Short Circuit Calculation
Short Circuit Calculation
Contents
1 Introduction o 1.1 Why do the calculation? o 1.2 When to do the calculation? 2 Calculation Methodology o 2.1 Step 1: Construct the System Model and Collect Equipment Parameters o 2.2 Step 2: Calculate Equipment Short Circuit Impedances 2.2.1 Network Feeders 2.2.2 Synchronous Generators and Motors 2.2.3 Transformers 2.2.4 Cables 2.2.5 Asynchronous Motors 2.2.6 Fault Limiting Reactors 2.2.7 Other Equipment o 2.3 Step 3: Referring Impedances o 2.4 Step 4: Determine Thvenin Equivalent Circuit at the Fault Location o 2.5 Step 5: Calculate Balanced Three-Phase Short Circuit Currents 2.5.1 Initial Short Circuit Current 2.5.2 Peak Short Circuit Current 2.5.3 Symmetrical Breaking Current 2.5.4 DC Short Circuit Component o 2.6 Step 6: Calculate Single-Phase to Earth Short Circuit Currents 3 Worked Example o 3.1 Step 1: Construct the System Model and Collect Equipment Parameters o 3.2 Step 2: Calculate Equipment Short Circuit Impedances o 3.3 Step 3: Referring Impedances o 3.4 Step 4: Determine Thvenin Equivalent Circuit at the Fault Location o 3.5 Step 5: Calculate Balanced Three-Phase Short Circuit Currents 3.5.1 Initial Short Circuit Current 3.5.2 Peak Short Circuit Current 4 Computer Software 5 What Next?
Introduction
This article looks at the calculation of short circuit currents for bolted three-phase and single-phase to earth faults in a power system. A short circuit in a power system can cause very high currents to flow to the fault location. The magnitude of the short circuit current depends on the impedance of system under short circuit conditions. In this calculation, the short circuit current is estimated using the guidelines presented in IEC 60909.
To specify fault ratings for electrical equipment (e.g. short circuit withstand ratings)
To help identify potential problems and weaknesses in the system and assist in system planning
Calculation Methodology
This calculation is based on IEC 60909-0 (2001, c2002), "Short-circuit currents in three-phase a.c. systems - Part 0: Calculation of currents" and uses the impedance method (as opposed to the per-unit method). In this method, it is assumed that all short circuits are of negligible impedance (i.e. no arc impedance is allowed for). There are six general steps in the calculation: Step 1: Construct the system model and collect the relevant equipment parameters Step 2: Calculate the short circuit impedances for all of the relevant equipment Step 3: Refer all impedances to the reference voltage Step 4: Determine the Thvenin equivalent circuit at the fault location Step 5: Calculate balanced three-phase short circuit currents Step 6: Calculate single-phase to earth short circuit currents
diagram should show all of the major system buses, generation or network connection, transformers, fault limiters (e.g. reactors), large cable interconnections and large rotating loads (e.g. synchronous and asynchronous motors). The relevant equipment parameters to be collected are as follows: Network feeders: fault capacity of the network (VA), X/R ratio of the network Synchronous generators and motors: per-unit sub-transient reactance, rated generator capacity (VA), rated power factor (pu) Transformers: transformer impedance voltage (%), rated transformer capacity (VA), rated current (A), total copper loss (W) Cables: length of cable (m), resistance and reactance of cable ( Asynchronous motors: full load current (A), locked rotor current (A), rated power (W), full load power factor (pu), starting power factor (pu) Fault limiting reactors: reactor impedance voltage (%), rated current (A) )
Network Feeders
Given the approximate fault level of the network feeder at the connection point (or point of common coupling), the impedance, resistance and reactance of the network feeder is calculated as follows:
Where
is reactance of the network feeder () is the nominal voltage at the connection point (Vac) is the fault level of the network feeder (VA) is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV) is X/R ratio of the network feeder (pu)
Where
is the resistance of the generator () is a voltage correction factor - see IEC 60909-0 Clause 3.6.1 for more details (pu) is the per-unit sub-transient reactance of the generator (pu) is the nominal generator voltage (Vac) is the nominal system voltage (Vac) is the rated generator capacity (VA) is the X/R ratio, typically 20 for for voltage 100MVA, 14.29
is a voltage factor which accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV) is the power factor of the generator (pu) For the negative sequence impedance, the quadrature axis sub-transient reactance can be applied in the above equation in place of the direct .
