Modbus Application Protocol V1 1a
Modbus Application Protocol V1 1a
5 6
Annex A (Informative): MODBUS RESERVED FUNCTION CODES, SUBCODES AND MEI TYPES ..................................................................................................................51 Annex B (Informative): CANOPEN GENERAL REFERENCE COMMAND .............................51
June 4, 2004
http://www.Modbus-IDA.org
1/51
Modbus-IDA
1
1.1
Introduction
Scope of this document
MODBUS is an application layer messaging protocol, positioned at level 7 of the OSI model, that provides client/server communication between devices connected on different types of buses or networks. The industrys serial de facto standard since 1979, MODBUS continues to enable millions of automation devices to communicate. Today, support for the simple and elegant structure of MODBUS continues to grow. The Internet community can access MODBUS at a reserved system port 502 on the TCP/IP stack. MODBUS is a request/reply protocol and offers services specified by function codes. MODBUS function codes are elements of MODBUS request/reply PDUs. The objective of this document is to describe the function codes used within the framework of MODBUS transactions. MODBUS is an application layer messaging protocol for client/server communication between devices connected on different types of buses or networks. It is currently implemented using: TCP/IP over Ethernet. See MODBUS Messaging Implementation Guide V1.0a. Asynchronous serial transmission over a variety of media (wire : EIA/TIA-232-E, EIA422, EIA/TIA-485-A; fiber, radio, etc.) MODBUS PLUS, a high speed token passing network.
Other Other
Figure 1:
Abbreviations
Application Data Unit Human Machine Interface Internet Engineering Task Force Input/Output http://www.Modbus-IDA.org 2/51
June 4, 2004
MODBUS Application Protocol Specification V1.1a IP MAC MB PDU PLC TCP Internet Protocol Medium Access Control MODBUS Protocol Protocol Data Unit Programmable Logic Controller Transport Control Protocol
Modbus-IDA
Context
The MODBUS protocol allows an easy communication within all types of network architectures.
MODBUS COMMUNICATION
Drive
PLC
HMI
I/ O
I/ O
PLC
I/ O
MODBUS ON TCP/IP
Gateway
Gateway
Gateway
MODBUS ON RS232
MODBUS ON MB+
MODBUS ON RS485
PLC I/ O I/ O
Device
Device
I/ O
Figure 2:
Every type of devices (PLC, HMI, Control Panel, Driver, Motion control, I/O Device) can use MODBUS protocol to initiate a remote operation. The same communication can be done as well on serial line as on an Ethernet TCP/IP networks. Gateways allow a communication between several types of buses or network using the MODBUS protocol.
4
4.1
General description
Protocol description
The MODBUS protocol defines a simple protocol data unit (PDU) independent of the underlying communication layers. The mapping of MODBUS protocol on specific buses or network can introduce some additional fields on the application data unit (ADU).
June 4, 2004
http://www.Modbus-IDA.org
3/51
Modbus-IDA
Data
Error check
The MODBUS application data unit is built by the client that initiates a MODBUS transaction. The function indicates to the server what kind of action to perform. The MODBUS application protocol establishes the format of a request initiated by a client. The function code field of a MODBUS data unit is coded in one byte. Valid codes are in the range of 1 ... 255 decimal (128 255 reserved for exception responses). When a message is sent from a Client to a Server device the function code field tells the server what kind of action to perform. Function code "0" is not valid. Sub-function codes are added to some function codes to define multiple actions. The data field of messages sent from a client to server devices contains additional information that the server uses to take the action defined by the function code. This can include items like discrete and register addresses, the quantity of items to be handled, and the count of actual data bytes in the field. The data field may be nonexistent (of zero length) in certain kinds of requests, in this case the server does not require any additional information. The function code alone specifies the action. If no error occurs related to the MODBUS function requested in a properly received MODBUS ADU the data field of a response from a server to a client contains the data requested. If an error related to the MODBUS function requested occurs, the field contains an exception code that the server application can use to determine the next action to be taken. For example a client can read the ON / OFF states of a group of discrete outputs or inputs or it can read/write the data contents of a group of registers. When the server responds to the client, it uses the function code field to indicate either a normal (error-free) response or that some kind of error occurred (called an exception response). For a normal response, the server simply echoes to the request the original function code.
Client
Initiate request
Function code Data Request
Server
Figure 4:
For an exception response, the server returns a code that is equivalent to the original function code from the request PDU with its most significant bit set to logic 1.
June 4, 2004
http://www.Modbus-IDA.org
4/51
Modbus-IDA
Client
Initiate request
Function code Data Request
Server
Exception code
Figure 5:
Note: It is desirable to manage a time out in order not to indefinitely wait for an answer which will perhaps never arrive.
The size of the MODBUS PDU is limited by the size constraint inherited from the first MODBUS implementation on Serial Line network (max. RS485 ADU = 256 bytes). Therefore: MODBUS PDU for serial line communication = 256 - Server address (1 byte) - CRC (2 bytes) = 253 bytes. Consequently: RS232 / RS485 ADU = 253 bytes + Server address (1 byte) + CRC (2 bytes) = 256 bytes. TCP MODBUS ADU = 253 bytes + MBAP (7 bytes) = 260 bytes. The MODBUS protocol defines three PDUs. They are : MODBUS Request PDU, mb_req_pdu MODBUS Response PDU, mb_rsp_pdu MODBUS Exception Response PDU, mb_excep_rsp_pdu
function_code = [1 byte] MODBUS function code corresponding to the desired MODBUS function code or requested through the client API, request_data = [n bytes] This field is function code dependent and usually contains information such as variable references, variable counts, data offsets, sub-function codes etc. The mb_rsp_pdu is defined as: mb_rsp_pdu = {function_code, response_data}, where function_code = [1 byte] MODBUS function code response_data = [n bytes] This field is function code dependent and usually contains information such as variable references, variable counts, data offsets, sub-function codes, etc. June 4, 2004 http://www.Modbus-IDA.org 5/51
Modbus-IDA
The mb_excep_rsp_pdu is defined as: mb_excep_rsp_pdu = {function_code, request_data}, where exception-function_code = [1 byte] MODBUS function code + 0x80 exception_code = [1 byte] MODBUS Exception Code Defined in table "MODBUS Exception Codes" (see section 7 ). 4.2 Data Encoding MODBUS uses a big-Endian representation for addresses and data items. This means that when a numerical quantity larger than a single byte is transmitted, the most significant byte is sent first. So for example Register size 16 - bits value 0x1234 the first byte sent is 0x12 then 0x34
4.3
MODBUS bases its data model on a series of tables that have distinguishing characteristics. The four primary tables are:
Primary tables Discretes Input Coils Input Registers Holding Registers Object type Single bit Single bit 16-bit word 16-bit word Type of Read-Only Read-Write Read-Only Read-Write Comments This type of data can be provided by an I/O system. This type of data can be alterable by an application program. This type of data can be provided by an I/O system This type of data can be alterable by an application program.
The distinctions between inputs and outputs, and between bit-addressable and wordaddressable data items, do not imply any application behavior. It is perfectly acceptable, and very common, to regard all four tables as overlaying one another, if this is the most natural interpretation on the target machine in question. For each of the primary tables, the protocol allows individual selection of 65536 data items, and the operations of read or write of those items are designed to span multiple consecutive data items up to a data size limit which is dependent on the transaction function code. Its obvious that all the data handled via MODBUS (bits, registers) must be located in device application memory. But physical address in memory should not be confused with data reference. The only requirement is to link data reference with physical address. MODBUS logical reference numbers, which are used in MODBUS functions, are unsigned integer indices starting at zero. Implementation examples of MODBUS model
The examples below show two ways of organizing the data in device. There are different organizations possible, but not all are described in this document. Each device can have its own organization of the data according to its application Example 1 : Device having 4 separate blocks June 4, 2004 http://www.Modbus-IDA.org 6/51
Modbus-IDA
The example below shows data organization in a device having digital and analog, inputs and outputs. Each block is separate because data from different blocks have no correlation. Each block is thus accessible with different MODBUS functions.
Device application memory
MODBUS access
Figure 6
Example 2: Device having only 1 block In this example, the device has only 1 data block. The same data can be reached via several MODBUS functions, either via a 16 bit access or via an access bit.
