Annunciator Panel API - Series 90a Installation Manual2
Annunciator Panel API - Series 90a Installation Manual2
AMETEK POWER Instruments 255 N. Union Street Rochester, New York 14605
IMPORTANT NOTES
THOROUGHLY READ AND UNDERSTAND THE SAFETY SECTION BEFORE ATTEMPTING TO INSTALL AND ENERGIZE A SYSTEM ***** UNAUTHORIZED MODIFICATIONS OR REPAIRS WILL INVALIDATE THE AMETEK WARRANTY PLEASE CONTACT THE AMETEK CUSTOMER SERVICES DEPARTMENT BEFORE TAKING SUCH ACTIONS ***** STANDARD DEFAULT SETTINGS ARE INDICATED IN THIS MANUAL, TO WHICH SERIES 90A ANNUNCIATORS WILL BE SET SHOULD NO SPECIFIC CONFIGURATION OR SET UP DETAILS BE SUPPLIED WITH PURCHASE ORDERS
Table of Contents
PRODUCT OVERVIEW ................................................................................................................ 1 SAFETY..................................................................................................................................... 1 Construction .............................................................................................................................. 1 System Front View ................................................................................................................. 1 System Rear View ................................................................................................................. 1 Module Cell ............................................................................................................................ 2
Cell Assembly ................................................................................................................................................... 2 Module Cell Configurations ............................................................................................................................... 3 Annunciator Windows ....................................................................................................................................... 3
Annunciator Model Code Definition ........................................................................................... 4 SYSTEM CONFIGURATION AND SET-UP ................................................................................. 6 Hardware Configuration ............................................................................................................. 7
Field Contact Type ............................................................................................................................................ 7 Field Contact Voltage (FCV) ............................................................................................................................. 8 CSM Address .................................................................................................................................................. 10
I/O Module Configuration ..................................................................................................... 11 I/O Module Configuration ..................................................................................................... 12 Display Module .................................................................................................................... 13 Common Service Modules ................................................................................................... 14 Communication Modules ..................................................................................................... 15
Serial............................................................................................................................................................... 15 Ethernet .......................................................................................................................................................... 16
Ground Fault Detector Module ............................................................................................ 17 Power Supply Modules ........................................................................................................ 17 Field Contact Voltage Supply Modules ................................................................................ 18 IRIG-B Module ..................................................................................................................... 18 INSTALLATION .......................................................................................................................... 19 Mounting .................................................................................................................................. 19 Panel Mounting (option PM, PC) ......................................................................................... 19 19 Rack Mounting (option RK) ........................................................................................... 21 NEMA Enclosure (option N4, N4PB) ................................................................................... 22 Surface (Wall) Mounting (option S) ...................................................................................... 23 Weather Tight NEMA Front Cover (option NCB, NCT) ....................................................... 25 External Power Supply Mounting ......................................................................................... 29
120/230VAC Power Supply............................................................................................................................. 29 125VDC Power Supply ................................................................................................................................... 29
Wiring ...................................................................................................................................... 30 Input Wiring.......................................................................................................................... 30 Common Field Contact Voltage ........................................................................................... 30 Isolated Field Contact Voltage ............................................................................................. 31
Input / Relay Wiring for Full Size Windows (using one I/O Card) .................................................................... 32 Input/Relay Wiring For Half Size Windows (using one I/O Card) ................................................................... 33 Input/Relay Wiring For Half Size Windows (using one I/O Card) ................................................................... 34 Input Wiring with Half Size Windows (using two I/O Cards) ........................................................................... 35 Repeat Relay Wiring for Half Size Windows (using two I/O Cards)................................................................. 36 Input/Relay Wiring for Quad Size Windows (using two I/O Cards) .................................................................. 38 Common Service Cell Wiring (with Integral Pushbuttons) ............................................................................... 39 Common Service Wiring (with I/O Modules) .................................................................................................. 40
Connecting Power ................................................................................................................... 41 120/230 VAC & 125VDC Input Power ................................................................................. 41 Field Contact Voltage .......................................................................................................... 41 Power Requirements ............................................................................................................... 42 External AC supply: ............................................................................................................. 42
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 1
SOFTWARE CONFIGURATION ................................................................................................ 53 Application ............................................................................................................................... 53 Software Installation ................................................................................................................ 53 Software Configuration Instructions ........................................................................................ 54 Reviewing or editing the Factory Configuration ................................................................... 54 Creating a new Configuration .............................................................................................. 55 Software Configuration Menus ................................................................................................ 56 Main menu overview ............................................................................................................ 56