The zero-sequence impedances need to be derived from manufacturer data, though the voltage correction factor also applies for solid neutral
Transformers
The positive sequence impedance, resistance and reactance of two-winding distribution transformers can be calculated as follows:
Where
is the resistance of the transformer () is the reactance of the transformer () is the impedance voltage of the transformer (pu) is the rated capacity of the transformer (VA) is the nominal voltage of the transformer at the high or low voltage side (Vac) is the rated current of the transformer at the high or low voltage side (I) is the total copper loss in the transformer windings (W) For the calculation of impedances for three-winding transformers, refer to IEC 60909-0 Clause 3.3.2. For network transformers (those that connect two separate networks at different voltages), an impedance correction factor must be applied (see IEC 60909-0 Clause 3.3.3). The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data, but also depends on the winding connections and fault path available for zero-sequence current flow (e.g. different neutral earthing systems will affect zero-sequence impedance).
Cables
Cable impedances are usually quoted by manufacturers in terms of Ohms per km. These need to be converted to Ohms based on the length of the cables:
Where
is the reactance of the cable {) is the quoted resistance of the cable { / km) is the quoted reactance of the cable { / km) is the length of the cable {m) The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data. In the absence of manufacturer data, zero sequence impedances can be derived from positive sequence impedances via a multiplication factor (as suggested by SKM Systems Analysis Inc) for magnetic cables:
Asynchronous Motors
An asynchronous motor's impedance, resistance and reactance is calculated as follows:
Where
is resistance of the motor () is reactance of the motor () is ratio of the locked rotor to full load current is the motor locked rotor current (A) is the motor nominal voltage (Vac) is the motor rated power (W) is the motor full load power factor (pu) is the motor starting power factor (pu)
The negative sequence impedance is equal to positive sequence impedance calculated above. The zero sequence impedance needs to be derived from manufacturer data.
Where
is reactance of the reactor() is the impedance voltage of the reactor (pu) is the nominal voltage of the reactor (Vac) is the rated current of the reactor (A) Positive, negative and zero sequence impedances are all equal (assuming geometric symmetry).
Other Equipment
Static converters feeding rotating loads may need to be considered, and should be treated similarly to asynchronous motors. Line capacitances, parallel admittances and non-rotating loads are generally neglected as per IEC 60909-0 Clause 3.10. Effects from series capacitors can also be neglected if voltage-limiting devices are connected in parallel.
Where
is the transformer nominal primary voltage (Vac) is the specified tap setting (%) Using the winding ratio, impedances (as well as resistances and reactances) can be referred to the primary (HV) side of the transformer by the following relation:
Where
is the impedance at the secondary (LV) side () is the transformer winding ratio (pu) Conversely, by re-arranging the equation above, impedances can be referred to the LV side:
The system model must first be simplified into an equivalent circuit as seen from the fault location, showing a voltage source and a set of complex impedances representing the power system equipment and load impedances (connected in series or parallel). The next step is to simplify the circuit into a Thvenin equivalent circuit, which is a circuit containing only a voltage source ( short circuit impedance ( ). ) and an equivalent
This can be done using the standard formulae for series and parallel impedances, keeping in mind that the rules ofcomplex arithmetic must be used throughout. If unbalanced short circuits (e.g. single phase to earth fault) will be analysed, then a separate Thvenin equivalent circuit should be constructed for each of the positive, negative and zero sequence networks (i.e. finding ( , and ).
Where
is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV) is the nominal system voltage at the fault location (V) is the equivalent positive sequence short circuit impedance ()
Where
Where
is the initial symmetrical short circuit current (A) For close to generator faults, the symmetrical breaking current will be higher. More detailed calculations can be made for increased accuracy in IEC 60909, but this is left to the reader to explore.
Where
is the initial symmetrical short circuit current (A) is the nominal system frequency (Hz) is the time (s) is the X/R ratio - see more below The X/R ratio is calculated as follows:
Where
and
is a factor to account for the equivalent frequency of the fault. Per IEC 60909-0 Section 4.4, the following factors should be used based on the product of frequency and time ( ):
Where
is the voltage factor that accounts for the maximum system voltage (1.05 for voltages <1kV, 1.1 for voltages >1kV) is the nominal voltage at the fault location (Vac) is the equivalent positive sequence short circuit impedance () is the equivalent negative sequence short circuit impedance () is the equivalent zero sequence short circuit impedance ()
Worked Example
In this example, short circuit currents will be calculated for a balanced threephase fault at the main 11kV bus of a simple radial system. Note that the single phase to earth fault currents will not be calculated in this example.