Device application memory
MODBUS access
Input Discrete
R W R
MODBUS Request
Figure 7
4.4
The MODBUS application protocol defines precisely PDU addressing rules. In a MODBUS PDU each data is addressed from 0 to 65535. It also defines clearly a MODBUS data model composed of 4 blocks that comprises several elements numbered from 1 to n. In the MODBUS data Model each element within a data block is numbered from 1 to n. June 4, 2004 http://www.Modbus-IDA.org 7/51
Modbus-IDA
Afterwards the MODBUS data model has to be bound to the device application ( IEC-61131 object, or other application model). The pre-mapping between the MODBUS data model and the device application is totally vendor device specific.
Device application
1 Discrete Input
. . .
Read input 0
Coils
1 . 5
.
Read Registers 54
Figure 8
The previous figure shows that a MODBUS data numbered X is addressed in the MODBUS PDU X-1.
4.5
The following state diagram describes the generic processing of a MODBUS transaction in server side.
June 4, 2004
http://www.Modbus-IDA.org
8/51
Modbus-IDA
ExeptionCode_1
ExceptionCode_2
ExceptionCode_3
ExceptionCode_4_5_6
[Invalid] [Valid]
Figure 9
Once the request has been processed by a server, a MODBUS response using the adequate MODBUS server transaction is built. Depending on the result of the processing two types of response are built : A positive MODBUS response : the response function code = the request function code A MODBUS Exception response ( see section 7 ): the objective is to provide to the client relevant information concerning the error detected during the processing ; the exception function code = the request function code + 0x80 ; an exception code is provided to indicate the reason of the error.
June 4, 2004
http://www.Modbus-IDA.org
9/51
Modbus-IDA
There are three categories of MODBUS Functions codes. They are : Public Function Codes Are well defined function codes , guaranteed to be unique, validated by the MODBUS-IDA.org community, publicly documented have available conformance test, includes both defined public assigned function codes as well as unassigned function codes reserved for future use. there are two ranges of user-defined function codes, i.e. 65 to 72 and from 100 to 110 decimal. user can select and implement a function code that is not supported by the specification. there is no guarantee that the use of the selected function code will be unique if the user wants to re-position the functionality as a public function code, he must initiate an RFC to introduce the change into the public category and to have a new public function code assigned. MODBUS Organization, Inc expressly reserves the right to develop the proposed RFC. Function Codes currently used by some companies for legacy products and that are not available for public use. Informative Note: The reader is asked refer to Annex A (Informative) MODBUS RESERVED FUNCTION CODES, SUBCODES AND MEI TYPES.
June 4, 2004
http://www.Modbus-IDA.org
10/51
Modbus-IDA
127
User Defined Function codes PUBLIC function codes User Defined Function codes
1
Figure 10 MODBUS Function Code Categories
5.1
Public Function Code Definition Function Codes code Sub (hex) Section code 6.2 02 02 01 05 15 04 03 06 16 23 22 24 20 21 07 08 11 12 17 43 43 01 05 0F 04 03 06 10 17 16 18 6 14 6 15 07 00-18,20 08 OB 0C 11 14 2B 13,14 2B 6.1 6.5 6.11 6.4 6.3 6.6 6.12 6.17 6.16 6.18 6.14 6.15 6.7 6.8 6.9 6.10 6.13 6.21 6.19
Physical Discrete Inputs Bit access Internal Bits Or Physical coils Physical Input Registers 16 bits access Internal Registers Or Physical Output Registers
Read Discrete Inputs Read Coils Write Single Coil Write Multiple Coils Read Input Register Read Holding Registers Write Single Register Write Multiple Registers Read/Write Multiple Registers Mask Write Register Read FIFO queue Read File record Write File record Read Exception status Diagnostic Get Com event counter Get Com Event Log Report Slave ID Read device Identification Encapsulated Interface Transport http://www.Modbus-IDA.org
Data Access
Diagnostics
11/51
Modbus-IDA 2B 6.20
6
6.1
This function code is used to read from 1 to 2000 contiguous status of coils in a remote device. The Request PDU specifies the starting address, i.e. the address of the first coil specified, and the number of coils. In the PDU Coils are addressed starting at zero. Therefore coils numbered 1-16 are addressed as 0-15. The coils in the response message are packed as one coil per bit of the data field. Status is indicated as 1= ON and 0= OFF. The LSB of the first data byte contains the output addressed in the query. The other coils follow toward the high order end of this byte, and from low order to high order in subsequent bytes. If the returned output quantity is not a multiple of eight, the remaining bits in the final data byte will be padded with zeros (toward the high order end of the byte). The Byte Count field specifies the quantity of complete bytes of data. Request
Function code Starting Address Quantity of coils 1 Byte 2 Bytes 2 Bytes 0x01 0x0000 to 0xFFFF 1 to 2000 (0x7D0)
Response
Function code Byte count Coil Status 1 Byte 1 Byte n Byte 0x01 N* n = N or N+1
The status of outputs 2720 is shown as the byte value CD hex, or binary 1100 1101. Output 27 is the MSB of this byte, and output 20 is the LSB. By convention, bits within a byte are shown with the MSB to the left, and the LSB to the right. Thus the outputs in the first byte are 27 through 20, from left to right. The next byte has outputs 35 through 28, left to right. As the bits are transmitted serially, they flow from LSB to MSB: 20 . . . 27, 28 . . . 35, and so on. In the last data byte, the status of outputs 38-36 is shown as the byte value 05 hex, or binary 0000 0101. Output 38 is in the sixth bit position from the left, and output 36 is the LSB of this byte. The five remaining high order bits are zero filled.
Note: The five remaining bits (toward the high order end) are zero filled.
June 4, 2004
http://www.Modbus-IDA.org
12/51
Modbus-IDA
NO
Function code supported YES NO 0x0001 Quantity of Outputs 0x07D0 YES NO Starting Address == OK AND Starting Address + Quantity of Outputs == OK YES Request Processing
ExceptionCode = 01
ExceptionCode = 03
ExceptionCode = 02
NO ReadDiscreteOutputs
== OK
EXIT
This function code is used to read from 1 to 2000 contiguous status of discrete inputs in a remote device. The Request PDU specifies the starting address, i.e. the address of the first input specified, and the number of inputs. In the PDU Discrete Inputs are addressed starting at zero. Therefore Discrete inputs numbered 1-16 are addressed as 0-15. The discrete inputs in the response message are packed as one input per bit of the data field. Status is indicated as 1= ON; 0= OFF. The LSB of the first data byte contains the input addressed in the query. The other inputs follow toward the high order end of this byte, and from low order to high order in subsequent bytes. If the returned input quantity is not a multiple of eight, the remaining bits in the final data byte will be padded with zeros (toward the high order end of the byte). The Byte Count field specifies the quantity of complete bytes of data. Request Function code Starting Address Quantity of Inputs Response Function code Byte count Input Status Error Error code June 4, 2004 1 Byte 0x82 13/51
0x02 N*
http://www.Modbus-IDA.org
Modbus-IDA
The status of discrete inputs 204197 is shown as the byte value AC hex, or binary 1010 1100. Input 204 is the MSB of this byte, and input 197 is the LSB. The status of discrete inputs 218213 is shown as the byte value 35 hex, or binary 0011 0101. Input 218 is in the third bit position from the left, and input 213 is the LSB.
Note: The two remaining bits (toward the high order end) are zero filled.
NO
Function code supported YES NO 0x0001 Quantity of Inputs 0x07D0 YES NO Starting Address == OK AND Starting Address + Quantity of Inputs == OK YES Request Processing
ExceptionCode = 01
ExceptionCode = 03
ExceptionCode = 02
NO ReadDiscreteInputs
== OK
ExceptionCode = 04
YES
EXIT
Figure 12:
June 4, 2004
http://www.Modbus-IDA.org
14/51
MODBUS Application Protocol Specification V1.1a 6.3 03 (0x03) Read Holding Registers
Modbus-IDA
This function code is used to read the contents of a contiguous block of holding registers in a remote device. The Request PDU specifies the starting register address and the number of registers. In the PDU Registers are addressed starting at zero. Therefore registers numbered 1-16 are addressed as 0-15. The register data in the response message are packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits. Request
Function code Starting Address Quantity of Registers 1 Byte 2 Bytes 2 Bytes
0x03 0x0000 to 0xFFFF 1 to 125 (0x7D)
Response
Function code Byte count Register value 1 Byte 1 Byte N * x 2 Bytes
0x03 2 x N*
The contents of register 108 are shown as the two byte values of 02 2B hex, or 555 decimal. The contents of registers 109110 are 00 00 and 00 64 hex, or 0 and 100 decimal, respectively.
