Version 1.0 Table of Contents This CD-Rom contains the information necessary to install, operate and maintain the Siemens, Cerberus Division MXL/MXLV and MXL-IQ Fire Protection Control Panels
Contents
MXL/MXLV Control Panel P/N 315-092036CD-8 MXL-IQ Control Panel P/N 315-093624CD-9
Navigation
There are three ways to navigate: 1) Use the left hand index column (which appears as you proceed) 2) Use the green buttons above to get to the corresponding manual 3) Use the arrows in the menu bar above There are 2 ways to enlarge or reduce: 1) Use the magnifying glass in the menu bar above 2) Use the three different page views in the menu bar.
Cerberus Division
CERBERUS PYROTRONICS
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932 P/N 315-093624CD-9
www.PDF-Zoo.com
Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
CAUTION ALL WIRING MUST BE DONE AS DESCRIBED BELOW TO OBTAIN SAFE AND PROPER SYSTEM OPERATION.
1. Earth ground the MXL-IQ enclosure properly; see the latest edition of the National Electrical Code for approved methods. Conduit ground is NOT adequate. 2. Separate all wiring for initiating devices (i.e., detectors, manual stations, TRI modules, etc.) from all other wiring in the MXL-IQ enclosure. To wire the System in compliance with UL 864, refer to the Installation and Power Limited Wiring Instructions for the MSE-3L Enclosure, P/N 315-095445. 3. INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded electrical box, including those in the MXL-IQ enclosure. 4. Connect shield cable drain wire ONLY inside the MXL-IQ enclosure. 5. No wiring used for any of the following can run outside the building: an ALD loop a RS-485 network an NAC circuit used for audibles a CZM-1B6 or CZM-4 initiating device loop For additional wiring information, refer to this manual or call Siemens Building Technologies, Inc. Technical Support Department at 1-800-248-7976.
www.PDF-Zoo.com
Table of Contents
Description ______________________________ 1 - 1
Introduction ___________________________________________________ 1 - 1 Software ______________________________________________________ 1 - 1
Minimum MXL-IQ Control Panel Configuration ________________________ 1 - 3
Chapter 1
www.PDF-Zoo.com
Table of Contents
Chapter 2
Installation ______________________________ 2 - 1
General Guidelines For Installing The MXL-IQ ________________________ 2 - 1
www.PDF-Zoo.com
ii
Table of Contents
Operation _______________________________ 3 - 1
Introduction ___________________________________________________ 3 - 1
Addresses ____________________________________________________ 3 - 1 System Modules _______________________________________________ 3 - 2 Remote System Modules ________________________________________ 3 - 2
Chapter 3
Alarm ________________________________________________________ 3 - 6
How The System Annunciates Fire Alarms __________________________ 3 - 6 Viewing the List of Alarms ________________________________________ 3 - 7 How to Block Acknowledge A Fire Alarm ____________________________ 3 - 7 How to Individually Acknowledge A Fire Alarm ________________________ 3 - 7 Silencing The System ___________________________________________ 3 - 7
Supervisories __________________________________________________ 3 - 8
How The System Annunciates Supervisories _________________________ 3 - 8 Viewing the List of Supervisories __________________________________ 3 - 8 How to Block Acknowledge a Supervisory ___________________________ 3 - 8 How to Individually Acknowledge a Supervisory _______________________ 3 - 9
Troubles ______________________________________________________ 3 - 9
How The System Annunciates Troubles _____________________________ 3 - 9 Viewing The List of Troubles ______________________________________ 3 - 9 How to Block Acknowledge a Trouble______________________________ 3 - 10 How to Individually Acknowledge a Trouble _________________________ 3 - 10
www.PDF-Zoo.com
iii
Table of Contents
Security Conditions_____________________________________________ 3 - 10
How The System Annunciates Security Conditions ___________________ 3 - 10 Viewing the List of Security Conditions _____________________________ 3 - 11 How to Individually Acknowledge a Security Condition _________________ 3 - 11
www.PDF-Zoo.com
iv
Table of Contents
www.PDF-Zoo.com
Table of Contents
Control Output on/off ___________________________________________ 3 - 38 Control Loop Arm _____________________________________________ 3 - 39 Control Loop Disarm ___________________________________________ 3 - 39 Control Net Link Request _______________________________________ 3 - 40 Control ANALASER ___________________________________________ 3 - 40 Control Percent/ft _____________________________________________ 3 - 41 Control Percent/ft - Senstvty _____________________________________ 3 - 41 Control Percent/ft - Pre-alarm ____________________________________ 3 - 41 Control Change Apps __________________________________________ 3 - 42
Chapter 4
www.PDF-Zoo.com
vi
Table of Contents
Chapter 5
Chapter 6
www.PDF-Zoo.com
vii
Table of Contents
Audible Silenced Event __________________________________________ 6 - 8 Override Event ________________________________________________ 6 - 8 Audible Unsilenced Event ________________________________________ 6 - 8 Password Event _______________________________________________ 6 - 8 Configuration Changed Event _____________________________________ 6 - 9 Manual Sensitivity Set Event ______________________________________ 6 - 9 Auto Sensitivity Set Event ________________________________________ 6 - 9 Logic Sensitivity Set Event ______________________________________ 6 - 10 History Print Formats At The MXL-IQ Panel _________________________ 6 - 10 MXL-IQ To CSG-M Download Formats _____________________________ 6 - 13 History Download Sequence _____________________________________ 6 - 14
Chapter 7
www.PDF-Zoo.com
viii
Table of Contents
Compatible Devices _____________________________________________ A - 1 Device Analog Voltages __________________________________________ B - 1 MXL-IQ Battery Calculations _______________________________________ C - 1 MXL-IQ Power Supply Load Calculations _____________________________ D - 1 Alarm Verification _______________________________________________ E - 1 Envirolink _____________________________________________________ F - 1 Latching/Non-Latching Troubles ____________________________________ G - 1 Installing A Security Point ________________________________________ H - 1 Application Specific Detection (ASD) ________________________________I - 1 MXL-IQ Trouble Messages _________________________________________ J - 1 Power Limited Wiring ____________________________________________ K - 1 New Two Stage Alarm ___________________________________________ L - 1 Pre-alarm, Dual Criteria Logic Functions, and Percent Per Foot Obscuration Features ___________________________________________ M - 1 MXL-IQ Spare Parts List __________________________________________ N - 1 New Features for MXL-IQ Revision 6.0 and Higher ______________________ O - 1
Appendix
www.PDF-Zoo.com
ix
Table of Contents
www.PDF-Zoo.com
+D=FJAH
Description
The CERBERUS PYROTRONICS MXL-IQ Control Panel is an advanced fire protection and alarm control panel that provides superior fire protection and multiplexed alarm reporting. The MXL-IQ Control Panel can monitor up to 4 analog loops, each containing up to 60 CERBERUS PYROTRONICS intelligent devices. The MXL-IQ Control Panel can control a wide variety of System outputs, such as: Conventional Form C relay contacts Solid State outputs Supervised outputs to control Alarm Notification Appliances Municipal Tie outputs Leased Line outputs The MXL-IQ Control Panel can process logical decisions based on the status of initiating devices. The System can respond with customer-specified sequences of output circuit operation. The System continuously checks all software and hardware for proper operation. It continuously checks all System memory components, control panel electronic hardware, and the System program. A hardwire watchdog circuit is provided to ensure that System programs are functioning properly. If a problem develops with the program or processor, the watchdog circuit places the System into a trouble condition and resets it. To ensure reliable operation, the MXL-IQ System is composed of independent modules, each with its own microprocessor. If the main panels central processing unit stops, these modules, operating in default, still annunciate any alarm or trouble through common lines called Any Alarm and Any Trouble. All of the modules communicate with the MXL-IQ Panel through a serial communications System. All modules are continuously supervised for their presence and for proper operation. Problems are shown on the display to aid in servicing and troubleshooting (See Using the Menu in the OPERATIONS section). The MXL-IQ System is designed so that fire alarm operation has first priority over all other modes of operation. If the System loses battery and commercial power, it automatically goes through an initialization routine when power returns.
INTRODUCTION
The MXL-IQ software was written in a highlevel language for ease of maintenance. The software incorporates a multitasking operating system that allows the microprocessor to handle many tasks almost simultaneously. This enables the MXL-IQ System to handle communications to all initiating and output option boards and to the annunciator. This also enables the MXL-IQ System to check that everything is running.
SOFTWARE
1-1
www.PDF-Zoo.com
Description
CERBERUS PYROTRONICS
MXL-IQ
Exterior View
Interior View
www.PDF-Zoo.com
1-2
Description
When the MXL-IQ Control Panel receives power, the System runs a start-up procedure that sets up all initial conditions. The System then starts the operating system and the initialization routines for all of the tasks, most of which concern handling System modules. When the display task is finished initializing, it displays the default time and date at power-up. Initialization of other modules may take several seconds, but this takes place in the background and so does not affect System operation. The MXL-IQ System polls all network addresses to see that all specified modules are present and that there are no unspecified modules. Any modules or devices that do not agree with the programmed data are reported as troubles on the annunciator.
Minimum MXL-IQ Control Panel Configuration To Meet NFPA 72 Local, Municipal Tie, Remote Station, Proprietary, And Central Station, UL 1076, And NFPA 12A, 13, And 2001
Table 1 presents the minimum configuration necessary to meet NFPA 72 Local, Municipal Tie, Remote Station, Proprietary, and Central Station, UL 1076, and NFPA 12A, NFPA 13 and NFPA 2001. NFPA Minimum Quantity
Module
SMB-2(c) MPS-6/12 MKB-4 MOM-2 MOM-4 CSM-4 CZM-4 ALD-2I CZM-1B6 ----------TSW-2 PIM-1 PIM-2 PAL-1 NET-7 MOI-7 MOD-16 MID-16 CRM-4 CMI-30 0 X = not required * **
Description
MXL-IQ Main Unit Power Supply Keyboard/Annunciator Panel Optional Module Card Cage Optional Module Card Cage Signal Module Conventional Zone Module Analog Loop Driver Remote Conventional Zone Module Batteries(e,f) Tamper Switch Peripheral Interface Module Peripheral Interface Module Logging Printer Communication Interface Voice and Annunciator Driver Output Driver Input Module Relay Module MXL/CXL Interface
12A, 13, or 20 01
Use Silent Knight listed models 5128/5129 and 5230. One CSM-4 circuit must be configured for alarm transmission. In addition, depending on the local authority having jurisdiction, additional circuits may be required for Supervisory or Trouble transmission. *** Any one of these modules is sufficient as an initiating device. **** Only TRI-60/B6, TRI-60R/B6R, and TRI-60D/B6D can be used as security devices.
NOTES: a. See pages 7-33 to 7-34 for NFPA 72 Central Station. b. Refer to the MXL-IQ Wiring Diagram, P/N 575-293638 at the end of the manual. c. The SMB-2 must be programmed by CSG-M for all System configurations (See CSG-M Programming Manual, P/N 315-090381). d. UL 1076 requires a Model TSW-2 tamper switch and a PAL-1 printer. e. The batteries available are: BP-61, BTX-1, and BTX-2. The BP-61 is a module consisting of four 6V, 15 AH batteries. The BTX-1 batteries are a pair of 12V, 31 AH batteries. The BTX-2 batteries are a pair of 12V, 55 AH batteries. Actual battery size depends on System configuration. f. See Appendix C for Battery Calculations. g. The CMI-300 is not listed for UL 1076 application. h. Refer to the CSM-4 Installation Instructions (P/N 315-090854) for programming.
TABLE 1 Minimum MXL-IQ Configuration to Meet NFPA 72 Local, Auxiliary, Remote Station, Proprietary, and Central Station Connections, UL 1076, and NFPA 12A, NFPA 13, and NFPA 2001 www.PDF-Zoo.com
1-3
Description
BATTERY
P1 MPS-6
P14 MPS-12
P2 BATTERY P3 POWER TO MOM-4 2 AMP MAX. 4 3 2 1 4 3 2 1 5 4 3 2 1 TB1 P15 S7 S4 P10 1 P4 PRINTER PROGRAMMER 1 P5 P6 MOM-4 1 TB2 LOOP 1 P13 GND FAULT DISCONNECT TO ANN-1 TB3 LOOP 2 F4 MOM-4 15 AMP F1 MPS-6 8 AMP P8 1
SMB-2
System read-only memories (EPROMs) System random-access memory (RAM) FLASH memory for CSG-M Watchdog circuitry Network interface circuitry
6
I C 1 1 0 I C 1 1 1 I C 1 1 2 I C 1 1 3 I C 1 1 4
TRBL
5 4 3
OFF 1 P17
ON ALR
2 1
D2300CP
24 VDC unregulated supply Two analog loops (initiating/control) Two notification appliance circuits (audible circuits) Two dry-contact relays (Form C)
www.PDF-Zoo.com
1-4
Description
www.PDF-Zoo.com
1-5
Description
PAL-1
The PAL-1 Logging Printer provides a paper record of the activity of the MXL-IQ System.
www.PDF-Zoo.com
1-6
Description
BP-61 Batteries
The BP-61 is a module consisting of four 6V, 15 AH batteries. The BP-61 is recommended for the NFPA 72 Local and Proprietary, and the UL 1076 Systems. Actual battery size depends on System configuration. See Appendix C for battery calculations.
BTX Batteries
The BTX-1 batteries are a pair of 12V, 31 AH batteries. The BTX-2 batteries are a pair of 12V, 55 AH batteries. Actual battery size depends on System configuration. See Appendix C for battery calculations.
The following modules are available as options to the MXL-IQ Control Panel: MOM-2 Card Cage MOM-4 Card Cage CSM-4 Signal Module CMI-300 Interface Module CRM-4 Relay Module CZM-4 Conventional Zone Module
ALD-2I Analog Loop Driver MOI-7 Voice and Annunciator Driver* MOD-16 Output Driver* MID-16 Input Module* NIM-1R Network Interface Module
OPTIONAL MODULES
www.PDF-Zoo.com
1-7
Description
S3
G1
S2
G2
The CSM-4 Signal module controls 2 supervised notification appliance circuits. Each circuit is capable of either Style Z (Class A) or Style Y (Class B) operation. Each circuit can be individually configured for notification appliances, municipal tie, leased line, or releasing service per NFPA 12A, NFPA 13, and NFPA 2001.
S4
www.PDF-Zoo.com
1-8
Description
www.PDF-Zoo.com
1-9
Description
The MOI-7 has two LEDs to indicate the status of the MXL-IQ network interface: the TRANSMIT LED blinks when the MXL-IQ/MOI-7 communication is working the TROUBLE LED goes to steady when MOI cannot communicate
S1
www.PDF-Zoo.com
1-10
Description
www.PDF-Zoo.com
1-11
Description
The intelligent/analog devices described below are available for use with the MXL-IQ Control Panel (SMB-2). The UL identifiers for compatibility are the same as the model names specified below. duct detector [ID-6OP(d)]. It uses either a DB-3S low profile mounting base, a DB-X3RS mounting base with relay, an AD-3P duct housing, or an ADBI-60 audible base.
www.PDF-Zoo.com
1-12
Description
www.PDF-Zoo.com
1-13
Description
www.PDF-Zoo.com
1-14
Description
The conventional devices described below are available for use with the MXL-IQ Control Panel. The UL identifiers for compatibility are the same as the model numbers.
CONVENTIONAL DEVICES
www.PDF-Zoo.com
1-15
Description
www.PDF-Zoo.com
1-16
+D=FJAH
Installation
Remove all system power before installation, first battery and then AC.
This section provides general installation instructions for mounting, wiring, and checkout of the CERBERUS PYROTRONICSTM MXL-IQ Control System. Read this section before installing the equipment to ensure proper installation. If you are not familiar with the MXL-IQ, also read the first section of the manual. Be sure to ask Siemens Building Technologies, Inc. Technical Support or an authorized Representative if you have any questions. Install and use the MXL-IQ System in accordance with the appropriate Local, NFPA, and NEC Code requirements.
INTRODUCTION
Follow Steps 1 through 13 for installation. Each step is thoroughly explained in the following pages. 1. Install the enclosure (page 2-2). 2. Install the TSW-2 Tamper Switch where required (page 2-2). 3. Pull the field wiring into the backbox and dress it to approximately where it will go (page 2-3). 4. Install the SMB-2 (page 2-3). 5. Install the MPS-6 (page 2-3). 6. Install the MKB-4 (page 2-4). 7. Install the PIM-1, PIM-2, and PAL-1 (If applicable) (page 2-5). 8. Install the MOM-2 or MOM-4 card (page 2-6). 9. Install the MOI-7, MOD-16, and MID-16 (If applicable) (page 2-9). 10. Install Field Wiring (page 2-10). 11. Check Field Wiring (page 2-10). 12. Start-up Procedure (page 2-10). 13. System Function Checkout (page 2-16).
WARNING!
Refer to the last page of the manual for a Warning Note required by the FCC for all commercial Class A computing equipment producing a clock frequency of 10K Hz or greater.
www.PDF-Zoo.com
2-1
Installation
the indicators and controls are easily accessible. NOTE: When the backbox is mounted semi-flush using the MET-3L kit, be sure that the position of the backbox permits the door to swing fully open. (See MET-3L Installation Instructions, P/N 315-095447.) When deadfront construction is required, use the IQ-DFL panel (See IQ-DFL Installation Instructions, P/N 315-095446.) When the MSE-3L is used for remote applications, use the IQ-Blank where there is no MKB-4 installed (See IQ-Blank Installation Instructions, P/N 315-095482.) To install the backbox: (Refer to Figure 21) a. Slip the door off the hinges of the box and put it to one side temporarily. b. Remove the knockouts in the backbox where field wiring is required (Refer to MSE-3L Power Limited Wiring Instructions, P/N 315-095445, for location of knockouts). c. Hold the empty enclosure against the wall at a height that provides easy access. d. Mark drill points on the wall in the center of the two slots on the upper rear of the MSE-3L. e. Drill the two holes and screw in the top screws, leaving a small gap between the wall and each top screw. f. Mount the MSE-3L on the 2 bolts and then install the bottom bolts.
Mounting height for visual and manual access to the MKB-4 Keyboard/annunciator Weight and size of enclosure Local Mounting codes Fasten the backbox securely to a clean, dry, shock-free, and vibration-free surface. Position the backbox clear of obstructions so that the door opens freely and so that
(Refer to Figure 22) If your configuration (UL 1076) requires the TSW-2 Tamper Switch, install it now. The TSW-2 mounts into the rectangular slot located in the lower right side of the MKB-4 panel. 1. Place the cable/connector and the switch terminals through the opening and press firmly into place.
2. Plug the cable on the TSW-2 into P9 on the SMB-2 after installing the SMB-2.
www.PDF-Zoo.com
2-2
Installation
(Refer to Figure 23) Unpack the SMB-2. Inspect the module, looking for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, packing material on the board, etc. The installation kit consists of the following items: Two #6 nuts Four #6 screws Six #6 washers Six #6 lockwashers Two resistors Battery cable with a wire a. Place the SMB-2 over the two studs in the upper right-hand portion of the backbox (See Figure 23). b. Secure in place using the hardware provided. Be sure the screws and nuts are tight, as they provide the earth ground connection for the SMB-2
(See Figure 24) The MXL-IQ is designed to operate from a 120 VAC, 60 Hz power source. Use a separate or dedicated circuit-breaker. Wire in accordance with local codes and Article 760 of the NEC, NFPA 70, latest edition. Run the earth ground from a suitable source to the MPS-6/12. Check local requirements. Conduit is not an acceptable conductor. Make sure that the dedicated circuit-breaker for the MXL-IQ is turned off at the mains. Place the mounting bracket for the MPS-6/ 12 over the two studs provided in the enclosure as shown in Figure 24. Secure the MPS-6/12 to the MSE-3L by slipping the flat washers, then the
www.PDF-Zoo.com
2-3
Installation
lockwashers, and finally the nuts over the two studs. Tighten them securely. Connect the AC mains to MPS-6/12 as follows: Terminal Black (hot) White (neutral) Green (earth ground) 1 2 3 Unpack the MKB-4. Inspect the module for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, and packing material on the board. NOTE: The MKB-4 is supplied with the keyboard/annunciator mounted to the hinged panel. Setting the Network Address (See Figure 25) a. Before installing the MKB-4 panel, set its network address on S1, the switch on the ANN-1 board located on the back of the MKB-4. Use dipswitches SW1 and SW2 on switch S1 to set the network address of the MKB-4. Refer to Table 2 for switch settings. b. The MKB-4 module address is always set within network addresses 248 through 251. c. One supervised MKB-4 must be installed at network address 251. Other supervised MKBs may be at the other addresses.
Install the 14 gauge green ground strap spade lug side to Terminal 3 (green, earth ground) of the MPS-6 or MPS-12. Secure the ring lug side of the ground strap to the nearest available stud in the enclosure. The stud size may vary depending on the actual system modules and enclosure used. Because the stud may be either a #10 thread of " thread, nuts for both have been provided. The ground strap provided is long enough for all applications and the ring lug is good for both #10 and " studs. If possible, install the ring lug under one of the lockwashers and nuts which secure the MPS-6 or MPS-12 itself. Connect the 3-wire cable coming from the MPS-6 to the SMB-2, P1, or connect the 8wire cable coming from the MPS-12 to the SMB-2, P14.250
Remove all system power before installation, first battery and then AC.
NOTE: Switches S1-SW3 and S1-SW4 are for future use. Switch S1-SW5 is used to select suptervision.
Setting Supervision: Use switch S1-SW5 on the ANN-1 to select or deselect supervision. If your ANN-1 has a switch with position 1 indicated on the left-hand side, ignore the printing on the switch. SW1 on S1 is at the extreme righthand side of S1, regardless of any other marking.
www.PDF-Zoo.com
2-4
Installation
NOTE: When you select non-supervision for an annunciator, there must also be one and only one supervised annunciator at the same address. The supervisory mode is independent of the network address. To set for supervision S1-SW5 = Closed (ON) To set for non-supervision S1-SW5 = Open (OFF) Mounting the MKB-4 (Refer to Figure 26) 1. Install three screws in the first group of three tapped holes in the right flange. Leave a 1/8-inch gap between the head of the screw and the flange. Slide the slots of the MKB-4 panel hinge under the head of the screws and tighten. 2. After the MKB-4 is mounted to the enclosure, connect the cable (P/N 555192238) between P1 on the ANN-1 (on the back of the MKB-4) and P8 on the SMB-2. CAUTION: Be sure the black tracer wire on the edge of the cable is close to the 1 on position 1 of connector P1 on the ANN-1 and the 1 on position 1 of P8 on the SMB-2.
P1 P2
MSE-3L
d Cable supplie with PIM-1 92242) (P/N 555-1
Back of MKB-
1 P1
ANN-1
TB1
PIM-1
B-4)
www.PDF-Zoo.com
2-5
Installation
PIM-2/PAL-1 The PIM-2 and printer require a standby power source in the event of a loss of primary input power (AC mains). Refer to Figure 28 for the connection of a UPS to meet this requirement. 1. Before installing a PIM-2 in the MXL-IQ system, a PIM-1 must be already installed. 2. Wiring from the PIM-1 to the PIM-2 must be within 25 feet in rigid conduit (Refer to Table 3).
TABLE 3 PIM-1 TO PIM-2 INTERFACE REQUIREMENTS (Supplied by installer)
PIM-1, TB 4 (Rx) 5 (Tx) 7 3 (BUSY) 2 (COMMON) TO PIM-2 Inpt Pin No. 2 (TxD) 3 (RxD) 4, 5 (RTS, CTS) 20 (DTR) 7 (GRD)
5. Set the dipswitches on the back of the PIM-2 to agree with the communications parameters configured in the CSG-M. Refer to Table 4 for the dipswitch definitions.
MOM-2
3 #10 nut s 3 #10 flat washers
MOM-4
4 #10 nut s 4 #10 flat washers 4 #10 lockwashers 1 8-conductor ribbon cable 2 2-wire cables 4 card guides
3. Figure 29 shows the proper installation of the PIM-2 with the MXL-IQ system. 4. Programming the CSG-M is required when using a PIM-2 and parallel printer. Configure one of the following four printer types on the MKB-4: Supervised PIM-2 Supervised PIM-2 Supervised PIM-2 80 column color 132 column color 80 column
3 #10 lockwashers 4 #6 x 7/16 screws 2 #6-32 x 5/16 screws 1 8-conductor ribbon cable 2 2-wire cables 2 card guides
www.PDF-Zoo.com
2-6
Installation
TABLE 4 SERIAL INTERFACE COMMUNICATION PARAMETERS
Dipswitch Position (SW1) -Located at rear of PIM-2 1 BAUD RATE 960 0 480 0 240 0 120 0 30 0 DATA BITS 8 7 PARITY Even Odd PARITY Disable Enable FLOW CONTROL Hardware Software PORT TYPE
NOTE: When setting Switch S1, OFF=UP=OPEN ON=DOWN=CLOSED
ANN-1
NOTES: 1. Maximum cable distance from PIM-1 to PIM-2 cable is 25 feet. The two modules must be in the same room. 2. The maximum distance from the PIM-2 to the parallel printer is 6 feet. The two modules must be in the same room. 3. PIM-2 power (PWR) is connected to the 5 VDC, 600mA transformer supplied with the PIM-2. The transformer requires 120 VAC, 60 Hz, 0.5A max. 4. For NFPA 72 Local, Auxiliary, and Remote Station configurations, connect the output of the PIM-2 to any UL listed EDP Centronics parallel printer. 5. The parallel printer must support the EPSON FX command set. 6. The PIM-2 input and output connectors are DB-25 female. 7. Pressing RESET on the PIM-2 causes the unit to read the SW1 settings. The status LED is lit when the unit is powered. Do not use the COPY button. 8. For NFPA Proprietary and UL 1076 configurations, use parallel printer Model PAL-1, a UL listed for fire Centronics parallel printer. 9. The parallel printer is supervised for AC, on/ off line, paper out, paper jam, and connection to the PIM-2. 10. The PIM-2 is supervised for power, connection to the printer, and connection to the PIM-1. 11. After loading paper in the PAL-1 printer, turn off the power and follow the steps below: While pressing the LOAD PARK button, turn on the power to the PAL-1 printer. Continue pressing the LOAD PARK button for 5 seconds. Release the LOAD PARK button. The current setting will print. When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON LINE button.
2 ON ON OFF OFF ON
3 OFF OFF ON ON ON
OFF ON OFF ON ON
MKB-4 PIM-1
SEE INSTL. INSTR. P/N 315-091462 TB1
(REFER TO TABLE 4)
CENTRONICS PARALLEL
OUTPUT
INPUT
SW1
PWR
CABLE SUPPLIED WITH PIM-2 (SEE NOTE 2) SUPERVISED (REFER TO NOTES 9 AND 10) THE CONNECTION IS NOT SUPERVISED FOR DATA INTEGRITY BETWEEN PIM-2 AND THE PRINTER.
PIM-2 POWER TRANSFORMER SUPPLIED WITH PIM-2 (SEE NOTE 3) INSTALL IN UL LISTED GANGBOX
XFMR
www.PDF-Zoo.com
2-7
Installation
To mount the MOM-2/4 in an MSE-3L enclosure: 1. Hold the MOM-2/4 so that terminal blocks TB2 and TB4 are on the left. 2. Place the module vertically on the mounting studs near the top left of the enclosure as shown in Figure 23 on page 2-3. 3. Fasten the MOM-2/4 in position with the No. 10 flatwashers, lockwashers, and nuts provided. To install the card guides (See Figures 30 and 31): Install the card guides included in the package using the #6 x 7/16 screws provided. (The MOM-4 is shipped with the mounting screws for the card guides already installed.) 1. Mount the long screws. 2. Make sure that the locating pin on the guide is seated in the hole on the MOM-2/4. 3. Tighten the screw. Repeat this process for the remaining card guide(s). The MOM-2/4 is now ready to accept the optional modules. If the system does not require the installation of any halfwidth modules, install the two #6 x 5/16 screws in the center holes where the additional card guides would be placed. Plug-in Cards for the MOM-2/4 Determine which optional plug-in modules are used in your CSG-M configuration. Next, decide where they should be installed by checking the following factors: 1. The size of each module. The CSM-4 and CRM-4 each occupy two adjacent slots. 2. How the field wiring will be installed. 3. The maximum load current permitted for the MOM-2/4 is 6 amps for the MPS-6 or 12 amps for the MPS-12. This current must be derated by the current drawn from SMB TB5 (CZM-1B6 power and NAC #1 and NAC #2). When the system includes an external auxiliary power supply, the maximum load current permitted depends on the application. Refer to Table 5 for the maximum current required by each module under full load conditions. MOM-2/4 Electrical Installation 1. Attach the 8-conductor ribbon cable to P6 on the SMB-2, engaging the locking rib of the cable with the locking tab on P6. 2. Attach the other end of the 8-conductor ribbon cable to P7 on the MOM-2/4, engaging the locking rib of the cable with the locking tab on P7. 3. Connect one end of the 2-wire 24 VDC cable to P3 on the SMB-2, using the locking tab to lock the cable onto P3.
MOM-2
www.PDF-Zoo.com
2-8
Installation
4. Connect the other end of the 2-wire cable into P5 on the MOM-2/4. The 2-wire cable that attaches P5 on the MOM-2/4 with P3 on the SMB-2 feeds 24 VDC full-wave unfiltered DC power to the MOM-2/4. This is the main power used by the optional modules. The 8-conductor ribbon cable supplies 5 VDC and communication between the SMB-2 and the MOM-2/4.
TABLE 5 MAXIMUM MODULE LOAD CURRENTS ALD-2I CMI-30 0 CRM-4 CSM-4 CZM-4 NIM-1R 90mA (120 devices in alarm) 96mA 75mA (4 relays energized) 34mA (no alarm indicating appliances connected) 720mA (maximum with 4 zones in alarm) 0mA
The following example assumes that no power is drawn from SMB-2 TB5 (CZM-1B6 power and NAC #1, NAC #2).
Example:
With 1 CZM-4 + 1 CRM-4 + 1 CSM-4, the total load current = 0.72 + 0.075 + 0.034 = 0.83A The remaining available current = 12.0 (MPS-12) or 6.0 (MPS-6) - 0.83 = 11.83 (MPS-12) or 5.83 (MPS-6). The remaining current may be used for NAC power.
3. If a connection to a MOD-16 module on another rail is required, use the optional cable P/N 555-190941. MID-16 (See Figure 19, page 1-11) 1. Mount the MID-16 in one System 3 type module space using the four screws provided. 2. Connect the MID-16 to the module to its left with the 10-position ribbon cable P/N 555-190940 provided. This module may be either an MOI-7, MOD-16, or MID-16. 3. If a connection to a module on another rail is required, use the optional cable P/N 555-190941.
MOD-16 (See Figure 18, page 1-10) 1. Mount the MOD-16 in one System 3 type module space using the four screws provided. 2. Connect the MOD-16 to the MOI-7 with the 10-position ribbon cable P/N 555190940 provided with the MOI-7.
www.PDF-Zoo.com
2-9
Installation
TABLE 6 WIRING TO THE SMB-2
Screw Terminal TB5 12-9 TB5 8-5 TB5 4-1 TB4 TB4 TB3 TB2 TB1 TB1 TB1 6-4 3-1 4-1 4-1 1-2 3 4-5 Application CZM-1B6 Power Notification Appliance Circuit 2 Notification Appliance Circuit 1 Trouble Relay Alarm Relay Analog Loop 2 Analog Loop 1 MXL-IQ Network for MOI-7 and RCC-1/1F Do Not Use MPS-6/12 and MOM-2/4
NOTE: See SMB-2 Connections and Ratings for a more detailed description of the screw terminals.
Initiating Devices Install all initiating device bases and end-ofline devices where applicable. Install all initiating devices. Refer to the specific installation instructions provided with each device. Notification Appliances Install all notification appliances (bells, strobes, etc.) Refer to the specific installation instructions provided with each device. Check Resistance Between Wiring Circuits Start with the wire that goes to TB5-12 on the SMB-2. Check the resistance between that wire and all other field wires that will be connected to the SMB-2. Also, check the resistance between that wire and all wires connected to the screw terminals on the MOM-2/4. Refer to Table 8 for acceptable resistance readings. If the readings are good, connect the wire to TB5-12. Repeat the above procedure for the next wire on the SMB-2. When the SMB-2 is complete, continue with the MOM-2/4 (if it is installed).