= 500 kW = 11,000 V = 200.7 A = 6.5 pu = 0.85 pu = 0.30 pu Length = 150m Size = 3C+E 35 mm2
(R = 0.668 \km, X = 0.115 \km) Transformer TX1 Transformer Cable C3 = 2,500 kVA = 11,000 V = 415 V = 0.0625 pu = 19,000 W = 0% Length = 100m Size = 3C+E 95 mm2
(R = 0.247 \km, X = 0.0993 \km) Motor M2 Motor M3 = 90 kW = 415 V = 1,217.3 A = 7 pu = 0.8 pu = 0.30 pu = 150 kW = 415 V = 1,595.8 A = 6.5 pu = 0.85 pu = 0.30 pu
The 415V motor impedances referred to the 11kV side is therefore: Equipment 415V Motor M2 415V Motor M3 Resistance () 46.0952 31.6462 Reactance () 146.5735 100.6284
kA
kA
Computer Software
Short circuit calculations are a standard component of power systems analysis software (e.g. ETAP, PTW, DIgSILENT, etc) and the calculations are far easier to perform with software than by hand. However manual calculations could be done as a form of verification to confirm that the software results are reasonable.
What Next?
The results from the short circuit calculations can be used to specify the fault ratings on electrical equipment (e.g. switchgear, protective devices, etc) and also for protection coordination studies.
Earthing Calculation
Contents
1 Introduction o 1.1 Why do the calculation? o 1.2 When to do the calculation? o 1.3 When is the calculation unnecessary? 2 Calculation Methodology o 2.1 Prerequisites o 2.2 Earthing Grid Conductor Sizing o 2.3 Touch and Step Potential Calculations 2.3.1 Step 1: Soil Resistivity 2.3.2 Step 2: Surface Layer Materials 2.3.3 Step 3: Earthing Grid Resistance 2.3.3.1 Simplified Method 2.3.3.2 Schwarz Equations 2.3.4 Step 4: Maximum Grid Current 2.3.4.1 Current Division Factor 2.3.4.2 Decrement Factor 2.3.5 Step 5: Touch and Step Potential Criteria 2.3.6 Step 6: Ground Potential Rise (GPR) 2.3.7 Step 7: Earthing Grid Design Verification 2.3.7.1 Mesh Voltage Calculation 2.3.7.1.1 Geometric Spacing Factor Km 2.3.7.1.2 Geometric Factor n 2.3.7.1.3 Irregularity Factor Ki 2.3.7.1.4 Effective Buried Length LM 2.3.7.2 Step Voltage Calculation 2.3.7.2.1 Geometric Spacing Factor Ks 2.3.7.2.2 Effective Buried Length LS 2.3.7.3 What Now? 3 Worked Example o 3.1 Step 1: Soil Resistivity o 3.2 Step 2: Surface Layer Materials o 3.3 Step 3: Earthing Grid Resistance o 3.4 Step 4: Maximum Grid Current o 3.5 Step 5: Touch and Step Potential Criteria o 3.6 Step 6: Ground Potential Rise (GPR) o 3.7 Step 7: Earthing Grid Design Verification 3.7.1 Mesh Voltage Calculation 3.7.2 Step Voltage Calculation 4 Computer Based Tools 5 What next?