June 4, 2004
http://www.Modbus-IDA.org
15/51
Modbus-IDA
NO
Function code supported YES NO 0x0001 Quantity of Registers 0x007D YES NO Starting Address == OK AND Starting Address + Quantity of Registers == OK YES Request Processing
ExceptionCode = 01
ExceptionCode = 03
ExceptionCode = 02
NO ReadMultipleRegisters
== OK
ExceptionCode = 04
EXIT
Figure 13:
6.4
This function code is used to read from 1 to approx. 125 contiguous input registers in a remote device. The Request PDU specifies the starting register address and the number of registers. In the PDU Registers are addressed starting at zero. Therefore input registers numbered 1-16 are addressed as 0-15. The register data in the response message are packed as two bytes per register, with the binary contents right justified within each byte. For each register, the first byte contains the high order bits and the second contains the low order bits. Request
Function code Starting Address Quantity of Input Registers 1 Byte 2 Bytes 2 Bytes
0x04 0x0000 to 0xFFFF 0x0001 to 0x007D
Response
Function code Byte count Input Registers 1 Byte 1 Byte N * x 2 Bytes
0x04 2 x N*
June 4, 2004
http://www.Modbus-IDA.org
16/51
Modbus-IDA
0A
Input Reg. 9 Lo
The contents of input register 9 are shown as the two byte values of 00 0A hex, or 10 decimal.
ENTRY MB Server receives mb_req_pdu
NO
Function code supported YES NO 0x0001 Quantity of Registers 0x007D YES NO Starting Address == OK AND Starting Address + Quantity of Registers == OK YES Request Processing NO ReadInputRegisters
ExceptionCode = 01
ExceptionCode = 03
ExceptionCode = 02
== OK
ExceptionCode = 04
EXIT
Figure 14:
6.5
This function code is used to write a single output to either ON or OFF in a remote device. The requested ON/OFF state is specified by a constant in the request data field. A value of FF 00 hex requests the output to be ON. A value of 00 00 requests it to be OFF. All other values are illegal and will not affect the output. The Request PDU specifies the address of the coil to be forced. Coils are addressed starting at zero. Therefore coil numbered 1 is addressed as 0. The requested ON/OFF state is specified by a constant in the Coil Value field. A value of 0XFF00 requests the coil to be ON. A value of 0X0000 requests the coil to be off. All other values are illegal and will not affect the coil. The normal response is an echo of the request, returned after the coil state has been written. Request
Function code Output Address Output Value 1 Byte 2 Bytes 2 Bytes
0x05 0x0000 to 0xFFFF 0x0000 or 0xFF00
June 4, 2004
http://www.Modbus-IDA.org
17/51
Modbus-IDA
Error
Error code Exception code 1 Byte 1 Byte
0x85 01 or 02 or 03 or 04
June 4, 2004
http://www.Modbus-IDA.org
18/51
Modbus-IDA
NO
Function code supported YES NO Output Value == 0x0000 OR 0xFF00 YES NO Output Address == OK YES ExceptionCode = 02 Request Processing
ExceptionCode = 01
ExceptionCode = 03
NO WriteSingleOutput
== OK
EXIT
This function code is used to write a single holding register in a remote device. The Request PDU specifies the address of the register to be written. Registers are addressed starting at zero. Therefore register numbered 1 is addressed as 0. The normal response is an echo of the request, returned after the register contents have been written. Request
Function code Register Address Register Value 1 Byte 2 Bytes 2 Bytes
0x06 0x0000 to 0xFFFF 0x0000 or 0xFFFF
Response
Function code Register Address Register Value 1 Byte 2 Bytes 2 Bytes
0x06 0x0000 to 0xFFFF 0x0000 or 0xFFFF
Error
Error code Exception code 1 Byte 1 Byte
0x86 01 or 02 or 03 or 04
June 4, 2004
http://www.Modbus-IDA.org
19/51
Modbus-IDA
NO
Function code supported YES NO 0x0000 Register Value 0xFFFF YES NO Register Address == OK YES ExceptionCode = 02 Request Processing
ExceptionCode = 01
ExceptionCode = 03
NO
WriteSingleRegister
== OK
YES
ExceptionCode = 04
EXIT
Figure 16:
6.7
This function code is used to read the contents of eight Exception Status outputs in a remote device. The function provides a simple method for accessing this information, because the Exception Output references are known (no output reference is needed in the function). The normal response contains the status of the eight Exception Status outputs. The outputs are packed into one data byte, with one bit per output. The status of the lowest output reference is contained in the least significant bit of the byte. The contents of the eight Exception Status outputs are device specific. Request
Function code 1 Byte
0x07
Response
Function code Output Data 1 Byte 1 Byte
0x07 0x00 to 0xFF
Error
Error code Exception code 1 Byte 1 Byte
0x87 01 or 04
June 4, 2004
http://www.Modbus-IDA.org
20/51
Modbus-IDA
In this example, the output data is 6D hex (0110 1101 binary). Left to right, the outputs are OFFONONOFFONONOFFON. The status is shown from the highest to the lowest addressed output.
ENTRY MB Server receives mb_req_pdu
NO
ExceptionCode = 01
NO
ReadExceptionStatus == OK
ExceptionCode = 04
EXIT
Figure 17:
6.8
MODBUS function code 08 provides a series of tests for checking the communication system between a client ( Master) device and a server ( Slave), or for checking various internal error conditions within a server. The function uses a twobyte sub-function code field in the query to define the type of test to be performed. The server echoes both the function code and sub-function code in a normal response. Some of the diagnostics cause data to be returned from the remote device in the data field of a normal response. In general, issuing a diagnostic function to a remote device does not affect the running of the user program in the remote device. User logic, like discrete and registers, is not accessed by the diagnostics. Certain functions can optionally reset error counters in the remote device. A server device can, however, be forced into Listen Only Mode in which it will monitor the messages on the communications system but not respond to them. This can affect the outcome of your application program if it depends upon any further exchange of data with the remote device. Generally, the mode is forced to remove a malfunctioning remote device from the communications system. The following diagnostic functions are dedicated to serial line devices. The normal response to the Return Query Data request is to loopback the same data. The function code and sub-function codes are also echoed. Request
Function code Sub-function 1 Byte 2 Bytes
0x08
June 4, 2004
http://www.Modbus-IDA.org
21/51
Modbus-IDA
Response
Function code Sub-function Data 1 Byte 2 Bytes N x 2 Bytes
0x08
Error
Error code Exception code 1 Byte 1 Byte
0x88 01 or 03 or 04
6.8.1
Here the list of sub-function codes supported by the serial line devices. Each sub-function code is then listed with an example of the data field contents that would apply for that diagnostic.
Sub-function code Hex Dec 00 00 01 01 02 02 03 03 04 04 05.. 09 0A 10 0B 11 0C 12 0D 13 0E 14 0F 15 10 16 11 17 12 18 13 19 14 20 N.A. 21 65535 Name Return Query Data Restart Communications Option Return Diagnostic Register Change ASCII Input Delimiter Force Listen Only Mode RESERVED Clear Counters and Diagnostic Register Return Bus Message Count Return Bus Communication Error Count Return Bus Exception Error Count Return Slave Message Count Return Slave No Response Count Return Slave NAK Count Return Slave Busy Count Return Bus Character Overrun Count RESERVED Clear Overrun Counter and Flag RESERVED
...