NOTE: See CSM-4 Connections and Ratings for a more detailed description of the screw terminals. 1-3 4-6 11-13 14-16 Dry Contact 1 Dry Contact 2 Dry Contact 3 Dry Contact 4
CRM-4
NOTE: See CRM-4 Connections and Ratings for a more detailed description of the screw terminals. 1-4 5-8 9-12 13-16 Conventional Conventional Conventional Conventional Zone 1 Zone 2 Zone 3 Zone 4
CZM-4
NOTE: See CZM-4 Connections and Ratings for a more detailed description of the screw terminals. CMI-30 0 1-4 CXL Modem Connection
NOTE: See CMI-30 0 Connections and Ratings for a more detailed description of the screw terminals. NIM-1R 1-2 3-4 12-16 XNET Network Pair A / FSI / AnaLASER XNET Network Pair B NCC XNET Interface
NOTE: See NIM-1R Connections and Ratings for a more detailed description of the screw terminals. ALD-2I 1-4 5-8 Analog Loop 1 Analog Loop 2
NOTE: See ALD-2I Connections and Ratings for a more detailed description of the screw terminals.
www.PDF-Zoo.com
2-10
Installation
1.System Status When beginning the start-up procedure, the condition of the system is as follows: All field wiring is connected to all screw terminals, except for the analog loops they should be disconnected. All field devices are installed. No modules are installed in the MOM-2/4 cage. 2.Create a Test Configuration Create a test configuration on your CSG-M that includes every module that will be on your final system. Do not include any initiating devices. You will use this test configuration in checking out the System. 3.SMB-2 Checkout Minus the Analog Loops Turn on the AC power to the system. The power light on the MKB-4 turns on the System displays the default message:
CERBERUS PYROTRONICS MXL
13. 8 (+) to 5 (-) 2.2K 10%
TABLE 8 FIELD WIRING CHECKOUT SMB-2 EXTERNAL WIRING AND TROUBLESHOOTING GUIDE
TB-5 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. Resistance Between Wires Chassis to 1-12 11 to 12 9 to 10 7 to 8 5 to 6 3 to 4 1 to 2 9 to 12 5 to 8 1 to 4 9-12 to 1-8 5-8 to 1-4 Desired Results >1 Meg <1.5 ohms <1.5 ohms <1.5 ohms <1.5 ohms <1.5 ohms <1.5 ohms >1 Meg >1 Meg >1 Meg >1 Meg >1 Meg Probable Cause Of Problem Short in wiring. Line open; Line too long. Line open; Line too long. Line open; Line too long. Line open; Line too long. Line open; Line too long. Line open; Line too long. Line shorted. Line shorted. Line shorted. Line shorted. Line shorted. Line shorted; Line open; Wrong EOL device; No EOL device; Device wired backward; Device not polarized. Line shorted; Line open; Wrong EOL device; No EOL device; Device wired backward; Device not polarized. Line shorted.
Transfer the test configuration from your computer to the MXL-IQ. Refer to the CSGM Manual (P/N 315-090381) for the correct procedure. After the transfer process is complete, MXL-IQ resets itself; after 5 minutes, the state of the system should be as follows: No trouble condition for the signaling circuits on the main board. A battery trouble condition if the battery option was selected. All optional modules configured on the system are in trouble since they are not yet installed. 4.SMB-2 Analog Loop Checkout Modify your test configuration by adding to it the analog devices that are connected to analog loop 1. Turn off the power and connect the field wiring to analog loop 1 on the SMB-2. Turn on the power. Wait for the System to initialize (approximately 3 minutes).
14.
4(+) to 1 (-)
2.2K 10%
15.
12 to 1-8 12 to TB2/3 1-4 12 to all MOM-2/4 8 to 1-4 8 to TB2/3 1-4 8 to all MOM-2/4 4 to TB2/3 1-4 4 to all MOM-2/4 Resistance Between Wires Chassis to all terminals 1 to 2 3 to 4 1 to 4 1 (+) to 4 (-) TB-2 (1-4) TB-3 (1-4) TB-2 (1-4) TB-5 (1-12) TB-3 (1-4) TB-5 (1-12)
>1 Meg >1 Meg >1 Meg >1 Meg >1 Meg >1 Meg >1 Meg >1 Meg Desired Results
16.
Line shorted.
Line shorted.
>1 Meg <50 ohms <50 ohms <.4F >10K ohms >1 Meg >1 Meg >1 Meg
Short in wiring. Open in wiring; Line too long. Open in wiring; Line too long. Too much wire. Line shorted. Line shorted. Line shorted. Line shorted.
(+) and (-) indicate meter lead polarity. > = greater than; < = less than
www.PDF-Zoo.com
2-11
Installation
Check the trouble list on the MKB for troubles on the devices that were just added. The troubles will be from among the following (See Appendix J for a complete list of Trouble Messages): Device multiple response Input device not responding Incorrect device ID Unspecified device responding Identify the addresses of the devices with troubles and eliminate them, reset the system, and verify that the troubles have cleared before proceeding. Modify your test configuration by adding to it the analog devices that are connected to analog loop 2. Turn off the power and connect the field wiring to analog loop 2 on the SMB-2. Turn on the power. Wait for the System to initialize (approximately 3 minutes). Check the trouble list on the MKB for troubles on the devices that were just added. The troubles will be from among the following (See Appendix J for a complete list of Trouble Messages): Device multiple response Input device not responding Incorrect device ID Unspecified device responding Identify the addresses of the devices with troubles and eliminate them, reset the system, and verify that the troubles have cleared. Unpack each module just before installation. Inspect the module, looking for such things as integrated circuits (ICs) not firmly seated in their sockets, bent IC pins, connectors not properly installed, dirt, and packing material on the board. To install the card guide that comes with the CRM-4 and the CSM-4 module: a Loosen the appropriate screw in the center of the MOM-2/4 and set the card guide in place. Make sure that the locating pin on the bottom of the card guide is in the hole on the MOM-2/4. b. Tighten the screw on the MOM-2/4 to secure the card guide.
6.ALD-2I Checkout Installing the ALD-2I Set the address of each ALD-2I. Refer to the CSG-M printout of the final configuration for the address to which each ALD-2I should be set. Refer to the ALD-2I Installation Instructions (P/N 315-091464) to set the address dipswitch. Install the ALD-2Is one at a time by inserting them in the appropriate card guides on the MOM-2/4. Make sure that the card is firmly seated in the card edge connector. Eliminate all troubles from each module before installing the next one. Modify your test configuration by adding to it any initiating devices that are connected to the first analog loop on the ALD-2I. Turn off the power; connect the field wiring to analog loop 1 on the ALD-2I. Turn on the power. Turn off the power and connect the field wiring to analog loop 1 on the SMB-2. Turn on the power. Wait for the System to initialize (approximately 3 minutes). Check the trouble list on the MKB for troubles on the devices that were just added. The troubles will be from among
www.PDF-Zoo.com
2-12
Installation
the following (See Appendix J for a complete list of Trouble Messages): Device multiple response Input device not responding Incorrect device ID Unspecified device responding Identify the addresses of the devices with troubles and eliminate them, reset the system, and verify that the troubles have cleared before proceeding. Modify your test configuration by adding to it any initiating devices that are connected to the second analog loop on the ALD-2I. Turn off the power; connect the field wiring to analog loop 2 on the ALD-2I. Turn on the power. Turn off the power and connect the field wiring to analog loop 1 on the SMB-2. Turn on the power. Wait for the System to initialize (approximately 3 minutes). Check the trouble list on the MKB for troubles on the devices that were just added. The troubles will be from among the following (See Appendix J for a complete list of Trouble Messages): Device multiple response Input device not responding Incorrect device ID Unspecified device responding Identify the addresses of the devices with troubles and eliminate them, reset the system, and verify that the troubles have cleared before proceeding.
Installing the CMI-300 Interface Module Before installing the CMI-300 in the MOM-2/4, you must do the following: 1. Check that there is a jumper installed for jumper J2, pins 1 and 2 on the CMI-300 module.
www.PDF-Zoo.com
2-13
Installation
2. Set the CMI-300 network address by using the dipswitch settings on switch SW1. Use Table 16 at the end of this chapter to set the network address. Plug the CMI-300 module in the MOM-2/4 card cage and connect the wiring as shown in CMI-300 Connections and Ratings. Eliminate all troubles from each module prior to installing the next one. Installing CRM-4 and CZM-4 Modules Set the address of each module. Refer to the CSG-M printout of the final configuration for each module address setting. Refer to the installation instructions for each module to set the address dipswitch. Install the optional modules one at a time by inserting them in the appropriate card guides on the MOM-2/4. Eliminate all troubles from each module prior to installing the next one. Installing the NIM-1R Network Interface Module The NIM-1R installs into the MOM-2/4 card cage where it occupies one full width slot. The wiring is connected to TB4 of the MOM-2 or TB3 of the MOM-4. The NIM-1R has two configuration dipswitches. Set the dipswitches before installing the NIM-1R into the MOM-2/4. Use switch SW1 to set the MXL-IQ network address. Set this switch according to the address where the NIM-1R is installed in the MXL-IQs network map. Refer to the CSG-M configuration printout for the address of the module. See Table 16 at the end of this chapter for settings. Use switch SW2 to set either the panel number for networked systems or to select FSI or AnaLASER operation. Refer to Table 9 for panel settings, Table 10 for FSI settings, or Table 11 for AnaLASER settings. 1. When installing the NIM-1R in a networked system, set the panel number to agree with the panel number for the NIM-1R assigned to the MXL-IQ System in CSG-M. 2. Switch position 8 selects Style 4 or 7 operation for the NIM-1R network. 3. When installing the NIM-1R for FSI operation, set the switch to all open (or OFF).
TABLE 10 FSI Programming
ADDR 000 87654321 OOOOOOOO O = Open or OFF
4. When installing the NIM-1R for AnaLASER connection, set the switch as follows: TABLE 11 AnaLASER Programming
ADDR AnaL ASER 87654321 XOOOOOOO
O = Open or OF F X = Closed or ON
After setting the switches, install the NIM-1R into the MOM-2/4 card cage. Make sure that the module is in the card guides and the card edge is firmly seated in the connectors on the MOM-2/4.
Installing the CSM-4 Signal Module Before installing the CSM-4 in the MOM-2/4, you must set the network address, configure each circuit according to the CSG-M program [as Local (NACs), Municipal Tie, Leased Line, or Releasing Service], and set the default modes (trouble and alarm) as follows. Refer to Table 12 for the Modes of Operation. a.Set the Network Address The network address is set on dipswitch S1 (See Figure 12, page 1-8). See the CSG-M printout for the proper address. Use Table 16 at the end of this chapter to set the switches.
www.PDF-Zoo.com
2-14
Installation
b.Set the Mode of Operation for Each Circuit The CSM-4 has one programming slide switch and one jumper for each of its two circuits. (See slide switches S3 and S4 and jumpers G1 and G2 on the CSM-4 board, Figure 12, page 1-8.) Setting these slide switches and jumpers allows the selection of four possible modes of operation. These modes correspond with NFPA standards 72 Local, Municipal Tie, Leased Line, and NFPA 12A, 13, and 2001 Releasing Service. Each circuit on the CSM-4 can be set independently for the type of operation desired. Table 12 shows how to set the switches and jumpers for circuits 1 and 2. The CSG-M printout shows the mode for each circuit.
TABLE 13 Setting the Mode of Operation for the CSM-4 (Using S3, S4 and G1, G2)
For Circuit 1 Local (NAC) Municipal Tie Leased Li ne Rel eas i ng Ser v i c e Illegal (Results in a trouble on t he CSM - 4) For Circuit 2 Local (NAC) Municipal Tie Leased Li ne Rel eas i ng Ser v i c e Illegal (Results in a trouble on t he CSM - 4) S3 Position 1 1 2 1 2 S4 Position 1 1 2 1 2 G1 No t C u t Cut No t C u t Cut Cut G2 No t C u t Cut No t C u t Cut Cut
c.Set the Degrade Modes of Operation There are two sources of degrade activation, the degrade alarm bus and the degrade trouble bus. These two buses become active ONLY when the MXL-IQ communication network fails. Dipswitch S2 on the CSM-4 sets the degrade mode of operation for each circuit.
Each circuit operates independently in the degrade mode. Dipswitch S2, positions SW1 and SW2, determines the degrade mode of operation when the trouble bus activates. Dipswitch S2, positions SW3SW6, determines the degrade mode of operation when the alarm bus activates.
www.PDF-Zoo.com
2-15
Installation
d.Degrade Trouble Activation The degrade trouble bus may ONLY be used when the circuit is used as a Leased Line trouble indicating circuit. (See Table 12.) When enabled, this trouble degrade mode ensures that a trouble will be transmitted to the receiving station even when the MXL-IQ communication network fails. Using the CSG-M printout, determine if either of the circuits is configured as a Leased Line trouble. Table 14 shows how to set dipswitch S2 (SW1 and SW2) to enable the degrade trouble activation for the desired circuit.
TABLE 14 Setting the Degrade Trouble Modes for the CSM-4 on S2
For Circuit 1 Leased Line Trouble No Trouble Activation For Circuit 2 Leased Line Trouble No Trouble Activation SW1 G1 On (Closed) Off (Open) SW2 G2 On (Closed) Off (Open)
Determine which type of degrade mode you want for each circuit and set dipswitch S2 (SW3-SW6) as shown in Table 15.
No t e : If Circuit 1 or Circuit 2 is not used for Leased Line trouble, switches SW1 or SW2 must be off (open).
e.Degrade Alarm Activation Each circuit on the CSM-4 can be set with dipswitch S2, positions SW3-SW6, to determine when the degrade alarm bus activates (See Table 12). There are three degrade alarm modes. Each circuit can be set independently from the other.
WARNING!
Prior to activating any initiating device, take steps to prevent output circuits from being activated. Failure to do so may result in building EVAC (bells), notification of fire department, elevator recall, etc. Test these operations in accordance with local codes and follow the direction of the authority having jurisdiction. Observe all safety precautions.
NOT E : When circuits are used for leased line supervisory, the alarm degrade modes must be OFF (Open).
www.PDF-Zoo.com
2-16
Installation
Test
1. Observe the display on the MKB-4.
Response
The POWER LED should be on steady. The TROUBLE LED should be off. The following message should appear on the alphanumeric display:
(Time and Date) (System Custom Message) SYSTEM NORMAL
(It may take a few minutes after power-up before the message System Normal appears.)
2. Activate every alarm causing initiating device on the System in groups of 100 or fewer. Reset the System prior to activating each group of 100.
Every device alarms and there are no troubles annunciated. Device LEDs should come on when the device is in alarm. As each device is alarmed, the custom message appears on the display, is recorded on the printer (if installed), and corresponds to the CSG-M printout for that device. The messages listed on the printer are in the order in which the devices were alarmed. Pressing the NEXT key on the MKB-4 displays the devices in reverse order. Check that all appropriate responses are activated.
Each device should cause a supervisory. As each device changes state, the custom message appears on the display, is recorded on the printer (if installed), and corresponds to the CSG-M printout for that device. The messages listed on the printer are in the order in which the devices were activated. Pressing the NEXT key displays the devices in reverse order. Check that all the appropriate responses are activated.
Each device should cause a security condition. As each device is activated, the custom message appears on the display, is recorded on the printer (if installed), and corresponds to the CSG-M printout for that device. Check that all appropriate responses are activated.
www.PDF-Zoo.com
2-17
Installation
Test
5. Activate all status devices on the System.
Response
None of the devices should cause an alarm or trouble condition. If there is a printer, the System should print the status of reporting devices. As each device is activated, the custom message recorded on the printer corresponds to the CSG-M printout for that device. Check that all appropriate responses are activated.
6. CRM-4 relays: Refer to Control Output On/Off, page 3-38, and toggle each CRM-4 relay assigned to the System. Reset the System when this test is complete.
7. CSM-4 relays: Refer to Control Output On/Off, page 3-38, and toggle each CSM-4 relay assigned to the System. Reset the System when this test is complete.
8. System Functions: Check all functions that are defined in the customer specifications.
Check that the correct relationships between initiating devices and output functions occur as defined by the customer specifications. Check that the appropriate NFPA and local codes are met (Refer to the CSG-M Logical Function Summary.)
www.PDF-Zoo.com
2-18
ADDR 192 193 194 195 196 197 198 199 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239 240 241 242 243 244 245 246 247 248 249 250 251 252 253 254 255
&%$#"!
XXOOOOOO XXOOOOOX XXOOOOXO XXOOOOXX XXOOOXOO XXOOOXOX XXOOOXXO XXOOOXXX XXOOXOOO XXOOXOOX XXOOXOXO XXOOXOXX XXOOXXOO XXOOXXOX XXOOXXXO XXOOXXXX XXOXOOOO XXOXOOOX XXOXOOXO XXOXOOXX XXOXOXOO XXOXOXOX XXOXOXXO XXOXOXXX XXOXXOOO XXOXXOOX XXOXXOXO XXOXXOXX XXOXXXOO XXOXXXOX XXOXXXXO XXOXXXXX XXXOOOOO XXXOOOOX XXXOOOXO XXXOOOXX XXXOOXOO XXXOOXOX XXXOOXXO XXXOOXXX XXXOXOOO XXXOXOOX XXXOXOXO XXXOXOXX XXXOXXOO XXXOXXOX XXXOXXXO XXXOXXXX XXXXOOOO XXXXOOOX XXXXOOXO XXXXOOXX XXXXOXOO XXXXOXOX XXXXOXXO XXXXOXXX ILLEGAL ILLEGAL ILLEGAL ILLEGAL ILLEGAL ILLEGAL ILLEGAL ILLEGAL
www.PDF-Zoo.com
2-19
Installation
www.PDF-Zoo.com
2-20
+D=FJAH
Operation
This section provides instructions for operating the MXL-IQ Control Panel. Please review the introduction to the MXL-IQ Control Panel at the beginning of this manual. NOTE: See the Table of Contents pages at the beginning of this manual for the order of this chapter. Use it to find the answers to specific questions when you are working with the System. ules and leaving gaps in the numbering, provided you do not use the fixed addresses. The specific addresses of the System modules are described in Table 17.
INTRODUCTION
Addresses
All modules and devices annunciated on the MXL-IQ are identified by an address (MMMDDD). Each address is in two partsa module address (MMM) and a device address (DDD). The number identifying the module may be as high as 254, and the number identifying the device may be as high as 248. Thus a device on a module may be identified by any number between 001-001 and 253-250. (See Table 17.) Fixed Addresses A module may be assigned to any address on the System, except for some fixed addresses that have already been assigned (See Table 17). The modules communicate to the MXL-IQ Control Panel through a serial communications network. The System continuously supervises all of the modules for presence and proper operation. You may assign a module to any address on the System, and assign addresses in any order, mixing different types of modModule Address
Module
0 01-060 0 01-060
MKB-4 MKB-4 MKB-4 MKB-4, No. 1 Reserved SMB-2 Programmer CSG-M Global (reserved)
0 01 to 250
www.PDF-Zoo.com
3-1
Operation
System Modules
ALD-2I Analog Loop Module The ALD-2I takes two adjoining module addresses. Loop 1 of the ALD-2I is at any module address and loop 2 at the next address. The analog loops on the SMB-2 are at module addresses 1 and 2 (See Table 17, page 3-1) and cannot be moved. The table below illustrates ALD-2I module addresses: ALD at Module Addresses 3 and 4 Loop 1 Loop 2
CZM-4 Conventional Zone Module The CZM-4 Conventional Zone module contains four conventional initiating device zones and two programmable LEDs. Their device addresses on the module are as follows: Zone 1 Zone 2 Zone 3 Zone 4 001 002 003 004 005 006
LED 1 LED 2
ALD at Module Addresses 15 and 16 Devices Loop 1 015-001 to 015-060 Loop 2 016-001 to 016-060 CSM-4 Signal Module The CSM-4 module contains two circuits and two programmable LEDs. Their device addresses on the module are as follows: Circuit 1 Circuit 2 LED 1 LED 2 001 002 005 006
For example, the address of zone 1 on the CZM-4, at module address 105, is 105-001. MKB-4 Keyboard/Annunciator The MKB-4 Keyboard/Annunciator occupies the fixed module address 251 (See Table 17, page 3-1). SMB-2 Main Board The SMB-2 occupies module addresses 1, 2, and 253. The module addresses 1 and 2 are analog loops. Module address 253 contains two notification appliance circuits (NACs) and two relays. The device addresses at module 253 are as follows: Common alarm relay Common trouble relay NAC 1 NAC 2 001 002 004 005
For example, the address of circuit 2 on the CSM-4 at module address 3 is 003-002. CRM-4 Relay Module The CRM-4 Relay module contains four relays and two controllable LEDs. Their device addresses on the module are as follows: Relay 1 Relay 2 Relay 3 Relay 4 LED 1 LED 2 001 002 003 004 005 006
For example, the address of the common alarm relay at module address 253 is 253-001.
For example, the address of relay 4 on the CRM-4 at module address 20 is 020-004.
www.PDF-Zoo.com
3-2
Operation
outputs and MID-16 general purpose inputs. This gives a maximum of 8 MOD-16 boards and 8 MID-16 boards. The MOI-7 subaddress map is as follows. 001-016 MOD-16/MID-16 #1 017-032 MOD-16/MID-16 #2 033-048 MOD-16/MID-16 #3 049-064 MOD-16/MID-16 #4 065-080 MOD-16/MID-16 #5 081-096 MOD-16/MID-16 #6 097-112 MOD-16/MID-16 #7 113-128 MOD-16/MID-16 #8 The MOI-7 has two status LEDs: The TRANSMIT LED indicates that the MOI-7 is sending information to the SMB-2. During normal operation this LED flashes periodically when the SMB-2 requests the MOI-7s status. The TROUBLE LED only lights when the MOI-7 cannot communicate with the MXL-IQ. This is an indication that the network connection between the MOI-7 and SMB-2 is damaged. MOD-16 (Open Collector Output Module) The MOD-16 does not occupy a network address. The MOD-16 is at a subaddress of the MOI-7 to which it is connected. The subaddresses of any given MOD-16s are determined by their position in the string of MOD-16s. The output cable from the MOI-7 connects to the first MOD-16, which has the subaddress of 001-016 as shown above. Each additional MOD-16 in the chain has the next block of 16 addresses. You may connect a maximum of 8 MOD-16s and MID-16s to an individual MOI-7 for a total of 128 open collector outputs and 128 general purpose inputs.
See Figure 32, page 3-4, for the location of the display keys and LEDs. When the MKB-4 Keyboard/ Annunciator Panel is installed, only the display, LEDs, and display control keys are visible. The ACKnowledge keys and other controls are hidden behind a locked door. Unlock and open the door to gain access to those keys and controls.
The Display
The display has two lines of 40 characters each. What is shown on the display depends on the state of the System. The display contains a back light which turns on automatically when any key is pressed or an event is reported. The back light turns off automatically after 5 minutes of system inactivity. The System has several displays. When the System is Normal, the display shows:
[time/date] [system message] SYSTEM NORMAL
When an event has been annunciated, the System alternates between the following three displays:
[address] [custom message] [ACK STATUS or BLANK] [event number] [device type] [trouble type] [IN or 0UT]
[address] [type of device in trouble] or [BLANK] [ACK STATUS or BLANK] [event number] [time/date] [IN or 0UT] ALARMS=nnn TROUBLES=nnn SUPERVISORIES=nnn SECURITIES=nnn
www.PDF-Zoo.com
3-3
Operation
The terms used in the displays described above are defined as follows: ACK appears if the event has been acknowledged; otherwise, the field is blank. IN is displayed when a condition occurs. OUT is displayed when a normal state is restored.
ALARM ACK - Press to acknowledge a fire alarm. AUD SIL - Press to silence or unsilence a notification appliance circuit. SUPV ACK - Press to acknowledge a supervisory. TRBL ACK - Press to acknowledge a trouble. SEC ACK - Press to acknowledge a security condition. RESET - Press to reset the System.
S Numeric Keypad
Q The Display
A 2-line display of 40 characters each that shows the state of the System. A back light turns on when any key is pressed or an event is reported.
Use the numeric keypad (keys 0 through 9) when the System asks for a model number, device number, password, time, date, or other information. The display shows each number as you press the key (except when you enter a password; the System shows an asterisk for each digit of the password that you type).
www.PDF-Zoo.com
3-4
Command Keypad Left arrow (|) - Press to select the item to the left of what is flashing on the display (unless entering a number). Right arrow (}) - Press to select the item to the right of what is flashing on the display (unless entering a number). Up arrow (~) - Press to go back to the previous item. ENTER - Press to select the item on which the cursor is flashing. When typing in numbers, press ENTER when finished to complete the entry. PRINT - Press to print selected lists and reports. FORM FEED - Press to advance the paper in the printer. CLEAR - Press to cancel printing begun by pressing PRINT. The System will print:
This listing prematurely terminated.
V Display Keys
Operation
The MXL-IQ has two display keys, NEXT and HOLD, located on the MKB-4. NEXT - Press NEXT to show the previous item in a list of Alarms, Supervisories, Troubles, or Security conditions. HOLD - Press HOLD at any time to freeze the present display. The display remains frozen until HOLD is released.
LEDs ALARM - This red LED flashes when there is at least one unacknowledged fire alarm; it glows steadily when all fire alarms are acknowledged. AUDIBLE SILENCE - This red LED flashes when at least one notification appliance circuit (NAC) is active; it glows steadily when all silenceable NACs are silenced. Under normal conditions, the LED is off. SUPERVISORY - This yellow LED flashes when there is at least one unacknowledged supervisory; it glows steadily when all supervisories are acknowledged. TROUBLE - This yellow LED flashes when there is at least one unacknowledged trouble; it glows steadily when all troubles are acknowledged. SECURITY - This yellow LED flashes when there is at least one unacknowledged security condition; it glows steadily when all security conditions are acknowledged. POWER - This green LED glows steadily to indicate that the AC power is on; it flashes when the System is on battery backup. PARTIAL SYSTEM DISABLE - This yellow LED glows steadily when any device is disabled.
Use the four function keys alone or in combination with ALT1 or ALT2 to provide a total of 12 special functions. When using a combination, hold the ALT key down and then press the function key. F1 F2 F3 F4 ALT1-F1 ALT1-F2 ALT1-F3 ALT1-F4 Hold ALT, then press ALT2-F1 function key. ALT2-F2 ALT2-F3 ALT2-F4 The special function keys are defined using the CSG-M Custom Software Generator (See CSG-M Programming Manual, P/N 315-090381). These definitions can be recorded in the box on the panel.
Modes Of Operation
The MXL-IQ alphanumeric display annunciator has five modes of operation: 1. 2. 3. 4. 5. Alarm Supervisory Trouble Security Normal
INTRODUCTION
www.PDF-Zoo.com
3-5
Operation
This order ensures that fire alarms always take priority over all other conditions. In turn, supervisories always take priority over troubles and troubles always take priority over security conditions. All of the above modes take priority over Normal mode, which is the absence of any alarms, supervisories, troubles, or security conditions.
System Status at 00:00:00 Jul 02, 20XX 0 0 0 0 ALARM SUPERV TROUBLE SECURITY 0 0 0 0 ALARM ACK SUPERV ACK TROUBLE ACK SECURITY ACK
Alarm
The alphanumeric display shows an alarm message when a fire alarm is received. See Alarm.
Alarm
RESPONDING TO AN ALARM 1. Follow the response plan approved by the local authority having jurisdiction. 2. When the MXL-IQ is installed, the ACKnowledge key and Audible Alarm Silence key (AUD SIL) on the MKB-4 are behind a locked door. The display, LEDs, and display control keys are visible and accessible. To acknowledge an alarm or trouble, or to silence an audible alarm, first unlock and open the door.
Supervisory
The alphanumeric display shows a supervisory message when the system receives a supervisory and no higher priority event is present. See Supervisories, page 3-8.
Trouble
The alphanumeric display shows a trouble message when a trouble is present and no higher priority event is present. See Troubles, page 3-9.
Security
The alphanumeric display shows a security message when a security condition is received and no higher priority event is present. See Security Conditions, page 3-10.
Normal Mode
Normal mode is the absence of any alarms, supervisories, troubles, or security conditions. In normal mode the display shows the following message:
11:59:59 DEC 31, 20XX SYSTEM [custom system message] NORMAL
Message 2:
1-001 [custom message] 002 [time/date] IN ALR
The POWER LED glows steadily in normal mode when the system has AC power. The ALARM, AUDIBLE SILENCE, SUPERVISORY, TROUBLE, and SECURITY LEDs are off and the internal audible is off. If your System has the printer option, the System prints a message in the following format every day at midnight, even when there are alarms or other conditions:
Message 3:
ALARMS=002 SUPERVISORIES=000 TROUBLES=000 SECURITIES=000
In addition, the System responds to alarms with programmed output functions such as other audible signals.
www.PDF-Zoo.com
3-6
Operation
In the messages above, 1-001 represents the address of the device reporting the alarm. NOTE: On the display, not all leading zeros are shown. If your System includes a printer, note that the leading zeros are not shown. 5. If you press ALARM ACK again, the System displays ALL ALARMS ACKNOWLEDGED. The ALARM LED glows steadily to indicate that all alarms are acknowledged. If there are no supervisories, troubles, or security conditions in the System, the internal audible goes silent; if any of those conditions still exist, the internal audible pulses.
002 in the first message tells you that this is the second (and the most recent) of two alarms received. The status information in the third message reports the total of alarms, supervisories, troubles, and security conditions. If your System includes a printer, it prints a message from two to four lines long similar to the following:
ALARM 1-1 11:59:59 DEC 31, 20XX #1 [custom message], [device type]
In the preceding printed message, ALARM indicates that the type of occurrence is a fire alarm; 1-1 is the device address; #1 is the number of the alarm in the list of fire alarms; [custom message] is a custom message entered using the CSG-M Custom Software Generator (See the CSG-M Programming Manual, P/N 315-090381); [device type] is the type of device which reported the alarm.
Note that the acknowledgments message includes the term ACK to indicate this alarm was acknowledged. 2. Continue acknowledging alarms as explained above until the System displays the following message: ALL ALARMS ACKNOWLEDGED. The ALARM LED glows steadily to indicate that all alarms are acknowledged. If there are no supervisories, troubles, or security conditions still in the System, the internal audible goes silent; if any of those conditions still exist, the internal audible pulses. 3. If your System includes a printer, it prints a message similar to the following:
ACK ALARM 12:05:44 DEC 31,20XX ALL ALARMS ACKNOWLEDGED
How to Block Acknowledge a Fire Alarm (NFPA 72 Local, Municipal Tie, and Remote Station)
1. Note the specific location of the alarm(s) by using the procedures described above. 2. Unlock and open the door. 3. Press ALARM ACK to acknowledge all alarms. The System displays the following message:
ALL ALARMS ACKNOWLEDGED.
4. If your System includes the printer option, it prints the following message:
ACK ALARM 11:59:59 DEC 31,20XX ALL ALARMS ACKNOWLEDGED
www.PDF-Zoo.com
3-7
Operation
thus, pressing AUD SIL alternately silences and unsilences the System.) If your System has a printer, it prints a message similar to the following:
AUD SILENCED/UNSIL. 11:01:00 DEC 31, 20XX AUDIBLES SILENCED
If your System includes a printer, it prints a message from two to four lines long similar to the following:
SUPERV 1-1 11:59:59 DEC 31, 20XX #1 [custom message], [device type]
Supervisories
How The System Annunciates Supervisories
When a supervisory is detected, the System causes the SUPERVISORY LED on the MKB-4 to flash, the Systems internal audible to sound, and the alphanumeric display on the MKB-4 to alternate in a sequence among the three messages shown below. This example assumes that two supervisories were received (See the explanations below). Message 1:
1-001 [custom message] 002 [device type] IN SUP
In the preceding message, SUPERV indicates that the type of occurrence is a supervisory; 1-1 is the device address; #1 is the number of the supervisory in the list of supervisories; [custom message] is a custom message entered using the CSG-M Custom Software Generator (See the CSG-M Programming Manual, P/N 315-090381); [device type] is the type of device which reported the supervisory.
How to Block Acknowledge a Supervisory (NFPA 72 Local, Municipal Tie, and Remote Station)
1. Note the specific location of the supervisories by using the procedures described above. 2. Unlock and open the door. 3. Press SUPV ACK to acknowledge all supervisories. The System displays the following message:
ALL SUPERVISORIES ACKNOWLEDGED.
Message 2:
1-001 [custom message] 002 [time/date] IN SUP
Message 3:
ALARMS=000 SUPERVISORIES=002 TROUBLES=000 SECURITIES=000
In addition, the System responds to supervisories with programmed output functions such as other audible signals. In the messages above, 1-001 represents the address of the device reporting the supervisory. 002 in the first message tells you that this is the second (and the most recent) of two supervisories received. The status information in the third message reports the total of alarms, supervisories, troubles, and security conditions.