Introduction
The earthing system in a plant / facility is very important for a few reasons, all of which are related to either the protection of people and equipment and/or the optimal operation of the electrical system. These include: Equipotential bonding of conductive objects (e.g. metallic equipment,
buildings, piping etc) to the earthing system prevent the presence of dangerous voltages between objects (and earth). The earthing system provides a low resistance return path for earth faults
within the plant, which protects both personnel and equipment For earth faults with return paths to offsite generation sources, a low
resistance earthing grid relative to remote earth prevents dangerous ground potential rises (touch and step potentials) The earthing system provides a low resistance path (relative to remote
earth) for voltage transients such as lightning and surges / overvoltages Equipotential bonding helps prevent electrostatic buildup and discharge,
which can cause sparks with enough energy to ignite flammable atmospheres The earthing system provides a reference potential for electronic circuits and
helps reduce electrical noise for electronic, instrumentation and communication systems This calculation is based primarily on the guidelines provided by IEEE Std 80 (2000), "Guide for safety in AC substation grounding". Lightning protection is excluded from the scope of this calculation (refer to the specific lightning protection calculation for more details).
main earth grid Ensure that the earthing design is appropriate to prevent dangerous step
Calculation Methodology
This calculation is based on IEEE Std 80 (2000), "Guide for safety in AC substation grounding". There are two main parts to this calculation: Earthing grid conductor sizing Touch and step potential calculations
IEEE Std 80 is quite descriptive, detailed and easy to follow, so only an overview will be presented here and IEEE Std 80 should be consulted for further details (although references will be given herein).
Prerequisites
The following information is required / desirable before starting the calculation: A layout of the site Maximum earth fault current into the earthing grid Maximum fault clearing time Ambient (or soil) temperature at the site Soil resistivity measurements at the site (for touch and step only) Resistivity of any surface layers intended to be laid (for touch and step only)
The minimum conductor size capable of withstanding the adiabatic temperature rise associated with an earth fault is given by re-arranging IEEE Std 80 Equation 37:
Where
is the energy of the maximum earth fault (A s) is the maximum allowable (fusing) temperature (C) is the ambient temperature (C) is the thermal coefficient of resistivity (C )
-1
The material constants Tm, r, r and TCAP for common conductor materials can be found in IEEE Std 80 Table 1. For example. commercial hard-drawn copper has material constants: Tm = 1084 C r = 0.00381 C r = 1.78 .cm TCAP = 3.42 Jcm C .
-3 -1 -1
As described in IEEE Std 80 Section 11.3.1.1, there are alternative methods to formulate this equation, all of which can also be derived from first principles). There are also additional factors that should be considered (e.g. taking into account future growth in fault levels), as discussed in IEEE Std 80 Section 11.3.3.
are performed in order to assess whether the earthing grid can dissipate the fault currents so that dangerous touch and step voltages cannot exist.
Where
is the soil resistivity (.m) is the resistivity of the surface layer material (.m)
is the thickness of the surface layer (m) This derating factor will be used later in Step 5 when calculating the maximum allowable touch and step voltages.
Simplified Method
IEEE Std 80 Equation 52 gives the simplified method as modified by Sverak to include the effect of earthing grid depth:
Where
is the soil resistivitiy (.m) is the total length of buried conductors (m) is the total area occupied by the earthiing grid (m )
2
Schwarz Equations
The Schwarz equations are a series of equations that are more accurate in modelling the effect of earthing rods / electrodes. The equations are found in IEEE Std 80 Equations 53, 54, 55 and 56, as follows:
Where
is the earth resistance of the grid conductors () is the earth resistance of the earthing electrodes () is the mutual earth resistance between the grid conductors and earthing electrodes () And the grid, earthing electrode and mutual earth resistances are:
Where
is the total length of buried grid conductors (m) is radius for conductors buried at depth metres, or simply metres and with cross-sectional
2
is the total area covered by the grid conductors (m ) is the length of each earthing electrode (m) is number of earthing electrodes in area is the cross-sectional radius of an earthing electrode (m) and are constant coefficients depending on the geometry of the grid can be approximated by the following: : : :
The coefficient
The coefficient
can be approximated by the following: : : : is the length-to-width ratio of the earthing grid.
found from the power systems studies or from manual calculation. Generally speaking, the highest relevant earth fault level will be on the primary side of the largest distribution transformer (i.e. either the terminals or the delta windings).