File Menu ........................................................................................................................................................56 Options Menu ..................................................................................................................................................56 View Menu ......................................................................................................................................................56 Connections Menu ..........................................................................................................................................56 Help Menu .......................................................................................................................................................56 File ..................................................................................................................................................................57 Options ............................................................................................................................................................59 View Configuration (Text) ................................................................................................................................60
DNP3.0 ................................................................................................................................ 83
Settings for Ethernet (Option ETH) .................................................................................................................83 Common DNP Configuration Settings .............................................................................................................84
SYSTEM SPECIFICATIONS ...................................................................................................... 87 Inputs....................................................................................................................................... 87 Display ................................................................................................................................. 87 Repeat Relay Outputs ......................................................................................................... 88 Alarm Sequence .................................................................................................................. 89 Controls ............................................................................................................................... 90 System Relays ..................................................................................................................... 90 Audible Devices ................................................................................................................... 90 Communications .................................................................................................................. 91 Time Stamped Alarms ......................................................................................................... 91 Power Requirements ........................................................................................................... 91 Mechanical .......................................................................................................................... 92 Connections / terminations .................................................................................................. 92 Environment ........................................................................................................................ 93 Electrical .............................................................................................................................. 93 Certifications ........................................................................................................................ 94
2 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Servicing .............................................................................................................................. 95 Module Removal ...................................................................................................................... 95 ESD ......................................................................................................................................... 96 APPENDIX A .............................................................................................................................. 97 Operational Sequences ........................................................................................................... 97 LEGEND ............................................................................................................................ 102 APPENDIX B ............................................................................................................................ 103 Modbus Data Formats ........................................................................................................... 103 Alarm State Mode .............................................................................................................. 103 Point Mode ......................................................................................................................... 104 AN3135 Mode .................................................................................................................... 105 Event Data ......................................................................................................................... 106 Modbus Addresses ............................................................................................................107 Default Values ................................................................................................................... 107 APPENDIX C ............................................................................................................................ 108 DNP Data Formats ................................................................................................................ 108 Device Profile Document ....................................................................................................... 108 Implementation Table ............................................................................................................ 109 Pushbutton Controls .............................................................................................................. 110 SERIES 90A Data Map ......................................................................................................... 111 Binary Inputs ...................................................................................................................... 111 Binary Input Change with Time (SER Option) ................................................................... 111 APPENDIX D ............................................................................................................................ 112 Window Assembly Details ..................................................................................................... 112 Window Legends ............................................................................................................... 112 Window Colors ................................................................................................................... 112 Window Assembly ............................................................................................................. 113 APPENDIX E ............................................................................................................................ 115 Telephone / Fax Number List ................................................................................................ 115 PROCEDURES FOR FACTORY REPAIR AND RETURN ....................................................... 117 Warranty ................................................................................................................................ 117
SCOPE
This manual describes the installation and configuration of the SERIES 90A annunciator system. This includes operation of its associated configuration software. Glossary of Terms Cell: Refers to a single module housing that can accommodate several boards. An Annunciator that is 3 rows high by 4 columns wide consists of 12 Cells. Refers to an individual electronic board. There are a variety of boards used in the Annunciator System for inputs, outputs, communications, etc. Normally Open. Contact state is open when normal, closes upon alarm. Normally Closed. Contact state is closed when normal, opens upon alarm. Typically refers to the relay coil state when normal. The coil de-energizes (voltage removed) when in alarm or while activated. Typically refers to the relay coil state when normal. The coil energizes (voltage applied) when in alarm or while activated. Type of relay contact, SPST (single pole, single throw). Open in the normal state, closes upon alarm or while activated. Type of relay contact, SPST (single pole, single throw). Closed in the normal state, opens upon alarm or while activated. Type of relay contact, SPDT (single pole, double throw). Open and closed contact with common pole. Both change state when in alarm or while activated. Field Contact Voltage. Field contact or wetting voltage for alarm inputs. Common Service Module. The CSM provides common alarm controls and output relays. Typically located in the bottom right cell. Input/Output. This refers to a board that accepts the customer Field Contact Inputs, provides outputs to the LED Display and can provide optional repeat relays.