5. If you press SUPV ACK again, the System displays ALL SUPERVISORIES ACKNOWLEDGED. The SUPERVISORY LED glows steadily to indicate that all supervisories are acknowledged. If there are no troubles or security conditions in the System, the internal audible goes silent; if any of those conditions still exist, the internal audible pulses.
www.PDF-Zoo.com
3-8
Operation
Message 2:
1-001 [device type] 002 [time/date] IN TBL
Message 3:
ALARMS=000 SUPERVISORIES=000 TROUBLES=002 SECURITIES=000
In addition, the System responds to troubles with programmed output functions. In the messages above, 1-001 represents the address of the device reporting the trouble. 002 in the first message tells you that this is the second (and the most recent) of two troubles received. The status information in the third message reports the total of alarms, supervisories, troubles, and security conditions. If your System includes a printer, it prints a message from two to four lines long similar to the following:
TROUBLE IN 1-1 11:59:59 DEC 31, 20XX #1 [custom message] [trouble type], [device type]
Note that the acknowledgment message includes the term ACK to indicate this supervisory was acknowledged. 2. Continue acknowledging supervisories as explained above until the System displays the following message: ALL SUPERVISORIES ACKNOWLEDGED. The SUPERVISORY LED glows steadily to indicate that all supervisories are acknowledged. If there are no troubles or security conditions still in the System, the internal audible goes silent; if any of those conditions still exist, the internal audible pulses. 3. If your System includes a printer, it prints the following message:
ACK SUPERVISORY 12:05:44 DEC 3,20XX ALL SUPERVISORIES ACKNOWLEDGED
Troubles
How The System Annunciates Troubles
When a trouble is detected, the System causes the TROUBLE LED on the MKB-4 to flash, the Systems internal audible to sound, and the alphanumeric display on the MKB-4 to alternate in a sequence among the three messages shown below. This example assumes that two troubles were received (See the explanations below). Message 1:
1-001 [custom message] 002 [trouble type] IN TBL
In the above printed message, TROUBLE indicates that the type of occurrence is a trouble; 1-1 is the device address; and #1 is the number of troubles in the list of troubles; [custom message] is a custom message entered using the CSG-M Custom Software Generator (See the CSG-M Programming Manual, P/N 315- 090381); [trouble type] is the type of trouble which reported; [device type] is the type of device in trouble.
www.PDF-Zoo.com
3-9
Operation
How to Block Acknowledge a Trouble (NFPA 72 Local, Municipal Tie, and Remote Station)
1. Note the specific location of the trouble(s) by using the procedures described above. 2. Unlock and open the door. 3. Press TRBL ACK to acknowledge all troubles. The System displays the following message: ALL TROUBLES ACKNOWLEDGED. 4. If your System includes a printer, it prints the following message:
ACK TROUBLE 11:59:59 DEC 31, 20XX ALL TROUBLES ACKNOWLEDGED
The TROUBLE LED glows steadily to indicate that all troubles are acknowledged. If there are no security conditions still in the System, the internal audible goes silent; if any of those conditions still exist, the internal audible pulses. 3. If your System includes a printer, it prints the following message:
ACK TROUBLE 12:05:44 DEC 31, 20XX ALL TROUBLES ACKNOWLEDGED
Security
How The System Annunciates Security Conditions
When a security condition is detected, the System causes the SECURITY LED on the MKB-4 to flash, the Systems internal audible to sound, and the alphanumeric display on the MKB-4 to alternate in a sequence among the three messages shown below. This example assumes that two security conditions were received (See the explanations below the messages). Message 1:
1-001 [custom message] 002 [device type] IN SEC
The TROUBLE LED glows steadily to indicate that all troubles are acknowledged. If there are no security conditions in the System, the internal audible goes silent; if any security conditions still exist, the internal audible pulses.
Message 2:
1-001 [custom message] 002 [time/date] IN SEC
Message 3:
ALARMS=000 TROUBLES=000 SUPERVISORIES=000 SECURITIES=002
Note that the acknowledgment message includes the term ACK to indicate this trouble was acknowledged. 2. Continue acknowledging troubles as explained above until the System displays the following message:
ALL TROUBLES ACKNOWLEDGED.
In addition, the System responds to security conditions with programmed output functions. In the messages above, 1-001 represents the address of the device reporting the security condition. 002 in the first message tells you that this is the second (and the most recent) of two security conditions received.
www.PDF-Zoo.com
3-10
Operation
The status information in the third message reports the total number of alarms, supervisories, troubles, and security conditions. If your System includes a printer, it prints a message from two to four lines long similar to the following:
SECURITY IN 1-1 11:59:59 DEC 31, 20XX #1 [custom message], [device type]
Reset Procedures
Hard Reset
Other terms for Hard Reset are Power-up, Initialization, and Cold Reset. Applying power to the System performs a Hard Reset which initializes (starts) the entire system. What Is Lost: Alarms, supervisories, troubles, security conditions Any user entries such as time and date
In the preceding printed message, SECURITY indicates that the type of occurrence is a security condition; 1-1 is the device address; #1 is the number of the security condition in the list of security conditions; [custom message] is a custom message entered using the CSG-M Custom Software Generator (See the CSG-M Programming Manual, P/N 315-090381); [device type] is the type of device which reported the security condition.
Arm/disarm Manual sensitivity adjustment Time-based control until time is reset What Is Not Lost: CSG-M program
Soft Reset
To perform a Soft Reset, press RESET on the MKB-4 (Refer to Figure 32, page 3-4). Soft reset does not work until you acknowledge all alarms, supervisories, troubles, and security conditions and silence the System. What Is Lost: Alarms, supervisories, troubles, security conditions Arm/disarm (unless option disabled by CSG-M) What Is Not Lost: Any user entries such as time and date. Arm/disarm (when enabled by CSG-M) CSG-M program Manual sensitivity adjustment Time-based control
Note that the acknowledgment message includes the term ACK to indicate this security condition was acknowledged. 2. Continue acknowledging security conditions as explained above until the System displays the following message: ALL SECURITY CONDITIONS ACKNOWLEDGED. The SECURITY LED glows steadily to indicate that all security conditions are acknowledged, and the internal audible goes silent.
www.PDF-Zoo.com
3-11
Operation
If you press RESET before acknowledging all conditions and silencing the audible alarms, the display shows a message similar to the following:
ALARMS NOT ALL ACKNOWLEDGED YET
(or)
SUPERVISORY NOT ALL ACKNOWLEDGED YET
(or)
TROUBLES NOT ALL ACKNOWLEDGED YET
(or)
SECURITY NOT ALL ACKNOWLEDGED YET
Limitations/Restrictions
As in all networked MXL Systems, the self-restoring trouble option is not allowed in any MXL. An MXL still may only contain a maximum of 4 supervised MKBs. This can be a mix of local and global MKBs. BLOCK ACK must be enabled in the CSG-M. The maximum number of supervised Global MKBs is 10. The maximum number of Global Printers is 2 (not TSP-40s).
(or)
AUDIBLES NOT ALL SILENCED YET
If your System has a printer, it prints a message similar to the following and adds SYSTEM NOT RESET on the bottom line:
RESET 0:1 1:58 Jul 03,20XX Not All Acknowledged Yet. System Not Reset.
When the System performs a Soft Reset, the display shows the following message:
SYSTEM RESET
The System then returns to Normal mode and the display shows the following:
11:59:59 DEC 31, 20XX [custom System message] SYSTEM NORMAL
If the System is already in Normal mode when you press RESET, it displays
SYSTEM ALREADY NORMAL
www.PDF-Zoo.com
3-12
Operation
SUPERVISORY The 3 event displays are formatted as follows for a supervisory condition:
NN:MMM-DDD [custom message] ACK 1 [time/date] IN SUP NN:MMM-DDD [custom message] ACK 1 [device type] IN SUP ALARMS=0 TROUBLES=0 SUPERVISORY=1 SECURITY=0
TROUBLE The 3 event displays are formatted as follows for a trouble condition:
NN:MMM-DDD [custom message] ACK 23 [trouble type] IN TRB NN:MMM-DDD [custom message] ACK 23 [time/date] IN TRB ALARMS=0 TROUBLES=23 SUPERVISORY=0 SECURITY=0
SECURITY The 3 event displays are formatted as follows for a security condition:
NN:MMM-DDD [custom message] ACK 2 [time/date] IN SEC NN:MMM-DDD [custom message] ACK 2 [device type] IN SEC ALARMS=0 TROUBLES=0 SUPERVISORY=0 SECURITY=2
Leading zeros are not included in addresses and counts. Additional data causes a three character shift right, resulting in the loss of three characters from the displayed message. Additional data also causes a two character shift to the right, resulting in the loss of two characters of the device or trouble type. The System queue totals are over 10,000 events. This expands the event number fields to 5 digits from 3. The order of these events is as follows: Queue priority (Alarm, Supervisory, Trouble, Security). Time and date of event (newest first). If the two previous items are identical, the lower node number takes priority.
www.PDF-Zoo.com
3-13
Operation
nodes as if a local audible unsilence had been requested. An error code (or success via a silence event message) allows the global MKB to keep up to date as to true System status. If any panel reports an error, the display status changes since some audibles have been unsilenced. RESET When the global reset key is pressed, each node is tested. If all nodes meet the conditions required for reset, the reset command is sent and executed. Otherwise, the corresponding error message is displayed. NEXT This key operates the same as in the local mode. However, it moves the user through the System events globally in the priority order established earlier. HOLD This key operates the same as in the local mode. Function Keys These keys operates the same as in the local MKB. Numeric Keypad These keys operates the same as in the local MKB.
The menu gives you wide control of the MXL-IQ System. You may use the menu no matter what mode the System is in. The discussion in this section is in the following order: Operation of the keys on the MKB-4 Keyboard/Annunciator Overview of the menus structure Beginning a menu session Introduction to each of the four menus: - Acknowledge menu - List menu - Control menu - Test menu - Entering your password - Entering module and device numbers Using the Acknowledge menu Using the List menu Using the Control menu Using the Test menu
Numeric Keypad
Use the numeric keypad (keys 0 through 9) when the System asks for a module number, device number, password, time, date, or other information. The display shows each number as you press the key. However, when you enter a password, the System shows asterisks in place of the digits entered.
www.PDF-Zoo.com
3-14
Operation
If you are in the menu and do not depress a numeric or arrow key at any time during a 1 minute period, the System returns to the previous item. The five Main Menu items and their subitems for Revision 6.0 and higher follow; the shortened terms used in the menu itself are in parentheses: List1 Control Test
Acknowledge
| on the display (unless entering a number). } flashing on the display (unless entering a
number). Select the item to the right of what is
Status Alarm Supervisory (Supervsry) Trouble Security Sensitivity (Senstvty) Voltages - Analog - Threshold - Sensitivity Temp Module type (Mod type) Device type (Dev type) Message Software version (SW version) Output States Device Usages Node Address Analaser - Smoke-lev - Flow-lev - Trip-pts Percent/ft - Senstvty - Pre-alarm - Analog ASD apps
1
Reset Sensitivity (Senstvty) - Hi_3 - Hi_2 - Hi_1 - Norm - Low_1 - Low_2 - Low_3 Arm/disarm (Arm/dis) - Arm - Disarm Output on/off - Arm - Disarm - Energize - De-Energize Loop Arm Loop Disarm Netlink Request Analaser - Alarm_Trip - Flow_Trip Percent/Ft - Sensitivity (Senstvty) - Pre_alarm Change_Apps
~
ENTER HELP PRINT FORM FEED CLEAR
Go back to the previous item. Press to select the item on which the cursor is flashing. After typing in numbers, press ENTER to complete the entry. Press to display a one-line message. Press to begin printing various lists and reports. Press to advance the paper in the printer.
You can generate a printed report or listing for every item in the List menu except Node Address; see the discussion under LIST Menu.
Set time Ground fault (Gnd_flt) - Main Power2 - Main - Voltage - Current Lamp test - LEDs - Display Device LED MOI_Lamp_Test X-Network M-Network Override Det_cleaned Event_log - Alrm_only - Trbl_only - Superv_only - Security_only - All_events - Hist_Ctrl - Hist_Erase Pyro_diags Pre_alarm ASD_Devices Summarize Manual_Activate
2
You can generate a printed report for this item; see the discussion under TEST Menu.
Press to cancel printouts begun by pressing PRINT. The System will print: This listing prematurely terminated.
Walktest
www.PDF-Zoo.com
3-15
Operation
ACKNOWLEDGE
LIST
CONTROL
TEST
For help in understanding what the List function does, press HELP when the L in LIST is blinking. The System displays:
TO LIST SYSTEM, DEVICE, CSGM INFO
The A in Acknowledge is blinking. Select Acknowledge by pressing ENTER while the A is blinking. Use the Left and Right arrow keys to move around in this four-item menu. To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.
Use this function to list information on the System and its devices. To return to the Main Menu display, press HELP again:
ACKNOWLEDGE LIST CONTROL TEST
For help in understanding what the Acknowledge function does, press HELP when the A in ACKNOWLEDGE is blinking. The System displays:
TO ACKNOWLEDGE INDIVIDUALLY
For help in understanding what the Control function does, press HELP while the C in CONTROL is blinking. The System displays:
TO MODIFY DATA FOR OPERATION
Use this menu function to acknowledge alarms, supervisories, troubles, and security conditions individually. To return to the Main Menu display, press HELP again:
ACKNOWLEDGE TEST LIST CONTROL
Use the Control function to reset the System and to change the settings of various devices. To return to the Main Menu display, press HELP again:
ACKNOWLEDGE LIST CONTROL TEST
For help in understanding what the Test function does, press HELP while the T in TEST is blinking. The System displays:
www.PDF-Zoo.com
3-16
Operation
TO TEST SYSTEM, LOOP & DEVICE
The System gives you three chances to enter an acceptable password before it returns you to the Main Menu. If the System accepts your password, it displays the Control, Test, or Walktest menu. We discuss those menus later in this section.
Use this function to test the System, its loops, and its devices, including ground fault, battery voltage and current, and the LEDs. To return to the Main Menu display, press HELP again:
ACKNOWLEDGE LIST CONTROL TEST
If you press HELP, the System explains this function; press HELP again to return to the previous display. Type your (1-5 digit) password, using the numeric keypad. The System shows an asterisk for each digit that you type. (Use the Left arrow key to erase an error.) When you have typed the entire password, press ENTER. If your password does not match a password stored in the System, the System briefly displays the following message and then returns you to the first password display:
ACCESS DENIED
If you press HELP at this point, the System displays the following explanation:
3 DIGIT MODULE NO., PRESS <ENTER>
Press HELP again to return to the previous display. Type all three digits, including leading zeros, and press ENTER. When you type the module number, use the Left arrow key as a backspace key to erase errors.
If your password level is not high enough to use the Test functions, the System briefly displays the following message and then returns you to the first password display:
PASSWORD LEVEL NOT HIGH ENOUGH
(If you press HELP at this point, the System displays the following explanation:
PASSWORD LEVELS Rev 5.0 and Above Highest Test Z Control Lowest Walktest
Below Rev 5.0 Highest
Y
Lowest
Press HELP again to return to the previous display. Type all of the digits, including leading zeros, and press ENTER.)
www.PDF-Zoo.com
3-17
Operation
When you type the module number and the device number, use the Left arrow key as a backspace key to erase errors. If All Alarms Are Acknowledged: If all the alarms are acknowledged, the System displays the following message and then returns you to the Acknowledge menu.
ALL ALARMS ACKNOWLEDGED
ACKNOWLEDGE Menu
The Acknowledge menu has four items from which to choose; the shortened terms used in the menu itself are in parentheses:
ALARM SUPERVISORY (SUPERVSRY) TROUBLE SECURITY
(If your System has a printer, it prints the above message as well.) If There Is an Unacknowledged Alarm: If there is at least one unacknowledged alarm, the menu shows the most recent unacknowledged alarm on both lines of the display, as in the following display:
29-041 [custom message] 007 [device type] IN ALR
Use this menu to individually acknowledge fire alarms, supervisories, troubles, and security conditions.
In the above display, 29 is the module number, 041 is the device number, the message on the first line is the custom message for the device at that location, 007 indicates that this is the seventh alarm, [device type] indicates the type of device in alarm, and IN ALR indicates that this is a fire alarm. (Press HELP if you want information on what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT TO SKIP.
NOTE:
To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.
Acknowledge: Alarm
Use this function to individually acknowledge fire alarms. Press ENTER when the A in ALARM is blinking to select ACKNOWLEDGE ALARM:
ACKNOWLEDGE: ALARM SUPERVISRY
Press HELP again to return to the previous display.) Press ENTER to acknowledge the alarm shown. The System prints a message similar to the following and removes that alarm from the unacknowledged alarm list:
ACK ALARM 29-041 16:11:41 Aug 28,20XX #7 [custom message], [device type]
If There Is No Alarm: If there is no current alarm, the System briefly displays the following message and then returns you to the Acknowledge menu:
NO ALARM EXISTS
In the above message, the time and date are the time and date that the alarm was acknowledged and 29-041 is the address. The System then displays the next alarm to acknowledge. To skip an alarm shown, press NEXT. The System displays the next alarm in the series. When the System has displayed all
(If your System has a printer, it prints the above message as well.)
www.PDF-Zoo.com
3-18
Operation
of the unacknowledged alarms, it returns to the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
If There Is An Unacknowledged Supervisory: The System does not let you acknowledge supervisory conditions if there are any unacknowledged alarms. If there is at least one unacknowledged alarm, the System briefly displays the following message and then returns you to the Acknowledge menu:
ALARM NOT ALL ACKNOWLEDGED YET
Acknowledge: Supervsry
Use this function to individually acknowledge supervisories. Select ACKNOWLEDGE from the Main Menu by pressing ENTER while the A in ACKNOWLEDGE is blinking. The System displays:
ACKNOWLEDGE: ALARM SUPERVISRY
Select ALARM and follow the instructions in ACKNOWLEDGE ALARM above. (If your System has a printer, it prints the above message as well.) After you acknowledge all alarms, the System allows you to acknowledge supervisories. If there is at least one unacknowledged supervisory, the menu shows the most recent unacknowledged supervisory on both lines of the display, as in the following display:
32-045 [custom message] 012 [device type] IN SUP
Press the Right arrow key once to cause the S in SUPERVISRY to blink. (If you press HELP at this time, the System explains the Acknowledge Supervisory function:
TO ACK SUPERVISORY INDIVIDUALLY
Press HELP again to return to the ACKNOWLEDGE: ALARM SUPERVISRY display.) Press ENTER while the S is blinking to select SUPERVISRY. If There Is No Supervisory: If there is no supervisory to acknowledge, the System briefly displays the following message and then returns you to the Acknowledge menu:
NO SUPERVISORY EXISTS
In the preceding display, 32 is the module number, 045 is the device number, the message on the first line is the custom message for the device at that location, 012 indicates that this is the twelfth supervisory, [device type] indicates the type of device causing the supervisory, and IN SUP identifies the item as an off-normal supervisory. (Press HELP if you want information on what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT TO SKIP
Press HELP again to return to the previous display.) Press ENTER to acknowledge the supervisory shown. The System prints a message similar to the following and removes that supervisory from the unacknowledged supervisory list:
ACK SUPERV 32-045 16:11:44 Aug 2,20XX #12 [custom message], [device type]
(If your System has a printer, it prints the above message as well.) If All Supervisories Are Acknowledged: If all supervisories are acknowledged, the System briefly displays the following message and then returns you to the Acknowledge menu:
ALL SUPERVISORIES ACKNOWLEDGED
In the above message, the time and date are the time and date the supervisory was acknowledged and 32-045 is the address.
www.PDF-Zoo.com
3-19
Operation
The System then displays the next supervisory to acknowledge. To skip a supervisory, press NEXT. The System displays the next supervisory in the series. When the System has displayed all of the unacknowledged supervisories, the System returns to the acknowledge menu on the second line of the display. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.) If All Troubles Are Acknowledged: If all the troubles are acknowledged, the System displays the following message and returns you to the Acknowledge menu:
ALL TROUBLES ACKNOWLEDGED
(If your System has a printer, it prints the above message as well.) If There Is An Unacknowledged Trouble: The System does not let you acknowledge troubles if there are any unacknowledged fire alarms or supervisories. Follow the instructions above to acknowledge them. After you acknowledge all fire alarms and supervisories, the System allows you to acknowledge troubles. If there is at least one unacknowledged trouble, the System shows the most recent unacknowledged trouble on both lines of the display, as in the following display:
36-050 [custom message] 018 [trouble type] IN TBL
Acknowledge: Trouble
Use this function to individually acknowledge troubles. Select ACKNOWLEDGE from the Main Menu by pressing ENTER while the A in ACKNOWLEDGE is blinking. The System displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
Press the Right arrow key twice. The System displays the Acknowledge menu with T in TROUBLE blinking:
ACKNOWLEDGE: SUPERVISRY TROUBLE
(If you press HELP at this time, the System explains the Acknowledge Trouble function:
TO ACK TROUBLE INDIVIDUALLY
In the above display, 36 is the module number, 050 is the device number, the message on the first line is the custom message for that device, 018 indicates that this is the eighteenth trouble, [trouble type] indicates the type of trouble, and IN TBL identifies the event as the occurrence of a trouble. (Press HELP if you want information on what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT TO SKIP.
Press HELP again to return to the acknowledge menu.) Press ENTER while the T is blinking to select Trouble. If There Is No Trouble: If there is no trouble to acknowledge, the System briefly displays the following message and returns you to the acknowledge menu:
NO TROUBLE EXISTS
Press HELP again to return to the previous display.) Press ENTER to acknowledge the trouble shown. The System prints a message similar to the following message and removes that trouble from the unacknowledged trouble list:
ACK TROUBLE 36-050 16:11:44 Aug 8, 20XX #18 [custom message], [trouble type] [device type]
(If your System has a printer, it prints the above message as well.)
www.PDF-Zoo.com
3-20
Operation
In the above message, the time and date are the time and date that the condition was acknowledged and 36-050 is the address. The System then displays the next trouble to acknowledge. When the System has displayed all of the unacknowledged troubles, it returns to the Acknowledge menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.) If All Security Conditions Are Acknowledged: If all security conditions are acknowledged, the System displays the following message and returns you to the Acknowledge menu:
ALL SECURITIES ARE ACKNOWLEDGED
(If your System has a printer, it prints the above message as well.) If There Is An Unacknowledged Security Condition: The System does not let you acknowledge security conditions if there are any unacknowledged alarms, supervisories, or troubles. If there is at least one unacknowledged alarm, the System briefly displays the following message and then returns you to the Acknowledge menu:
ALARMS NOT ALL ACKNOWLEDGED YET
Acknowledge: Security
Use this function to individually acknowledge security conditions. Select ACKNOWLEDGE from the Main Menu by pressing ENTER while the A in ACKNOWLEDGE is blinking. The System displays the first Acknowledge menu:
ACKNOWLEDGE: ALARM SUPERVISRY
(If your System has a printer, it prints the above message as well.) Follow the instructions above to acknowledge any unacknowledged alarms, supervisories, and troubles. After you acknowledge all fire alarms, supervisories, and troubles, the System allows you to acknowledge security conditions. If there is at least one unacknowledged security condition, the System displays the most recent unacknowledged security condition:
42-058 [custom message] 005 [device type] IN SEC
Press the Right arrow key three times. The System displays the second Acknowledge menu, with the S in SECURITY blinking:
ACKNOWLEDGE: TROUBLE SECURITY
(If you press HELP at this time, the System explains the Acknowledge Security function:
TO ACK SECURITY INDIVIDUALLY
Press HELP again to return to the Acknowledge menu.) Press ENTER while the S is blinking to select Security. If There Is No Security Condition to Acknowledge: If there is no Security condition to acknowledge, the System briefly displays the following message and then returns you to the Acknowledge menu:
NO SECURITY EXISTS
In the above display, 42 is the module number, 058 is the device number, the message on the first line is the custom message for the device at that location, 005 indicates that this is the fifth security condition, [device type] indicates the type of device causing the security condition, and IN SEC identifies this as an off-normal security condition. (Press HELP if you want information on what to do. The System displays:
PRESS ENTER TO ACK. PRESS NEXT TO SKIP.
(If your System has a printer, it prints the above message as well.)
www.PDF-Zoo.com
3-21
Operation
Press ENTER to acknowledge the security condition shown. The System prints a message similar to the following message and removes that security condition from the unacknowledged security list:
ACK SECURITY 42-058 16:11:44 Aug 8,20XX #5 [custom message], [device type]
Software version (SW version) Output states Device usages Node address Analaser Percent/ft ASD_apps
In the above message, the time and date given are the time and date when the security condition was acknowledged, and 42-058 is the address. The System then displays the next security report to acknowledge. To skip a security condition, press NEXT. The System displays the next security condition in the series. When the System has displayed all of the unacknowledged security conditions, it returns to the Acknowledge menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Use the List menu to learn the following information: Status of the System Alarm information Supervisory information Trouble information Security information Detector sensitivity Detector voltage Analog Threshold (Thresh) Sensitivity (Sens) Temperature of FP-11 or FPT-11 Type of module Type of device Custom message of the given address Version of the System software Output states Device usages Panel's X-Network node address Percent per foot obscuration Sensitivity Pre-alarm Analog Device application (ASD setting)
LIST Menu
The List menu has eighteen items from which to choose; the shortened terms used in the menu are in parentheses. You can generate a printed list or report for every item on the List menu except Node Address. See the discussion for each item that follows. Status Alarm Supervisory (Supervsry) Trouble Security Sensitivity (Senstvty) Voltages Temp Module type (Mod type) Device type (Dev type) Message
www.PDF-Zoo.com
3-22
Operation
Press ENTER to select LIST. The System displays the first List menu, with the S in STATUS blinking:
LIST: STATUS ALARM SUPERVSRY
In the above printed message, there are two alarms, both of them acknowledged, no supervisory conditions, 30 trouble conditions, all acknowledged, and no security conditions. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
List: Status
The List Status function shows you the number of acknowledged and unacknowledged alarms, supervisories, troubles, and security conditions, in that order. From the List menu, use the Right or Left arrow keys to cause the S in STATUS to blink. (If you press HELP at this point, the System explains the List Status function:
SHOW NUMBER OF ACKED & UNACKED
List: Alarm
The List Alarm function shows you all the fire alarms currently in the System in the order they occurred. From the List menu, use the Left or Right arrow key to cause the A in ALARM to begin blinking. If you press HELP at this point, the System explains the List Alarm function:
SHOW INDIVIDUAL ALARM STATUS
Press HELP again to return to the List menu. Press HELP again to return to the List menu.) When you press ENTER to select List Status, the display first shows the total number of alarms and the number of acknowledged alarms:
2 ALARM 2 ALARM ACK
Press ENTER to select ALARM and display alarm information on the MKB-4 display. If There Is No Fire Alarm: If there is no fire alarm, the System briefly displays the following message and then returns you to the List menu:
NO ALARM EXISTS
To view, in order, the status of supervisories, troubles, and security conditions, press NEXT. After the Security display, the System returns to the List menu. To make a printed list of current status, press PRINT when the S in STATUS is blinking. The System will print a listing similar to the following:
System Status at 11:02:26 Jul 01, 20XX: 2 ALARM 2 ALARM ACK 0 SUPERV 0 SUPERV ACK 30 TROUBLE 30 TROUBLE ACK 0 SECURITY 0 SECURITY ACK
If There Is a Fire Alarm: If there is at least one fire alarm, the System shows the most recent alarm, alternating between the following two displays:
1-001 [custom message] 002 [device type] IN ALR
IN ALR
Press NEXT to show the two displays for the previous alarm in the sequence. (Pressing HOLD freezes a display for as long as you keep HOLD depressed.)
www.PDF-Zoo.com
3-23
Operation
When the System has shown all current fire alarms, it returns to the List menu. To obtain a full printed list of alarms in the following formatone item for each current alarmpress PRINT when the A in ALARM is blinking.
Listing of all Alarm at 14:35:20 Oct 09,20XX: ALARM 1-5 14:34:22 Oct 09,20XX #1 [custom message], [device type]
IN SUP
In the above listing, 1-5 is the address of the device in alarm, the time is the time the device went into alarm, #1 is the number of this alarm in the current list, [custom message] is the custom message for the device in alarm, and [device type] is the type of device in alarm. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Press NEXT to show the two displays for the previous supervisory in the sequence. (Pressing HOLD freezes a display for as long as you keep HOLD depressed.) When the System has shown all current supervisories, it returns to the List menu. To obtain a full printed list of supervisories in the following formatone item for each current supervisorypress PRINT when the S in SUPERVISORY is blinking.
Listing of all Supervsry at 14:35:20 Oct 09,20XX: SUPERV IN 32-45 14:34:22 Oct 09, 20XX #7 [custom message], [device type]
List: Supervisory
The List Supervisory function shows you all the supervisories currently in the System in the order they occurred. From the List menu, use the Left or Right arrow key to cause the S in SUPERVSRY to blink. (If you press HELP at this point, the System explains the List Supervisory function:
SHOW INDIVIDUAL SUPERVISORY
In the preceding listing, 32-45 is the address of the device in supervisory, #7 is the number of the supervisory in the current list, [custom message] is the custom message for the device in supervisory, and [device type] is the type of device in supervisory. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Press HELP again to return to the List menu.) Press ENTER to select SUPERVSRY and display supervisory information on the MKB-4 display. If There Is No Supervisory: If there is no supervisory, the System briefly displays the following message and then returns you to the List menu:
NO SUPERVISORY EXISTS
List: Trouble
The List Trouble function shows you all the troubles currently in the System in the order they occurred. From the List menu, use the left or right arrow key three times to cause the T in TROUBLE to blink. (If you press HELP at this point, the System explains the List Trouble function:
SHOW INDIVIDUAL TROUBLE STATUS
If There Is a Supervisory: If there is at least one supervisory, the System shows the most recent supervisory,
www.PDF-Zoo.com
3-24
Operation
Press ENTER to select TROUBLE and display trouble information on the MKB-4 display. If There Is No Trouble: If there is no trouble, the System briefly displays the following message and then returns to the List menu:
NO TROUBLE EXISTS.
If There Is a Trouble: If there is at least one trouble, the System shows the most recent trouble, alternating between the following two displays:
1-001 [custom message] 002 [trouble type] IN TBL
Press HELP again to return to the List menu.) Press ENTER to select SECURITY and display security information on the MKB-4 display. If There Is No Security Condition: If there is no security condition, the System briefly displays the following message and then returns you to the List menu:
NO SECURITY EXISTS
IN TBL
Press NEXT to show the two displays for the previous trouble in the sequence. (Pressing HOLD freezes a display for as long as you keep HOLD depressed.) When the System has shown all current troubles, it returns to the List menu. To obtain a full printed list of troubles in the following formatone item for each current troublepress PRINT when the T in TROUBLE is blinking.
Listing of all Trouble at 14:35:20 Oct 09, 20XX: TROUBLE IN 29-41 14:34:22 Oct 09, 20XX #7 [custom message],[trouble type], [device type]
If There Is a Security Condition: If there is at least one security condition, the System shows the most recent security condition, alternating between the following two displays:
1-001 [custom message] 002 [device type] IN SEC
IN SEC
In the above listing 29-41 is the address of the device in trouble, the time tells when the device went into trouble, #7 is the number of this trouble in the current list, [custom message] is the custom message for the device in trouble, [trouble type] is the type of trouble, and [device type] is the type of device in trouble. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Press NEXT to show the two displays for the previous security condition in the sequence. (Pressing HOLD freezes a display for as long as you keep HOLD depressed.) When the System has shown all current security conditions, it returns to the List menu. To obtain a full printed list of security conditions in the following format one item for each current security condition press PRINT when the S in SECURITY is blinking.
www.PDF-Zoo.com
3-25
Operation
Listing of all Security at 14:35:20 Oct 09,20XX: SECURTY IN 29-42 14:34:22 Oct 09,20XX #7 [custom message], [device type]
In the above listing 29-42 is the address of the device causing the security condition, the time when the device caused the security condition, #7 is the number of this security condition, [custom message] is the custom message for the device causing the security condition, and [device type] is the type of device causing the security condition. To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.
Press NEXT to display the address and sensitivity setting of each succeeding smoke detector. When the System has shown the sensitivity settings of all smoke detectors on that analog loop, it returns to the List menu. To leave the List Sensitivity menu without going through the entire analog loop, press the Up arrow key. The System displays the List menu. Print the Sensitivity Setting of All Smoke Detectors Assigned to a Specified Module Press PRINT when the S in SENSTVTY is blinking. The System then asks for a module number.
TYPE IN MODULE NUMBER: [module number]
Type the three-digit module number and press ENTER. (Enter all leading zeros.) The System prints the sensitivity settings (Hi_3, Hi_2, Hi_1, Norm, Low_1, Low_2 or Low_3, or ... if there is no smoke detector) of all the devices assigned to the analog loop.
Sensitivities for module 1
1- HI_3 6- ... 11- NORM 2- ... 3- NORM 4- ... 5- ... 7- ... 8- ... 9- ... 10- ... 12- ... 13- ... 14- ... 15- LOW1
NOTE: You cannot print the sensitivity setting of a single smoke detector. Note that List Sensitivity shows the sensitivity of smoke detectors only. Press HELP again to return to the List menu.) Display the Sensitivity Setting of One Device Press ENTER to select List Sensitivity. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE: 001-001
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
List: Voltages
Use List Voltages to show the voltages of initiating devices on analog loops. From the List menu press the Left or Right arrow key to cause the V in VOLTAGES to start blinking:
LIST: SECURITY, SENSTVTY, VOLTAGES
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System displays the sensitivity setting of the device specified (Hi_3, Hi_2, Hi_1, Norm, Low_1, Low_2 or Low_3 ).
www.PDF-Zoo.com
3-26
Operation
(If you press HELP at this point, the System displays:
SHOW DETECTOR VOLTAGES
If the module number entered is not an analog loop, the System displays:
Not Analog Loop.