Decrement Factor
The symmetrical grid current is not the maximum grid current because of asymmetry in short circuits, namely a dc current offset. This is captured by the decrement factor, which can be calculated from IEEE Std 80 Equation 79:
Where
is the duration of the fault (s) is the dc time offset constant (see below) The dc time offset constant is derived from IEEE Std 80 Equation 74:
Where
is the system frequency (Hz) The maximum grid current is lastly calculated by:
One of the goals of a safe earthing grid is to protect people against lethal electric shocks in the event of an earth fault. The magnitude of ac electric current (at 50Hz or 60Hz) that a human body can withstand is typically in the range of 60 to 100mA, when ventricular fibrillation and heart stoppage can occur. The duration of an electric shock also contributes to the risk of mortality, so the speed at which faults are cleared is also vital. Given this, we need to prescribe maximum tolerable limits for touch and step voltages that do not lead to lethal shocks. The maximum tolerable voltages for step and touch scenarios can be calculated empirically from IEEE Std Section 8.3 for body weights of 50kg and 70kg: Touch voltage limit - the maximum potential difference between the surface potential and the potential of an earthed conducting structure during a fault (due to ground potential rise):
50kg person:
70kg person:
Step voltage limit - is the maximum difference in surface potential experience by a person bridging a distance of 1m with the feet without contact to any earthed object:
50kg person:
Where
70kg person: is the touch voltage limit (V) is the step voltage limit (V) is the surface layer derating factor (as calculated in Step 2) is the soil resistivity (.m) is the maximum fault clearing time (s)
The choice of body weight (50kg or 70kg) depends on the expected weight of the personnel at the site. Typically, where women are expected to be on site, the conservative option is to choose 50kg.
a maximum potential potential difference and that earth potentials around the site will vary relative to the point of fault. The maximum GPR is calculated by:
Where
is the maximum grid current found earlier in Step 4 (A) is the earthing grid resistance found earlier in Step 3 ()
Where ::
is the maximum grid current found earlier in Step 4 (A) is the geometric spacing factor (see below) is the irregularity factor (see below) is the effective buried length of the grid (see below)
Where
is the depth of buried grid conductors (m) is the cross-sectional diameter of a grid conductor (m) is a weighting factor for depth of burial = is a weighting factor for earth electrodes /rods on the corner mesh for grids with earth electrodes along the grid perimeter or corners
perimeter
Geometric Factor n
The geometric factor is calculated from IEEE Std 80 Equation 85:
With
for square and rectangular grids, or otherwise for square, rectangular and L-shaped grids, or
is the length of grid conductors on the perimeter (m) is the total area of the grid (m )
2
and
are the maximum length of the grids in the x and y directions (m)
is the maximum distance between any two points on the grid (m)
Irregularity Factor Ki
The irregularity factor is calculated from IEEE Std 80 Equation 89:
Where
For grids with few or no earthing electrodes (and none on corners or along the perimeter):
Where
is the total length of earthing electrodes / rods (m) For grids with earthing electrodes on the corners and along the perimeter:
Where
is the total length of earthing electrodes / rods (m) is the length of each earthing electrode / rod (m) and are the maximum length of the grids in the x and y directions (m)
Where ::
is the maximum grid current found earlier in Step 4 (A) is the geometric spacing factor (see below) is the irregularity factor (as derived above in the mesh voltage calculation) is the effective buried length of the grid (see below)
Where
is the depth of buried grid conductors (m) is a geometric factor (as derived above in the mesh voltage calculation)
Where
What Now?
Now that the mesh and step voltages are calculated, compare them to the maximum tolerable touch and step voltages respectively. If: then the earthing grid design is safe. , and
If not, however, then further work needs to be done. Some of the things that can be done to make the earthing grid design safe: Redesign the earthing grid to lower the grid resistance (e.g. more grid conductors, more earthing electrodes, increasing cross-sectional area of conductors, etc). Once this is done, re-compute the earthing grid resistance (see Step 3) and re-do the touch and step potential calculations. Limit the total earth fault current or create alternative earth fault return paths Consider soil treatments to lower the resistivity of the soil Greater use of high resistivity surface layer materials
Worked Example
In this example, the touch and step potential calculations for an earthing grid design will be performed. The proposed site is a small industrial facility with a network connection via a transmission line and a delta-wye connected transformer.