00 Return Query Data The data passed in the request data field is to be returned (looped back) in the response. The entire response message should be identical to the request. Sub-function Data Field (Request) Data Field (Response) 00 00 Any Echo Request Data 01 Restart Communications Option The remote device serial line port must be initialized and restarted, and all of its communications event counters are cleared. If the port is currently in Listen Only Mode, no response is returned. This function is the only one that brings the port out of Listen Only Mode. If the port is not currently in Listen Only Mode, a normal response is returned. This occurs before the restart is executed. When the remote device receives the request, it attempts a restart and executes its powerup confidence tests. Successful completion of the tests will bring the port online. A request data field contents of FF 00 hex causes the ports Communications Event Log to be cleared also. Contents of 00 00 leave the log as it was prior to the restart. Sub-function Data Field (Request) Data Field (Response) 00 01 00 00 Echo Request Data 00 01 FF 00 Echo Request Data
02 Return Diagnostic Register The contents of the remote devices 16bit diagnostic register are returned in the response. June 4, 2004 http://www.Modbus-IDA.org 22/51
03 Change ASCII Input Delimiter The character CHAR passed in the request data field becomes the end of message delimiter for future messages (replacing the default LF character). This function is useful in cases of a Line Feed is not required at the end of ASCII messages. Sub-function Data Field (Request) Data Field (Response) 00 03 CHAR 00 Echo Request Data 04 Force Listen Only Mode Forces the addressed remote device to its Listen Only Mode for MODBUS communications. This isolates it from the other devices on the network, allowing them to continue communicating without interruption from the addressed remote device. No response is returned. When the remote device enters its Listen Only Mode, all active communication controls are turned off. The Ready watchdog timer is allowed to expire, locking the controls off. While the device is in this mode, any MODBUS messages addressed to it or broadcast are monitored, but no actions will be taken and no responses will be sent. The only function that will be processed after the mode is entered will be the Restart Communications Option function (function code 8, sub-function 1). Sub-function Data Field (Request) Data Field (Response) 00 04 00 00 No Response Returned 10 (0A Hex) Clear Counters and Diagnostic Register The goal is to clear all counters and the diagnostic register. Counters are also cleared upon powerup. Sub-function Data Field (Request) Data Field (Response) 00 0A 00 00 Echo Request Data 11 (0B Hex) Return Bus Message Count The response data field returns the quantity of messages that the remote device has detected on the communications system since its last restart, clear counters operation, or powerup. Sub-function Data Field (Request) Data Field (Response) 00 0B 00 00 Total Message Count 12 (0C Hex) Return Bus Communication Error Count The response data field returns the quantity of CRC errors encountered by the remote device since its last restart, clear counters operation, or powerup. Sub-function Data Field (Request) Data Field (Response) 00 0C 00 00 CRC Error Count 13 (0D Hex) Return Bus Exception Error Count The response data field returns the quantity of MODBUS exception responses returned by the remote device since its last restart, clear counters operation, or powerup. Exception responses are described and listed in section 7 . Sub-function Data Field (Request) Data Field (Response) 00 0D 00 00 Exception Error Count 14 (0E Hex) Return Slave Message Count The response data field returns the quantity of messages addressed to the remote device, or broadcast, that the remote device has processed since its last restart, clear counters operation, or powerup. Sub-function Data Field (Request) Data Field (Response) 00 0E 00 00 Slave Message Count June 4, 2004 http://www.Modbus-IDA.org 23/51
Modbus-IDA
15 (0F Hex) Return Slave No Response Count The response data field returns the quantity of messages addressed to the remote device for which it has returned no response (neither a normal response nor an exception response), since its last restart, clear counters operation, or powerup. Sub-function Data Field (Request) Data Field (Response) 00 0F 00 00 Slave No Response Count 16 (10 Hex) Return Slave NAK Count The response data field returns the quantity of messages addressed to the remote device for which it returned a Negative Acknowledge (NAK) exception response, since its last restart, clear counters operation, or powerup. Exception responses are described and listed in section 7 . Sub-function Data Field (Request) Data Field (Response) 00 10 00 00 Slave NAK Count 17 (11 Hex) Return Slave Busy Count The response data field returns the quantity of messages addressed to the remote device for which it returned a Slave Device Busy exception response, since its last restart, clear counters operation, or powerup. Sub-function Data Field (Request) Data Field (Response) 00 11 00 00 Slave Device Busy Count 18 (12 Hex) Return Bus Character Overrun Count The response data field returns the quantity of messages addressed to the remote device that it could not handle due to a character overrun condition, since its last restart, clear counters operation, or powerup. A character overrun is caused by data characters arriving at the port faster than they can be stored, or by the loss of a character due to a hardware malfunction. Sub-function Data Field (Request) Data Field (Response) 00 12 00 00 Slave Character Overrun Count 20 (14 Hex) Clear Overrun Counter and Flag Clears the overrun error counter and reset the error flag. Sub-function Data Field (Request) Data Field (Response) 00 14 00 00 Echo Request Data 6.8.2 Example and state diagram
Here is an example of a request to remote device to Return Query Data. This uses a subfunction code of zero (00 00 hex in the twobyte field). The data to be returned is sent in the twobyte data field (A5 37 hex).
Request Field Name Function Sub-function Hi Sub-function Lo Data Hi Data Lo (Hex) 08 00 00 A5 37 Response Field Name Function Sub-function Hi Sub-function Lo Data Hi Data Lo (Hex) 08 00 00 A5 37
The data fields in responses to other kinds of queries could contain error counts or other data requested by the sub-function code.
June 4, 2004
http://www.Modbus-IDA.org
24/51
Modbus-IDA
NO
ExceptionCode = 01
Data Value == OK
YES Request Processing
ExceptionCode = 03
NO
Diagnostic == OK
YES
EXIT
Figure 18:
6.9
This function code is used to get a status word and an event count from the remote device's communication event counter. By fetching the current count before and after a series of messages, a client can determine whether the messages were handled normally by the remote device. The devices event counter is incremented once for each successful message completion. It is not incremented for exception responses, poll commands, or fetch event counter commands. The event counter can be reset by means of the Diagnostics function (code 08), with a subfunction of Restart Communications Option (code 00 01) or Clear Counters and Diagnostic Register (code 00 0A). The normal response contains a twobyte status word, and a twobyte event count. The status word will be all ones (FF FF hex) if a previouslyissued program command is still being processed by the remote device (a busy condition exists). Otherwise, the status word will be all zeros. Request
Function code 1 Byte
0x0B
Response
Function code Status Event Count 1 Byte 2 Bytes 2 Bytes
0x0B 0x0000 to 0xFFFF 0x0000 to 0xFFFF
Error
Error code Exception code 1 Byte 1 Byte
0x8B 01 or 04
June 4, 2004
http://www.Modbus-IDA.org
25/51
Modbus-IDA
Here is an example of a request to get the communications event counter in remote device:
Request Field Name Function (Hex) 0B Response Field Name Function Status Hi Status Lo Event Count Hi Event Count Lo (Hex) 0B FF FF 01 08
In this example, the status word is FF FF hex, indicating that a program function is still in progress in the remote device. The event count shows that 264 (01 08 hex) events have been counted by the device.
ENTRY MB Server receives mb_req_pdu
NO
ExceptionCode = 01
NO
GetCommEventCounter == OK
ExceptionCode = 04
YES
EXIT
Figure 19:
6.10
This function code is used to get a status word, event count, message count, and a field of event bytes from the remote device. The status word and event counts are identical to that returned by the Get Communications Event Counter function (11, 0B hex). The message counter contains the quantity of messages processed by the remote device since its last restart, clear counters operation, or powerup. This count is identical to that returned by the Diagnostic function (code 08), sub-function Return Bus Message Count (code 11, 0B hex). The event bytes field contains 0-64 bytes, with each byte corresponding to the status of one MODBUS send or receive operation for the remote device. The remote device enters the June 4, 2004 http://www.Modbus-IDA.org 26/51
Modbus-IDA
events into the field in chronological order. Byte 0 is the most recent event. Each new byte flushes the oldest byte from the field. The normal response contains a twobyte status word field, a twobyte event count field, a twobyte message count field, and a field containing 0-64 bytes of events. A byte count field defines the total length of the data in these four fields. Request
Function code 1 Byte
0x0C
Response
Function code Byte Count Status Event Count Message Count Events 1 Byte 1 Byte 2 Bytes 2 Bytes 2 Bytes ( N -6) x 1 Byte
0x0C N* 0x0000 to 0xFFFF 0x0000 to 0xFFFF 0x0000 to 0xFFFF
*N = Quantity of Events + 3 x 2 Bytes, (Length of Status, Event Count and Message Count) Error
Error code Exception code 1 Byte 1 Byte
0x8C 01 or 04
Here is an example of a request to get the communications event log in remote device:
Request Field Name Function (Hex) 0C Response Field Name Function Byte Count Status Hi Status Lo Event Count Hi Event Count Lo Message Count Hi Message Count Lo Event 0 Event 1 (Hex) 0C 08 00 00 01 08 01 21 20 00
In this example, the status word is 00 00 hex, indicating that the remote device is not processing a program function. The event count shows that 264 (01 08 hex) events have been counted by the remote device. The message count shows that 289 (01 21 hex) messages have been processed. The most recent communications event is shown in the Event 0 byte. Its content (20 hex) show that the remote device has most recently entered the Listen Only Mode. The previous event is shown in the Event 1 byte. Its contents (00 hex) show that the remote device received a Communications Restart. The layout of the responses event bytes is described below. What the Event Bytes Contain An event byte returned by the Get Communications Event Log function can be any one of four types. The type is defined by bit 7 (the highorder bit) in each byte. It may be further defined by bit 6. This is explained below. Remote device MODBUS Receive Event The remote device stores this type of event byte when a query message is received. It is stored before the remote device processes the message. This event is defined by bit 7 set to logic 1. The other bits will be set to a logic 1 if the corresponding condition is TRUE. The bit layout is: Bit 0 1 June 4, 2004 Contents Not Used Communication Error http://www.Modbus-IDA.org 27/51
MODBUS Application Protocol Specification V1.1a 2 3 4 5 6 7 Not Used Not Used Character Overrun Currently in Listen Only Mode Broadcast Received 1
Modbus-IDA
Remote device MODBUS Send Event The remote device stores this type of event byte when it finishes processing a request message. It is stored if the remote device returned a normal or exception response, or no response. This event is defined by bit 7 set to a logic 0, with bit 6 set to a 1. The other bits will be set to a logic 1 if the corresponding condition is TRUE. The bit layout is: Bit 0 1 2 3 4 5 6 7 Contents Read Exception Sent (Exception Codes 1-3) Slave Abort Exception Sent (Exception Code 4) Slave Busy Exception Sent (Exception Codes 5-6) Slave Program NAK Exception Sent (Exception Code 7) Write Timeout Error Occurred Currently in Listen Only Mode 1 0
Remote device Entered Listen Only Mode The remote device stores this type of event byte when it enters the Listen Only Mode. The event is defined by a content of 04 hex. Remote device Initiated Communication Restart The remote device stores this type of event byte when its communications port is restarted. The remote device can be restarted by the Diagnostics function (code 08), with sub-function Restart Communications Option (code 00 01). That function also places the remote device into a Continue on Error or Stop on Error mode. If the remote device is placed into Continue on Error mode, the event byte is added to the existing event log. If the remote device is placed into Stop on Error mode, the byte is added to the log and the rest of the log is cleared to zeros. The event is defined by a content of zero.