Press HELP again to return to the List menu.) Display the Voltage of One Device Press ENTER to select List Voltages. The System asks you for a module number and device number. Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System shows the following menu for that device (the A in ANALOG will be blinking):
001-001 ANALOG THRESH SENS
If the device address has no device assigned by CSG-M, the System displays:
No Device Assigned.
When displaying sensitivities, if the device is not a smoke detector, the System displays:
Not a Smoke Detector.
Press ENTER to show the Analog voltage for that device. When you ask for any voltage, the System displays Please wait for response until it receives a reading from the device; if you have just reset the System, it alternates the above message with the message Device being initialized. The display for Analog voltage is similar to the following (readings are dynamic):
001-001 ANALOG2 = 2.75 VOLTS
Print the Voltage of All Devices Assigned to a Specified Module Press PRINT when the V in Voltages is blinking. The System asks you for a module number. Type the three-digit module number and press ENTER. (Enter all leading zeros.)
002-001 Analog Thresh Sens
Press ENTER to print the Analog voltage for all devices assigned to the module (ND = No Device).
ANALOG VOLTAGES FOR MODULE 1 1- 2.00 2- 2.00 3- ND 4- ND 5- ND 6- ND 7- ND 8- ND 9- ND 10- ND 11- ND 12- ND 13- ND 14- ND 15- ND
Press ENTER to return to the previous display. To view the Threshold or Sensitivity voltage of any device listed, use the Right and Left arrow keys to highlight the first letter of the category desired and press ENTER. The display for Threshold voltage is similar to the following:
001-001 THRESHOLD = 4.75 VOLTS
To print the Threshold voltages of all the devices for the specified module, use the arrow keys to cause the T in THRESH to blink and press PRINT. The System prints those threshold voltages in a format similar to the following (ND = No Device):
THRESHOLD VOLTAGES FOR MODULE 1 1- 4.75 2- 4.75 3- ND 4- ND 5- ND 6- ND 7- ND 10- ND 8- ND 9- ND 11- ND 12- ND 13- ND 14- ND 15- ND
The display for Sensitivity voltage is similar to the following (readings are dynamic):
001-001 SENSITIVITY = 2.62 VOLTS
Press the Up arrow key to return to the List: Voltage Mod_type Dev_type menu.
www.PDF-Zoo.com
3-27
Operation
To print the Sensitivity voltages of all the smoke detectors for the specified module, use the arrow keys to cause the S in SENS to blink and press PRINT. The System prints those sensitivity voltages in a format similar to the following (ND = No Device, or device not a smoke detector):
SENSITIVITY VOLTAGES FOR 1- 2.75 2- 2.62 3- ND 6- ND 7- ND 10- ND 11- ND 12- ND 13- ND MODULE 1 4- ND 5- ND 8- ND 9- ND 14- ND 15- ND
To leave the Temp menu without going through all subaddresses, press the Up arrow key. The System displays the List menu.
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
(If you press HELP at this point, the System explains this function:
SHOW THE TYPE OF MODULE
List: Temp
Use List Temp to display the current temperature on the LCD display at the location where the detector is installed. From the List menu use the left or right arrow key to cause the T in Temp to start blinking:
LIST: TEMP
Press HELP again to return to the List menu.) Display the Module Type of One Module Press ENTER when the M in MOD_ TYPE is blinking. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Press ENTER to select List Temp. The System asks you for a module and device number:
Type In Module & Device:
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. If the device is not installed or is not an FP-11 or FPT-11, the system displays following message:
Not Applicable or No Device:
Type the three-digit module number using the numeric keypad and press ENTER. (Enter the leading zeros.) The System displays the module type for the module number specified:
MOD 074 TYPE: CZM4
If you press NEXT, the System displays the module type for the next module number in the sequence:
MOD 075 TYPE: ALD
If the device is an FP-11 or FPT-11, the temperature is displayed in the following format:
001-001 25 DEG C / 77 DEG F
NOTE:
If you enter a module number not assigned in CSG-M, the System displays:
NO MOD ASSIGNED
Press NEXT to display the temperature of the FP-11 or FPT-11 at the next higher address in the same loop.
With each press of NEXT, the System continues to display module types through
www.PDF-Zoo.com
3-28
Operation
number 255, the highest module number allowed by the System. It then returns to the List menu. Print the Module Type and Network Address of All Modules Press PRINT when the M in MOD_ TYPE is blinking to print a full list of module types and their Network addresses. The System prints a list similar to the following:
Listing of Module Types: 1- V7 ALD 2- V7 ALD 3- V4 CZM-4 251- V5 MKB-4 253- V1 MXL-IQ Panel
meric keypad and press ENTER. (Enter all leading zeros.) The System displays the device type for the address specified:
004-001 TYPE: [device type]
If you press NEXT, the System displays the device type for the next device in the sequence:
004-002 TYPE: [device type]
In the above display, the number following the V (for example, V7) is the software version number of the software installed in the module. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
With each press of NEXT, the System continues to display device types until there are no more devices for that module. The System then returns to the List menu. To proceed to another module, follow the preceding instructions. Print a List of Devices Assigned to a Specified Module Press PRINT when the D is blinking to select LIST DEVICE. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type only the module number and press PRINT. (Enter all leading zeros.) The System prints a list of all device types assigned to the specified module in a format similar to the following:
Listing of Device Types Module 1 (ALD): 1-TRI-60D Dual Switch Input 2-TRI-60D Dual Switch Input 4-TRI-60D Switch input + Relay 5-TRI-60 Switch Input 7-TRI-60 Switch Input 10-ID-60T-135 Thermal Detector 11-ID-60T-135 Thermal Detector 15-ID-60I Ionization Detector 16-ID-60I Ionization Detector
Press HELP again to return to the List menu.) Display the Device Type of a Specified Device Press ENTER when the D is blinking to select LIST DEV_TYPE. The System asks you for a module and device number:
TYPE IN MODULE & DEVICE:
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
List: Message
Use List Message to show the CSG-M assigned custom message of a particular device.
Type the three-digit module number and three-digit device number using the nu-
www.PDF-Zoo.com
3-29
Operation
From the List menu use the Left or Right arrow key to cause the M in MESSAGE to start blinking:
LIST: MOD TYPE DEV TYPE MESSAGE
Type only the module number and press PRINT. (Enter all leading zeros.) The System prints a list of all the custom device messages for the specified module in a format similar to the following:
Listing of Messages in Module 1 (ALD): 4-Conf.Rm 5-Cafeteria 6-Exec. Off. 1 7-Cmptr Rm 8-Exec. Off. 2 9-Camera Rm 10-Exec. Off. 3 11-Conf. Rm
Press HELP again to return to the previous display.) Display the Device Message of a Specified Device Press ENTER when the M in MESSAGE is blinking to select List Message. The System asks you for a module and device number:
TYPE IN MODULE & DEVICE:
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. The System displays the message for the address specified:
069-001 [custom message]
(If you press HELP at this point, the System displays: If you press NEXT, the System displays the message for the next device number in the sequence:
069-002 [custom message] SHOW SOFTWARE VERSION
Press HELP again to return to the previous display.) Display the Software Version of Your System Software Press ENTER when the S is blinking to select List S/W_VERSION. The System displays the CSG-M assigned System custom message:
MSG [system custom message]
With each press of NEXT, the System continues to display device messages until there are no more devices for that module. To proceed to another module, follow the preceding instructions.
Print a List of System Messages for a Specified Module Press PRINT when the M in MESSAGE is blinking to select List Message. The System asks you for a module number:
TYPE IN MODULE NUMBER:
www.PDF-Zoo.com
3-30
Operation
Press NEXT again to display the version of CSG-M used to create this System.
CSG VERSION: [version number]
Press HELP again to return to the List menu.) Display the Output States of One Device Press ENTER to select List Output States. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE: 001-001
Press NEXT again to display the date and time of CSG-M installation:
LOADED: [time and date]
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System displays the output state of the device specified. Press NEXT to display the address and output state of each succeeding device. When the System has shown the output states of all devices at that address, it returns to the List menu. To leave the List output state menu without going through all subaddresses, press the Up arrow key. The System displays the List menu. Print the Device Output State of Devices Assigned to a Specified Module Press PRINT when the O in Output States is blinking. The System then asks for a module number.
TYPE IN MODULE NUMBER: [module number]
Print the Software Version of Your System Software Press PRINT when the S in SW_ VERSION is blinking to select List S/ W_Version. The System prints the System Custom Message, MXL-IQ Software Version, Version of CSG-M Used to Create the System, CSG-M File Name Installed, and Date and Time of Installation:
Software Version Information at 11:35:30 Jul 01, 20XX Installation: [system custom message] MXL-IQ Version: 1.00 CSG Version: 6.09 Source: 05OCT00 Loaded: 16:09:35 Oct 05, 20XX
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Type the three-digit module number and press ENTER. (Enter all leading zeros.) The System prints the output state of all of the devices assigned to that module.
Listing of Output States for Module 1 (ALD): 1-Auxiliary Output: OFF 2-Auxiliary Output: ON 3-Auxiliary Output: ON 4-Auxiliary Output: OFF
www.PDF-Zoo.com
3-31
Operation
From the List menu, use the left or right arrow key to cause the D in DEV_USAGES to start blinking:
LIST: DEV USAGES
Listing of Device Usages for module 1 (ALD) 1- ALARM 2- TROUBLE 3- STATUS 4- ALARM 5- TROUBLE 6- OUTPUT ONLY
Use List Node Address to show the panel's X-Net node address. From the List menu, use the left or right arrow key to cause the N in NODE ADDRESS to start blinking:
LIST: NODE ADDRESS
Press HELP again to return to the List menu.) Display the Usage of One Device Press ENTER to select List Dev_usages. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE: 001-001
Display the Node Address Press ENTER to select List Node Address. The System displays the X-Net node address for that particular MXL-IQ panel.
List: Analaser
Use List ANALASER to display operational characteristics of the AnaLASER devices.
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System displays the use of the device specified (i.e., Alarm, Trouble, or Status). Press NEXT to display the address and use of each succeeding device. When the System has shown the uses of all devices at that address, it returns to the List menu. To leave the List Dev_usage menu without going through all subaddresses, press the Up arrow key. The System displays the List menu. Print the Device Usages of Devices Assigned to a Specified Module Press PRINT when the D in DEV_USAGES is blinking. The System then asks for a module number.
TYPE IN MODULE NUMBER: [module number]
Press ENTER when the A in ANALASER is blinking to select List ANALASER. Use the Left or Right arrow to move to the following selections:
ANALASER: Smoke Lev Trip Pts Flow Lev
Press HELP again to return to the List menu.) List Analaser Smoke_Lev Press ENTER when the S in SMOKE_LEV is blinking to select List ANALASER SMOKE_LEV. The System asks you for a module and device number:
TYPE IN MODULE & DEVICE
Type the three-digit module number and press ENTER. (Enter all leading zeros.) The System prints the uses of all of the devices assigned to that module.
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device address number using the numeric keypad
www.PDF-Zoo.com
3-32
Operation
and press ENTER. The system displays the smoke level for the address specified:
010-004 50% >>!* *<< PRE1 TYPE IN MODULE & DEVICE
The bar graph in the example above shows the following information for the AnaLASER device at address 010-004: 50% = 50% of full scale smoke level ! = active trip point at 30% * = inactive trip point at 60% and 100% PRE1 indicates the device is in PreAlarm 1 PRE2 and ALRM indicate the PreAlarm 2 and Alarm states, respectively. The bargraph continuously updates to reflect the current state of the AnaLASER zone that is being viewed. Print the AnaLASER Smoke Level Press PRINT when the S in SMOKE_LEV is blinking to print the ANALASER SMOKE_LEV. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device address number using the numeric keypad and press ENTER. The System displays the air flow level for the address specified:
010-004 50% >>! * << NORM
The bar graph in the example above shows the following information for the AnaLASER device at address 010-004: 50% = 50% of full scale air flow level ! = low air flow trip point at 20% * = high air flow trip point at 90% NORM indicates that the current air flow level is at a normal level, HIGH indicates airflow is too high, and LOW indicates airflow is too low. The bar graph continuously updates to reflect the current state of the AnaLASER zone that is being viewed. Print the AnaLASER Flow Level Press PRINT when the F in FLOW_LEV is blinking to print the ANALASER FLOW_LEV. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1R (ANA) module number and press ENTER. The System sends smoke levels for all devices on the selected MODULE to the printer.
AnaLASER Smoke Levels at 13:23:31 Jan 03, 20XX 010-001 13:23:31 Jan 03,20XX 0% Scale >> . . .<< NORM, Cust Msg 1 010-002 13:23:32 Jan 03,20XX 100% Scale >>!!!<< ALRM, Cust Msg 010-010 13:23:31 Jan 03,20XX 42% Scale >>! . .<< PRE1, Cust Msg 10 010-011 13:23:32 Jan 03,20XX 100% Scale >>!! .<< PRE2, Cust Msg 11
Type the three-digit NIM-1R (ANA) module number and press ENTER. The System sends air flow levels for all devices on the selected MODULE to the printer.
AnaLASER Air Flow Levels at 13:23:31 Jan 03, 20XX 010-001 13:23:31 Jan 03,20XX 0% Scale >> . . << LOW, Cust Msg 1 010-002 13:23:32 Jan 03,20XX 100% Scale >>! !<< HIGH, Cust Msg 010-010 13:23:31 Jan 03,20XX 42% Scale >>! . << NORM, Cust Msg 10 010-011 13:23:32 Jan 03,20XX 100% Scale >>! . << NORM, Cust Msg 11
For printed bar graphs, the characters shown below indicate the following: . = an inactive trip point ! = an active trip point List Analaser Flow_Lev Press ENTER when the F in FLOW_LEV is blinking to select LIST ANALASER FLOW_LEV. The System asks you for a module and device number:
List Analaser Trip_pts Press ENTER when the T in TRIP_PTS is blinking to select LIST ANALASER TRIP_PTS.
www.PDF-Zoo.com
3-33
Operation
The System prompts you to select between ALARM_TRIP and FLOW_TRIP. Press ENTER when the A in ALARM_TRIP is blinking to select LIST TRIP_PTS ALARM_TRIP. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE
dress number using the numeric keypad and press ENTER. The System displays the current air flow trip point settings for the address specified:
010-004 LOW: 20% HIGH: 80%
Print the AnaLASER Flow Trip Pts Press PRINT when the F in FLOW_TRIP is blinking to print the ANALASER FLOW_TRIP points. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device address number using the numeric keypad and press ENTER. The System displays the current alarm trip point settings for the address specified:
010-004 P1: 20% P2: 60% ALM: 90%
Type the three-digit NIM-1R (ANA) module number and press ENTER. The System sends air flow trip point levels for all devices on the selected MODULE to the printer.
AnaLASER Air Flow Trip Points at 13:23:31 Jan 03, 20XX 010-001 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 90%, Cust Msg 1 010-002 13:23:31 Jan 03,20XX, LOW: 20% HIGH: 80%, Cust Msg 1 010-010 13:23:31 Jan 03,20XX, LOW: 30% HIGH: 70%, Cust Msg 1 010-011 13:23:31 Jan 03,20XX, LOW: 10% HIGH: 80%, Cust Msg 1
Print the AnaLASER Alarm Trip Pts Press PRINT when the A in ALARM_TRIP is blinking to print the ANALASER ALARM_TRIP points. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Type the three-digit NIM-1R (ANA) module number and press ENTER. The System sends alarm trip point levels for all devices on the selected MODULE to the printer.
AnaLASER Alarm Trip Points at 13:23:31 Jan 03, 20XX 010-001 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 30% ALRM: 100%, Cust Msg 1 010-002 13:23:31 Jan 03,20XX, PRE1: 30% PRE2: 50% ALRM: 90%, Cust Msg 2 010-010 13:23:31 Jan 03,20XX, PRE1: 10% PRE2: 50% ALRM: 100%, Cust Msg 10 010-011 13:23:31 Jan 03,20XX, PRE1: 50% PRE2: 80% ALRM: 100%, Cust Msg 11
List: Percent/ft
Use List Percent/ft to show settings in percent/ft obscuration of the ILI and ILP Series detectors. From the List menu, use the left or right arrow key to cause the P in PERCENT/FT to start blinking:
LIST: PERCENT/FT
Press ENTER when the F in FLOW_TRIP is blinking to select LIST TRIP_PTS FLOW_TRIP. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE
Press ENTER to select List Percent/ft. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE: 001-001
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device ad-
Type in the three-digit module number and the three-digit device number using the numeric keypad and press ENTER. The System displays the following menu for that device (the S in Senstvty will be blinking):
www.PDF-Zoo.com
3-34
Operation
002-003 SENSTVTY PRE-ALARM ANALOG
The System prints either the Sensitivity, Prealarm, or Analog of all the devices for the specified module in a format similar to the following (NA = ID-60 detector):
%/ft SENSITIVITIES FOR MODULE 2 1-3.00 2-NA 3-1.4 4-3.1 5-1.4 6-1.4 7-ND 8-ND 9-ND 10-ND 11-ND 12-ND 13-ND 14-ND 15-ND 16-ND 17-ND 18-ND 19-ND 20-ND 21-ND 22-ND 23-ND 24-ND 25-ND 26-ND 27-ND 28-ND 29-ND 30-ND 31-ND 32-ND 33-ND 34-ND 35-ND 36-ND 37-ND 38-ND 39-ND 40-ND 41-ND 42-ND 43-ND 44-ND 45-ND 46-ND 47-ND 48-ND 49-ND 50-ND 51-ND 52-ND 53-ND 54-ND 55-ND 56-ND 57-ND 58-ND 59-ND 60-ND
List: ASD_apps
Use List ASD_apps to display operational characteristics of the ASD devices.
From the List menu use the left or right arrow key to cause the A in ASD_Apps to start blinking:
LIST: ASD APPS
To leave the Percent/ft menu without going through all subaddresses, press the Up arrow key. The System displays the List menu. Print the Analog Loops Current Readings in Percent/ft Obscuration Press PRINT when the P in Percent/ft is blinking. The System asks you for a module number.
TYPE IN MODULE NUMBER:
Display the Operational Characteristics of One Device Press ENTER to select ASD_apps. The System asks you for a module and device number:
TYPE IN MODULE & DEVICE:
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System displays the currently assigned application for the device specified. (Refer to the ASD Submenu Abbreviations on page I-1.) Press NEXT to display the address and assigned application of each succeeding device. The System will exit the ASD_Apps menu if there are no more ASD devices in that module. To leave the List ASD_Apps menu at any time, press the Up arrow key. The System displays the List menu.
Type the three-digit module number using the numeric keypad and press ENTER. The System shows the following menu for that device (the S in Senstvty will be blinking):
001-001 SENSTVTY PRE-ALARM ANALOG
www.PDF-Zoo.com
3-35
Operation
To print the operational characteristics of the ASD devices assigned to an ALD Loop Press PRINT when the A in ASD_Apps is blinking. The System asks you for a module number:
TYPE IN MODULE NUMBER:
Arm/Disarm (Arm/dis) Arm Disarm Output_on/off Arm Disarm Energize De_energize Loop arm/disarm arm disarm Net_link_request Analazer Alarm-trip Flow-trip Percent/ft Sensitivity(Senstvty) Pre-alarm Change-apps Use the Control menu to perform the following functions: Reset the System Change the sensitivity of a smoke detector
Type the three-digit module number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System prints a list of all the applications currently assigned to all the ASD devices in that ALD loop in a format similar to the following (ND = No Device):
1-NONE 6-ND 11-ND 16-ND 21-ND 26-ND 31-ND 36-ND 41-ND 46-ND 51-ND 56-ND 2-PARK 7-ND 12-ND 17-ND 22-ND 27-ND 32-ND 37-ND 42-ND 47-ND 52-ND 57-ND 3-ND 8-ND 13-ND 18-ND 23-ND 28-ND 33-ND 38-ND 43-ND 48-ND 53-ND 58-ND 4-ND 9-ND 14-ND 19-ND 24-ND 29-ND 34-ND 39-ND 44-ND 49-ND 54-ND 59-ND 5-ND 10-ND 15-ND 20-ND 25-ND 30-ND 35-ND 40-ND 45-ND 50-ND 55-ND 60-ND
CONTROL Menu
Arm or disarm an initiating device Arm an output device Disarm and energize an output device Disarm and de-energize an output device Arm and disarm a loop Send a request to the Network Command Center (NCC) to disconnect the MXL from the network Change AnaLASER Alarm Trip points and Flow Trip points Change sensitivity and pre-alarm settings in percent/ft obscuration of the ILI and ILP detectors Change the application of an ASD device
The Control menu has nine items from which to choose; six of the items have submenus, as follows (the shortened terms used in the menu are in parentheses): Reset Sensitivity (Senstvty) Hi_3 Hi_2 Hi_1 Norm Low_1 Low_2 Low_3
www.PDF-Zoo.com
3-36
Operation
If the System is normal, when SYSTEM RESET is selected, the System displays the following:
SYSTEM ALREADY NORMAL
Press HELP again to return to the Main Menu.) Press ENTER to select CONTROL. The System asks you for a password before it allows you to use the Control functions. Enter your one- to five-digit password, using the numeric keypad, and press ENTER (See the discussion under Entering Your Password on page 3-17). If the System accepts your password, it displays the first Control menu, with the R in RESET blinking:
CONTROL: RESET SENSTVTY ARM/DIS
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Control: Sensitivity
Use Control Sensitivity to change the sensitivity settings of smoke detectors on analog loops. From the Control menu, press the Right or Left arrow key to cause the S in SENSTVTY to start blinking:
CONTROL: RESET SENSTVTY ARM/DIS
(If you press HELP at this point, the System displays: (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
CHANGE SENSITIVITY
Press HELP again to return to the above menu.) Note that Control Sensitivity allows you to change the sensitivity settings of smoke detectors only; if you attempt to change the sensitivity setting of another type of device, the System displays:
[001-001] NOT SMOKE DETECTOR
Control: Reset
Use Control Reset to initiate a system reset at any time. From the Control menu, use the Left or Right arrow key to cause the R in RESET to start blinking:
CONTROL: RESET SENSTVTY ARM/DIS
If you enter any address for which there is no device assigned, the System displays: (If you press HELP while the R in RESET is blinking, the System explains this function:
RESET SYSTEM NO DEVICE ASSIGNED
Press ENTER while the S in SENSTVTY is blinking to select CONTROL SENSTVTY. Press HELP again to return to the above menu.) Press ENTER to reset the System and display the following message:
SYSTEM RESET
The System asks you for a module number and device number:
TYPE IN MODULE & DEVICE:
www.PDF-Zoo.com
3-37
Operation
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. The System shows the following display:
001-001 Norm Hi 1 Hi 2 Hi 3
The System asks you for the module number and device number of the detector you wish to arm or disarm. Type the threedigit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System displays:
001-001 ARM DISARM
The current sensitivity setting is highlighted. The System offers you a choice of seven levels of sensitivity: Hi_3, Hi_2, Hi_1, Norm, Low_1, Low_2 or Low_3. Use the Right and Left arrow keys to highlight the level you wish to set for the smoke detector specified and press ENTER. The System makes the change in sensitivity setting. Press NEXT to move through the devices until you display the ones you want to change, and follow the instructions above for making the changes. When the System has displayed the highest numbered device for the module specified, it returns to the Control menu. You can select another address by selecting SENSTVTY and following the instructions above. To leave the Control Sensitivity displays without going through the entire list, press the Up arrow key. The System displays the Control menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
The System offers you a choice of arming or disarming the device. Use the Right and Left arrow keys to highlight your choice and press ENTER. The System makes the change. When you disarm an input device, the System automatically annunciates the disarming as a Trouble and lights the PARTIAL SYSTEM DISABLE LED. Press NEXT to move through the devices until you display the ones you want to change; follow the instructions above for making the changes. When the System has displayed the highest numbered device for the module specified, it returns to the Control menu. To arm or disarm another module device, select ARM/DIS and follow the preceding instructions. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Control: Arm/dis
Use Control Arm/dis to enable or disable the operation of an initiating device. From the Control menu, press the Left or Right arrow key to cause the A in ARM/DIS to start blinking. (If you press HELP at this point, the System displays:
DISARM OR ARM DEVICES
Press HELP again to return to the Control menu.) Press ENTER while the A in ARM/DIS is blinking to select Control Arm/dis.
www.PDF-Zoo.com
3-38
Operation
Press HELP again to return to the above menu.) Press ENTER while the O in OUTPUT is blinking to select CONTROL_OUTPUT ON/ OFF. The System asks for a module number and device number of the device you wish to turn on or off (energize or de-energize). Type the three-digit module number and threedigit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) The System shows the following display:
253-005 ARM DISARM
(To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
The System offers you a choice of arming or disarming the device. Use the Right and Left arrow keys to highlight your choice and press ENTER. If you have armed the device, you can press NEXT to display the number of the next device in the sequence. You can also press the Up arrow key to return to the Control menu. NOTE: You must first disarm a device if you wish to energize or de-energize it. When you disarm an output device, the System automatically annunciates the disarming as a Trouble and a Partial System Disable. If you choose to disarm an output device, the System then asks if you wish to energize it or de-energize it:
253-005 ENERGIZE DE ENERGIZE
Press HELP again to return to the Control menu.) Press ENTER while the L in LOOP_ARM is blinking to select Control Loop_arm. The System asks you for the module number of the ALD loop you wish to arm. Type the three-digit module number using the numeric keypad and press ENTER. (Enter all leading zeros.) When you arm input devices, the System automatically annunciates the arming as a Trouble OUT, and lights the PARTIAL SYSTEM DISABLE LED. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Use the Right or Left arrow key to energize or de-energize the device and press ENTER. Press NEXT to move through the outputs until you display the ones you want to change; follow the instructions above for making the change. When the System has displayed the highest numbered device for the module specified, it returns to the Control menu. To arm or disarm and energize or de-energize a device on a different module, follow the preceding instructions.
www.PDF-Zoo.com
3-39
Operation
Press ENTER while the L in LOOP_DISARM is blinking to select Control Loop_disarm. The System asks you for the module number of the ALD loop you wish to disarm. Type the three-digit module number using the numeric keypad and press ENTER. (Enter all leading zeros.) When you disarm input devices, the System automatically annunciates the disarming as a Trouble IN, and lights the PARTIAL SYSTEM DISABLE LED. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.) Press ENTER when the A in ANALASER is blinking to select Control ANALASER. The System prompts you to select between ALARM_TRIP and FLOW_TRIP. Press ENTER when the A in ALARM_TRIP is blinking to select CONTROL ALARM_TRIP. The System asks you for a module and device number.
TYPE IN MODULE & DEVICE
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device address number using the numeric keypad and press ENTER. The system displays the current alarm trip point settings for the address specified:
010-004 P1: 20% P2: 60% ALM: 90%
Use the numeric keypad and the left and right arrow keys to modify the value for P1, P2, and ALM (Alarm). Note that the following provisions apply: P1 must be less than or equal to P2 which must be less than or equal to ALM. If these values are different, the System will reject the settings. P1, P2, and ALM must be even multiples of 10% or the System will reject the settings. Press ENTER when you are finished modifying the settings. The display should then show:
TRIP POINTS ACCEPTED
Press HELP again to return to the Control menu.) Press ENTER while the N in NET_LINK_REQUEST is blinking to disconnect the panel from the X-Network. To reconnect the panel to the X-Network, from the Control menu, press the Left or Right arrow key to cause the N in NET_LINK_REQUEST to start blinking and press ENTER.
or
TRIP POINTS INVALID.
Press ENTER when the F in FLOW_TRIP is blinking to select Control FLOW_TRIP. The System asks you for a module and device number.
Control: Analaser
Use Control ANALASER to display and change the operational characteristics of the AnaLASER devices.
Type the three-digit NIM-1R (ANA) module number and three-digit ACC device address number using the numeric keypad
www.PDF-Zoo.com
3-40
Operation
and press ENTER. The system displays the current air flow trip point settings for the address specified:
010-004 LOW: 20% HIGH: 60%
Use the left and right arrow keys on the keypad to lower or raise the %/ft reading. (Refer to the Sensitivity and Pre-Alarm Settings chart that follows.)
Use the numeric keypad and the left and right arrow keys to modify the value for LOW and HIGH. Note that the following provisions apply: LOW must be less than HIGH, or the System will reject the settings. The System will reject the settings if they are not even multiples of 10%. Press ENTER when you are finished modifying the settings. The display should then show TRIP POINTS ACCEPTED.
PHOTO
Pre-alarm adjust increment Pre-alarm range Pre-alarm default .25% / ft. .25 - 2.0% / ft. 1.5% / ft.
ION
.12% / ft. .25 - .75% / ft. .75% / ft.
Control: Percent/ft
Use Control Percent/ft to change sensitivity and pre-alarm settings in percent/ft obscuration of the ILI and ILP series of detectors. From the Control menu, press the Left or Right arrow key to cause the P in Percent/ft to start blinking. The System asks you for a module number and device number.
TYPE IN MODULE & DEVICE:
After you change the sensitivity setting, the System prints the information for the selected device in a format similar to the following:
CMD CHANGE SENS 06:38:20 JUN 2, 20XX 002-004 1.4%/FT NORM
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. The System displays the following:
001-001 SENSTVTY PRE-ALARM
Control Percent/ft - Pre-alarm The display for Pre-alarm supplies the current pre-alarm setting read back from the detector and is similar to the following (readings are dynamic):
002-003 PRE-ALARM .75%/FT NORM
Control Percent/ft - Senstvty The display for Sensitivity supplies the current sensitivity as read back from the detector and is similar to the following (readings are dynamic):
002-003 SENS 1.4%/FT NORM
In the previous message, 002-003 is the address. Pre-alarm is the type of response (Sensitivity or Pre-alarm). .75%/ft is the smoke detector reading in %/ft obscuration and Norm is the text sensitivity range corresponding to the %/ft readings. Use the left and right arrow keys on the keypad to lower or raise the %/ft reading. (Refer to the Sensitivity and Pre-Alarm Settings chart.)
In the previous message, 002-003 is the address. Sens is the type of response (Sensitivity or Pre-alarm). 1.4%/ft is the smoke detector reading in %/ft obscuration and Norm is the text sensitivity range corresponding to the %/ft readings.
www.PDF-Zoo.com
3-41
Operation
After you change the pre-alarm setting, the System prints the information for the selected device in a format similar to the following:
CMD CHANGE PRE-ALM 06:38:20 JUN 2, 20XX 002-004 1.4%/FT NORM
[Press ENTER]
Type in Module & Device: 001-001 [Enter module-device number, including all leading zeros] 001-001 NONE OFFC WHSE LOBY > [Use arrow keys to select the desired application] 001-001 NONE OFFC WHSE LOBY > [Press ENTER]
NOTE: Because the pre-alarm and sensitivity settings overlap, set the pre-alarm to at least an increment below the sensitivity setting.
To leave the Change_Apps menu at any time, press the Up arrow key. NOTE: If the ASD application is changed while Test ASD is on, the changes will not be effective until Test ASD is turned off.
TEST Menu
Press HELP again to return to the Control menu.) Press ENTER while the C in Change_Apps is blinking to select Control Change_Apps. The System asks you for the module and device number.
TYPE IN MODULE & DEVICE:
The Test menu has sixteen items from which to choose; three of those items have submenus, as follows (the shortened terms used in the menu itself are in parentheses): Set_time Ground fault (GND_FLT) Power* Main Voltage Current Lamp_test LEDs Display Device_LED MOI_Lamp_test X_Network* M_Network* Override Det_cleaned Event_log Alrm_only Trbl_only Superv_only Security_only
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. (Enter all leading zeros.) Use the arrow keys to cycle through the 11 supported applications described in the ASD Submenu Abbreviations on page I-1, in Appendix I, and press ENTER to select the desired application. The transaction and the time that it occurs will be printed on the printer as a confirmation. The example shown below assumes that no application is currently assigned to module 001, device 001:
www.PDF-Zoo.com
3-42
Operation
All_events Hist_Ctrl Hist_Erase PYRO_Diags PRE_ALARM ASD_DEVICES SUMMARIZE MANUAL_ACTIVATE
*You can print a report of the information produced by these functions. See the discussions for Test Power and Test Network.