A rectangular earthing grid (see the figure right) with the following parameters is proposed: Length of 90m and a width of 50m 6 parallel rows and 7 parallel columns Grid conductors will be 120 mm and buried at a depth of 600mm
2
22 earthing rods will be installed on the corners and perimeter of the grid Each earthing rod will be 3m long
Using the simplified equation, the resistance of the earthing grid with respect to remote earth is:
kA
V The GPR far exceeds the maximum allowable touch and step potentials, and further analysis of mesh and step voltages need to be performed.
is:
is:
and
are the width and length of the grid respectively (e.g. 50m and
is the number of parallel rows and columns respectively (e.g. 6 and 7) is:
is:
is:
V The maximum allowable touch potential is 1,720V, which exceeds the mesh voltage calculated above and the earthing system passes the touch potential criteria (although it is quite marginal).
is:
V The maximum allowable step potential is 5,664V, which exceeds the step voltage calculated above and the earthing system passes the step potential criteria. Having passed both touch and step potential criteria, we can conclude that the earthing system is safe.
As can be seen from above, touch and step potential calculations can be quite a tedious and laborious task, and one that could conceivably be done much quicker by a computer. Even IEEE Std 80 recommends the use of computer software to calculate grid resistances, and mesh and step voltages, and also to create potential gradient visualisations of the site. Computer software packages can be used to assist in earthing grid design by modeling and simulation of different earthing grid configurations. The tools either come as standalone packages or plug-in modules to power system analysis software (such as PTW's GroundMat or ETAP's Ground Grid Design Assessment. Examples of standalone packages include SES Autogrid and SafeGrid.
What next?
The minimum size for the earthing grid conductors can be used to specify the earthing grid conductor sizes in the material take-offs and earthing drawings. The touch and step potential calculations (where necessary) verify that the earthing grid design is safe for the worst earth faults to remote earth. The earthing drawings can therefore be approved for the next stage of reviews. Category: Calculations
1 Introduction o 1.1 Why do the calculation? o 1.2 When to do the calculation? 2 General Methodology o 2.1 Step 1: Data Gathering 2.1.1 Load Details 2.1.2 Cable Construction 2.1.3 Installation Conditions o 2.2 Step 2: Cable Selection Based on Current Rating 2.2.1 Base Current Ratings 2.2.2 Installed Current Ratings 2.2.3 Cable Selection and Coordination with Protective Devices 2.2.3.1 Feeders 2.2.3.2 Motors o 2.3 Step 3: Voltage Drop 2.3.1 Cable Impedances 2.3.2 Calculating Voltage Drop 2.3.3 Maximum Permissible Voltage Drop 2.3.4 Calculating Maximum Cable Length due to Voltage Drop o 2.4 Step 4: Short Circuit Temperature Rise 2.4.1 Minimum Cable Size Due to Short Circuit Temperature Rise 2.4.2 Initial and Final Conductor Temperatures 2.4.3 Short Circuit Energy o 2.5 Step 5: Earth Fault Loop Impedance 2.5.1 The Earth Fault Loop 2.5.2 Maximum Cable Length 3 Worked Example o 3.1 Step 1: Data Gathering o 3.2 Step 2: Cable Selection Based on Current Rating o 3.3 Step 3: Voltage Drop o 3.4 Step 4: Short Circuit Temperature Rise o 3.5 Step 5: Earth Fault Loop Impedance 4 Waterfall Charts 5 International Standards o 5.1 IEC o 5.2 NEC o 5.3 BS o 5.4 AS/NZS 6 Computer Software 7 What next?
Introduction
This article examines the sizing of electrical cables (i.e. cross-sectional area) and its implementation in various international standards. Cable sizing methods do differ across international standards (e.g. IEC, NEC, BS, etc) and some standards emphasise certain things over others. However the general principles underlying any cable sizing calculation do not change. In this article, a general methodology for sizing cables is first presented and then the specific international standards are introduced.
General Methodology
All cable sizing methods more or less follow the same basic six step process: 1) Gathering data about the cable, its installation conditions, the load that it will carry, etc 2) Determine the minimum cable size based on continuous current carrying capacity 3) Determine the minimum cable size based on voltage drop considerations 4) Determine the minimum cable size based on short circuit temperature rise 5) Determine the minimum cable size based on earth fault loop impedance
6) Select the cable based on the highest of the sizes calculated in step 2, 3, 4 and 5
Load Details
The characteristics of the load that the cable will supply, which includes: Load type: motor or feeder Three phase, single phase or DC System / source voltage Full load current (A) - or calculate this if the load is defined in terms of
power (kW) Full load power factor (pu) Locked rotor or load starting current (A) Starting power factor (pu) Distance / length of cable run from source to load - this length should be as
close as possible to the actual route of the cable and include enough contingency for vertical drops / rises and termination of the cable tails
Cable Construction
The basic characteristics of the cable's physical construction, which includes: Conductor material - normally copper or aluminium Conductor shape - e.g. circular or shaped Conductor type - e.g. stranded or solid Conductor surface coating - e.g. plain (no coating), tinned, silver or nickel Insulation type - e.g. PVC, XLPE, EPR Number of cores - single core or multicore (e.g. 2C, 3C or 4C)
Installation Conditions
How the cable will be installed, which includes: Above ground or underground Installation / arrangement - e.g. for underground cables, is it directly buried
or buried in conduit? for above ground cables, is it installed on cable tray / ladder, against a wall, in air, etc.