PRODUCT OVERVIEW
SAFETY
The following safety symbols are used on the SERIES 90A:
Protective Earth Conductor Terminal The SERIES 90A is CE certified for operation under the following conditions: Indoor Use (unless mounted in NEMA-4 enclosure option) Altitude up to 2000 m Operating Temperature Range: Relative Humidity: Mains supply voltage fluctuations: Transient Over voltages: Category II) Pollution Degree 2 In product configurations with 125VDC or 120VAC Field Contact Voltage (options: D, DC, D/ISO, Y/ISO), the system must be equipped with the lockable front door (options NCB, NCT) or NEMA Enclosure (options N4, N4PB) Annunciator Model Code Definition on page 4. For FM option (refer to option codes), the required door may be supplied by Ametek, a panel shop or the customer. The door must meet the FM standard for requiring a tool to open or remove the door to allow access to the front of the Annunciator. Also, 120/230VAC & 125 VDC Input Power (options A, B, C) must use external power supplies, unless the front door or NEMA enclosure is used. All other product configurations can be installed in any enclosure as specified in the model number table, item 1. Installation and start-up must be carried out by trained and qualified personnel.
1
-20 TO 50 OC (-4 to 122OF) 20-95% RH +/- 10% of nominal 2500 V (Installation or Measurement
If the unit is not installed and operated as specified the protection provided by the unit may be impaired. Before start-up it is important to ensure that: Before start-up, it is important to ensure that: 1. 2. 3. 4. The unit can be switched off by a switch, or a circuit breaker, clearly marked as the disconnecting device for the unit. The minimum rating of the disconnecting device is: 5 Amps for 120 Vac or 230 Vac power 10 Amps for 24 or 48 VDC power The disconnecting device is located in close proximity to the unit and must be marked as the disconnecting device for the unit. The protective earth terminal is properly connected to protective earth. The line has been connected correctly and protection is provided against electric shock.
Proper ventilation is provided by at least 6 inches (15.25 cm) above and below the unit
CONSTRUCTION
The SERIES 90A is a modular design constructed from a matrix of cells up to 13 high by 13 wide. The cells can be configured for 1, 2, 3 or 4 points per cell. Each cell provides front access to the electronics and all wiring connections are made to the rear of the unit. Each cell can accept several modules in various combinations, consisting of I/O Cards, Common Service Modules, Power Supplies and Option Modules. The Common Service Module (CSM) is typically located at the lower right cell of the unit and the other cells are used for I/O.
SIL
ACK
CSM Cell
TEST RESET
Integral Pushbuttons
SYSTEM STATUS
FAIL
REMOTE COMM
GROUND FAULT
I/O Cell
I/O Cell
Module Cell
The Annunciator is a modular construction made from individual cells, allowing any size high or wide up to 13. All cards are removable from the front of the unit, after removing the window or pushbutton assembly.
Cell Assembly
7 5 1 9 3
8 10
6 13 11 14 12 4
Item # 1 2 3 4 5
Part Description Module Cell Window Divider Back-plane Housing Display Housing Rear Cell Housing
Item # 6 7 8 9 10
Part Description Display Board Back-plane Assembly Interconnect Board Module (see list) Row Interconnect Board
Item # 11 12 13 14
Available Modules:
2
Input / Output Module, with optional Repeat Relays LED Display Module Common Service Module & Sequential Events Recording CSM COMM Communication Module: Serial & Ethernet) PS Power Supply: Integral AC/DC Universal, Integral DC/DC FCV Supply Field Contact Voltage Supply: Integral AC/DC Universal IRIG-B Time Synchronization Input Module used for Sequential Events Recording Ground Fault Ground Fault Detector Module
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
I/O CELL
Front View
Note: Slot 5 of the I/O cell is also used for a row to row interconnect board (item #10 on cell assembly figure), which is installed for every row of the Annunciator. When installed; no other card or power supply can be inserted in that slot. All other unused slot 5 positions in that row can be used for power supplies or a ground detector. (This will be factory configured)
Annunciator Windows
The Annunciator windows come in four sizes as shown below. Legends can be laser printed on transparency film and inserted into the window frame. Colored filters are inserted behind the legends. Reference the appendix for additional details.