Press ENTER to select TEST. The System asks you for a password before it allows you to use the Test functions. Enter your one- to five-digit password, using the numeric keypad, and press ENTER (See the discussion under Entering Your Password on page 3-17). If the System accepts your password, it displays the first Test menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Use the Test menu for the following functions: Change the time and date in the System Test ground fault state Display the Systems power condition Test the LEDs or the display on the MKB-4 Test the LEDs on an analog device Perform lamp test on MOD-16 of MOI-7 Display network performance characteristics Alarm verification/confirmation override IEC detector cleaned function Event (History) log menu Test Pre-alarm logic Test ASD detectors Record one summarized trouble for an entire module Perform testing on input points and simutale alarms Press HELP again to return to the above menu.) Press ENTER when the S in SET_ TIME is blinking to select TEST SET_ TIME. The System shows you the current System time, using a 24-hour clock, and the date:
SET TIME = 12:34:56 12/23/20XX
The Help display tells you to type the time and date, using the numeric keypad, in the following format: hour: minute: seconds_month/day/year, and then to press ENTER to set the time and date. Use the Right and Left arrow keys to skip over a correct digit.
www.PDF-Zoo.com
3-43
Operation
Press HELP again to return to the above menu.) Type the time and date as explained above and press ENTER. The System prints the current time and date on the printer and returns you to the Test menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Test: Power
Use Test Power to test the Systems battery voltage, AC voltage, and battery charge current. From the Test menu, use the Left or Right arrow key to cause the P in POWER to start blinking:
TEST: GND-FLT POWER
DISPLAY POWER
Press HELP again to return to the above menu.) Press ENTER when the P is blinking and the menu displays:
POWER: MAIN
Press HELP again to return to the Test menu.) Press ENTER when the G is blinking and the menu displays:
GND FLT: MAIN
Display the AC Voltage, Battery Voltage, and Charging Current of the Main System From the Power menu, press ENTER when the M in MAIN is blinking to select Main Power. The System shows the following menu:
MAIN: VOLTAGE CURRENT
Press ENTER when the V in VOLTAGE is blinking to display the battery voltage:
BATTERY VOLTAGE = X.X VOLTS
From the Ground Fault menu, press ENTER when the M in MAIN is blinking. The System tests dynamically for ground fault and reports the results of the test on the display (OK, PLUS, or MINUS):
GROUND FAULT IS MINUS
If the message is other than OK, locate the loop and the device responsible. The display automatically changes to OK when the ground fault problem is corrected. (During this test, the System and its devices remain operational.) (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Press the Up arrow key to return to the Main Power menu. Use the Right arrow key to cause the C in CURRENT to start blinking and press ENTER. The System shows the battery charge current in amps:
BATT CHG CUR = XX.X AMPS
www.PDF-Zoo.com
3-44
Operation
Print the AC Voltage, Battery Voltage, and Charging Current of the Main System From the Power menu, press PRINT when the M in MAIN is blinking to select MAIN POWER. The System will print information in a format similar to the following:
Power Supply Statistics at 11:23:52 May 01, 20XX: Battery Voltage = 26.0 volts Charging CUR = 0.5 AMPS AC VOLTAGE = 113 VOLTS
Press HELP again to return to the above menu.) Press ENTER when the D is blinking to select TEST DEVICE_LED. The System asks you to type the module and device numbers. Type the three-digit module number and the three-digit device number and press ENTER. (Enter all leading zeros.) The System displays the following menu for the device (the O in ON will be blinking):
001-001 ON OFF
(If you press HELP at this point, the System explains this function:
MKB-4 LAMP TEST
Press HELP again to return to the above menu.) Press ENTER when the L is blinking to select TEST LAMP_TEST. The System displays the following menu:
LAMP TEST: LED'S DISPLAY
To turn on the LED for that device, press ENTER. The System turns on the LED for that device. Turning on a device LED automatically causes a Trouble to be annunciated. Use the NEXT key to move through the devices until you display the ones whose LEDs you wish to test. Follow the instructions above. When the System has displayed the highest numbered device for the module specified, it returns to the Test menu. To turn on a device LED for a different module, select DEVICE_ LED from the Test menu and follow the preceding instructions. (To end a menu session and return to the Main Menu, or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Press ENTER to test the LEDs and the audible on the MKB-4. The LEDs light for 5 seconds and then return to their previous state. To test the alphanumeric display, press the Right arrow key once to cause the D in DISPLAY to start blinking and then press ENTER. The System tests the display and then returns to the Lamp Test menu. (To end a menu session and return to the Main Menu or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
www.PDF-Zoo.com
3-45
Operation
Press HELP again to return to the above menu.) Press ENTER when the O in OVERRIDE is blinking and the menu displays:
Use the Left or Right arrow key to switch between ALR_VERIFY and ALR_CONFIRM. (If you press HELP at this point, the System displays:
TO TEST MOI-7 / MOD-16 LAMPS
Press HELP again to return to the above menu.) Press ENTER when the M is blinking to select MOI_LAMP_TEST. The System asks you to type the module number. Type the three-digit module number and press ENTER. (Enter all leading zeros.) If the MOI-7 module is present in CSG-M the MOD-16 outputs will be placed in a 30second lamp test mode. After 30 seconds, these outputs return to their previous state. (To end a menu session and return to the Main Menu, or to leave the menu at any time, press the Up arrow key to go backward one menu each time.)
Override the Alarm Verification CSG-M Selection From the Override menu, press ENTER when the A in ALR_VERIFY is blinking to select Alarm Verification. The System shows the following menu:
OVERRIDE: YES NO
A blinking Y in YES indicates that Alarm Verification Override is currently enabled. A blinking N in NO indicates that the Alarm Verification Override is currently disabled. To enable Alarm Verification Override, use the Left or Right arrow key to cause the Y in YES to start blinking. Pressing ENTER when the Y in YES is blinking will cause Alarm Verification Override to be enabled. The System will display the following message:
OVERRIDE ENABLED
Test: Override
Use Test Override to override the CSG-M selected options for Alarm Verification and Alarm Confirmation. From the Test menu, use the Left or Right arrow key to cause the O in OVERRIDE to start blinking. (If you press HELP at this point, the System displays:
OVERRIDE ALARM VERIFY & CONFIRM
To disable Alarm Verification Override, use the Left or Right arrow key to cause the N in NO to start blinking. Pressing ENTER when the N in NO is blinking will cause Alarm Verification Override to be disabled. The System will display the following message:
OVERRIDE DISABLED
In either case, if the Alarm Verification option was not selected in CSG-M, the System will display the following message:
FEATURE NOT ENABLED IN CSG
www.PDF-Zoo.com
3-46
Operation
Override the Alarm Confirmation CSG-M Selection From the Override menu, press ENTER when the A in ALR_CONFIRM is blinking to select Alarm Confirmation. The System shows the following menu:
OVERRIDE: YES NO
Press HELP again to return to the above menu.) Press ENTER when the D is blinking to select DET_CLEANED.
A blinking Y in YES indicates that Alarm Confirmation Override is enabled. A blinking N in NO indicates that the Alarm Confirmation Override is disabled. To enable Alarm Confirmation Override, use the Left or Right arrow key to cause the Y in YES to start blinking. Pressing ENTER when the Y in YES is blinking enables Alarm Confirmation Override. The System will display the following message:
OVERRIDE ENABLED
The System asks you to type the module and device numbers. Type the three-digit module number and the three-digit device number and press ENTER. (Enter all leading zeros.) After entering the module-device, the MXL-IQ determines if the device is subject to IEC. If the device is not subject to IEC or if IEC is not enabled for the system, error messages display (Device not subject to IEC; IEC not enabled in CSGM). If the device is an IEC detector, the MXL-IQ will display and print the time, date, moduledevice and custom message of the cleaned device.
To disable Alarm Confirmation Override, use the Left or Right arrow key to cause the N in NO to start blinking. Pressing ENTER when the N in NO is blinking disables Alarm Confirmation Override. The System will display the following message:
OVERRIDE DISABLED
Test: Pyro_diags
Use Test Pyro-diags to display a series of statistics typically used by Siemens Building Technologies, Inc. to evaluate the operation of the System. A special password is required for access to this function.
In either case, if the Alarm Confirmation option was not selected in CSG-M, the System will display the following message:
FEATURE NOT ENABLED IN CSG
Use Test Pre_alarm to test pre-alarm logic. From the Test menu, use the left or right arrow key to cause the P in Pre_alarm to start blinking:
TEST: PRE ALARM
The System asks you for a module number and device number.
TYPE IN MODULE & DEVICE:
www.PDF-Zoo.com
3-47
Operation
Type the three-digit module number and the three-digit device number using the numeric keypad and press ENTER. The System then sends information to force this detector into pre-alarm. Once it prealarms, or after a delay, the MXL-IQ then restores the detector to its proper pre-alarm setting. Pressing ENTER a second time will cause the following message to be printed out:
TROUBLE OUT 253 08:25:50 AUG 08, 20XX #9 CERBERUS PYROTRONICS , ASD TESTING DISABLED, MXL PANEL
Test: ASD_Devices
Use Test ASD_Devices to disable ASD parameters and allow timely response to test gas. From the Test menu, use the Left or Right arrow key to cause the A in ASD_Devices to start blinking. (If you press HELP at this point, the system displays:
TEST: ASD DETECTORS
If Test ASD_Devices is activated and left alone, the system will automatically disable the test (time out) after four hours.
Test: Summarize
Use Test Summarize to ignore known troubles, and instead view one summarized trouble for an entire module. This is typically used during installation and commissioning. Select Summarize and press ENTER. The System displays the following menu:
Select Mods ON OFF
Press HELP again to return to the Test menu.) Press ENTER to test the ASD devices present in the system. The System displays:
TESTING OF ASD DEVICE ENABLED
Test: Summarize - Select_Mods Use Test Summarize Select_Mods to scroll through all installed (CSG-M) module addresses and enable/disable the summarize feature for each module address. Choose Select_Mods and press ENTER. The System displays the following:
001 YES NO
Press the ENTER key to toggle between Testing Enabled (Trouble In) and Testing Disabled (Trouble Out). When toggling between Testing Enabled and Testing Disabled, there is a three minute time period that separates the two states. Activating the ASD_Devices command will post a Trouble into the system which will be printed out as:
TROUBLE IN 253 08:24:53 AUG 08, 20XX #8 CERBERUS PYROTRONICS , ASD TESTING ENABLED, MXL PANEL
The System flashes the currently active summarize selection for the module address. The operator may then press the right or left arrow keys to highlight either YES or NO and then press the ENTER key to accept and program the selection. When ENTER is pressed, the System scrolls to the next installed module address. The Up arrow key terminates the Select_Mods mode. All Select_Mods selections remain intact until the System is turned off, even if summarize mode is toggled.
www.PDF-Zoo.com
3-48
Operation
One trouble is posted per module address, regardless of how many troubles are detected at that module address. A trouble is not posted unless at least one trouble is detected at that module address. The trouble report is consistent with existing MXL-IQ trouble messages and the text reads Troubles summarized. The MXL-IQ only reports TRBL-INs when summary mode is enabled at an address. Alarm, supervisory, security, and status event reporting are not effected. Modules which are NOT selected for summary report their troubles as usual, even if summary mode is turned on for other module addresses. When a module address is summarized, individually occurring troubles are not broadcast to XNET; the single Troubles summarized trouble is broadcast to XNET. The Troubles summarized trouble is implemented as any other system trouble, being logged to history, taking up one of the 300 trouble slots, and appearing in List Troubles requests. All summarize selections are unaffected through RESET and default to CSG-M setting at power up. Test: Summarize - OFF When Summarize OFF is selected, the System annunciates the following trouble:
System Commissioning Mode TRBL OUT
and turns on the Partial System Disable LED. The System displays one summarized trouble for the total system.
Test: Manual_Activate
Use Test Manual_Activate to: Perform testing on input points and the associated output logic expected when the point is activated. Generate alarms and associated output activations. Select Manual_Activate and press ENTER. The System asks you for a module number and device number.
Type In Module & Device: -
Type the three-digit module number and three-digit device number using the numeric keypad and press ENTER. Upon entering the device address, the System performs as follows based on the point type:
MANUAL INPUT POINT ACTIVATION
No Input Point Error message. Analog Smoke System issues command to place device into the alarm state via Detectors sensitivity adjustment. Device then reports alarm as if an actual alarm occurred. Associated outputs follow. All Other Inputs System will not issue any command to device, but will synthesize the reporting of alarm in by the device. Associated outputs follow.
and turns off the Partial System Disable LED. Preexisting Troubles summarized events remain and the System reverts to normal trouble reporting and processing for all new troubles. Test: Summarize - ON When Summarize ON is selected, the System annunciates the following trouble:
System Commissioning Mode TRBL IN
Test: Manual_Activate - Test This provides a remote switch that upon activation/deactivation of the TRI, the MXL-IQ reads the module-device address provided and performs the operations outlined above. This use is primarily for, but not limited to, testing intelligent duct detectors.
www.PDF-Zoo.com
3-49
Operation
www.PDF-Zoo.com
3-50
+D=FJAH
To ensure maximum safety, follow the procedure described below. To ensure proper and reliable operation, we recommend the following inspection and testing schedule:
Every Year
1. Check that the System operates as programmed by CSG-M and in accordance with specifications. 2. Perform any other applicable tests required by national or local fire codes.
Fuse Replacement
Fuse ratings are as follows:
Fuse
F1 F2 F3 F4
For
Main Power Battery CZM-1B6 Power 24V Output
Rating
8A, 3 AG, Normal Blow 15A, 3 AG, Normal Blow 2A, 3 AG, Normal Blow 15A, 3AG, Normal Blow
The fuses are located on the upper portion of the SMB-2 (See Figure 2, page 1-4).
www.PDF-Zoo.com
4-1
TROUBLESHOOTING
Troubleshooting both the external wiring and the MXL-IQ System wiring follows the steps in System Function Checkout on page 2-16. If a fault occurs, refer to the Troubleshooting Guide. Locate the type of fault or any trouble message displayed and follow the directions in the Corrective Action column.
Sometimes you can locate a fault quickly using the Troubleshooting Guide. When this is not possible, continue with the checkout procedure on page 2-16 and then the Troubleshooting Guide until all faults and troubles are corrected. Then repeat the checkout procedure to ensure that no additional problems were introduced and that the original problem was corrected.
TABLE 19 TROUBLESHOOTING GUIDE This guide assumes that all modules, devices, and wiring are installed. Note: Do NOT change modules or wiring unless power is OFF. If available, use your printer during troubleshooting operations.
SYMPTOM
1. POWER LED is not lit; display on MKB-4 is blank.
PROBABLE CAUSE
No AC Battery
CORRECTIVE ACTION
Check AC and battery. Check fuses F1 and F2 on the SMB-2 and the circuitbreaker on the MPS-6. Check AC and battery wiring. If power connections are OK, check the cable between the SMB-2 and MKB-4 for proper installation.
2. POWER LED is on, MKB-4 display is blank. 3. MKB-4 display shows the following default message: CERBERUS PYROTRONICS MXL
Problem on the MKB-4. Improper address on MKB-4 No communication between SMB-2 and MKB-4. Defective MKB-4. If MOM-2/4 installed, defective network modules(s). Defective SMB-2
Adjust contrast control R14 on the ANN-1 board. Remove the MKB-4 and check cable from ANN-1 to the display. If MKB-4 is defective, replace it. Correct address setting on the MKB-4 using S1. See the installation instructions for the MKB-4, page 2-4. Check the cable between the SMB-2 and the MKB-4. Replace the cable if defective. Replace the MKB-4. Disconnect the MOM-2/4 from the SMB-2. If probelm resolved, reconnect MOM-2/4 and remove all modules from MOM-2/4. Reinstall all modules one at a time. Replace any that cause the problems to reoccur. Replace SMB-2
Check loop wiring for shorts, opens, etc. using the Field Wiring Checkout Guide (page 2-11). Check that all analog devices are I or IL Series devices, or are CZM-1B6s. See the list of compatible devices in the appendixes. Check that all devices are installed. Check that all devices installed comply with the configuration printout from CSG-M. Check printed trouble list for ID troubles and correct device IDs as required. Check devices using the FPI-32 Programmer Tester. Replace devices that fail to respond.
www.PDF-Zoo.com
4-2
PROBABLE CAUSE
End-of-line resistor improperly or not installed. Notification appliances improperly installed.
CORRECTIVE ACTION
Check that the end-of-line resistor is 2.2K, W and is installed according to the instructions. Check notification appliances for presence of polarizing diodes and correct device wiring. Check NACs for proper wiring (shorts, opens, etc.). Use the Field Wiring Checkout Guide, page 2-11.
Incompatible notification appliance connected. Error in control logic functions. 6. Output devices connected to System relays do not work. Power source for ouput devices missing or not connected. Improper wiring of connected devices. Connected devices are not compatible with power source. 7. CZM-1B6 reports a trouble. No power to CZM-1B6. Wiring error on initiating device circuit. 8. Modules in MOM-2/4 do not work. No power to MOM-2/4. No communications between SMB-2 and MOM-2/4. Modules are not properly seated in edge connectors. Modules are not properly addressed. 9. CSM-4 does not respond to output logic commands. Fuses are blown. CSM-4 is improperly configured. Incompatible notification appliances are connected. Error in control logic functions.
Check P/N 315-096363 for a list of compatible notification appliances. Replace incompatible devices. Check the logic functions using the printout from CSG-M; correct and reload the System from CSG-M into the SMB-2. Check that the power source is connected and that power is available.
Check that output devices are properly wired. Check that power source and ouput devices are compatible. On the SMB-2, check fuse F3. At the CZM-1B6 check power input; DC power must be 16-31 VDC. Check polarity. Check for opens or incorrect or missing end-of-line resistor (4.7K, W). Check power cable connectors between the SMB-2 (P3) and the MOM-2/4 (P5). Replace the power cable, if defective. Check communications cable connections between the SMB-2 (P6) and the MOM-2/4 (P7). Replace the communications cable, if defective. Remove and reseat all modules. Address the modules correctly using the printed configuration from CSG-M (See CSG-M Programming Manual, P/N 315-090381). Check wiring for shorts using the Field Wiring Checkout Guide (page 2-11). Replace fuses. Check and correct the configuration using the installation instructions for the CSM-4 (P/N 315-090854) and the printed configuration from CSG-M (See CSG-M Programming Manual, P/N 315-090381). Check P/N 315-096363 for a list of compatible notification applicances. Replace incompatible devices. Check the logic functions using the printout from CSG-M; correct and reload the System from CSG-M into the SMB-2 (See CSG-M Programming Manual, P/N 315-090381). Replace CSM-4.
Defective CSM-4.
www.PDF-Zoo.com
4-3
PROBABLE CAUSE
Power source for device is missing or not connected. Error in control logic functions. Connected devices are incompatible with power source. Defective CRM-4.
CORRECTIVE ACTION
Check that the power source to the CRM-4 is connected and that power is available. Check the logic functions using the printout from CSG-M; correct and reload the System from CSG-M into the SMB-2 ( See CSG-M Programming Manual, P/N 315-090381. ) Check that the power source and output devices are compatible.
Replace CRM-4. Check for wiring errors using the Field Wiring Checkout Guide ( page 2-11) and the installation instructions for the CZM-4 ( page 2-14) . Check that the end-of-line capacitor is the proper value and is properly connected. Unused zones must have end-of-line capacitors installed on MOM-2/4 screw terminals ( 50 MFD, 50 VDC polarized electrolytic capacitor) . See the installation instructions for the CZM-4 ( page 2-14) . Replace the CZM-4.
Defective CZM-4.
www.PDF-Zoo.com
4-4
+D=FJAH
INTRODUCTION
The table below shows the selections in the Walktest Menu and their related help messages.
HELP MESSAGE
www.PDF-Zoo.com
5-1
System w/AUD
Select this option to walktest all CZM-4 zones, CZM-1B6 zones, MID-16 inputs, and ALD inputs with audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions.
Cancel
Select this option from the menu while in the Walktest mode to set the Walktest timer at the 1 minute left in Walktest mark. This allows the MXL-IQ to complete Walktest sequencing on devices placed in test (alarm) just before cancellation. The MXL-IQ completes the final 60 seconds of the Walktest as indicated in Walktest Ending Sequence (See page 5-4).
System SIL
Select this option to walktest all CZM-4 zones, CZM-1B6 zones, MID-16 inputs, and ALD inputs without audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions.
Extend
Select this option from the menu while in the Walktest mode to reset the Walktest timer to the 4 hours remaining mark.
Loop w/AUD
Select this option to walktest input devices on a specific ALD loop, MOI-7 (MID-16) group, or on all four zones of a CZM-4 with audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD loop or CZM-4 conventional zones in Walktest. WARNING A device placed in Walktest is disconnected from its usual functions. Alarm causing devices in Walktest DO NOT CAUSE ALARMS until the MXL-IQ is out of the trouble of Walktest.
Loop SIL
Select this option to walktest input devices on a specific ALD loop, MOI-7 (MID-16) group, or all four zones of a CZM-4 without audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions for the ALD loop or CZM-4 conventional zones in Walktest.
In order to reduce the chance of problems, the following procedure must be followed before performing the Walktest. 1. Inform the person in charge of the MXL-IQ fire alarm system that a Walktest is to be performed and that part or all of the fire detection system will be disabled. It is also advisable (or may be required) to notify the fire department of the test. 2. Use the MXL-IQs LIST menu to obtain a printout of the device types and custom messages for ALL modules to be walktested. 3. Review the list with the person in charge of the fire protection equipment to ensure that the custom messages provide adequate information for locating and testing the devices in question. 4. Disable the ASD applications in the system using ASD_Device in the TEST menu prior to performing the walktest.
Zone wAUD
Select this option to walktest an individual conventional zone (CZM-1B6 or CZM-4 zone) with audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions for the conventional zone in Walktest.
Zone SIL
Select this option to walktest an individual conventional zone (CZM-1B6 or CZM-4) without audible feedback to the technician. This mode inhibits the MXL-IQ from annunciating real alarm conditions for the conventional zone in Walktest.
5-2
www.PDF-Zoo.com
Press ENTER, or wait 60 seconds and the MXL-IQ returns to the Walktest menu. (The MXL-IQ is in system Walktest.) The LCD indicates the time remaining in Walktest in the last five positions on the display. The time is indicated in HH:MM (hours:minutes) until less than one hour remains, then it is indicated in MM:SS (minutes:seconds). Locate the device to be tested and place that device in alarm (or trouble). When the event is reported to the MXL-IQ, the following sequence occurs: 1. When the System is in the audible Walktest mode, all silenceable and nonsilenceable audibles that are not already active or disarmed sound the code, depending on how the device is used in the CSG-M. The codes are: EVENT
ALARM SUPERVISORY TROUBLE SECURITY STATUS/OTHER
NOTE: The Walktest Ending Sequence (See page 5-4) occurs with audible warnings in the audible Walktest modes. NOTE: The MXL-IQ will not allow a walktest to be initiated if there are Alarms or Supervisory events in the event queues.
CODE
2 seconds on, then off 2 one-second pulses (on-off) 4 seconds on, then off 4 one-second pulses (on-off) 6 seconds on, then off
5-3
www.PDF-Zoo.com
Move the cursor to the L in Loop wAUD for a Walktest with audible feedback or to Loop SIL for a silent Walktest. Press ENTER. The MXL-IQ prompts the user for the module number to be tested. Enter the desired module network address, including all leading zeros, followed by ENTER. If the network address entered is not an ALD, MOI-7, or CZM-4, the message Invalid type for Walktest is displayed for 2 seconds on the LCD. The display then returns to the Walktest menu. If the module type is an ALD, MOI-7, or CZM-4 in the CSG-M, the following events take place: - the PARTIAL SYSTEM DISABLE LED lights - the TROUBLE LED flashes - the internal audible sounds - the Walktest activated trouble for the module appears on the trouble list - if a printer is installed, the trouble is also printed The LCD display on the MKB-4 reads:
In Walktest. Normal operation disabled. ENTER to continue.
3. The LCD displays the device address, custom message, WLK IN/OUT [event type], and device type for 8 seconds. 4. If the ALD device has an LED, it turns on for 30 seconds to provide additional feedback to the technician. If the MXL-IQ detects multiple events, they are automatically spaced 8-10 seconds apart to allow for separation of the coding. Up to five simultaneous events may be queued for processing.
Press ENTER or wait 60 seconds and the MXL-IQ will return to the Walktest menu. (The MXL-IQ is in system Walktest.) The LCD indicates the time remaining in Walktest in the last five positions on the display. The time is indicated in HH:MM (hours:minutes) until less than 1 hour remains; then it is indicated in MM:SS (minutes:seconds). Locate the device to be tested and place that device in alarm (or trouble). When the event is reported to the MXL-IQ, the following sequence occurs:
5-4
www.PDF-Zoo.com
CODE
2 seconds on, then off 2 one-second pulses (on-off) 4 seconds on, then off 4 one-second pulses (on-off) 6 seconds on, then off
When 45 seconds remain, all silenceable and non-silenceable audibles that are not already active or disarmed cycle on-off until Walktest times out. Do NOT continue to walktest devices. This 45 second period of no new Walktest events ensures that all devices are reset when the Walktest timer expires and the System returns to normal operation. Alarming a device during this period might result in the reporting of erroneous events when the system returns to normal operation.
NOTE: If an alarm or supervisory is reported from a device that is NOT in Walktest, the Walktest is suspended immediately. No further Walktest events are annunciated or coded. The Walktest remains running in the background of the MXL-IQ until it times out or is canceled. WARNING: When performing a partial system Walktest, DO NOT TEST any devices that are not in the Walktest as this will cause an alarm in the system.
2. When a printer is installed, the printer prints a message similar to the following:
WLK [event type] IN/OUT device address time/date device type, custom message, trouble type (if applicable)
3. The LCD displays the device address, custom message, WLK IN/OUT [event type], and device type for 8 seconds. 4. If the ALD device has an LED, it turns on for 30 seconds to provide additional feedback to the technician. If the MXL-IQ detects multiple events, they are automatically spaced 8-10 seconds apart to allow for separation of the coding. Up to five simultaneous events may be queued for processing.
5-5
2. When a printer is installed, the printer prints a message similar to the following:
WLK [event type] IN/OUT device address time/date device type, custom message, trouble type (if applicable)
3. The LCD displays the device address, custom message, WLK IN/OUT [event type], and device type for 8 seconds. 4. If the ALD device has an LED, it turns on for 30 seconds to provide additional feedback to the technician. If the MXL-IQ detects multiple events, they are automatically spaced 8-10 seconds apart to allow for separation of the coding. Up to five simultaneous events may be queued for processing. When 5 minutes remain, the system begins the Walktest Ending Sequence (See page 5-5). NOTE: If an alarm or supervisory is reported from a device that is NOT in Walktest, the Walktest is suspended immediately. No further Walktest events are annunciated or coded. The Walktest remains running in the background of the MXL-IQ until it times out or is canceled.
Press ENTER or wait 60 seconds and the MXL-IQ returns to the Walktest menu. (The MXL-IQ is in system Walktest.) The LCD indicates the time remaining in Walktest in the last five positions on the display. The time is indicated in HH:MM (hours:minutes) until less than 1 hour remains, then it is indicated in MM:SS (minutes:seconds). Locate the device to be tested and place that device in alarm (or trouble). When the event is reported to the MXL-IQ, the following sequence occurs: 1. When the System is in the audible Walktest mode, all silenceable and nonsilenceable audibles that are not already active or disarmed sound the code, depending on the device usage in the CSG-M. The codes are as follows: EVENT
ALARM SUPERVISORY TROUBLE SECURITY STATUS/OTHER
WARNING: When performing a partial system Walktest, DO NOT TEST any devices that are not in the Walktest as this will cause an alarm in the system.
CODE
2 seconds on, then off 2 one-second pulses (on-off) 4 seconds on, then off 4 one-second pulses (on-off) 6 seconds on, then off
5-6
www.PDF-Zoo.com
+D=FJAH
History Log
The MXL-IQ history system has five major parts. They are: 1. CSG-M options that control the type and number of events the MXL-IQ records. 2. Logging lists that record MXL-IQ hardware events. 3. Event viewing and listing in the MXL-IQ through the MKB-4 and attached printer. 4. History removal and collation outside the MXL-IQ. 5. Report generation and analysis on an external PC.
INTRODUCTION
Fire Protection Company Name CSG-M Memory=2900 used, 316848 free Options, System Message, Authorizations CONFIG => TEST1
Options, System Message, Authorizations Other System Flags History Recording Options System Holidays
www.PDF-Zoo.com
6-1
History Log
Fire Protection Company Name CSG-M Memory=2900 used, 316852 free History Recording Options CONFIG => TEST1
History mode -------------------> Log alarms ---------------------> Log troubles -------------------> Log supervisories --------------> Log securities -----------------> Log status ---------------------> Log verification ---------------> Log output ---------------------> Log resets ---------------------> Log block acks. ----------------> Log audible changes ------------> Log manual sens. changes -------> Log logic sens. changes --------> Log arm/disarm -----------------> Log energize/deenergize --------> Log time changes ---------------> Log passwords ------------------> Log overrides ------------------> Enable History Log Via MKB Menu >
Small YES YES YES YES NO NO NO YES YES YES NO NO YES YES YES YES NO NO ESC = Prev. Menu
Screen 2 shows the default conditions for the history option when it is selected for the first time. Keep in mind that the external data base may not contain all events that were ever detected. The completeness of the data base depends on whether the system operator extracts all event log information before it is lost.
When the event storage area becomes 80% full, a system trouble begins.
the trouble audible sounds the trouble indicator lights the message Event Log 80% full shows on the LCD display this trouble operates like any other trouble in the system
Logging Methods
1. Small list 2. Circular list
When the event storage area becomes 90% full, a new system trouble begins.
www.PDF-Zoo.com
6-2
History Log
the trouble audible sounds the trouble indicator lights the message Event Log 90% full shows on the LCD display this trouble operates like any other trouble in the system events are stored in non-volatile memory. Once all available storage is used, the oldest history entries are replaced by newer ones. It is assumed that the end user selects this mode because he does not wish to maintain an external history data base. Therefore, only two warning troubles are issued: 1. When the number of recorded events reaches 80% of the total. 2. When the number of recorded events reaches 90% of the total. Once this trouble is acknowledged, it disappears until 80% of events is reached in the next cycle. Using the circular logging mode does not prevent the storage of history information into an external data base. However, there is a high probability of loosing old events because of the limited warnings given when events are about to be overwritten. Beginning with MXL-IQ Rev. 6.0, the user can suppress the Circular History Log Full Trouble. This option must be set in CSG-M and is only available if the history is in circular mode.
When the event log is full, an new trouble condition occurs which causes the trouble audible to activate.
the message Log FULL, Events will be lost appears on the display panel upon reset this trouble reappears, replacing the 90% trouble message when the log is full, all new events are lost This system encourages removing history information into an external data base before the log overflows.
Circular Logging
In the circular logging mode, the MXL-IQ guarantees that the most current 500
Fire Protection Company Name CSG-M Memory=2900 used, 316852 free DISPLAY MXL-IQ Panel Info CONFIG => TEST1
MXL-IQ PANEL INFO: MXL-IQ ROM Version -------------------> MXL-IQ Main Board Version ------------> MXL-IQ Minimum Allowable Board Ver.---> RAM size -----------------------------> EEROM size ---------------------------> MXL-IQ Dictionary Version ------------> MXL-IQ Alt. Dictionary Version--------> History Memory Available -------------> IEC Storage Memory Available ---------> PROGRAMMING INFO: Configuration Source Filename --------> Configuration Size -------------------> Last Programming Date ----------------> Configuration Revision Level ---------> Programming Info CHECKSUM ------------>
Rev. 1.00 2 Rev. 1.00 163840 bytes 114688 bytes 0 0 818 (11) elements (used) 8189 bytes
6-3
History Log
Logging Item Selection The system designer can log one or many event types. The selection is determined by the system requirements, the amount of event storage, and the external data base design. The following list summarizes event types that can be selected. * ALARMS * TROUBLES * SUPERVISORIES * SECURITIES STATUS CHANGES DEVICE VERIFICATION OUTPUT ACTIVATIONS * RESET * BLOCK ACKNOWLEDGE * AUDIBLE CONTROL SET SENSITIVITY AUTO SET SENSITIVITY * ARM/DISARM * ENERGIZE/DE-ENERGIZE * SET TIME * PASSWORD OVERRIDE *The items marked with an asterisk are set as default when the logging option is first selected. At least one event type must be selected. Pressing ENTER erases the History section in the flash no matter what state the History is currently in (manually turned on or off); pressing any other key aborts the action. Manual manipulation of History using the MKB is logged in History as in the following examples:
History Manually Erased History Manually Turned off History Manually Turned on
System Message Authorization, then select History Recording Options. From History Recording Options, move the cursor down to the line that reads Enable History Log Via MKB Menu, and select YES to compile the CSG-M program and download it to the MXL-IQ. (Refer to Screen 2.)
Effective with MXL-IQ Revision 6.0, this option allows the user with the highest level password to turn on, turn off, or erase the History, provided that this system option has been enabled in the CSG-M and the History mode is other than NONE (that is, either small or circular).
