Holiday Test Procedure
Holiday Test Procedure
---------------------------------------------------------------------------------------------------P.O. BOX NO. 6811, DAMMAM 31452. Tel.(03) 8431838, Fax. (03) 8427580 Email: [email protected]
11050D-P355P002-Q73-031-A
Page 1 of 6
Contents
1. 2. 3. 4. 5. 6. 7. 8. 9. 10. SCOPE REFERENCE DOCUMENTS DEFINITIONS RESPONSIBILITY INSPECTION BEFORE LINING APPLICATION INSPECTION DURING LINING APPLICATION INSPECTION AFTER LINING APPLICATION QA/QC FORMS SAFETY ATTACHMENTS
---------------------------------------------------------------------------------------------------P.O. BOX NO. 6811, DAMMAM 31452. Tel.(03) 8431838, Fax. (03) 8427580 Email: [email protected]
11050D-P355P002-Q73-031-A
Page 2 of 6
1.
SCOPE :
This procedure governs the use of Low Voltage Wet Sponge Holiday Detector for finding disconuities such as nicks, scrapes and pinholes in the coating film inside the tanks at Wasit Gas Program. This shall be used on coating upto 20 mils (500 microns) in thickness. This procedure shall comply the requirements of Saudi Aramco Project Specifications, SSPC and Data Sheets.
2.
REFERENCE DOCUMENTS:
32SAMSS005, Manufacture of Atmospheric Tanks. API-650, Welded Steel Tanks for Oil Storage. SAESH100, Coating Materials & Application Requirements for Industrial Facilities. SAES-H-001, Coating Selection &Application Requirements for Industrial Plants &
Equipment.
Data Sheet.
3.
DEFINITIONS:
Owner Contractor Sub-Contractor : : : Saudi Aramco SK Engineering & Construction Al-Khodari Heavy Industries
4.
RESPONSIBILITY:
Holiday testing shall be done by qualified QC personnel. Repair work shall be done by qualified group in accordance with the approved painting procedure and shall be re tested.
---------------------------------------------------------------------------------------------------P.O. BOX NO. 6811, DAMMAM 31452. Tel.(03) 8431838, Fax. (03) 8427580 Email: [email protected]
11050D-P355P002-Q73-031-A
Page 3 of 6
5.
5.1 5.2 5.3 5.4 5.5 5.6
6.
6.1
Product dilution shall be checked. Meteorological and environment conditions shall be checked. Wet lining thickness shall be checked. All the testing gauges shall have valid calibration date.
7.
7.1 7.2 7.3
---------------------------------------------------------------------------------------------------P.O. BOX NO. 6811, DAMMAM 31452. Tel.(03) 8431838, Fax. (03) 8427580 Email: [email protected]
11050D-P355P002-Q73-031-A
Page 4 of 6
7.4 7.5
The full coat of the repair coating shall be holiday tested when cured. Adhesion test as per ASTM D-3359 shall be carried out.
8.
8.1
QA/QC FORMS:
All holiday testing results shall be recorded in the applicable forms.
9.
9.1
SAFETY:
Requirements of safety are in accordance to KHI Safety plan and Saudi Aramco Safety manual and will be conducted by the Contractor Safety Officer.
10.
ATTACHMENTS:
Holiday Detector Test Report FM-09-03/6 (See Page 6 of 6).