22-14) draft standard is intended to promote improved understanding between the manufacturer and customer through adequate description of performance and related test methods.
/