NOTES: 1. The operator should download the history log for future reference before erasing the MXL-IQs History, since once the history is erased it cannot be undeleted. 2. The history menu options do not alter the history mode selected in the CSG-M.
www.PDF-Zoo.com
6-4
History Log
There is a limited set of query selection and filter options available within the MXL-IQ. More complex options are only possible using an IBM PC that is running the MXL-IQ history support program. The user can get history log information from the MKB-4 control panel by choosing the TEST menu, selecting EVENT_LOG, and pressing ENTER. A submenu of filter selections is then displayed. The choices are as follows: Alrm_Only Only display or print alarm events Trbl_Only Only display or print trouble events Superv_Only Only display or print supervisory events Security_Only Only display or print supervisory events All_events Display or print all recorded history events Hist_Ctrl Use to turn History on/off Hist_Erase Use to Erase History If the user makes a selection from the filter menu using the ENTER key of the MKB-4, the output goes to the LCD display. If the filter menu is selected using the PRINT key of the MKB-4, then the output goes to the system printer. If the group of events selected is empty, then the MXL-IQ displays or prints, as appropriate, NO HISTORY ITEMS FOUND.
Cursor left or right until the desired filter type (See Query Filters, below) is reached and then press ENTER to display to the LCD, or PRINT to print on the MXL-IQ system printer. The MXL-IQ asks for a starting date and time. If a time is entered, it suppresses the display or printing of older events. This initial display of time and date indicates the oldest history event recorded in memory. If the operator presses the ENTER key without making any numeric input, then all events in the log are selected.
Query Filters
A limited set of event type filters is available from the MXL-IQ control panel. The mutually exclusive filters are: ALARMS The Alrm_Only filter selection displays or prints incoming alarms, alarm acknowledgments, audible control, and resets. This set of events gives the operator a clear picture of the important events that constitute an alarm condition. TROUBLES The Trbl_Only filter displays or prints troubles and resets. SUPERVISORIES The Superv_Only filter displays or prints supervisories and resets. SECURITIES The Security_Only filter displays or prints securities, device arms, device disarms, and resets. ALL The All_events filter displays or prints all events.
Query Selection
The MXL-IQ supports one query selection option when generating listings or printouts from the MXL-IQ control panel. From the TEST menu, move the cursor to the EVENT_LOG item and press the ENTER key to select history information. The MXL-IQ responds with a submenu that allows an event type filter to be selected.
HISTORY ON/OFF The Hist_Ctrl filter turns the History events on/off. HISTORY ERASE The Hist_Erase filter erases the History events.
www.PDF-Zoo.com
6-5
History Log
Where: 001001 The module/device address. The division sign indicates that this is a history log display. 1ST FLOOR EAST WING The custom message assigned to this input. 321 The history log sequence number. ACK Optional field indicating that this is an acknowledgment event. This field is blank when the initiating event is displayed. 12:24:48 Mar 10, 20XX The time that the event was logged. IN The event direction. The possible event direction types are: IN DEVICE REPORTS ACTIVE STATE
When the operator selects the LCD display mode, the NEXT and HOLD keys are used to navigate through the log list. When the history log list first displays, the oldest history event shows in the display. Use the NEXT key to select the next newest event in the list and the HOLD key to select the next oldest event in the list. When either end of the history log list is reached, the message End of History List displays. Continuing to press either key wraps the list to the oldest or newest event, as appropriate. The MXL-IQ remains in the history log list display mode until the up arrow key is pressed. As with all menu operations, if no keys are depressed for one minute, the current activity is canceled.
OFF DEVICE TURNED OFF DIS DEVICE DISARMED (always occurs with ARM)
ALR The event type. The possible abbreviations for Device Event types are: ALR TBL ALARMS TROUBLES
If the line begins with an event type name, such as Block Acknowledge, then the first line of the display reads:
mmm BLOCK ACKNOWLEDGE
where mmm is the module number of the MKB-4 or SMB that caused the event.
DEV DEVICE (used for ON and OFF indications) ARM DEVICE ARMED (disarmed when used with DIS)
Device Event
A device event is any alarm, trouble, supervisory, or security input change of state. This change of state can be into or out of an active condition. The LCD displays:
001001 1ST FLOOR EAST WING ACK 321 12:24:48 Mar 10,20XX IN ALR
Reset Event
A reset event is any cold, warm, manual, or watchdog reset. The LCD displays:
www.PDF-Zoo.com
6-6
History Log
253 10100 WATCHDOG RESET 1:22:04 Mar 10,20XX
SET TIME The message describing this display as a set time event. 10100 The history log sequence number. 2:00:30 Mar 10, 20XX The date and time in the MXL-IQ before the SET TIME function was performed. 2:10:45 Mar 10, 20XX The time when the event was logged. Note that this is also the new date and time in the MXL-IQ as a result of this operation.
Where: 253 The module address where the reset occurred. In this example, the watchdog reset originated on the SMB-2 at fixed address 253. The division sign indicates that this is a history log display. WATCHDOG RESET The message describing the type of reset that occurred. The possible messages for this field are: COLD RESET WARM RESET MANUAL RESET WATCHDOG RESET 10100 The history log sequence number. 1:22:04 Mar 10,20XX The time that the event was logged.
Where:
251 The module address where the block acknowledge occurred. In this example, the block acknowledge originated from the MKB-4 at address 251. The division sign indicates that this is a history log display. All Alarms Acknowledged The message that describes this display as an alarm block acknowledge event. The text changes to reflect one of the following four types of block acknowledgments, as appropriate: All Alarms Acknowledged All Troubles Acknowledged All Supervisories Acknowledged All Security Acknowledged 4211 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Where: 251 The module address where the time change occurred. In this example, the set time originated from the MKB-4 at address 251. The division sign indicates that this is a history log display.
www.PDF-Zoo.com
6-7
History Log
OVERRIDE The action that is being applied to the feature. The selections in this field are: OVERRIDE NORMAL 4212 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Where: 251 The module address where the audible silence occurred. In this example, the audible silence originated on an MKB-4 at address 251. The division sign indicates that this is a history log display. AUDIBLE SILENCED The message that describes this event. 4212 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Where: 251 The module address where the audible unsilence occurred. In this example, the audible unsilence originated on an MKB-4 at address 251. The division sign indicates that this is a history log display. AUDIBLE UNSILENCED The message that describes this event. 4213 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Override Event
This event occurs when an operator overrides a verification or confirmation. The LCD displays:
251 CONFIRMATION OVERRIDE 4212 11:25:14 Mar 11,20XX
Where: 251 The module address where the override operation occurred. In this example, the confirmation override originated on an MKB-4 at address 251. The division sign indicates that this is a history log display. CONFIRMATION The feature that is either being overridden or returned to normal. This selections in this field are: CONFIRMATION VERIFICATION
Password Event
This event occurs when an operator enters a new password at an MKB-4. The LCD displays:
251 PASSWORD LEVEL : 1 4214 11:25:14 Mar 11,20XX
Where: 251 The module address where the password event occurred. In this example, the
www.PDF-Zoo.com
6-8
History Log
password change originated on an MKB-4 at address 251. The division sign indicates that this is a history log display. PASSWORD LEVEL : 1 The message that describes this as a password event and indicates the new password authorization level that was entered. 4214 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Where: 001001 The module/device address. The division sign indicates that this is a history log display. 1ST FLOOR EAST WING The custom message assigned to this input. 321 The history log sequence number. 12:24:48 Mar 10, 20XX The time that the event was logged. NORMAL The sensitivity value sent to the device. The selectable values include: Hi_3 Hi_2 Hi_1 NORMAL Low_1 Low_2 Low_3
Where: 254 The module addres where the configuration change occurred. In this example, the configuration change originated from the field programmer at address 254. The division sign indicates that this is a history log display. Configuration changed The message that describes this as a configuration change event. 10 The old configuration modification sequence number. 11 The new configuration modification sequence number. Note: These values may not be consecutive. They depend on the number of modifications made to the configuration by the CSG-M. 4214 The history log sequence number. 11:25:14 Mar 11, 20XX The time that the event was logged.
Where: 001001 The module/device address. The division sign indicates that this is a history log display. 1ST FLOOR EAST WING The custom message assigned to this input.
www.PDF-Zoo.com
6-9
History Log
321 The history log sequence number. 2.12 Indicates that this is an IEC (Enviro-Link) set sensitivity event. The detector sensitivity has been set to 2.12 volts. (The voltage can range from 0-5 volts.) This field may contain the word CLEAN to indicate that this detector was cleaned and restored to its base sensitivity. + This symbol represents the type of automatic correction that was made. A plus sign (+) indicates that the sensitivity was increased, a minus sign (-) indicates that the sensitivity was decreased. 12:24:48 Mar 10, 20XX The time that the event was logged.
The history printout format available at the MXL-IQ control panel appears in the same format as all other listing type reports. The listing output is in the higher character density mode of the output device. The vertical pitch varies to clearly distinguish one event from another. If the target printer has variable point spacing, each event is separated by a 0.5 line gap. On printers without variable point spacing, there is one full blank line between events. To interrupt the listing operation at any time, press the CLEAR key. Significant system activities, such as alarms, troubles, etc., automatically terminate the listing. The printout always indicates when the listing has been prematurely terminated. (Refer to the History Log Sample Printout on the following page) The basic format of the history printout is: <Listing Date> <Listing Conditions> <Event Type [Modifier]> <Event Locator> <Event Time> <Event Sequence #> <Event Description> (repeated for each event having matching conditions) <Listing Terminator>
Where: FN0012 The label of the logical function that generated this sensitivity set. The division sign indicates that this is a history log display. SENSITIVITY SET BY LOGIC The message describing this as a logic sensitivity set event. 321 The history log sequence number. 12:24:48 Mar 10, 20XX The time that the event was logged. NORMAL The sensitivity value sent to the device. Hi_3 Hi_2 Hi_1 NORMAL Low_1 Low_2 Low_3 www.PDF-Zoo.com
Where: Listing Date Identifies the report type (in this case the history log) and the date that the report was generated. Listing Conditions Shows the filter and starting date for this report.
6-10
History Log
History Log Sample Printout
1 Line 1 Line 2 Line 3 Line 4 Line 5 Line 6 Line 7 Line 8 Line 9 Line 10 Line 11 Line 12 Line 13 Line 14 Line 15 Line 16 Line 17 Line 18 Line 19 Line 20 Line 21 Line 22 Line 23 Line 24 Line 25 Line 26 Line 27 Line 28 10 20 30 40 50 Listing of History Log at 14:32:22 Apr 04,20XX This is a FULL list beginning at 09:20:02 Mar 01,20XX: SENS NORM. FN0012 SENS Hi_1 FN0013 06:00:00 19:00:00 Mar 02,20XX Mar 02,20XX #1 #2 60 70 80
Sensitivity set by output logic Sensitivity set by output logic UTILITY CABINET, Input Dev.
TROUBLE IN 1-1 22:10:11 Mar 02,20XX #3 Response Too Low, TRI-2R Switch Input + Relay ACK. TRBL. 251 MAN. RST. 251 SENS NORM. FN0012 SENS Hi_1 FN0013 22:15:24 22:50:03 06:00:00 19:00:00 Mar 02,20XX Mar 02,20XX Mar 03,20XX Mar 03,20XX Mar 03,20XX #4 #5 #6 #7 #8
Troubles Block Acknowledged Manual Panel Reset Sensitivity set by output logic Sensitivity set by output logic ROOM 101 FIRST FLOOR, ID-60I
#9 #10
VERIFY 12-23 10:42:20 Ionization Detector ALARM IN 12-23 10:43:12 Ionization Detector OUTPUT ON FN0103 OUTPUT ON FN0010 ACK. ALARM 251 SILENCE 251 10:43:13 10:43:13 10:45:21 10:45:22 10:45:25 10:50:53
Mar 04,20XX
#11
Mar 04,20XX Mar 04,20XX Mar 04,20XX Mar 04,20XX Mar 04,20XX Mar 04,20XX Mar 04,20XX
Output logic operation Output logic operation Alarms Block Acknowledged Audibles silenced Manual Panel Reset Operator Login to Level 2 ROOM 221 SECOND FLOOR, ID-60I
DISARM 12-23 10:51:23 Ionization Detector DISARM ENERGIZE 7-2 7-2 10:52:04 10:52:24 19:00:00
FAN #1, CRM-4 Relay Output FAN #1, CRM-4 Relay Output Sensitivity set by logic
www.PDF-Zoo.com
6-11
History Log
Event Type Identifies the type of history event that is being reported. The following event types are arranged in groups. The modifier fields for each group are different. Group 1 types: ACK. ALARM Alarm block acknowledge ACK. TRBL. ACK. SEC. Trouble block acknowledge Security block acknowledge Supervisory block acknowledge Manual reset via MKB-4 Hard reset from power off Hard reset via reset jumper Hard reset via 6805 watchdog Alarm verify Energize an output Group 3 types: Hi_3 Hi_2 Hi_1 NORMAL Low_1 Low_2 Low_3 Group 4 types: 0 Lowest access 1 2 3 Highest access Group 5 types: ON OFF Condition now active Condition now inactive Group 1 type: No modifiers for this group Group 2 types: IN Condition now active OUT Condition now inactive ACK Condition now acknowledged SECURTY SUPERVS Security causing device event Supervisory causing device event
Group 3 types: SENS Sensitivity set Group 4 types: LOGIN Operator login Group 5 types: OUTPUT Output logic event
ACK. SUP.
Modifier The modifier is an optional field that extends the meaning of the event type. For example, ALARM IN, where IN explains the ALARM type.
VERIFY ENERGIZE
DE-ENERGIZE De-energize an output ARM DIS-ARM SILENCE UNSILENCE Arm a device Disarm a device Silence audibles Unsilence audibles
CONFIG.
Group 2 types: ALARM Alarm causing device event TROUBLE Trouble causing device event
www.PDF-Zoo.com
6-12
History Log
of the event as either a module number, module-device pair, or function name. 2. Destructive modeinformation can be extracted from the MXL-IQ and incorporated into a data base (See Screen 4). If the information is extracted from the MXL-IQ, the history is erased from the system, and the system is reset. Access to the destructive mode is password and vendor ID protected. The history contents and organization of the CSG-M configuration change over the lifetime of the system. As a result, the history extraction process must download both the encoded history log and its configuration in the CSG-M. At the conclusion of the extraction process, an .IMH file is created which contains fixed data that is common to all history extractions from a given CSG. This technique has the advantage of eliminating the need for a complex code in the MXL-IQ to reorganize the data, shifting that burden to programs in the PC environment which are more easily modified. However, this technique requires time to perform the download. Each access of the history, whether in the examine or extract mode, requires the transmission of the entire CSG-M configuration from the MXL-IQ to the PC host. For very large configurations, this could take many minutes for the first download after a
Event Time The time and date of this event. Event Sequence # The sequence number of this event in the history log list. The maximum value of this number depends on the type of logging selected and the length of time since the last download. Event Description The event description is either the custom message associated with a device, or for non-devices, it is a descriptive message.
Download from the MXL-IQ history log to the CSG-M history support feature occurs while the MXL-IQ maintains all normal operations. There are two ways to access history log events: 1. Non-destructive modeinformation can be examined only.
Fire Protection Company Name CSG-M Memory=2900 used, 316848 free CONFIG => TEST1 Transfer a System to or from an MXL-IQ Panel
SEND System Configuration TO MXL-IQ Panel READ System Configuration FROM MXL-IQ Panel VERIFY System Configuration in MXL-IQ Panel DISPLAY MXL-IQ Panel Info EXTRACT MXL-IQ Panel History
ESC=Prev. Menu
www.PDF-Zoo.com
6-13
History Log
configuration is changed. If the .IMH file is present after the first download of a configuration, the operation will run more quickly on subsequent downloads. not, the user is prompted to change disks. 4. The PC creates a raw data file that contains an identifying header. 5. The PC downloads the compressed history log data and appends it to the file. 6. The PC downloads the configuration data and appends it to the file. 7. The resulting file is closed and then tested for integrity. Any irregularity in this validation ends the extraction process and signals the user. 8. If this is a non-destructive download, then the process is complete.
If this is a destructive download, then the clearing of the history log in the MXL-IQ begins. A warm reset occurs in the MXL-IQ at the end of the extraction process.
www.PDF-Zoo.com
6-14
+D=FJAH
ALD-2I Wiring
www.PDF-Zoo.com
7-1
www.PDF-Zoo.com
7-2
MOM-2/4
1 2 3 4
TB1
CABLE MIN*
TB2
2-WIRE 18 AWG
LLM-1
1 2 3 4
TB2
LLM-1
1 2 3 4
CXM-1
NOTES 1. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 2. All circuits are rated 2 volts peak to peak, 1.3mA. All circuits are supervised. 3. Operates in full conformance with Style 4.
TB1
www.PDF-Zoo.com
7-3
MOM-2/4
1 2 3 4
TB1
TB1
LLM-1
TB2 TB2
LLM-1
4 1 2 3 4
*USE 2-WIRE
TWO 2-WIRE 18 AWG CABLE MIN* 600 OHM MAX LINE RESISTANCE TOTAL PER PAIR
NOTES 1. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 2. All circuits are rated 2 volts peak to peak, 1.3mA. All circuits are supervised. 3. Operates in full conformance with Style 7.
TB1
TB1
LLM-1
TB2
LLM-1
4
TB2
CXM-1
CONDITIONED NON-SWITCHED LEASED TELEPHONE LINE, 600 OHMS IMPEDANCE TYPICAL CLASS B (STYLE 4) CONNECTION
NOTES 1. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 2. All circuits are rated 2 volts peak to peak, 1.3mA. All circuits are supervised. 3. Operates in full conformance with Style 4.
MOM-2/4
1 2
R1 560 OHMS, 1/2W, 5% P/N 140-820366
TB1
TB1
LLM-1
TB2
LLM-1
4
TB2
R2
CXM-1
CMI-300 Wiring - Typical Class B (Style 4) Connection Using Conditioned, Non-Switched Telephone Line
www.PDF-Zoo.com
7-4
NOTES 1. Contact rating: 2A, 30VDC/120 VAC resistive. 2. Use only with power limited / Class 2 circuits. 3. Coils are supervised when de-energized. 4. Contacts are not supervised. 5. All relay contacts are shown in normal (de-energized) state.
www.PDF-Zoo.com
7-5
www.PDF-Zoo.com
7-6
Electrical ratings:
Supervisory 24V unfiltered, full wave rectified 12mA max 24V unfiltered, full wave rectified 1.5A max
Alarm
NOTIFICATION APPLIANCES
+
MOM-4 (TB1, TB2, TB3, or TB4) or MOM-2 (TB2 or TB4)
2 3 4
NO CONNECTION
2.2K, 1/2W
NO CONNECTION
+
1 5 6 7 8 9
10 11 12 13 14 15 16
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 3 ohms total. 4. End of line device: 2.2K, W, P/N 140-820380. 5. Either circuit may be wired Class A or B. 6. Both circuits are supervised. 7. Polarity shown in supervisory state.
www.PDF-Zoo.com
7-7
NOTES 1. Both circuits are not power limited. 2. The total loop resistance from the LLM-1 to the Municipal Tie, including the 14.5 ohms in the Municipal Tie, should not exceed 22.5 ohms. 3. Either circuit may be used. 4. Polarity shown in supervisory state.
Electrical ratings:
Trip Coil Trip Current Supervisory Current Voltage 14.5 ohms 220 to 320mA DC (momentary) 12mA DC 24V unfiltered, full wave rectified
Electrical Ratings:
24V unfiltered, full wave rectified Load must be a compatible polarity reversal labeled remote station receiver unit Rated current 3mA to 9mA, alarm/supervisory External circuit resistance 2K to 5K ohms Minimum emergency power 60 hour standby 5 minute alarm
When a CSM-4 circuit is used as a Leased Line trouble output, SW1 and SW2 on switch S2 must be set. These positions permit the degrade trouble bus to activate the trouble line.
www.PDF-Zoo.com
7-8
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. External resistance: 2K-5K ohms. 3. Both circuits are not supervised. 4. Polarity shown in supervisory state.
RELEASING SERVICE (Per NFPA 12A, NFPA 13, and NFPA 2001)
All wiring must be in accordance with Article 760 of NEC and the local building codes. Set all positions of switch S2 to OFF (OPEN).
Application NFPA 13 (Pre-Action Deluge) NFPA 12A (Halon) NFPA 20 01 (FM-20 0) Make Skinner ASCO ASCO ASCO Pyro Pyro Pyro Pyro Pyro Model LV2LBX25, 24V T8210A107, 24V R8210A107, 24V 8210A107, 24V 50 0-982631, 24V 50 0-286652, 24V 50 0-083377, 24V 50 0-086929, 24V ECHS-24 EXP
Electrical Ratings:
Solenoids 24 VDC 16.8 watts max 700mA max 12mA max 800mA max
Supervisory Alarm
NOTES 1. Releasing zones are not power limited. 2. Maximum resistance: 3 ohms total. 3. No end of line device required. 4. Both circuits are supervised for opens only. 5. Polarity show in supervisory state.
CSM-4 Loop Wiring for use as Releasing Service (per NFPA 12A, NFPA 13, and NFPA 2001)
www.PDF-Zoo.com
7-9
www.PDF-Zoo.com
7-10
NOTES: 1. Use only listed solenoids from the following table:
Application NFPA 13 (Pre-Action Deluge) NFPA 12A (Halon) NFPA 20 01 (FM-20 0) Make Skinner ASCO ASCO ASCO Pyro Pyro Pyro Pyro Pyro Model LV2LBX25, 24V T8210A107, 24V R8210A107, 24V 8210A107, 24V 50 0-982631, 24V 50 0-286652, 24V 50 0-083377, 24V 50 0-086929, 24V ECHS-24 EXP
2. 3. 4. 5.
Solenoids supervised for opens only. Polarity shown in supervisory condition. Releasing circuits are not power limited. No end-of-line device used on Pre-Action/Deluge or releasing circuits. 6. Configure CSM-4 Pre-Action/Deluge circuits as Municipal Tie. 7. Maximum of 4 zones per MOM-2. 8. Each MOM-2 must be powered from a separate ALARM-SAF power supply. 9. Set all positions of S2 on the CSM-4 to OFF (OPEN).
MXL-IQ Releasing Service Wiring Diagram Using MOM-2 (NFPA 12A, 13, and 2001)
8210A107, 24V 50 0-982631, 24V 50 0-286652, 24V 50 0-083377, 24V 50 0-086929, 24V ECHS-24 EXP
5 8 8 8 8 8
TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 P1 P2 CSM-4 N N C C N N N N C C C C N N C C N N N N C C C C N C1 P5 2 1 TB6
TO SMB-1/-2 P6
N N C C P7
N N N N C C C C
N N C C
Pyro
MOM-4
CSM-4 P8 N C 1 TB7 2 1 N N C C P10 DO NOT USE P4 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 TB2 N N C C N N N N C C C C N N C C N N N N C C C C
2. 3. 4. 5. 6.
Solenoids supervised for opens only. Polarity shown in supervisory condition. Releasing circuits are not power limited. No end of line device used. Each MOM-4 must be powered from a separate ALARM-SAF power supply. 7. Set all positions of S2 on the CSM-4 to OFF (OPEN).
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 N N N N N N N N N N N N N N N N C C C C C C C C C C C C C C C C
MXL -IQ Releasing Service Wiring Using MOM-4 (per NFPA 12A, NFPA 13, and NFPA 2001)
ASCO
R8210A107, 24V
www.PDF-Zoo.com
24 VAC + BATTERY _ CHASSIS 120 VAC INPUT CHASSIS NEUTRAL HOT DC OUT FAULT + _ + _ 1 2 3 4 1 2 3 4 ALARM - SAF MODEL AS/PS5-BFS-24-UL UL GUIDE UTRZ FILE NO. S3584
VAI-1
TRI-60/B6
8 7 6 5 4 3 2 1 N N N C C C CHASSIS END OF LINE RESISTOR 3.6K, 1/4W P/N 140-820185 To Analog loop on MMB-1/2 or ALD-2I. Program TRI-60/B6 + as trouble causing program _ for normally open operation. Refer to TRI-60 Installation Instructions, P/N 315-092329 and TRI-B6 Installation Instructions, P/N 315-093315.
1 2 3 4
BATTERY ENCLOSURE UL LISTED FOR FIRE PROTECTIVE SERVICE _ 12 VDC LEAD ACID BTX-1 31 AH + _ 12 VDC LEAD ACID BTX-1 31 AH +
SOLENOID
SOLENOID
SOLENOID
SOLENOID
N N N N C C C C TB3
For FM Approved Deluge/Pre-Action: All initiating devices connected to the system MUST be wired Class A.
7-11
www.PDF-Zoo.com
7-12
Initiating Devices
The CZM-1B6 supports one zone of initiating devices in either Class A (Style D) or Class B (Style B). The initiating devices are connected to terminals 5-8 on the CZM-1B6 terminal block. Only the devices listed in Appendix A, Table 1 - Conventional Detectors: Compatible With CZM-1B6 on page A-1 may be used. Use up to 15 detectors, any combination of those listed. Only one PB-1191, and no additional devices, can be connected to a CZM-1B6. Detector operated accessories cannot be used with the CZM-1B6. The model numbers listed are the UL compatibility identifiers.
Alarm
Electrical connections:
There are three basic connections to the CZM-1B6 as follows:
STYLE B (CLASS B)
STYLE D (CLASS A)
+ + -
EOL
+ +
+ +
+ +
POWER
+ + EOL
POWER
+
EARTH
ANALOG LOOP
EARTH
ANALOG LOOP
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 35 ohms total. 4. Each detector or group of detectors, requires a two-wire circuit of thermoplastic fixture wire enclosed in conduit or limited energy shielded cable without conduit, if permitted by local building codes. 5. End of line device: 4.7K, W, P/N 140-820188. 6. Either circuit may be wired Class A (Style D) or Class B (Style B) 7. 15 devices maximum per circuit. 8. Initiating circuit is supervised.
www.PDF-Zoo.com
7-13
PB-1191 Installation
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 100 ohms total. 4. Maximum capacitance: 0.4F between + loop and loop. 0.8F between + loop and chassis. 0.8F between loop and chassis. 5. Each detector or group of detectors, requires a two-wire circuit of thermoplastic fixture wire enclosed in conduit or limited energy shielded cable without conduit, if permitted by local building codes. 6. No end of line device required. 7. Operates in full conformance with Style 6. 8. Operates in full conformance with Style 4. 9. Either loop may be wired Class A or B. 10. 60 devices maximum per loop. 11. T-tapping is NOT allowed on Class A loops. 12. Both circuits are supervised.
Analog Loops
The CZM-1B6 communicates with the MXL-IQ via the MXL-IQs analog loops, which may be on the SMB-2 or the optional ALD-2I module. The analog loops may be wired Class A (Style 6) or Class B (Style 4).
TB2
SMB-2
TB3
LOOP 2 4 3 2 1
CLASS A INSTALLATION 1
CZM-1B6
2 3 4 5 6 7 8
1 2 3
CZM-1B6
4 5 6 7 8
1 2 3 4
CZM-1B6
5 6 7 8
+ +
4 3 2 1
8 7 6 5
4 3 2 1
8 7 6 5
4 3 2 1
4 3 2 1
CLASS B INSTALLATION
See note 8.
1 7 8 2 3
1 2 3
CZM-1B6
4 5 6
CZM-1B6
4 5 6 7 8
1 2 3
CZM-1B6
4 5 6 7 8
CZM-1B6
1 2 3 4 5 6 7 8
www.PDF-Zoo.com
7-14
CZM-1B6 Power
The CZM-1B6 receives its power from the CZM-1B6 power output on the SMB-2. This power is available on TB5 of the SMB-2 on terminals 9-12. The power may be wired as Class A or Class B. Since the CZM-1B6 monitors the power at its screw terminals, it is possible to T-tap the power connection; this can be done only in the Class B configuration.
SMB-2 TB5
CLASS A INSTALLATION
See note 6.
12 11 10 9
CZM-1B6
5 6 7 8 1 2 3
CZM-1B6
5 6 7 8 1 2 3
CZM-1B6
5 6 7 8
11 10 9
www.PDF-Zoo.com
12
CLASS B INSTALLATION
4 1 2 3
CZM-1B6
5 6 7 8 1 2 3
CZM-1B6
5 6 7 8 1 2 3
CZM-1B6
5 6 7 8
CZM-1B6
4 1 2 3
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 4 ohms total. 4. No end of line device required. 5. Circuit is supervised. 6. T-tapping is NOT allowed on Class A loops. 7. For loop resistance, refer to the SMB-2 Installation Instructions, P/N 315-095097.
+ + -
CZM-1B6
5 6 7 8
7-15
NOTES 1. Intrinsically Safe Output: Open Circuit Voltage: 28 VDC Short Circuit Current: 93mA 2. Maximum loop resistance must not exceed 35 ohms. 3. A maximum of ten DI-3IS Ionization Detectors or up to five S121 or S122 Flame Detectors can be used in addition to mechanical (non-energy storing) shorting devices. 4. Maximum safe system voltage is 250 VAC. 5. For mounting and installation of the ISI-1, see the ISI-1 instructions. 6. Only mechanical (non-energy storing) shorting devices
such as the MS-51 Manual Station may be used. 7. WARNING: Do not make any connection to terminal 6 of the DB-3S base. Such a connection would void use in an intrinsically safe application. 8. In addition, S121 and S122 are also approved for use in Class II and Class III, Groups E, F, and G. 9. For guidance on installation see ANSI/ISA RP 12.6, Installation of Intrinsically Safe Instrument Systems in Class I Hazardous Locations. 10. For DI-3IS information, see the DI-3 Series installation instructions, P/N 315-081943. 11. For S121 and S122 information, see the installation instructions, P/N 315-085258.
www.PDF-Zoo.com
7-16
Alarm
Max ripple
STYLE B (CLASS B)
STYLE D (CLASS A)
STYLE B (CLASS B)
ZONE 1
ZONE 2
ZONE 3
ZONE 4
+ 1
+ 2
+ 5
+ 6
+
+ 9
+ 10
11
12
+ 13
+ 14
+
15
16
MOM-4 TERMINALS TB1 (UPPER SLOT) OR TB2 (LOWER SLOT) OR MOM-2 TERMINAL TB2
50uF 50V *
50uF 50V *
PBA-1191
Linear Beam Detector
- + - + - +
+
50uF, 50V *
DO NOT USE
* EOL CAPACITOR (P/N 100-115588) ** EOL RESISTOR (P/N 140-820188) EOL 4.7K, 1/4W **
CZM-4 Wiring
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 70 ohms total (40 ohms if relay bases are used). 4. Each detector or group of detectors, requires a two-wire circuit of thermoplastic fixture wire enclosed in conduit or limited energy shielded cable without conduit, if permitted by local building codes. 5. Loops may be wired Class A (Style D) or Class B (Style B). 6. 30 devices maximum per loop. 7. All circuits are supervised. 8. Do not connect more than one PBA-1191 to each zone. (Refer to PBA-1191 instruction, P/N 315-095424 for further information.) 9. Do not mix smoke detectors with the PBA-1191. 10. The PBA-1191 requires Rev. 3 or higher of CZM-4 firmware.
www.PDF-Zoo.com
7-17
www.PDF-Zoo.com
7-18
Electrical connections
The MOI-7 is shipped with one cable as described below. 5V Power The MOI-7 receives its 5 volt power on connector P1. This power can be sent to other modules requiring 5 volts from P2. Pin 1 is the positive input; pin 2 the return. Use the supplied cable, P/N 600-291261. MXL-IQ Network Connection For Style 4 wiring use only terminals 1 and 2 of TB1; terminals 3 and 4 of TB1 are not used. In a Style 4 network, make only Network A connections and ignore all Network B connections. Do not use connector P5 in this configuration.
www.PDF-Zoo.com
7-19
NETWORK A
TB4
N E 3 T W O 2 R K 1
RCC-1/1F (PS-5N7)
D D O O N N O O T T U S E U S E
STYLE 4
SEE MOI-7 WIRING
NOTES: 1. 18 AWG minimum. 2. 80 ohms maximum per pair. 3. Use twisted pair or shielded twisted pair. 4. Terminate the shield at the SMB-2 enclosure only. 5. Power limited to NFPA 70 per NEC 760. 6. Maximum voltage 8V p-p. 7. Maximum current 150mA.