June 4, 2004
http://www.Modbus-IDA.org
28/51
Modbus-IDA
NO
ExceptionCode = 01
NO
GetCommEventLog == OK
ExceptionCode = 04
YES
EXIT
This function code is used to force each coil in a sequence of coils to either ON or OFF in a remote device. The Request PDU specifies the coil references to be forced. Coils are addressed starting at zero. Therefore coil numbered 1 is addressed as 0. The requested ON/OFF states are specified by contents of the request data field. A logical '1' in a bit position of the field requests the corresponding output to be ON. A logical '0' requests it to be OFF. The normal response returns the function code, starting address, and quantity of coils forced. Request PDU
Function code Starting Address Quantity of Outputs Byte Count Outputs Value 1 Byte 2 Bytes 2 Bytes 1 Byte N * x 1 Byte
0x0F 0x0000 to 0xFFFF 0x0001 to 0x07B0 N*
Error
Error code Exception code 1 Byte 1 Byte
0x8F 01 or 02 or 03 or 04
Here is an example of a request to write a series of 10 coils starting at coil 20: The request data contents are two bytes: CD 01 hex (1100 1101 0000 0001 binary). The binary bits correspond to the outputs in the following way: Bit: 1 1 0 0 1 1 0 1 0 0 0 0 0 0 0 1 Output: 27 26 25 24 23 22 21 20 29 28 The first byte transmitted (CD hex) addresses outputs 27-20, with the least significant bit addressing the lowest output (20) in this set. June 4, 2004 http://www.Modbus-IDA.org 29/51
Modbus-IDA
The next byte transmitted (01 hex) addresses outputs 29-28, with the least significant bit addressing the lowest output (28) in this set. Unused bits in the last data byte should be zerofilled.
Request Field Name Function Starting Address Hi Starting Address Lo Quantity of Outputs Hi Quantity of Outputs Lo Byte Count Outputs Value Hi Outputs Value Lo
ENTRY MB Server receives mb_req_pdu
(Hex) 0F 00 13 00 0A 02 CD 01
Response Field Name Function Starting Address Hi Starting Address Lo Quantity of Outputs Hi Quantity of Outputs Lo
(Hex) 0F 00 13 00 0A
NO
ExceptionCode = 01
0x0001 Quantity of Outputs 0x07B0 AND Byte Count = N* YES NO Starting Address == OK AND Starting Address + Quantity of Outputs == OK YES Request Processing
ExceptionCode = 03
ExceptionCode = 02
NO WriteMultipleOutputs
== OK
ExceptionCode = 04
EXIT
Figure 21:
6.12
This function code is used to write a block of contiguous registers (1 to approx. 120 registers) in a remote device. The requested written values are specified in the request data field. Data is packed as two bytes per register. The normal response returns the function code, starting address, and quantity of registers written. Request
Function code Starting Address Quantity of Registers Byte Count Registers Value 1 Byte 2 Bytes 2 Bytes 1 Byte N * x 2 Bytes
0x10 0x0000 to 0xFFFF 0x0001 to 0x0078 2 x N* value
June 4, 2004
http://www.Modbus-IDA.org
30/51
Modbus-IDA
Error
Error code Exception code 1 Byte 1 Byte
0x90
01 or 02 or 03 or 04
NO
Function code supported YES NO 0x0001 Quantity of Registers 0x007B AND Byte Count == Quantity of Registers x 2 YES NO Starting Address == OK AND Starting Address + Quantity of Registers == OK YES Request Processing
ExceptionCode = 01
ExceptionCode = 03
ExceptionCode = 02
NO WriteMultipleRegisters
== OK
ExceptionCode = 04
EXIT
Figure 22:
June 4, 2004
http://www.Modbus-IDA.org
31/51
MODBUS Application Protocol Specification V1.1a 6.13 17 (0x11) Report Slave ID (Serial Line only)
Modbus-IDA
This function code is used to read the description of the type, the current status, and other information specific to a remote device. The format of a normal response is shown in the following example. The data contents are specific to each type of device. Request
Function code 1 Byte 1 Byte 1 Byte device specific 1 Byte
0x11 0x11
Response
Function code Byte Count Slave ID Run Indicator Status Additional Data
Error
Error code Exception code 1 Byte 1 Byte
0x91 01 or 04
NO
ExceptionCode = 01
NO
ReportSlaveID == OK
ExceptionCode = 04
EXIT
This function code is used to perform a file record read. All Request Data Lengths are provided in terms of number of bytes and all Record Lengths are provided in terms of registers. A file is an organization of records. Each file contains 10000 records, addressed 0000 to 9999 decimal or 0X0000 to 0X270F. For example, record 12 is addressed as 12. June 4, 2004 http://www.Modbus-IDA.org 32/51
Modbus-IDA
The function can read multiple groups of references. The groups can be separating (noncontiguous), but the references within each group must be sequential. Each group is defined in a separate sub-request field that contains 7 bytes: The reference type: 1 byte (must be specified as 6) The File number: 2 bytes The starting record number within the file: 2 bytes The length of the record to be read: 2 bytes. The quantity of registers to be read, combined with all other fields in the expected response, must not exceed the allowable length of the MODBUS PDU : 253 bytes. The normal response is a series of sub-responses, one for each sub-request. The byte count field is the total combined count of bytes in all sub-responses. In addition, each subresponse contains a field that shows its own byte count. Request
Function code Byte Count Sub-Req. x, Reference Type Sub-Req. x, File Number Sub-Req. x, Record Number Sub-Req. x, Register Length Sub-Req. x+1, ... 1 1 1 2 2 2 Byte Byte Byte Bytes Bytes Bytes
0x14 0x07 to 0xF5 bytes 06 0x0000 to 0xFFFF 0x0000 to 0x270F N
Response
Function code Resp. data Length Sub-Req. x, File Resp. length Sub-Req. x, Reference Type Sub-Req. x, Record Data Sub-Req. x+1, ... 1 Byte 1 Byte 1 Byte 1 Byte N x 2 Bytes
0x14 0x07 to 0xF5 0x07 to 0xF5 6
Error
Error code Exception code 1 Byte 1 Byte
0x94 01 or 02 or 03 or 04 or 08
Here is an example of a request to read two groups of references from remote device: Group 1 consists of two registers from file 4, starting at register 1 (address 0001). Group 2 consists of two registers from file 3, starting at register 9 (address 0009).