flat?
Ambient or soil temperature of the installation site Cable bunching, i.e. the number of cables that are bunched together Cable spacing, i.e. whether cables are installed touching or spaced Soil thermal resistivity (for underground cables) Depth of laying (for underground cables) For single core three-phase cables, are the cables installed in trefoil or laid
International standards and manufacturers of cables will quote base current ratings of different types of cables in tables such as the one shown on the right. Each of these tables pertain to a specific type of cable construction (e.g. copper conductor, PVC insulated, 0.6/1kV voltage grade, etc) and a base set of installation conditions (e.g. ambient temperature, installation method, etc). It is important to note that the current ratings are only valid for the quoted types of cables and base installation conditions. In the absence of any guidance, the following reference based current ratings may be used.
where
is the base current rating (A) are the product of all the derating factors For example, suppose a cable had an ambient temperature derating factor of kamb = 0.94 and a grouping derating factor of kg = 0.85, then the overall derating factorkd = 0.94x0.85 = 0.799. For a cable with a base current rating of 42A, the installed current rating would be Ic = 0.799x42 = 33.6A. In the absence of any guidance, the following reference derating factors may be used.
Where
Motors
Motors are normally protected by a separate thermal overload (TOL) relay and therefore the upstream protective device (e.g. fuse or circuit breaker) is not required to protect the cable against overloads. As a result, cables need only to be sized to cater for the full load current of the motor, i.e.
Where
is the installed cable current rating (A) Of course, if there is no separate thermal overload protection on the motor, then the protective device needs to be taken into account as per the case for feeders above.
voltage drop Impedance of the conductor the larger the impedance, the higher the
voltage drop
Cable Impedances
The impedance of the cable is a function of the cable size (cross-sectional area) and the length of the cable. Most cable manufacturers will quote a cables resistance and reactance in /km. The following typical cable impedances for low voltage AC and DC single core and multicore cables can be used in the absence of any other data.
Where
is the nominal full load or starting current as applicable (A) is the ac resistance of the cable (/km) is the ac reactance of the cable (/km) is the load power factor (pu) is the length of the cable (m) For a single phase system:
Where
is the nominal full load or starting current as applicable (A) is the ac resistance of the cable (/km) is the ac reactance of the cable (/km) is the load power factor (pu) is the length of the cable (m) For a DC system:
Where
is the nominal full load or starting current as applicable (A) is the dc resistance of the cable (/km) is the length of the cable (m)
nominal voltage at full load) rather than the voltage drop itself. For example, by doing this it is possible to construct tables showing the maximum lengths corresponding to different cable sizes in order to speed up the selection of similar type cables. The maximum cable length that will achieve this can be calculated by re-arranging the voltage drop equations and substituting the maximum permissible voltage drop (e.g. 5% of 415V nominal voltage = 20.75V). For a three phase system:
Where
is the maximum permissible three phase voltage drop (V) is the nominal full load or starting current as applicable (A) is the ac resistance of the cable (/km) is the ac reactance of the cable (/km) is the load power factor (pu) For a single phase system:
Where
is the maximum permissible single phase voltage drop (V) is the nominal full load or starting current as applicable (A) is the ac resistance of the cable (/km) is the ac reactance of the cable (/km) is the load power factor (pu) For a DC system:
Where
is the maximum permissible dc voltage drop (V) is the nominal full load or starting current as applicable (A) is the dc resistance of the cable (/km) is the length of the cable (m)
materials and other components, which can prematurely degrade the condition of the cable. As the cross-sectional area of the cable increases, it can dissipate higher fault currents for a given temperature rise. Therefore, cables should be sized to withstand the largest short circuit that it is expected to see.