P1 P2
1
4 3 2 1
TB1
TB2
DO NOT USE
P5
MOI-7
www.PDF-Zoo.com
7-20
MOD-16
Electrical ratings:
Supervisory 40V peak 2mA 40V peak 850mA
MID-16
Electrical ratings:
Module power 5VDC 2mA max
Alarm
50mA
MOI-7 Wiring
www.PDF-Zoo.com
7-21
NOTES 1. 18 AWG minimum for LED and 24V lamp connections. 2. 14 AWG minimum for supply connections (TB1-9 and 10, TB2-9 and 10). 3. All wiring must be in accordance with NEC 760. 4. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 5. All wiring to MID-16, MOD-16, or MOI-7 (non-network) modules is unsupervised. Any wiring leaving the enclosure must be within 20 feet, in rigid conduit, and must not leave the room. 6. For additional information see MOI-7 Installation Instructions, P/N 315-092799. 7. A maximum of 8 MOD-16s can be used with the MOI-7. 8. Both TB1-9 (or 10) and TB2-9 (or 10) must be connected to the common of the power supply. 9. When using SR-35, refer to table on this page.
TB1, 1-8, PROVIDES CONTROLLED OUTPUTS S1, 1-8 CONNECT TO CORRESPONDING OUTPUTS TB1, 1-8
TB1
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8
SW1
P1
P2
NOTE: THE CABLE P/N 555-190940 IS SUPPLIED. IF THE CONNECTION IS TO ANOTHER RAIL IN THE ENCLOSURE, USE OPTIONAL CABLE P/N 555-190941.
MOD-16
TO NEXT MOD-16 OR MID-16 (CABLE P/N 555-190940) NOTE: SWITCH S2-8 IS OPEN TO PROVIDE A 2.7K LIMITING RESISTOR.
1 2 3 4 5 6 7 8
SW2
TB2
1 2 3 4 5 6 7 8 9 10
LED
OR ANY AUXILIARY POWER SUPPLY U.L. LISTED FOR FIRE PROTECTION SIGNALING USE
MOD-16 Wiring
Connection To SR-35 Module*
MOD-16 TB1-1 TB1-2 TB1-8 SR-35 Screw Terminal 4 8 32
SMB-2, TB5-12 or PS-35, TB1-5 SMB-2, TB5-9 or PS-35, TB1-6 *For additional information see: SR-35 Instructions (P/N 315-087691) PS-35 Instructions (P/N 315-085062) SMB-2 Instructions (P/N 315-095931)
33
35
www.PDF-Zoo.com
7-22
NOTES 1. 18 AWG minimum for all input connections. 2. 14 AWG minimum for supply connections (TB1-9 and 10, TB2-9 and 10). 3. All wiring must be in accordance with NEC 760. 4. All wiring must conform to local codes and to the authority having jurisdiction over the installation. 5. All wiring to MID-16, MOD-16, or MOI-7 (non-network) modules is unsupervised. Any wiring leaving the enclosure must be within 20 feet, in rigid conduit, and must not leave the room. 6. For additional information see MOI-7 Installation Instructions, P/N 315-092799 7. A maximum of 8 MID-16s can be used with the MOI-7. 8. P1 is connected in parallel with TB1. 9. P2 is connected in parallel with TB2.
TB1
1 2 3 4 5 6 7 8 9 10
10
P1
DO NOT USE
P4
1
P3
1
P5
NOTE: THE CABLE P/N 555-190940 IS SUPPLIED. IF THE CONNECTION IS TO ANOTHER RAIL IN THE ENCLOSURE, USE OPTIONAL CABLE P/N 555-190941.
MID-16
10 10
SWITCH
1 10
P2
TB2
1 2 3 4 5 6 7 8 9 10
OR ANY AUXILIARY POWER SUPPLY U.L. LISTED FOR FIRE PROTECTION SIGNALING USE
MID-16 Wiring
www.PDF-Zoo.com
7-23
www.PDF-Zoo.com
7-24
www.PDF-Zoo.com
7-25
EXAMPLE: With: one CZM-4 and one CRM-4 and one CSM-4
Total load current = 0.720 + 0.075 + 0.034 = 0.83A With MPS-6/6W: Remaining Available Current = 2.0 - 0.83 = 1.17A (SMB-1) 6.0 - 0.83 = 5.17A (SMB-2) with no CZM-1B6 load With MPS-12/12W: Remaining Available Current = 2.0 - 0.83 = 1.17 (SMB-1) 12.0 - 0.83 = 11.17 (SMB-2) with no CZM-1B6 load
www.PDF-Zoo.com
7-26
NOTE: When a CSM-4 is used, you may add notification appliances to it if the maximum load current to the MOM-4 does not exceed 2 amps (SMB-1); or with an SMB-2, 6 amps (MPS-6/6W) or 12 amps (MPS-12/12W). Include the total alarm current on each CSM-4 notification appliance circuit when performing the calculations.
www.PDF-Zoo.com
7-27
EXAMPLE: With: one CZM-4 and one CRM-4 and one CSM-4
Total load current = 0.720 + 0.075 + 0.034 = 0.83A With MPS-6/6W: Remaining Available Current = 2.0 - 0.83 = 1.17A (SMB-1) 6.0 - 0.83 = 5.17A (SMB-2) with no CZM-1B6 load With MPS-12/12W: Remaining Available Current = 2.0 - 0.83 = 1.17 (SMB-1) 12.0 - 0.83 = 11.17 (SMB-2) with no CZM-1B6 load
www.PDF-Zoo.com
7-28
NIM-1R Network
Up to 32 MXL-IQ Systems can be connected in the network with an NIM-1R installed in each MXL-IQ System. For the highest level of fault protection, install the NIM-1R in the enclosure with the SMB-2, although this is not necessary. When connecting more than 32 MXL-IQ Systems, a REP-1/D2300CP repeater is required. Refer to the REP-1 Installation Instructions, P/N 315-092686 or the D2300CP Installation Instructions, P/N 315-092882, for the wiring diagram.
EOLR 120 OHMS, 1/4W P/N 140-820150 CABLE P/N 555-190506 TO SMB-2 DO NOT USE TB1, 1-16
1
EOLR 120 OHMS, 1/4W P/N 140-820150 DO NOT USE SEE FIGURE 2
10 11 12 13 14 15
EOLR 120 OHMS, 1/4W P/N 140-820150 CABLE P/N 555-190506 TO SMB-2
16
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 80 ohms per pair. 4. Use twisted pair or shielded twisted pair. 5. Terminate the shield ONLY at MXL-IQ panel 1. 6. Maximum voltage: 8V P-P. 7. Maximum current: 150mA. 8. For Style 4 omit all Network Pair B connections. 9. Do not use terminals 12 - 16 if NCC is not connected.
EOLR 120 OHMS, 1/4W P/N 140-820150 DO NOT USE SEE FIGURE 2
10 11 12 13 14 15 16
DO NOT USE
SEE FIGURE 2
10 11 12 13 14 15
P7
TB3
P7
TB3
P7
TB3
NIM-1R
NIM-1R
P3
NIM-1R
P3
MOM-2/-4
MOM-2/-4
MOM-2/-4
P3
www.PDF-Zoo.com
7-29
The total number of panels in the network must not exceed 64, including the NCC. For NIM-1Rs that are not connected to an NCC, leave terminals 1216 disconnected.
BROWN
WHITE RED
BLACK
GREEN
DB9 FEMALE
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum cable length 25 feet. 4. Cable must be in rigid conduit and can not leave the room. 5. Shielded cable is not recommended. 6. Maximum voltage: 24V peak to peak. 7. Maximum current: 20mA per circuit.
13
14
15
16
TB1
P7
12
13
14
15
16
TB3
NIM-1R
P1 P2 P3
MOM-4
2 3 4 5 6 7 8 9 10 11 12
P4
TB2
1
TB4
13
14 15 16 1 2 3 4 5 6 7 8 9 10 11 12
13
14
15
16
www.PDF-Zoo.com
7-30
For networked systems, each FSI port must be configured as either local or global in the CSG-M. Local FSI ports display information only on the MXL-IQ System to which they are connected. Global FSI ports display all events in all MXL-IQ Systems. Refer to the CSG-M Manual, P/N 315-090381, for further information.
CONNECT ONLY TO UL EDP OR ETI LISTED EQUIPMENT SUPERVISED EOLR 120 OHMS, 1/4W P/N 140-820150
TRANSMIT ENABLE RECEIVE EOLR 120 OHMS, 1/4W P/N 140-820150 DO NOT USE
TB1
P7
10
11
12
13
14
15
16
TB3
NIM-1R
P1 P2 P3
MOM-4
2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
P4
TB2
1
TB4
16
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 80 ohms per pair. 4. Use twisted pair or shielded twisted pair. 5. Terminate the shield ONLY at NIM-1R enclosure. 6. Maximum voltage: 8V P-P. 7. Maximum current: 150mA.
www.PDF-Zoo.com
7-31
AnaLASER Interface
The AnaLASER interface connects to the MOM-4/-2, TB3 or TB4, terminals 1 and 2, depending on where the NIM-1R is installed. Up to 31 AnaLASER detectors can be connected to a single NIM-1R. The ACC-1 requires an RS-485 to RS-232 converter which mounts in the back of the ACC-1 enclosure. The converter model number is AIC-4Z. The AIC-4Z supports from one to four AnaLASER detectors. Refer to the AIC-4Z Installation Instructions, P/N 315-093792, for the mounting and configuration of the converter and the ACC-1s.
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 80 ohms per pair. 4. Use twisted pair or shielded twisted pair. 5. Terminate the shield ONLY at NIM-1R enclosure. 6. Maximum voltage: 8V P-P. 7. Maximum current: 150mA.
EOLR 120 OHMS, 1/4W P/N 140-820150 CABLE P/N 555-190506 TO SMB-2
1
Complete wiring of the converter before installing the ACC-1 in the enclosure. Place the end-of-line resistors in the locations specified in Figure 4 below. Install the cable, P/N 500-693801 between the converter and the ACC-1. Refer to the AnaLASER Air Sampling Smoke Detection Manual, P/N 315092893, for connection to the AnaLASER detector and power supply, as well as mechanical mounting of the ACC-1.
DO NOT USE
14 15 16
DO NOT USE
16 15 14 13 12 11 10 9 8 7 6 5 4 3
P7
10
11
12
13
16 15 14 13 12 11 10
TB3
TB1
TB1
NIM-1R
P3
AIC-4Z
2 1 3 2 1 3 2 1
AIC-4Z
SINGLE ZONE CON1
2 1 3 2 1 3 2 1
MOM-4
JUMPER SETTINGS
LK1 1-2 JUMPERED LK2 2-3 JUMPERED LK3 2-3 JUMPERED
JUMPER SETTINGS
LK1 1-2 JUMPERED LK2 2-3 JUMPERED LK3 2-3 JUMPERED
CON4
CON3
CON2
CON4
CON3
CON2
REFER TO THE ANALASER AIR SAMPLING SMOKE DETECTION MANUAL, P/N 315-092893, FOR CONNECTION OF THE ACC, THE POWER SUPPLY, AND THE ANALASER DETECTOR AND AIR SAMPLING NETWORK.
TO ACC #1, P4
www.PDF-Zoo.com
7-32
Electrical connections:
The MXL-IQ Control Panel connects to the Silent Knight Model 5128/5129 Digital Fire Communicator using the Alarm, Trouble, and Supervisory dry contacts on the MXL-IQ Main Board. Refer to the Silent Knight 5128/5129 Fire Slave Communicator Installation Manual, P/N 150805, provided with Silent Knight Model 5128/5129 for dialer instructions. The Silent Knight Model 5128/5129 monitors all System troubles through the MXL-IQ trouble relay. The MXL-IQ delays the AC fail trouble signal in accordance with NFPA and UL requirements. In NFPA 72 Remote Station, install batteries to provide 60 hour standby capacity. For signalling service DACT wire according to the diagram on the following page.
www.PDF-Zoo.com
7-33
www.PDF-Zoo.com
7-34
TB5
12
CZM-1B6 POWER
11 10 9 8 7 6 5 4 3 2 1
CHASSIS
NOT SUPERVISED
SMB-2
SUPERVISED
TELCO 1 TIP (RED)
(RED)
TROUBLE
5 4 3
* *
ALARM
2 1
TO RJ31X
TB4
P2 - CHANNEL INPUTS
SUPERVISED
NOTES 1. TRI-60R/B6R input must be programmed in CSG-M as trouble causing. 2. TRI-60R/B6R output must be programmed in CSG-M to transfer on loss of AC Mains. 3. All wiring supervised except as noted. 4. For Remote Station, provide 60 hour battery capacity.
TO RJ31X
6 5
4 3
TRI-B6R
MPS-6/6W- Install the MPS-6/6W (See MPS-6/6W Instructions, P/N 315-090334/W). With the AC mains disconnected, connect the MPS-6/6W power cable to P1 of the SMB-2. Be sure that the jumper assembly is installed in P14 of the SMB-2. If this jumper is not installed, the SMB-2 will detect a permanent AC fail or indicate auxiliary power voltage is low. MPS-12/12W - Install the MPS-12/12W (See MPS-12/12W Instructions, P/N 315092030/W). Remove and discard the jumper assembly installed in P14 of the SMB-2. Disconnect the AC mains. Connect the MPS-12/12W power cable to P14 of SMB-2.
www.PDF-Zoo.com
7-35
FIELD WIRING
SMB-2
The screw terminals for the field wiring circuits are located on the left and right sides of the SMB-2. They are labeled TB1 through TB5. The field wiring circuits available are: CZM-1B6 power Analog device loop 1 Analog device loop 2 Notification appliance circuit 1 Notification appliance circuit 2 Common alarm relay Common trouble relay Style 4 RS-485 Network (MNET) The following sections describe each circuit type and give the related instructions. Refer also to the wiring diagrams.
CZM-1B6 power
CZM-1B6 12 11 10 9 TB5
+
DO NOT USE DO NOT USE
Auxiliary power is available on TB5, terminals 9 through 12 of the SMB-2. The circuit is power limited per NEC Article 760 and is rated at 1 amp, 18-31 VDC. This power supply is for use with the CZM-1B6 Remote Conventional Zone module. You may connect a maximum of 20 CZM-1B6s to this power source. T-tapped wiring can be used to obtain the maximum of 20 CZM-1B6s. Each tap can support a maximum of 10 CZM1B6s, 4 ohms max. Multiple power connections can be used provided you do not exceed the ratings above (20 CZM-1B6s max and 4 ohms per run max). For example, you could have four individual T-tapped power runs, for a total of 20 devices (6, 4, 3, and 7 CZM1B6s), each of the four runs not exceeding 4 ohms resistance.
CZM-1B6
T-TAPPING ALLOWED
CZM-1B6
www.PDF-Zoo.com
7-36
Only the devices listed in Appendix A, Table 2 - Analog Addressable Detectors on page A-1 may be used. The UL identifiers for compatibility are the same as the model names specified.
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Each detector or group of detectors requires the following: a 2-wire circuit of 18 AWG minimum thermoplastic fixture wire enclosed in a conduit. or 18 AWG limitedenergy shielded cable without conduit, if permitted by local building codes. 3. Maximum resistance: 100 ohms total. 4. Maximum capacitance: 0.4F between + loop and loop. 0.8F between + loop and chassis. 0.8F between loop and chassis. 5. Refer to Wiring Guide for compatible wire types.
6. Maximum voltage: Supervisory 30 VDC peak. Alarm 30 VDC peak. 7. Maximum current: Supervisory 66mA Alarm 66mA 8. No end of line device required. 9. Operates in full conformance with Style 4. 10. Operates in full conformance with Style 6. 11. Either loop may be wired Class A or B. 12. 60 devices maximum per loop. 13. T-tapping is NOT allowed on Class A loops. 14. Both circuits are supervised.
Analog loop electrical ratings: Supervisory 30 VDC peak 66mA max Alarm 30 VDC peak 66mA max (60 devices in alarm)
All wiring must be in accordance with Article 760 of NEC and the local building codes.
www.PDF-Zoo.com
7-37
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 3 ohms total. 4. End of line device: 2.2K, W, P/N 140-820380. 5. Either circuit may be wired Class A or B. 6. Both circuits are supervised. 7. Polarity shown in supervisory state.
ALARM
Alarm
Only the devices listed in Compatible Notification Appliances, P/N 315-096363 may be used. The UL identifiers for compatibility are the same as the model names specified.
www.PDF-Zoo.com
7-38
NOTES 1. Power limited to NFPA 70 per NEC 760. 2. Minimum wire size: 18 AWG. 3. Maximum resistance: 80 ohms total. 4. Use twisted pair or shielded twisted pair. 5. Terminate the shield ONLY at the SMB-2 chassis. 6. Maximum voltage: 8V P-P. 7. Maximum current: 150mA.
SMB-2
SMB-2 Fuses
NOTE: The fuses are located on the upper left and right corners of the SMB-2 board.
FUSE RATINGS
F1 F2 F3 F4 MPS-6 Input Battery Reversal CZM-1B6 Power 8A, 3 AG, Normal Blow 20A, 3 AG, Normal Blow 2A, 3 AG, Normal Blow
www.PDF-Zoo.com
7-39
www.PDF-Zoo.com
7-40
Appendix A
Compatible Devices
TABLE 2 ANALOG ADDRESSABLE DEVICES
TABLE 1 CONVENTIONAL DEVICES
Detector
DI-3/3H DI-A3/A3H DI-B3/B3H DT-11
5
Device
CZM-1B6 FP-11/FPT-11
4
Base
Installation Instructions
315-095355-2
Base
DB-3S AD-3I/ILP AD-3RI/3RP
Installation Instructions
315-081943-15 315-093234-4 315-086591-7
Compatible With
CZM-1B6 CZM-1B6 CZM-1B6
1,6
DB-11, DB-X11RS DB-3S + DB-ADPT 315-095921-4 DB-X3RS + DB-ADPT ADBI-60 + DB-ADPT AD-11P/11XPR DB-3S, DB-X3RS AD-3I AD-3XRI DB-3S, DB-X3RS AD-3I AD-3XRI DB-3S, DB-X3RS AD-3ILP AD-3XRILP DB-3S, DB-X3RS AD-3ILP AD-3XRILP DB-3S 315-095659-2 315-095306-3 315-090287-2 315-093234-4 315-093235-4 315-095387-1 315-093234-4 315-093235-4 315-092594-5 315-093234-4 315-093235-4 315-095028-1 315-093234-4 315-093235-4 315-093336-1 315-090903-3 315-093329-1 315-095302-1 315-093613-1 315-093315-3 315-094547-1 315-096242-2
FP-11 (d) 8, 10
4
1,6
1,6
PBA-1191 PE-3/3T
CZM-4 CZM-4
4
PE-11/PE-11T
CZM-1B6
1,6
CZM-4
FM Approved Only
DI-3IS + ISI-1 S121/S122 + ISI-1 DB-3S 315-081943-15 315-085258C CZM-1B6 CZM-1B6
2,6 3
ILP-2(d) 9, 10
1. May use up to 15 detectors of any type. 2. May use up to 10 DI-3IS ionization detectors in addition to mechanical (non-energy storing) shorting devices. 3. May use up to five S121 or S122 flame detectors in addition to mechanical (non-energy storing) shorting devices. 4. May use up to 30 detectors of any type, except PB-1191. 5. Do not use with alarm verification. 6. Do not use detector operated accessories with CZM-1B6. 7. Only one PB-1191, and no additional device, can be connected to a CZM-4 initiating zone. 8. The FP-11 is only compatible with MXL-IQ Rev. 6.0 or greater firmware. 9. Must use MXL-IQ Rev 3.0 or greater firmware. 10. When the CSG-M is configured, the DUCT application must be selected when the device is used in an air duct housing or in a spot duct application.
www.PDF-Zoo.com
A-1
Appendix A
www.PDF-Zoo.com
A-2
Appendix B
Device
CZM-1B6
Input State
Normal Alarm Trouble Normal Alarm Trouble Normal Alarm Trouble Normal Alarm Trouble Normal Alarm Trouble Normal Alarm Trouble Normal Alarm Trouble Not Available Not Available Not Available
Voltage Response
0.50-4.19 4.20-5.0 0 0.0 0-0.47 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 1.80-3.0 0 3.10-5.0 0 0.0 0-1.79 Not Available Not Available Not Available
LOW3 LOW2 LOW1 NOR M HI-1 HI-2 HI-3 LOW3 LOW2 LOW1 NOR M HI-1 HI-2 HI-3 LOW3 LOW2 LOW1 NOR M HI-1 HI-2 HI-3 LOW3 LOW2 LOW1 NOR M HI-1 HI-2 HI-3 LOW3 LOW2 LOW1 NOR M HI-1 HI-2 HI-3
5.25-10.0 0 5.12-10.0 0 5.0 0-10.0 0 4.88-10.0 0 4.75-10.0 0 4.63-10.0 0 4.50-10.0 0 5.25-10.0 0 5.12-10.0 0 5.0 0-10.0 0 4.88-10.0 0 4.75-10.0 0 4.63-10.0 0 4.50-10.0 0 5.12-10.0 0 5.0 0-10.0 0 4.88-10.0 0 4.75-10.0 0 4.63-10.0 0 4.50-10.0 0 4.38-10.0 0 5.12-10.0 0 5.0 0-10.0 0 4.88-10.0 0 4.75-10.0 0 4.63-10.0 0 4.50-10.0 0 4.38-10.0 0 5.12-10.0 0 5.0 0-10.0 0 4.88-10.0 0 4.75-10.0 0 4.63-10.0 0 4.50-10.0 0 4.38-10.0 0
4.25-5.12 4.12-5.0 0 4.0 0-4.88 3.88-4.75 3.75-4.63 3.63-4.50 3.50-4.38 4.25-5.12 4.12-5.0 0 4.0 0-4.88 3.88-4.75 3.75-4.63 3.63-4.50 3.50-4.38 4.12-5.0 0 4.0 0-4.88 3.88-4.75 3.75-4.63 3.63-4.50 3.50-4.38 3.88-4.25 4.12-5.0 0 4.0 0-4.88 3.88-4.75 3.75-4.63 3.63-4.50 3.50-4.38 3.88-4.25 4.12-5.0 0 4.0 0-4.88 3.88-4.75 3.75-4.63 3.63-4.50 3.50-4.38 3.88-4.25
0.63-4.12 0.63-4.0 0 0.63-3.88 0.63-3.75 0.63-3.63 0.63-3.50 0.63-3.38 0.63-4.12 0.63-4.0 0 0.63-3.88 0.63-3.75 0.63-3.63 0.63-3.50 0.63-3.38 0.88-4.0 0 0.88-3.88 0.88-3.75 0.88-3.63 0.88-3.50 0.88-3.38 0.88-3.25 0.88-4.0 0 0.88-3.88 0.88-3.75 0.88-3.63 0.88-3.50 0.88-3.38 0.88-3.25 0.88-4.0 0 0.88-3.88 0.88-3.75 0.88-3.63 0.88-3.50 0.88-3.38 0.88-3.25
0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.50 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75 0.0 0-0.75
ID-60T-135 ILT-1
MSI-10/20
ID-60P
MSI-10B/20B
MSI-MB6
ILP-1/ILPT-1 ILPT-1(d)
MSI-B6F
www.PDF-Zoo.com
B-1
Appendix B
www.PDF-Zoo.com
B-2
Appendix C
www.PDF-Zoo.com
C-1
Appendix C
NOTES The following modules draw no 24 VDC current and do not need to be included in the battery calculations: MOM-2 MOM-4 TSW-2 1. Use this column for battery size calculations. 2. Power is supplied by a separate UPS. 3. EOL currents included.
Load Current Per Circuit Standby 24 VDC Total Standby 24 Module Quantity Module Current VDC Module (See Note 1) End of Line Device Device Current Current 175mA SMB-2 12mA per NAC 1.1mA per device MKB-4 5mA 0 0 RCC-1/1F 75mA 0 0 TSP-40 70mA 0 0 10mA 0 CSM-4 12mA 15mA CRM-4 15mA per active relay 55mA CZM-4 0 3mA 105mA ALD-2I 0 1.1mA per device CMI-30 0 30mA 0 0 NIM-1R 70mA 0 NA MOI-7 120mA 0 0 MOD-16 2mA 0 0 MID-16 2mA 0 0 6mA CZM-1B6 5mA NA ICP-B6 18mA 2.5mA NA PIM-1 10mA 0 NA PIM-2 (See Note 2) 0 NA PAL-1 (See Note 2) 0 NA D230 0CP 50mA 0 0 Silent Knight 60 mA 0 0 Total System Current NFPA Local (72A), Proprietary (72D), UL 1076 (MMB-2 only) - Total AH x 24 = NFPA Municipal Tie (72B), Remote Station (72C) - Total AH x 60 = FM Approved Deluge/PreAction - Total AH x 90 = Battery Size (with Alarm Reserve Correction) x 1.3 =
www.PDF-Zoo.com
C-2
Appendix D
www.PDF-Zoo.com
D-1
Appendix D
The following modules draw no current from either the 5 VDC or 24 VDC power supplies and do not need to be included in these calculations: MOM-2 MOM-4 PAL-1 PIM-2 TSW-2
Module
Quantity
SMB-2 MKB-4 RCC-1/1F TSP-40 CSM-4 CRM-4 CZM-4 ALD-2I CMI-30 0 NIM-1R MOI-7 MOD-16 MID-16
(See Note 3) 0 80mA 70mA 34mA + 1.5A max per circuit 75mA 720mA 4 zones in alarm 105mA + 1.1mA per device 0 0 120mA 850mA max 32mA max 50mA 1.5A 0 0 130mA TOTAL 0 0 0 0 0
(See Note 3) 15mA 0 0 30mA 30mA 24mA 0 96mA 160mA 175mA 2mA 2mA 0 0 25mA 20 0mA 0 TOTAL 0 0 0 0 0 0
1. Use this column to calculate total current from 24 VDC supply to make sure it is not overloaded. 2. Use this column to calculate total current from 5 VDC supply to make sure it is not overloaded. 3. SMB-2 supplies 5V at 500mA, 24V at 6A (MPS6), 24V at 12A (MPS-12).
www.PDF-Zoo.com
D-2
Appendix E
Alarm Verification
The Alarm Verification feature provides the MXL-IQ with a way to verify an alarm from area type addressable smoke detectors connected to the analog loops or from standard smoke detectors connected to the CZM-4 module. This feature reduces the incidence of false alarms. When a detector is supervised with Alarm Verification, it is turned off immediately after the System first detects alarm causing data from it. The length of time that the detector is verified is fixed at 50 seconds. In MXL-IQ, an addressable detector is turned off by the System ignoring its data; a standard detector is turned off by the power actually being removed from the detector. After the turnoff period, the panel puts that detector into alarm if it has alarm causing data within 60 seconds of being turned back on. See the figure below for a graphic illustration of Alarm Verification You can select Alarm Verification for none, all, or any combination of addresssable smoke detectors. MXL-IQ supports a global verification feature called Device Confirmation. It provides adjustable AB verification times for all addressable: Ionization detectors Photo detectors Ionization and photo detectors
A____________________B________________________C Time
A AB BC Time at which the System initially recognizes an alarm from a smoke detector. The 50 seconds during which the System ignores the alarm data The 60 seconds during which the System alarms if the device is returning alarm data
CAUTION Use only detectors which are subjected to air velocities of less than 100 feet per minute with Alarm Verification. Under dynamic air velocity conditions, smoke may be swept from a smoke detector after the initial alarm. That may cause a long delay before verification. Do not select Alarm Verification for such applications.
www.PDF-Zoo.com
E-1
Appendix E
With Device Confirmation, the BC verification time known as System Justified Alarm time is also adjustable. It is the same time used by both ionization and photo detectors. If a device is individually selected for alarm verification, the alarm verification feature takes priority over the device confirmation option. For adjustment ranges, refer to the CSG-M Programming Manual, P/N 315-090381. There is an Override menu selection in the Test menu of MXL-IQ. Select Alr_Verify to disable all alarm verification or select Alr_Confirm to disable all alarm confirmation for a period of up to 4 hours or until manually re-enabled.
www.PDF-Zoo.com
E-2
Appendix F
Envirolink
SENSITIVITY VOLTAGE
Analog Voltage
0 Volts
www.PDF-Zoo.com
F-1
Appendix F
If a detector with Envirolink (IEC) reports an alarm condition before the detectors alarm threshold is adjusted, the alarm delays until the alarm threshold is adjusted. If the device continues to report an alarm condition once its alarm threshold is adjusted, the alarm reports. If the CSG-M and the device ID do not agree, the IEC for that device does not activate until the trouble condition is removed from the system and the panel is reset. The trouble conditions shown above are annunciated on a detector-by-detector basis as each detector is checked. MXL-IQ annunciates a trouble condition for a detector when its alarm threshold reaches a predetermined limit. The operator should acknowledge the trouble, clean the detector if possible, and reset the control panel. If the detector is not cleaned, the control panel annunciates this trouble condition after every panel reset until the detector is cleaned. When it is cleaned, that is detected by the Auto Clean Detection feature.
MXL-IQ Power On
When a system is brought on-line, or when there is a complete loss of power in an MXL-IQ enclosure containing detectors with IEC applied, the operator must perform a reset sequence for the IEC devices in that MXL-IQ and also reset the MXL-IQ. When an MXL-IQ is powered the first time, and there is no data for IEC devices, MXL-IQ leaves these devices at the default alarm threshold. However, if former IEC data is available, MXL-IQ adjusts the device alarm threshold accordingly.
NOTE: Automatic detection and documentation of the cleaning of a detector by MXL-IQ may take as long as 1 hour. To avoid this, use the Det cleaned option in the Test menu to avoid automatic clean detection. When you enter the address of the detector that was cleaned, MXL-IQ adjusts that detectors Norm sensitivity setting reference.
Detector Cleaned
IEC must be enabled in the CSG-M in order to have access to the Det_cleaned option through the MXL-IQ Annunciator Panel. At the Test menu, use the Left or Right arrow key to cause the D in Det_cleaned to start blinking:
OR
IEC LIMIT REACHED. SERVICE REQ
www.PDF-Zoo.com
F-2
Appendix F
The System asks you to type the module and device numbers. Type the three-digit module number and the three-digit device number (mmm/ddd), including all leading zeroes. Press ENTER. After entering the module-device, MXL-IQ checks whether the device is subject to IEC. If the device is not subject to IEC, or if IEC is not enabled for the system, an error messages displays:
If the device is an IEC detector, MXL-IQ displays and prints the time, date, device, and custom message of the cleaned device.
www.PDF-Zoo.com
F-3
Appendix F
www.PDF-Zoo.com
F-4
Appendix G
Latching/Non-Latching Troubles
This feature is not available for Networked MXL-IQ Systems. For NFPA 72 Proprietary systems, the following criteria must be met if the trouble is to be removed from the trouble queue: Module and device numbers must be identical Trouble type must be identical Both IN/OUT conditions must be recorded in the queue All printers being used must print both IN/OUT conditions Both IN and OUT conditions must be acknowledged and printed When all these conditions are met, MXL-IQ removes both the in and out occurrence of this trouble from the queue. If there are no other events in the system (alarm, supervisory, trouble, or security), MXL-IQ returns to the SYSTEM NORMAL display. If there are other events in the system, MXL-IQ updates the display. Not all troubles can be removed from the trouble queue. If there is no OUT condition reported (i.e., Class A loop trouble), MXL-IQ requires an acknowledgement and reset.
When the Latching/Non-Latching (self restoring) trouble option is set to YES in the CSG-M, MXL-IQ automatically removes trouble conditions from the trouble queue when the OUT OF TROUBLE condition is detected. For NFPA 72 Local, 72 Municipal Tie, and 72 Remote Station systems, the following criteria must be met in order for the trouble to be removed from the trouble queue: Module and device numbers must be identical Trouble type must be identical Both IN/OUT conditions must be recorded in the queue All printers being used must print both IN/OUT conditions When all these conditions are met, the MXL-IQ removes both the in and out occurrence of this trouble from the queue. If there are no other events in the system (alarm, supervisory, trouble, or security), MXL-IQ returns to the SYSTEM NORMAL display (without a system reset). If there are other events in the system, MXL-IQ updates the display.
www.PDF-Zoo.com
G-1
Appendix G
www.PDF-Zoo.com
G-2
Appendix H
UL 1076 requires a TSW-2 tamper switch as well as a supervised printer (PAL-1/ PAL-2). Other supervised printers that are selectable in CSG-M are the TI-820 and the LA-50. Only Models TRI-60/-60D/-60R or TRI-B6/-B6D/-B6R may be used as security points. A COMMUNICATION FAILURE with a TRI device configured for SECURITY results in a SECURITY ALARM as well as a communication trouble. When installing a TRI device in the CSG-M, be sure to set the device usage field to security; otherwise, the device usage defaults to fire alarm.