Request Field Name Function Byte Count Sub-Req. 1, Sub-Req. 1, Sub-Req. 1, Sub-Req. 1, Sub-Req. 1, Sub-Req. 1, Sub-Req. 1, Sub-Req. 2, Sub-Req. 2, Sub-Req. 2, Sub-Req. 2, Sub-Req. 2, Sub-Req. 2, Sub-Req. 2,
Ref. Type File Number Hi File Number Lo Record number Hi Record number Lo Record Length Hi Record Length Lo Ref. Type File Number Hi File Number Lo Record number Hi Record number Lo Record Length Hi Record Length Lo
(Hex) 14 0E 06 00 04 00 01 00 02 06 00 03 00 09 00 02
Response Field Name Function Resp. Data length Sub-Req. 1, File resp. length Sub-Req. 1, Ref. Type Sub-Req. 1, Record. Data Hi Sub-Req. 1, Record. Data Lo Sub-Req. 1, Record. Data Hi Sub-Req. 1, Record. Data Lo Sub-Req. 2, File resp. length Sub-Req. 2, Ref. Type Sub-Req. 2, Record. Data Hi Sub-Req. 2, Record. Data Lo Sub-Req. 2, Record. Data Hi Sub-Req. 2, Record. Data Lo
(Hex) 14 0C 05 06 0D FE 00 20 05 06 33 CD 00 40
June 4, 2004
http://www.Modbus-IDA.org
33/51
Modbus-IDA
NO
Function code supported YES NO 0x07 Byte Count 0xF5 YES For each Sub-Req
ExceptionCode = 01
ExceptionCode = 03 NO
Reference Type == OK AND File Num ber == OK AND Record num ber == OK AND Starting Address + Register length == OK
ExceptionCode = 02
NO ReadGeneralReference
== OK
ExceptionCode = 04
EXIT
Figure 24:
6.15
This function code is used to perform a file record write. All Request Data Lengths are provided in terms of number of bytes and all Record Lengths are provided in terms of the number of 16-bit words. A file is an organization of records. Each file contains 10000 records, addressed 0000 to 9999 decimal or 0X0000 to 0X270F. For example, record 12 is addressed as 12. The function can write multiple groups of references. The groups can be separate, i.e. non contiguous, but the references within each group must be sequential. Each group is defined in a separate sub-request field that contains 7 bytes plus the data: The reference type: 1 byte (must be specified as 6) The file number: 2 bytes The starting record number within the file: 2 bytes The length of the record to be written: 2 bytes The data to be written: 2 bytes per register. The quantity of registers to be written, combined with all other fields in the request, must not exceed the allowable length of the MODBUS PDU : 253bytes. The normal response is an echo of the request. Request
Function code Request data length 1 Byte 1 Byte
0x15 0x07 to 0xF5
June 4, 2004
http://www.Modbus-IDA.org
34/51
Modbus-IDA
Response
Function code Response Data length Sub-Req. x, Reference Type Sub-Req. x, File Number Sub-Req. x, Record number Sub-Req. x, Record length Sub-Req. x, Record Data Sub-Req. x+1, ... 1 Byte 1 Byte 1 Byte 2 Bytes 2 Bytes 2 Bytes
N x 2 Bytes 0x15
Error
Error code Exception code 1 Byte 1 Byte
0x95
01 or 02 or 03 or 04 or 08
Here is an example of a request to write one group of references into remote device: The group consists of three registers in file 4, starting at register 7 (address 0007).
Request Field Name Function Request Data length Sub-Req. 1, Ref. Type Sub-Req. 1, File Number Hi Sub-Req. 1, File Number Lo Sub-Req. 1, Record number Hi Sub-Req. 1, Record number Lo (Hex) 15 0D 06 00 04 00 07 00 03 06 AF 04 BE 10 0D Response Field Name Function Request Data length Sub-Req. 1, Ref. Type Sub-Req. 1, File Number Hi Sub-Req. 1, File Number Lo Sub-Req. 1, Record number Hi Sub-Req. 1, Record number Lo Sub-Req. 1, Record length Hi Sub-Req. 1, Record length Lo Sub-Req. 1, Record Data Hi Sub-Req. 1, Record Data Lo Sub-Req. 1, Record Data Hi Sub-Req. 1, Record Data Lo Sub-Req. 1, Record Data Hi Sub-Req. 1, Reg. Data Lo (Hex) 15 0D 06 00 04 00 07 00 03 06 AF 04 BE 10 0D
1, 1, 1, 1, 1, 1, 1, 1,
Record length Hi Record length Lo Record Data Hi Record Data Lo Record Data Hi Record Data Lo Record Data Hi Reg. Data Lo
June 4, 2004
http://www.Modbus-IDA.org
35/51
Modbus-IDA
NO
Function code supported YES NO 0x07 Byte Count 0xF5 YES For each Sub-Req
ExceptionCode = 01
ExceptionCode = 03 NO
Reference Type == OK AND File Number == OK AND Record number == OK AND Starting Address + Register length == OK YES Request Processing
ExceptionCode = 02
NO W riteGeneralReference
== OK
ExceptionCode = 04
EXIT
This function code is used to modify the contents of a specified holding register using a combination of an AND mask, an OR mask, and the register's current contents. The function can be used to set or clear individual bits in the register. The request specifies the holding register to be written, the data to be used as the AND mask, and the data to be used as the OR mask. Registers are addressed starting at zero. Therefore registers 1-16 are addressed as 0-15. The functions algorithm is: Result = (Current Contents AND And_Mask) OR (Or_Mask AND (NOT And_Mask)) For example: Current Contents= And_Mask = Or_Mask = (NOT And_Mask)= Result =
Note :
Hex 12 F2 25 0D 17
Binary 0001 0010 1111 0010 0010 0101 0000 1101 0001 0111
If the Or_Mask value is zero, the result is simply the logical ANDing of the current contents and And_Mask. If the And_Mask value is zero, the result is equal to the Or_Mask value.
June 4, 2004
http://www.Modbus-IDA.org
36/51
Modbus-IDA
The contents of the register can be read with the Read Holding Registers function (function code 03). They could, however, be changed subsequently as the controller scans its user logic program.
The normal response is an echo of the request. The response is returned after the register has been written. Request
Function code Reference Address And_Mask Or_Mask 1 2 2 2 Byte Bytes Bytes Bytes
0x16 0x0000 to 0xFFFF 0x0000 to 0xFFFF 0x0000 to 0xFFFF
Response
Function code Reference Address And_Mask Or_Mask 1 2 2 2 Byte Bytes Bytes Bytes
0x16 0x0000 to 0xFFFF 0x0000 to 0xFFFF 0x0000 to 0xFFFF
Error
Error code Exception code 1 Byte 1 Byte
0x96 01 or 02 or 03 or 04
Here is an example of a Mask Write to register 5 in remote device, using the above mask values.