FULL SIZE WINDOW HALF SIZE WINDOWS THIRD SIZE WINDOWS QUAD SIZE WINDOWS
_____
Item 6 Active Points
_____
_____
_____
Item 9 Repeat Relay
_____
_____
_____
_____
Item 14 Options
_____
IMO
GF
RLY
Item 14 Options
ETH Ethernet Port (RJ-45 , T1 connection) SW (Used with Modbus or DNP Communication options. Must select option MB or DNP. Replaces RS232/485 Serial Port.) FR 1 msec Input Response (50 msec Standard) (This will capture alarms that last 1 msec or longer. If Time Stamping is required, select option SER instead) Time Stamping of alarms (4 ms resolution) (Each alarm is accompanied with a time stamp, containing point #, alarm state, time & date. The Time Stamp output can be selected as Serial ASCII Data to a printer or terminal [must select option SD], Modbus [must select option MB] or DNP [must select option DNP]. ) Time Stamping of alarms (1 ms resolution) (Each alarm is accompanied with a time stamp, containing point #, alarm state, time & date. The Time Stamp output can be selected as Serial ASCII Data to a printer or terminal [must select option SD], Modbus [must select option MB] or DNP [must select option DNP]. Option limited to 25 Cells) IRIG-B Time Sync Input (used with SER Option) (Standard BNC Input) STM FM HN AS
SER
FS
CE SERFR
IB
1 group 50 msec Non-Critical Form A Factory Configured Per Model Number De-Energized Follows Input Form A De-Energized Critical Horn & Non-Critical Horn None Selected RS-232 Out Master
CSM Functions
Energized or De-Energized Relays Repeat Relay Operation Auxiliary Contact Output Type (Form A, Form B) Auxiliary Contact Output Mode (Energized or De-Energized) Auxiliary Contact Output Operation (Horn, Reflash, Fault, Watchdog, Power Monitor, Ground Fault) Other system-wide functions
Serial RS-232 , RS-485 Communication RS-485 Termination Jumper Module Flash Synchronization (master/slave)
* NO/NC Field Inputs can be configured via the software or hardware, but not both. Choose one method only.
HARDWARE CONFIGURATION
Each Input/Output (I/O) module can accept up to two field contact inputs, with field contact voltage (FCV) provided either internally by the Annunciator or externally by the customer. Each input includes optical coupler isolation and can be selected for Normally Open (N/O) or Normally Closed (N/C) Field Contact Inputs through the software configuration or module jumpers. The I/O module provides outputs to the Display Module. Optional relays can be added to the I/O module for repeating the alarm status. Up to two I/O cards can be inserted into Card Slots 1 & 3 of a single cell for a maximum of 4 points per cell. The Cell with the Common Service Module can also support one I/O Module (in slot 3), in place of the Integral Pushbuttons. There are two versions of input modules. One version has headers and jumpers used to configure the FCV and the CSM address, while the other versions are designed with an input circuit capable of accepting an input range of 24vDC to 125vDC and use a rocker switch for the CSM Address. Both versions of the I/O module are configured via jumpers for: (NO/NC) and Form A, B, C Relay Contacts. Refer to the following table and to the part number affixed to the module to determine the type of module. Note that all modules in a systems shipped from the factory will contain the same type of configuration.
Repeat Relay Configuration Table Relay Operation Mode Repeat Relay Output Follows Input Contact State Relay Contact Status (shown in Normal State) OPEN OPEN (Form B) (Form A) Relay Coil Status (shown in Normal State) ENERGIZED DE-ENERGIZED ENERGIZED DE-ENERGIZED ENERGIZED DE-ENERGIZED ENERGIZED DE-ENERGIZED
CLOSED (Form A) CLOSED (Form B) Repeat Relay Output Latches on Alarm until Acknowledged or Reset OPEN OPEN (Form B) (Form A)
NOTE: Option FRC uses a Form C output, which is a SPDT (Single Pole Double Throw) contact. Option 2RR indicates two Repeat Relays for a single alarm input. (used with 1E & 2S Window Sizes) Jumpers P2,3,4 are used to select Form A, B and C modes. The options for the Relay Operation Mode and Relay Coil Status (normally energized or de-energized relays) are selected using the software configuration tool. (Reference the instruction manual section for Software Configuration.