TRI-60 / TRI-B6
TRI-60R / TRI-B6R
TRI-60D / TRI-B6D
1 2 3 4 5 6 7 8
+ ANALOG - LOOP IN
SWITCH
1 2 3 4 5
+ ANALOG - LOOP IN
SWITCH
1 2 3 4 5 6 7 8
+ ANALOG - LOOP IN
SWITCH A
NOT USED
6 7 8
SWITCH B
NC
GND
GND * END OF LINE DEVICE: P/N 140-820185 REFER TO TRI INSTALLATION INSTRUCTIONS, P/N 315-092329 OR 315-093315, AS APPLICABLE
www.PDF-Zoo.com
H-1
Appendix H
www.PDF-Zoo.com
H-2
Appendix I
COMP
Computer Room
Dormitory Healthcare Parking Garage Utility (Transformer) Room Precious Storage (Sensitive Environment) Hostile Environment Duct (Open air or duct housing)
www.PDF-Zoo.com
I-1
Appendix I
device, the tester may find it extremely difficult to alarm the detector since the algorithms are designed not to be fooled by a deceptive phenomenon such as test gas. Once the Test ASD_Devices option has been enabled using the test menu, the tester should wait 3 minutes before attempting to test the ASD devices. This time may vary slightly with the number of ALDs and ASD detectors in a system. This will ensure that the ASD R-algorithm has been defeated for test purposes. The system will not reset until the Test ASD_Devices option has been disabled.
www.PDF-Zoo.com
I-2
Appendix J
Trouble Message
Carrier Lost
www.PDF-Zoo.com
J-1
Appendix J
Trouble Message
CMI-300 General Trouble
www.PDF-Zoo.com
J-2
Appendix J
Trouble Message
Ground Fault Plus
History Manually Turned Off History Manually Turned On History Manually Erased IEC Limit Reached. Service Req
Incorrect Device ID
Input Disarmed
www.PDF-Zoo.com
J-3
Appendix J
Trouble Message
Log FULL, Events Will Be Lost
www.PDF-Zoo.com
J-4
Appendix J
Trouble Message
MOI-1 Zone Disarmed
More Than 60 Supervisory More Than 60 Troubles Multiple Module Response Multiple Response Analog Poll
Node Disconnected
www.PDF-Zoo.com
J-5
Appendix J
Trouble Message
Node Not Responding
Output Disarmed
Printer Off Line/Fault Printer Out Of Paper Relay Coil Open Relay Disarmed
www.PDF-Zoo.com
J-6
Appendix J
Trouble Message
Signal Mod A/D Convert Fail Signal Module Zone Code Software Key Violation
Tamper Switch
Troubles Summarized
www.PDF-Zoo.com
J-7
Appendix J
Trouble Message
Unspecified Mod Responding
WALKTEST Activated
The MXL-IQ has been placed in the walk test mode. The hardware reset input to the MXL-IQ was used. The watch dog circuit on the SMB-2 triggered. Broken wire on CZM-4 circuit. Shorted wire on CZM-4 circuit. The CZM-4 zone at this address has lost its 24 volt input.
Warm Reset
www.PDF-Zoo.com
J-8
Appendix K
Enclosure
LLM-1 MSE-3 MSE-3L
Installation Instructions
315-093530-2 315-093831-1 315-095445-1
www.PDF-Zoo.com
K-1
Appendix K
www.PDF-Zoo.com
K-2
Appendix L
For use in Canada only with MXL-IQ software version 1.0 and higher
Fire Protection Company Name CSG-M Memory=2864 used, 243212 free Other System Flags CONFIG => TWOSTG
Sensitivity Adjustments Allowed -----------------> Block Alarm and Trouble Acknowledge Allowed -----> Multienclosure System ---------------------------> Device disarm through RESET ---------------------> Self restoring troubles -------------------------> NFPA 71 connection ------------------------------> NET 7 panel checking ---------------------------->
NO YES NO NO NO NO NO
Network Repeater Used ---------------------------> NO Independent Function Keys -----------------------> NO New Two Stage Configuration ---------------------> YES
www.PDF-Zoo.com
L-1
Appendix L
Select NO for the old system flag driven version of Two Stage Select YES for the new control function version of Two Stage NOTE: When recompiling an older implementation of Two Stage Alarm under CSG-M 6.07 or higher, make certain that the New Two Stage Configuration flag is set to NO before compiling and uploading to the MXL-IQ. Zone codes must be entered on a point by point basis. Zone codes will be output first by priority, second by queue order. In order to have the codes sound in the queue order only, all priorities must be the same.
Note that each selection contains a slash (/) which separates the Stage 1 audible signal from the Stage 2 audible signal as shown in the following example.
False
True
Example:
Stage 1 audible Stage 2 audible
True
True
When zone coding is selected for Stage 1, the system displays the Zone Coding Characteristics menu. (See Figure on the next page.) This menu allows the system designer to program the number of rounds, minimum number of rounds, etc. The final state will always be STEADY no matter what is selected in this menu.
Multiple Two Stage control functions may be used in a configuration. A single coded audible may appear on the output list of more than one Two Stage control function. Due to the potential conflict between the functions controlling the same coded output, the following rule applies to the Two Stage control function:
www.PDF-Zoo.com
L-2
Appendix L
Fire Protection Company Name CSG-M Memory=2900 used, 316874 free CONFIG => TWOSTG Options, System Message, Authorizations
System Message -----------------> Authorization Code-Level 1 -----> Authorization Code-Level 2 -----> Authorization Code-Level 3 -----> COUNTRY where installed --------> Language Selection -------------> NFPA System Designation --------> Backup Power Type --------------> Zone Coded Audible Format ------> Function Evaluation Limit ------> Photo Detector Confirmation ----> Ion Detector Confirmation ------> Sys. Justified Alarm Time ------> Intelligent Env. Compensation -->
----- CERBERUS Pyrotronics ----11111 22222 33333 Canada ENGLISH and FRENCH NFPA A System 15 Amp Hour TWO STAGE AUDIBLE - ZONE CODED/STEADY 32 0 0 60 OFF
VDT Password Time Out (hh:mm) --> 00:05 Zone Coding Characteristics Move Cursor to Highlight Selection, then ENTER ESC=Prev. Menu
Fire Protection Company Name CSG-M Memory=2900 used, 316874 free Zone Coding Characteristics CONFIG => TWOSTG
# rounds (3-15) ----------------> Tempo --------------------------> Final output status ------------> Inter-digit time (0.5-15 secs) -> Inter-round time (0.5-15 secs) -> Inter-group time (0.5-15 secs) -> Minimum # round (3-15) ---------> Zone Code Alarms After Silence ->
ESC=Prev. Menu
www.PDF-Zoo.com
L-3
Appendix L
When a coded audible appears on the output list of more than one Two Stage control function and there is a conflict (that is, some functions indicate Stage 1 and some functions indicate Stage 2), then Stage 2 has priority over Stage 1. As a result, the coded audibles in question will output Stage 2 (either 120 SPM, steady, or temporal, as selected). NOTE: When zone coding is selected as the Stage 1 audible output, Stage 2 always has priority over the Stage 1 coding. Once the coded circuit is driven into Stage 2 by logic, all zone codes will stop for that circuit no matter what the minimum rounds are.
Keyswitch Devices
There are two keyswitch types available in the MXL-IQ. All logic associated with a keyswitch device is CSG-M programmable. The only MXL-IQ defined aspects of a keyswitch are as follows: Keyswitch Type 1 1. If a Type 1 keyswitch is activated, an alarm event will result. 2. The event will be recorded on the alarm queue and all standard MXL-IQ functions associated with an alarm will occur (that is, the ANY ALARM flag will be set to TRUE, the ANY NEW ALARM flag will pulse, etc.). 3. This is true even if there are no previous alarms. Keyswitch Type 2 1. If a Type 2 keyswitch is activated when no alarms are present in the system, it will result in a trouble condition at the MXL-IQ. 2. If an alarm is detected while this trouble condition is present on the trouble queue, the active Type 2 keyswitch will be added to the system as an alarm event (added to alarm queue). 3. If the keyswitch is activated when an alarm is present in the system, the keyswitch will be treated as an alarm. All other system behavior is determined by output logic design.
*The default value of Reset Inhibit is FALSE if the system does not require a Reset Inhibit. If the Two Stage Audible Then the Normal Audible State flag is held:** Silence (Red MKB key) is: False True Inhibited Not Inhibited
**The default value of Two Stage Audible State is TRUE if the system does not require a Two Stage Audible State Inhibit.
www.PDF-Zoo.com
L-4
Appendix L
Basic Two Stage System The figure on page L-6 demonstrates a basic Two Stage system design. Its operation is summarized below: This system will output Stage 1 audibles when the first alarm occurs. If the alarm is not acknowledged prior to the expiration of stg1_timer, coded audibles will be forced output Stage 2 audibles. If the alarm is acknowledged during Stage 1, only a keyswitch will place the system in the second stage. If the system is reset after the alarm has been acknowledged and coded audibles silenced, the system may be reset (provided the RESET INHIBIT logic permits). If a keyswitch is activated after the ANY_ALARM flag is TRUE, the system will output the second stage audibles. In either stage, the audible silence flag/key controls the silencing and unsilencing of the coded audibles. The Panel Reset flag is used to assure timers and latches are reset for the next event after reset.
Trigger (ALL)
30 Sec
Run
True
Cancel
False Typical RESET INHIBIT Timer Function Panel Reset
Cancel
Any_keyswch Any alarm Keyswch List of Keyswitch Inputs OR (ANY) AND (ALL)
www.PDF-Zoo.com
L-5
Appendix L
Complex Two Stage System The figure on the next page demonstrates a more complex Two Stage system. The basic principles of operation are the same as the basic Two Stage system with a slight variation. In this example, several Two Stage control functions are used in the system design. Together with the proper glue logic, a modified Two Stage system is the result. In this system, the floors above and below the alarm signal Stage 1 coded audibles while the floor of alarm codes Stage 2 audibles. The general differences between the basic and complex systems are as follows: The first alarm will result in Stage 1 coding on that floor. An activation of a keyswitch will place the system in second stage. Therefore, the floors above and below the alarm will code Stage 1; Stage 2 will code on the floor of alarm. If an adjacent floor generates an alarm, that floor will code Stage 2. This same principle may be applied to networked MXL-IQs using external references. For example: The building in alarm codes Stage 2 while the adjacent buildings code Stage 1. Visual indications are made using MOD-16 outputs. Simply connect the signal in the logic diagram to the desired LED or other function to indicate the system stage. For example: Connect Stage 1 and Stage 2 inputs to an LED function to indicate the system state. NOTE: Since other audibles may be present in the system besides coded (Two Stage) audibles, the AUDIBLE SILENCE LED on the MKB will indicate the state of the AUDIBLE SILENCE flag as usual. Its state will only change with manual intervention (manual silence/unsilence).
Stg2 Stg1 Stg_ctl Stg1_ssi AND (ALL)
Any Alarm
www.PDF-Zoo.com
L-6
Audible Silence
True
Panel Reset
False Reset
Trigger (ALL)
Enable
Stg1_timer
Cancel
Start Timer
Run
Any Alarm All Alarms Ackd
Trigger (ANY)
Enable
Stg2_timer
Cancel
Panel Reset Reset Clear
Start Timer
Set Q
Stg1_to
AND (ALL)
Run
Stg2_ran AND (ALL)
Audible Silence
Stg2_sil
OR (ANY)
xxxx
www.PDF-Zoo.com
Stg1_ssz1
Stg1_timer Any Alarm To input list of stg1_ssz1, stg1_ssz2, stg1_ssz3 All Alarms Ackd True stg1_timer Stg1_to Floor 1 alarm pts
AND (ALL)
Audible Silence
AND (ALL) Stg2_sils Floor 1 alarm pts
Any Alarm
AND (ALL)
Panel Reset Stg2_enb Any Alarm False Panel Reset Set Reset Clear Q any_keyswch Stg2_timer stg1_timer Floor 2 alarm pts
Stg1_ssz2
stg1_flr2
AND (ALL)
Audible Silence
Stg2_sils
OR (ANY) stg2_flr2
Enable
Stg2_can Panel Reset Audible Silence OR (ANY)
Start Timer
AND (ALL)
Cancel
Stg1_ssz3
stg1_timer Floor 3 alarm pts
Stg2_sil
AND (ALL)
Audible Silence
Stg2_sils OR (ANY) Stg2_sils Floor 3 alarm pts
Appendix L
AND (ALL)
L-7
Appendix L
www.PDF-Zoo.com
L-8
Appendix M
Pre-alarm, Dual Criteria Logic Functions, and Percent Per Foot Obscuration Features
The pre-alarm feature provides an early warning of smoke conditions at a more sensitive reading than alarm level. This indication can be in the following form: a displayed and printed pre-alarm report output logic control both Dual criteria logic allows for the distinction between the chamber or thermal detector of the ILPT-1 photo thermal. The pre-alarm and dual criteria logic function (ILPT-1 only) features of the ILI or ILP series of detectors are enabled by the FPI-32 Field Programmer. Note: FPI-32 Rev. 1.3 or higher is required. ILI ion detectors and ILP photoelectric detectors are available as I/O device types for ALD-2s (or ALD-2Is). These device types tell the CSG-M and the MXL-IQ that they have the features of pre-alarm, dual criteria (photo thermal only), and ability to display readings in percent per foot (%/ft) obscuration. These detectors appear in the CSG-M with the existing ID-60I and ID-60P detectors. The MXL-IQs Custom Software Generator (CSG-M) allows the installation of the ILI or ILP detectors at any valid ALD address.
CSG-M Software
Pre-alarm
Pre-alarm must be selected to either annunciate a detectors pre-alarm or use the detector in a Criteria Selection function. Pre-alarm can be enabled at each device when it is installed as a Yes/No (Y/N) option. The CSG-M provides the following system options for pre-alarm: annunciate (Y/N) automatic adjust (Y/N) annunciation type trouble learning period (1 - 30 days) activate detector LED (Y/N)
The FPI-32 also gives these detectors new unique IDs so that they can be identified at the MXL-IQ as different from the ID-60I and ID-60P series. The ID-60I and ID60P detectors still exist in the CSG-M, but the features described in this appendix do not apply to them.
www.PDF-Zoo.com
M-1
Appendix M
IEC and pre-alarm is 8K. Each IEC device uses 2 bytes and each pre-alarm device uses 1 byte, allowing a maximum of slightly over 2500 devices with both IEC and prealarm. Manual pre-alarm settings can be set at the MXL-IQ by using the CONTROL PERCENT/FT PRE_ALARM command (See Pre-alarm and Sensitivity Settings below). Any valid pre-alarm reading within the range specified in the table on page M-3 can be used. Pre-alarm adjustments are in %/ft obscuration. Manual settings override the learning mode settings. However, they do not take effect until the end of the learning period.
www.PDF-Zoo.com
M-2
Appendix M
PHOTO Pre-alarm adjust increment Pre-alarm range Pre-alarm default .25% / ft. .25 - 2.0% / ft. 1.5% / ft. ION .12% / ft. .25 - .75% / ft. .75% / ft.
Because the pre-alarm and sensitivity settings overlap, set the pre-alarm to at least an increment below the sensitivity setting.
The FPI-32 (Rev. 1.3 or higher) must be used to enable the programming of the ILI and ILP IDs. The IDs tell the smoke detector it has the advanced features such as pre-alarm. For more information about using the FPI-32 with IL series detectors, refer to the FPI-32 Programmer/Tester Operations Manual, P/N 315-090077.
www.PDF-Zoo.com
M-3
Appendix M
www.PDF-Zoo.com
M-4
Appendix N
www.PDF-Zoo.com
N-1
Appendix N
www.PDF-Zoo.com
N-2
Appendix O
Revision 10.01, P/N 315-096220, for setting this option. NOTE: The ALD Fast Polling option can only be used with Non-Fireprint Detectors.
The system designer can connect the MID-16 or CZM-4 inputs to another system via a relay or have a remote reset input. When this input changes state to the offnormal position, the MXL-IQ resets in the same way as a RED KEY reset. Existing events do not need to be acknowledged and audibles do not need to be silenced. NOTE: This option is limited to NFPA 72A systems. In networked systems, the scope of the reset is local.
www.PDF-Zoo.com
O-1
Appendix O
the timer if the delay time is other than zero. No AC failure trouble is reported at this time. At the end of this delay time, if the AC still fails, the MXL-IQ posts the AC Failure trouble; otherwise, it goes back to the original state. When programmed into the CSG-M, this pager interface can be either supervised or unsupervised. The CCU/M interface is an application specific output device, and not a global MKB printer for a 72D system. Therefore, if it is installed on a 72D networked system, it does not satisfy the compile check for a supervised printer. To pass this compile error, add a supervised printer to a local MKB in every node in a 72D system. Despite the above limitation, in both 72A and 72D systems the CCU/M interface counts as one GMKB printer available in a networked system. Only the normal print messages for events are sent to the CCU/M interface. Information such as acknowledge, reset, time changes, etc., do not output. The output formatting is considered as a generic ASCII printer.
www.PDF-Zoo.com
O-2
Index
A
Acknowledge menu. See Menu: Acknowledge addresses, 3 - 1 fixed addresses, 3 - 1 alarm verification, E - 1 to E - 2 ALD fast polling. See new features - rev.6.0 and higher ALD-2I connections and ratings, 7 - 1 description, 1 - 10 installation, 2 - 12 module address, 3 - 2 analog loop, 1 - 1 analog voltages. See device analog voltages application specific detection, I - 1 to I - 2 ASD. See application specific detection
CRM-4 connections and ratings, 7 - 5 description, 1 - 9 installation, 2 - 14 module address, 3 - 2 CSM-4 connections and ratings NFPA 12A, NFPA 1 - 1 and NFPA 2001, 7 - 9 NFPA 72 Local, 7 - 7 NFPA 72 Municipal Tie, 7 - 8 NFPA 72 Remote Station, 7 - 8 description, 1 - 8 installation, 2 - 14 module address, 3 - 2 CZM-1B6 connections and ratings, 7 - 13 analog loops, 7 - 14 initiating devices, 7 - 13 power, 7 - 15 description, 1 - 14 CZM-4 connections and ratings, 7 - 17 description, 1 - 9 installation, 2 - 14 module address, 3 - 2
B
battery calculations, C - 1 BP-61 batteries description, 1 - 7 BTX batteries description, 1 - 7
C
Canadian two stage alarm, L - 1 to L - 7 CCU pager interface. See new features - rev.6.0 and higher CMI-300 connections and ratings, 7 - 3 description, 1 - 9 installation, 2 - 13 compatible devices, A - 1
D
delay of AC failure report. See new features - rev.6.0 and higher device analog voltages, B - 1 devices, compatible. See compatible devices DI Series of detectors description, 1 - 15 DT-11 description, 1 - 15 dual criteria logic, M - 1 to M - 3
www.PDF-Zoo.com
Index - 1
Index
E
Envirolink, F - 1 to F - 3
IEC. See Envirolink ILI Series of detectors description, 1 - 13 ILP Series of detectors description, 1 - 13 ILT description, 1 - 13
F
FP Series of detectors description, 1 - 12
H
History Log display, 6 - 6 to 6 - 10 audible silenced event, 6 - 8 audible unsilenced event, 6 - 8 auto sensitivity set event, 6 - 9 block acknowledge event, 6 - 7 configuration changed event, 6 - 9 event, 6 - 6 formats, 6 - 6 manual sensitivity set event, 6 - 9 override event, 6 - 8 password event, 6 - 8 reset event, 6 - 6 set time event, 6 - 7 download formats, 6 - 13 sequence, 6 - 14 local log query, 6 - 5 logging methods, 6 - 2 to 6 - 4 options, 6 - 1 enable, disable and erase, 6 - 4 overview, 6 - 1 print formats, 6 - 10 to 6 - 13
L
latching/non-latching troubles, G - 1 LIM-1 description, 1 - 14
M
Menu. See MKB-4: operation Acknowledge, 3 - 18 Alarm, 3 - 18 to 3 - 19 Security, 3 - 21 to 3 - 22 Supervisory, 3 - 19 to 3 - 20 Trouble, 3 - 20 to 3 - 21 Control, 3 - 36 to 3 - 42 Analaser, 3 - 40 Arm/dis, 3 - 38 Change Apps, 3 - 42 Loop Arm, 3 - 39 Loop Disarm, 3 - 39 to 3 - 40 Net Link Request, 3 - 40 Output on/off, 3 - 38 to 3 - 39 Percent/ft, 3 - 41 to 3 - 42 Reset, 3 - 37 Sensitivity, 3 - 37 List, 3 - 22 to 3 - 36 Alarm, 3 - 23 to 3 - 24 Analaser, 3 - 32 to 3 - 34 ASD_apps, 3 - 35 to 3 - 36 Device Type, 3 - 29 Device Usages, 3 - 31 to 3 - 32
I
ICP / ICP-B6 description, 1 - 12 ID Series of detectors description, 1 - 12 to 1 - 13
www.PDF-Zoo.com
Index - 2
Index
Message, 3 - 29 to 3 - 30 Module, 3 - 28 to 3 - 29 Node Address, 3 - 32 Output States, 3 - 31 Percent/ft, 3 - 34 to 3 - 35 Security, 3 - 25 to 3 - 26 Sensitivity, 3 - 26 Software Version, 3 - 30 to 3 - 31 Status, 3 - 23 Supervisory, 3 - 24 Temp, 3 - 28 Trouble, 3 - 24 to 3 - 25 Voltages, 3 - 26 to 3 - 28 Test, 3 - 42 to 3 - 49 ASD_Devices, 3 - 48 Det_cleaned, 3 - 47 Device LED, 3 - 45 Event Log, 3 - 47 Ground Fault, 3 - 44 Lamp Test, 3 - 45 Manual Activate, 3 - 49 MOI Lamp Test, 3 - 46 Override, 3 - 46 to 3 - 47 Power, 3 - 44 to 3 - 45 Pre-alarm, 3 - 47 to 3 - 48 Pyro-diags, 3 - 47 Set Time, 3 - 43 to 3 - 44 Summarize, 3 - 48 to 3 - 49 Test Network (X-Net, M-Net), 3 - 46 Menu overview, 3 - 15 MID-16 connections and ratings, 7 - 21 description, 1 - 11 installation, 2 - 9 MKB-4 description, 1 - 5 global operation, 3 - 12 to 3 - 14 display format, 3 - 12 keypad, 3 - 13 to 3 - 14 limitations and restrictions, 3 - 12 installation, 2 - 4 local operation, 3 - 3 alarm, 3 - 6 to 3 - 8 command keypad, 3 - 5 display, 3 - 3 display keys, 3 - 5 internal audible, 3 - 4 LEDs, 3 - 5 modes of operation, 3 - 5 numeric keypad, 3 - 4 security, 3 - 10 to 3 - 11 special (alt + function) keypad, 3 - 5 supervisories, 3 - 8 to 3 - 9 troubles, 3 - 9 to 3 - 10 using the menu, 3-14 walktest. See Walktest: operating instructions module address, 3 - 2 MOD-16 connections and ratings, 7 - 21 description, 1 - 10 installation, 2 - 9 operation, 3 - 3 Module Addresses. See Addresses MOI-7 connections and ratings, 7 - 19 description, 1 - 10 installation, 2 - 9 module address, 3 - 2 operation, 3 - 3 MOM-2 connections and ratings, 7 - 25 description, 1 - 8 installation, 2 - 6 to 2 - 9
www.PDF-Zoo.com
Index - 3
Index
MOM-4 connections and ratings, 7 - 27 description, 1 - 8 installation, 2 - 6 to 2 - 9 MPS-6/-6W, MPS-12/-12W description, 1 - 5 installation, 2 - 3 to 2 - 4 MSE-3L installation, 2 - 2 MSI Series of manual stations description, 1 - 14 MXL Power Supply Load Calculations, D - 1 MXL-IQ basic components, 1 - 4 battery calculations, C - 1 description, 1 - 1 minimum configuration, 1 - 3 new features - rev.6.0 and higher, O - 1 power supply load calculations, D - 1 software, 1 - 1
P
PAL-1 description, 1 - 6 installation, 2 - 6 PBA-1191 description, 1 - 15 PE Series of detectors description, 1 - 15 percent per foot obscuration, M - 1 to M - 3 PIM-1 description, 1 - 6 installation, 2 - 5 PIM-2/PAL-1 installation, 2 - 6 power limited wiring, K - 1 power supply load calculations, D - 1 pre-alarm, M - 1 to M - 3
R
reset causing zone for MID-16 or CZM-4. See new features - rev.6.0 and higher: reset causing zone reset procedures hard reset, 3 - 11 soft reset, 3 - 11 to 3 - 12
N
new features - rev.6.0 and higher, O - 1 to O - 2 24 hour trouble resound /reminder timer, O - 1 ALD fast polling, O - 1 CCU pager interface, O - 2 delay of AC failure report, O - 1 to O - 2 reset causing zone, O - 1 trouble delay time for damper control using TRI, O - 1 NIM-1R connections and ratings, 7 - 29 to 7 - 32 AnaLaser interface, 7 - 32 foreign system interface (FSI), 7 - 31 network, 7 - 29 network command center (NCC), 7 - 30 description, 1 - 11 installation, 2 - 14
S
security point, installing, H - 1 self restoring troubles. See latching/non-latching troubles Silent Knight Model 5128/5129 connections and ratings, 7 - 33 SMB-2 connections and ratings, 7 - 35 field wiring, 7 - 36 to 7 - 38 internal wiring, 7 - 35 description, 1 - 4 installation, 2 - 3 module address 3 - 2
www.PDF-Zoo.com
Index - 4
Index
spare parts list, N - 1 start up procedure, 2 - 10 to 2 - 16 system operation, global, 3 - 12 to 3 - 14 system test, 4 - 1
T
testing procedures, 4 - 1 TRI Series of interface modules description, 1 - 14 trouble delay time for damper control using TRI. See new features - rev.6.0 and higher trouble messages, J - 1 to J - 8 trouble resound / reminder timer. See new features rev.6.0 and higher Troubleshooting Guide, 4 - 2 TSW-2 description, 1 - 6 installation, 2 - 2 two stage alarm, Canadian, L - 1 to L - 7
W
Walktest, 5 - 1 to 5 - 6 operating instructions, 5 - 4 overview, 5 - 1 suggested procedure, 5 - 2 to 5 - 3
www.PDF-Zoo.com
Index - 5
Index
www.PDF-Zoo.com
Index - 6
WARNING:
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference.
www.PDF-Zoo.com
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932 P/N 315-093624CD-9
www.PDF-Zoo.com
Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
NOTES: 1. For Installation Instructions for the MXL-IQ modules refer to the Table below. 2. Waterflow Alarm must be AccuLINK (CSG-M) configured to at least one non-silenceable NAC. 3. Refer to the MXL-IQ OPERATION, INSTALLATION, AND MAINTENANCE MANUAL (P/N 315-093624) for minimum NFPA configurations and additional information. 4. Use the following batteries: BTX-1, BTX-2, or BP-61. 5. The CSM-4 module is capable of the following functions: Leased Line Circuit Supervised Local Energy Auxiliary Trip (Municipal Tie) Supervised Notification Appliance Circuit Releasing Service 6. CRM-4 relay coils are supervised when not energized; contacts are not. 7. For alternate configurations using CZM-1/1B6s, consult Technical Support. 8. Optional transient suppressors Model CP2341 and CP2297 may be used in addition to the transient protection incorporated in the panel and not in lieu of that protection. Use them for extreme lightning conditions. For CP2297 refer to instructions P/N 315-092355. For CP2341 refer to instructions P/N 315- 092390. 9. For the Silent Knight 5128/5129 Central Station, Remote Station connection (NFPA 72), refer to instructions P/N 315-093294. 10. The modules indicated with an asterisk in the Table below are rated power limited on all terminals. Refer to the MXL-IQ Power Limited Wiring Instructions, P/N 315-095445, for separation of power limited wiring. 11. When the CSM-4 is configured for Municipal Tie or Releasing Service, terminals 1 and 4 and/or terminals 9 and 12 are non-power limited. In all other applications, the CSM-4 is power limited on all terminals. 12. For a list of Compatible Notification Appliances, refer to P/N 315-096363.
5 ) ( 1 / 2 . 1 0 ) 40 / . - 3 ' ;:) ) 20/. -3' 02( 7(2 9,-(8 7(2 ) ,,78 ,2 7(2 1. 21*. /6
> * 7 (2 =. ', 2 < >&A#@ :-0),3 $,,7 >&A#@ C:B $,,7 >&A#@ BI&#GHGAF E,D(2 :$J#@" BI&#K BI&#GHGAF B>&#K C:B $,,7 B>&#K &*-.1.70) L.( B>&#K $(0'(+ $.-( B>&#K 4()(0'.-3 >(2=.1(
*See Note 7
CONNECTION DIAGRAM
$ . - ( " ? 7 (+ 0- 1( /(( OLAE A@? NHML "% 2FKHFE JFIHGFED 8( OLAE A@? NHML "&<;. 2FKHFE JFIHGFED ) OLAE A@? 0 OLAE A@?! V/( +3*$/</54E A@?U /(( OLAE A@? NHML "% 2FKHFE JFIHGFED 8( OLAE A@? NHML "&<;. 2FKHFE JFIHGFED ,( OLAE A@? )8 OLAE A@? ) OLAE A@? ##T8 OLAE A@? VHRGPSJHRX PO@JU #T86 OLAE VHRGPSJFE PHRF @RJ PO@JU ) OLAE A@?
#0C SRQHPMFKFJ ;=1B /' A@? )( C%+B 4(A' A@? #($#0T8 C%+ 0A' A@? /9$#0T8 C%+ 0A' A@? #0C SRQHPMFKFJ ;=1B /#A' A@? #0C SRQHPMFKFJ ;=1B )$-A' A@? #0 C%+ /#A' A@? ;=1 Y ;SPP =@IF 1FGMHQHFJ
#0C SRQHPMFKFJ ;=1B /' A@? )( C%+B 4(A' A@? #0T8 C%+ A@? /9(A' A@? #0T8 C%+ A@? 08A' A@? #0C SRQHPMFKFJ ;=1B ##($)#(A' VAOAFRM@KWU #0C SRQHPMFKFJ ;=1B )$-A' A@? #0 C%+ 9((A' A@?
#0C SRQHPMFKFJ ;=1B /#A' A@? #0C SRQHPMFKFJ ;=1B /T8A' A@?
For Proprietary Burglary Application (1076) use a TSW-2 tamper switch to monitor the main enclosure. Monitor each TRI-60/60R/60D or TRI-B6/B6R/B6D related to this application (1076) for 24 hours by a listed motion detector to prevent tampering.
FP-11*(d) FPT-11*
ID-60I/IH/IA/IAH ID-60IB/IBH
&%$#"! &,+*)(' '&%$#"! +*"$)((! +.##-, +.#)0/ +1*$0 +2*$0 +3*$/! +3*$/54! +3*$0! "+.! "+.$54! &"*$/! *"%$/4 *65$0 *7%$/4
"-'/0))0/.,"-'/2*1/.,-' )/8$(-/040$8 )/8$(-/#8-$8 )/8$(-#)88$# )/8$(-#-)($# )/8$(-(98)+ )/8$(-(980$)/8$(-(,#8$9 )/8$(-8)88$# )/8$(-(,#4$, )/8$(-#0,0$4 )/8$(-8)(4$# )/8$(-#/)8$8 )/8$(-/94($# )/8$(-)8,8$) )/8$(-(9)($0
&%$#"! &,+*)(' *7"$,! *7*$# *7*$0 *.2$4 *.2$/# :"*$/1 .'&$/ ."*$/! ."*$# .2$8' .2$8:,! 1++$/</; 2*5$# >2=$#
"-'/0))0/.,"-'/2*1/.,-' )/8$(-#,--$# )/8$(-#,,,$8 )/8$(-(98#$, )/8$(-())0$) )/8$(-#()($) )/8$(-#-8)$0 )/8$(-#0(9$8 )/8$(-/04#$/( )/8$(-#0(9$8 )/8$(-#)4,$0 )/8$(-#,#-$4 )/8$(-8)40$# )/8$(-8-)/$# )/8$(-#0))$#
ILI-1/1H/1A/1AH ILP-1 ILP-1 (d) ILPT-1 ILP-2** ILP-2**(d) ILT-1 MSI-10/-20 MSI-10B/-20B MSI-B6F MSI-MB6 TRI-B6/B6D/B6R TRI-B6M TRI-S/D/R
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932 Siemens Building Technologies, Ltd. 50 East Pearce Street Richmond Hill, Ontario L4B 1B7 CN
PE-11/11T*
PE-11/11T
See Note 11
*The FP-11 is only com pat ible w it h M XL-I Q R ev. 6. 0 or great er f irm w are. **The I LP-2 i s onl y com pat i bl e wi t h M XL-I Q Rev. 3. 0 or great er f i rm ware. When t he CSG-M i s conf i gured, t he DUCT appl i cat i on m ust be sel ect ed when t he devi ce i s used i n an ai r duct housi ng or i n a spot duct appl i cat i on.
*M ay use up t o 30 det ect ors of any t ype. **Onl y one PBA-1191, and no addi t i onal devi ces, can be connect ed t o a CZM -4 i ni t i at i ng zone.
M a y u s e u p t o 1 5 d e t e c t o rs o f a n y t y p e . *D o n o t u s e A D - 1 1 P R o r d e t e c t o r - o p e r a t e d a c c e s s o r i e s w i t h t h e
C Z M -1 / -1 B 6 .