Request Field Name Function Reference address Hi Reference address Lo And_Mask Hi And_Mask Lo Or_Mask Hi Or_Mask Lo (Hex) 16 00 04 00 F2 00 25 Response Field Name Function Reference address Hi Reference address Lo And_Mask Hi And_Mask Lo Or_Mask Hi Or_Mask Lo (Hex) 16 00 04 00 F2 00 25
June 4, 2004
http://www.Modbus-IDA.org
37/51
Modbus-IDA
NO
ExceptionCode = 01
ExceptionCode = 02
NO
ExceptionCode = 03
NO MaskW riteRegister
== O K
ExceptionCode = 04
EXIT
Figure 26:
6.17
This function code performs a combination of one read operation and one write operation in a single MODBUS transaction. The write operation is performed before the read. Holding registers are addressed starting at zero. Therefore holding registers 1-16 are addressed in the PDU as 0-15. The request specifies the starting address and number of holding registers to be read as well as the starting address, number of holding registers, and the data to be written. The byte count specifies the number of bytes to follow in the write data field. The normal response contains the data from the group of registers that were read. The byte count field specifies the quantity of bytes to follow in the read data field. Request
Function code Read Starting Address Quantity to Read Write Starting Address Quantity to Write Write Byte Count Write Registers Value 1 Byte 2 Bytes 2 Bytes 2 Bytes 2 Bytes 1 Byte N *x 2 Bytes
0x17 0x0000 0x0001 0x0000 0x0001 2 x N*
to to to to
Modbus-IDA
Here is an example of a request to read six registers starting at register 4, and to write three registers starting at register 15:
Request Field Name Function Read Starting Address Hi Read Starting Address Lo Quantity to Read Hi Quantity to Read Lo Write Starting Address Hi Write Starting address Lo Quantity to Write Hi Quantity to Write Lo Write Byte Count Write Registers Value Hi Write Registers Value Lo Write Registers Value Hi Write Registers Value Lo Write Registers Value Hi Write Registers Value Lo (Hex) 17 00 03 00 06 00 0E 00 03 06 00 FF 00 FF 00 FF Response Field Name Function Byte Count Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers Read Registers (Hex) 17 0C 00 FE 0A CD 00 01 00 03 00 0D 00 FF
value value value value value value value value value value value value
Hi Lo Hi Lo Hi Lo Hi Lo Hi Lo Hi Lo
June 4, 2004
http://www.Modbus-IDA.org
39/51
Modbus-IDA
NO
Function code supported YES NO 0x0001 Quantity of Read 0x007D AND 0x0001 Quantity of Write 0x0079 AND Byte Count == Quantity of Write x 2 YES
ExceptionCode = 01
ExceptionCode = 03
NO
Read Starting Address == OK AND Read Starting Address + Quantity of Read == OK AND Write Starting Address == OK AND Write Starting Address + Quantity of Write == OK YES Request Processing Write operation before read operation NO Read/WriteMultipleRegisters == OK
ExceptionCode = 02
ExceptionCode = 04
EXIT
Figure 27:
June 4, 2004
http://www.Modbus-IDA.org
40/51
MODBUS Application Protocol Specification V1.1a 6.18 24 (0x18) Read FIFO Queue
Modbus-IDA
This function code allows to read the contents of a First-In-First-Out (FIFO) queue of register in a remote device. The function returns a count of the registers in the queue, followed by the queued data. Up to 32 registers can be read: the count, plus up to 31 queued data registers. The queue count register is returned first, followed by the queued data registers. The function reads the queue contents, but does not clear them. In a normal response, the byte count shows the quantity of bytes to follow, including the queue count bytes and value register bytes (but not including the error check field). The queue count is the quantity of data registers in the queue (not including the count register). If the queue count exceeds 31, an exception response is returned with an error code of 03 (Illegal Data Value). Request
Function code FIFO Pointer Address 1 Byte 2 Bytes
0x18 0x0000 to 0xFFFF
Response
Function code Byte Count FIFO Count FIFO Value Register 1 Byte 2 Bytes 2 Bytes N * x 2 Bytes
0x18 31
Here is an example of Read FIFO Queue request to remote device. The request is to read the queue starting at the pointer register 1246 (0x04DE):
Request Field Name Function FIFO Pointer Address Hi FIFO Pointer Address Lo (Hex) 18 04 DE Response Field Name Function Byte Count Hi Byte Count Lo FIFO Count Hi FIFO Count Lo FIFO Value Register FIFO Value Register FIFO Value Register FIFO Value Register (Hex) 18 00 06 00 02 01 B8 12 84
Hi Lo Hi Lo
In this example, the FIFO pointer register (1246 in the request) is returned with a queue count of 2. The two data registers follow the queue count. These are: 1247 (contents 440 decimal -- 0x01B8); and 1248 (contents 4740 -- 0x1284).
June 4, 2004
http://www.Modbus-IDA.org
41/51
Modbus-IDA
NO
Function code supported YES NO 0x0000 FIFO Pointer Address 0xFFFF YES NO FIFO Count 31 YES Request Processing
ExceptionCode = 01
ExceptionCode = 02
ExceptionCode = 03
NO ReadFIFOQueue
== OK
YES
ExceptionCode = 04
EXIT
Figure 28:
6.19
Informative Note: The user is asked to refer to Annex A (Informative) MODBUS RESERVED FUNCTION CODES, SUBCODES AND MEI TYPES. Function Code 43 and its MEI Type 14 for Device Identification is one of two Encapsulated Interface Transport currently available in this Specification. The following function codes and MEI Types shall not be part of this published Specification and these function codes and MEI Types are specifically reserved: 43/0-12 and 43/15-255. The MODBUS Encapsulated Interface (MEI)Transport is a mechanism for tunneling service requests and method invocations, as well as their returns, inside MODBUS PDUs. The primary feature of the MEI Transport is the encapsulation of method invocations or service requests that are part of a defined interface as well as method invocation returns or service responses.
June 4, 2004
http://www.Modbus-IDA.org
42/51
Modbus-IDA
Client Application
MEI Type X
MEI Type Y
MEI Type X
MEI Type Y
Network Interface
Network Interface
Network
Figure 29: MODBUS encapsulated Interface Transport
The Network Interface can be any communication stack used to send MODBUS PDUs, such as TCP/IP, or serial line. A MEI Type is a MODBUS Assigned Number and therefore will be unique, the value between 0 to 255 are Reserved according to Annex A (Informative) except for MEI Type 13 and MEI Type 14. The MEI Type is used by MEI Transport implementations to dispatch a method invocation to the indicated interface. Since the MEI Transport service is interface agnostic, any specific behavior or policy required by the interface must be provided by the interface, e.g. MEI transaction processing, MEI interface error handling, etc. Request
Function code MEI Type* MEI type specific data 1 Byte 1 Byte n Bytes
0x2B 0x0E
Error
Function code MEI Type Exception code 1 Byte 1 Byte 1 Byte
0xAB : Fc 0x2B + 0x80 0x0E 01, 02, 03, 04
As an example see Read device identification request. 6.20 43 / 13 (0x2B / 0x0D) CANopen General Reference Request and Response PDU
The CANopen General reference Command is an encapsulation of the services that will be used to access (read from or write to) the entries of a CAN-Open Device Object Dictionary as well as controlling and monitoring the server device, the CANopen system, and devices. The MEI Type 13 (0x0D) is a MODBUS Assigned Number licensed to CiA for the CANopen General Reference.
June 4, 2004
http://www.Modbus-IDA.org
43/51
Modbus-IDA
The system is intended to work within the limitations of existing MODBUS networks. Therefore, the information needed to query or modify the object dictionaries in the system is mapped into the format of a MODBUS message. The command will have the 256 Byte limitation in both the Request and the Response message. Informative: Please refer to Annex B for a reference to a specification that provides information on MEI Type 13. 6.21 43 / 14 (0x2B / 0x0E) Read Device Identification
This function code allows reading the identification and additional information relative to the physical and functional description of a remote device, only. The Read Device Identification interface is modeled as an address space composed of a set of addressable data elements. The data elements are called objects and an object Id identifies them. The interface consists of 3 categories of objects : Basic Device Identification. All objects of this category are mandatory : VendorName, Product code, and revision number. Regular Device Identification. In addition to Basic data objects, the device provides additional and optional identification and description data objects. All of the objects of this category are defined in the standard but their implementation is optional . Extended Device Identification. In addition to regular data objects, the device provides additional and optional identification and description private data about the physical device itself. All of these data are device dependent. Object Id 0x00 0x01 0x02 0x03 0x04 0x05 0x06 0x07 0x7F 0x80 0xFF Request
Function code MEI Type* Read Device ID code Object Id 1 Byte 1 Byte 1 Byte 1 Byte
0x2B 0x0E
Object Name / Description VendorName ProductCode MajorMinorRevision VendorUrl ProductName ModelName UserApplicationName Reserved Private objects may be optionally defined. The range [0x80 0xFF] is Product dependant.