Where
is the prospective short circuit current (A) is the duration of the short circuit (s) is a short circuit temperature rise constant The temperature rise constant is calculated based on the material properties of the conductor and the initial and final conductor temperatures (see the derivation here). Different international standards have different treatments of the temperature rise constant, but by way of example, IEC 60364-5-54 calculates it as follows:
(for copper conductors) (for aluminium conductors) Where is the initial conductor temperature (deg C)
Where is the earth fault current required to trip the protective device within the minimum disconnection time (A) is the phase to earth voltage at the protective device (V) is the impedance of the earth fault loop () It can be seen from the equation above that the impedance of the earth fault loop must be sufficiently low to ensure that the earth fault current can trip the upstream protection.
Where
is the impedance of the active conductor () is the impedance of the earth conductor () Assuming that the active and earth conductors have identical lengths, the earth fault loop impedance can be calculated as follows:
is the length of the cable (m) are the ac resistances of the active and earth conductors respectively
Where
is the phase to earth voltage at the protective device (V) is the earth fault current required to trip the protective device within the minimum disconnection time (A) The maximum cable length can therefore be calculated by the following:
Where
is the phase to earth voltage at the protective device (V) is the earth fault current required to trip the protective device within the minimum disconnection time (A)
Note that the voltage V0 at the protective device is not necessarily the nominal phase to earth voltage, but usually a lower value as it can be downstream of the main busbars. This voltage is commonly represented by applying some factor to the nominal voltage. A conservative value of = 0.8 can be used so that:
Worked Example
In this example, we will size a cable for a 415V, 30kW three-phase motor from the MCC to the field.
A voltage drop of 7.593V is equivalent to , which is lower than the maximum permissible voltage dorp of 5%. Therefore the cable is suitable for the motor based on voltage drop considerations.
In this example, we also use the fuse for earth fault protection and it needs to trip within 5s, which is at the upper end of the adiabatic period where the short circuit temperature rise equation is still valid. Therefore, it's a good idea to also check that the cable can withstand the short circuit temperature rise for for a 5s fault. The 80A motor fuse has a 5s melting current of 550A. The short circuit temperature rise is thus:
The cable run is 90m and the maximum length allowed is 108m, therefore our cable is suitable based on earth fault loop impedance. In fact, our 25 mm2 cable has passed all the tests and is the size that should be selected.
Waterfall Charts
Sometimes it is convenient to group together similar types of cables (for example, 415V PVC motor cables installed on cable ladder) so that instead of having to go through the laborious exercise of sizing each cable separately, one can select a cable from a pre-calculated chart. These charts are often called "waterfall charts" and typically show a list of load ratings and the maximum of length of cable permissible for each cable size. Where a particular cable size fails to meet the requirements for current carrying capacity or short circuit temperature rise, it is blacked out on the chart (i.e. meaning that you can't choose it). Preparing a waterfall chart is common practice when having to size many like cables and substantially cuts down the time required for cable selection.
International Standards
IEC
IEC 60364-5-52 (2009) "Electrical installations in buildings - Part 5-52: Selection and erection of electrical equipment - Wiring systems" is the IEC standard governing cable sizing.
NEC
NFPA 70 (2011) "National Electricity Code" is the equivalent standard for IEC 60364 in North America and includes a section covering cable sizing in Article 300.
BS
BS 7671 (2008) "Requirements for Electrical Installations - IEE Wiring Regulations" is the equivalent standard for IEC 60364 in the United Kingdom.
AS/NZS
AS/NZS 3008.1 (2009) "Electrical installations - Selection of cables - Cables for alternating voltages up to and including 0.6/1 kV" is the standard governing low voltage cable sizing in Australia and New Zealand. AS/NZS 3008.1.1 is for Australian conditions and AS/NZS 3008.1.2 is for New Zealand conditions.
Computer Software
Cablesizer is a free online application for sizing cables to IEC standards. Most of the major electrical analysis packages (e.g. ETAP, PTW, etc) have a cable sizing module. There also exists other (offline) software packages that include cable sizing (for example from Solutions Electrical UK).
What next?
Having sized the power / load-bearing cables, the cable schedule can now be developed and then the cable material take-offs (MTO).