Type ASCII ASCII ASCII ASCII ASCII ASCII ASCII String String String String String String String
M/O Mandatory Mandatory Mandatory Optional Optional Optional Optional Optional Optional
category Basic
Regular
device dependant
Extended
01 / 02 / 03 / 04 0x00 to 0xFF
01 / 02 / 03 / 04
00 / FF Object ID number
June 4, 2004
http://www.Modbus-IDA.org
44/51
Modbus-IDA
Error
Function code MEI Type Exception code 1 Byte 1 Byte 1 Byte
0xAB : Fc 0x2B + 0x80 0x0E 01, 02, 03, 04
Request parameters description : A MODBUS Encapsulated Interface assigned number 14 identifies the Read identification request. The parameter " Read Device ID code " allows to define four access types : 01: 02: 03: 04: request request request request to get the basic device identification (stream access) to get the regular device identification (stream access) to get the extended device identification (stream access) to get one specific identification object (individual access)
An exception code 03 is sent back in the response if the Read device ID code is illegal. In case of a response that does not fit into a single response, several transactions (request/response ) must be done. The Object Id byte gives the identification of the first object to obtain. For the first transaction, the client must set the Object Id to 0 to obtain the beginning of the device identification data. For the following transactions, the client must set the Object Id to the value returned by the server in its previous response. Remark : An object is indivisible, therefore any object must have a size consistent with the size of transaction response. If the Object Id does not match any known object, the server responds as if object 0 were pointed out (restart at the beginning). In case of an individual access: ReadDevId code 04, the Object Id in the request gives the identification of the object to obtain, and if the Object Id doesn't match to any known object, the server returns an exception response with exception code = 02 (Illegal data address). If the server device is asked for a description level ( readDevice Code )higher that its conformity level , It must respond in accordance with its actual conformity level. Response parameter description : Function code : Function code 43 (decimal) 0x2B (hex) MEI Type ReadDevId code : Conformity Level 14 (0x0E) MEI Type assigned number for Device Identification Interface Same as request ReadDevId code : 01, 02, 03 or 04 Identification conformity level of the device and type of supported access 01 : basic identification (stream access only) 02 : regular identification (stream access only) 03 : extended identification (stream access only) 81 : basic identification (stream access and individual access) 82 : regular identification (stream access and individual access) 83 : extended identification (stream access and individual access) In case of ReadDevId codes 01, 02 or 03 (stream access), If the identification data doesn't fit into a single response, several request/response transactions may be required. 00 : no more Object are available FF : other identification Object are available and further MODBUS transactions are required In case of ReadDevId code 04 (individual access), this field must be set to 00. If "MoreFollows = FF", identification of the next Object to be asked for. If "MoreFollows = 00", must be set to 00 (useless) http://www.Modbus-IDA.org 45/51
More Follows
MODBUS Application Protocol Specification V1.1a Number Of Objects Object0.Id Object0.Length Object0.Value ObjectN.Id ObjectN.Length ObjectN.Value Identification of the last Object (within the response) Length of the last Object in byte Value of the last Object (ObjectN.Length bytes) Number of identification Object returned in (for an individual access, Number Of Objects = 1)
Identification of the first Object returned in the PDU (stream access) or the requested Object (individual access) Length of the first Object in byte Value of the first Object (Object0.Length bytes)
Example of a Read Device Identification request for "Basic device identification" : In this example all information are sent in one response PDU.
Request Field Name Function MEI Type Read Dev Id code Object Id Value 2B 0E 01 00 Response Field Name Function MEI Type Read Dev Id Code Conformity Level More Follows NextObjectId Number Of Objects Object Id Object Length Object Value Object Id Object Length Object Value Object Id Object Length Object Value Value 2B 0E 01 01 00 00 03 00 16 " Company identification" 01 0D " Product code XX" 02 05 "V2.11"
In case of a device that required several transactions to send the response the following transactions is intiated. First transaction :
Request Field Name Function MEI Type Read Dev Id code Object Id Value 2B 0E 01 00 Response Field Name Function MEI Type Read Dev Id Code Conformity Level More Follows NextObjectId Number Of Objects Object Id Object Length Object Value Object Id Object Length Object Value Value 2B 0E 01 01 FF 02 03 00 16 " Company identification" 01 1C " Product code XXXXXXXXXXXXXXXX"
Second transaction :
Request Field Name Function MEI Type Read Dev Id code Object Id
Value 2B 0E 01 02
Response Field Name Function MEI Type Read Dev Id Code Conformity Level More Follows
Value 2B 0E 01 01 00
June 4, 2004
http://www.Modbus-IDA.org
46/51
Modbus-IDA
00 03 02 05 "V2.11"
ExceptiCode = 01
Except.Code = 02
EXIT
Figure 30:
June 4, 2004
http://www.Modbus-IDA.org
47/51
Modbus-IDA
When a client device sends a request to a server device it expects a normal response. One of four possible events can occur from the masters query: If the server device receives the request without a communication error, and can handle the query normally, it returns a normal response. If the server does not receive the request due to a communication error, no response is returned. The client program will eventually process a timeout condition for the request. If the server receives the request, but detects a communication error (parity, LRC, CRC, ...), no response is returned. The client program will eventually process a timeout condition for the request. If the server receives the request without a communication error, but cannot handle it (for example, if the request is to read a nonexistent output or register), the server will return an exception response informing the client of the nature of the error.
The exception response message has two fields that differentiate it from a normal response: Function Code Field: In a normal response, the server echoes the function code of the original request in the function code field of the response. All function codes have a most significant bit (MSB) of 0 (their values are all below 80 hexadecimal). In an exception response, the server sets the MSB of the function code to 1. This makes the function code value in an exception response exactly 80 hexadecimal higher than the value would be for a normal response. With the function codes MSB set, the client's application program can recognize the exception response and can examine the data field for the exception code. Data Field: In a normal response, the server may return data or statistics in the data field (any information that was requested in the request). In an exception response, the server returns an exception code in the data field. This defines the server condition that caused the exception. Example of a client request and server exception response
Request Field Name Function Starting Address Hi Starting Address Lo Quantity of Outputs Hi Quantity of Outputs Lo (Hex) 01 04 A1 00 01 Response Field Name Function Exception Code (Hex) 81 02
In this example, the client addresses a request to server device. The function code (01) is for a Read Output Status operation. It requests the status of the output at address 1245 (04A1 hex). Note that only that one output is to be read, as specified by the number of outputs field (0001). If the output address is nonexistent in the server device, the server will return the exception response with the exception code shown (02). This specifies an illegal data address for the slave. A listing of exception codes begins on the next page.
June 4, 2004
http://www.Modbus-IDA.org
48/51
Modbus-IDA
Code 01
02
03
04 05
06
08
0A
MODBUS Exception Codes Name Meaning The function code received in the query is not an ILLEGAL FUNCTION allowable action for the server (or slave). This may be because the function code is only applicable to newer devices, and was not implemented in the unit selected. It could also indicate that the server (or slave) is in the wrong state to process a request of this type, for example because it is unconfigured and is being asked to return register values. The data address received in the query is not an ILLEGAL DATA ADDRESS allowable address for the server (or slave). More specifically, the combination of reference number and transfer length is invalid. For a controller with 100 registers, a request with offset 96 and length 4 would succeed, a request with offset 96 and length 5 will generate exception 02. A value contained in the query data field is not an ILLEGAL DATA VALUE allowable value for server (or slave). This indicates a fault in the structure of the remainder of a complex request, such as that the implied length is incorrect. It specifically does NOT mean that a data item submitted for storage in a register has a value outside the expectation of the application program, since the MODBUS protocol is unaware of the significance of any particular value of any particular register. An unrecoverable error occurred while the server SLAVE DEVICE FAILURE (or slave) was attempting to perform the requested action. Specialized use in conjunction with programming ACKNOWLEDGE commands. The server (or slave) has accepted the request and is processing it, but a long duration of time will be required to do so. This response is returned to prevent a timeout error from occurring in the client (or master). The client (or master) can next issue a Poll Program Complete message to determine if processing is completed. Specialized use in conjunction with programming SLAVE DEVICE BUSY commands. The server (or slave) is engaged in processing a longduration program command. The client (or master) should retransmit the message later when the server (or slave) is free. Specialized use in conjunction with function codes MEMORY PARITY ERROR 20 and 21 and reference type 6, to indicate that the extended file area failed to pass a consistency check. The server (or slave) attempted to read record file, but detected a parity error in the memory. The client (or master) can retry the request, but service may be required on the server (or slave) device. Specialized use in conjunction with gateways, GATEWAY PATH UNAVAILABLE indicates that the gateway was unable to allocate an internal communication path from the input port to the output port for processing the request. http://www.Modbus-IDA.org 49/51
June 4, 2004
Modbus-IDA
0B
DEVICE
Usually means that the gateway is misconfigured or overloaded. Specialized use in conjunction with gateways, indicates that no response was obtained from the target device. Usually means that the device is not present on the network.
June 4, 2004
http://www.Modbus-IDA.org
50/51
Modbus-IDA
Annex A (Informative): MODBUS RESERVED FUNCTION CODES, SUBCODES AND MEI TYPES
The following function codes and subcodes shall not be part of this published Specification and these function codes and subcodes are specifically reserved. The format is function code/subcode or just function code where all the subcodes (0-255) are reserved: 8/19; 8/2165535, 9, 10, 13, 14, 41, 42, 90, 91, 125, 126 and 127. Function Code 43 and its MEI Type 14 for Device Identification and MEI Type 13 for CANopen General Reference Request and Reponse PDU are the currently available Encapsulated Interface Transports in this Specification. The following function codes and MEI Types shall not be part of this published Specification and these function codes and MEI Types are specifically reserved: 43/0-12 and 43/15-255. In this Specification, a User Defined Function code having the same or similar result as the Encapsulated Interface Transport is not supported. MODBUS is a registered trademark of Schneider Automation Inc.
June 4, 2004
http://www.Modbus-IDA.org
51/51