CSM Address
Each I/O Module requires an address in order for communications to the CSM module. The Address settings are required for configuring any per point parameters and for mapping of serial communications. There are two versions of input modules using different methods of setting the address. Refer to Refer to Table-1 Module Types to determine which module is in your system. Older version
( Part numbers starting with 1085-)
The CSM address uses jumpers (J9) to indicate a binary address, starting at 0 and incrementing by one for every module in the system, from left to right, top to bottom. In cases where there is only one module per cell ( Window code 1E) the binary address will increment by two. Starting at 0 in the first cell, 2 in the second cell, 4 in the third cell etc. Zero is set when all jumpers are removed. Newer version
( Part numbers starting with 1087-)
The CSM address uses a rocker switch (SW1) to indicate a binary address, starting at 0 and incrementing by one for every module in the system, from left to right, top to bottom. In cases where there is only one module per cell ( Window code 1E) the binary address will increment by two. Starting at 0 in the first cell, 2 in the second cell, 4 in the third cell etc. Zero is set when all switches are set of off. NOTE: Care should be taken when removing and replacing I/O modules to insure that they are replaced into the cell from which they are removed. Failure to do so will result in out-of sequence address.
10
P1 FCV Selection
P5, 6 NO / NC Inputs
J9 Address Selection
(Configured at Factory)
11
C17
VR2 R23
C7
R7
Q2
R1
D5
RF1
1
R25
1
L1 RV1 L2
R2
RV3
R4 Q3 R8
C19
R3
P5, 6 NO / NC Inputs
1
C15 C16
R22
R52
R24
U7
R26
J2 D4 D6
J1
RV2 RF4
J8
R51
U10 R42
J6 1
C14
C23
L3
P13
2 R46 R44
D2
J7
C20
K1
CR1
C21
VR1
F1 P11
R41 R40 U1
Q1
C24
R32
R34
R39 C25
U3
D1
C13
1 P2
P4 1
P12 1 U9 P3
R50
1 K2
R16
RF2
P5 U6
P6 U8 1
C6
D3
C27 +
U11
R43
J4
C18
C8
U4
R20 7 R14 C12
C10
C3 C2 R13 C5 RF3 C4 C1
R15 R19
U5
R33
R29
R17 R18
R12 R9
0 1 2 3 4 5 6 7
SW1
C9
1 J5
R21
J3
MSB Spare
LSB
P2,P3,P4: RELAY OUTPUT SELECTION FORM A (N.O.) RELAY #1: P2 P3 P4 FORM B (N.C.) P2 P3 P4 FORM C (SPDT) P2 N/A P4
RELAY #2:
12
Display Module
The Display Module provides the LED indication for up to 4 window sizes (Full Size, Half, Third and Quad). Each display module plugs into one or two I/O cards, depending on the window size and input quantities. There are several variations of display modules as noted by the window size in the model number: Version
1 2 3 4
4 Point and all options shown for reference Not all configurations have all of the displayed components.
13
14
Communication Modules
The optional Communication Modules plug directly into the CSM Module through card slot 2 and provide either a serial or Ethernet output. Only one Communication Module per CSM is allowed.
Serial
The Serial Communication Module provides RS-232/485 serial data output or inputs via Modbus or DNP protocols. When used with the SER CSM, it can be used to provide an output of time stamped alarms in ASCII format in addition to Modbus or DNP. The Serial Communication Module can be configured via jumpers for RS-232/485 communications. It can be configured via software for all Modbus and DNP settings.
RS-485 TERMINATOR J2 RS-232/RS-485 SELECTION J5 RS-232 RS-485
15
Ethernet
The Ethernet Communication Module has no configuration jumpers. When installed this module is mounted onto the Common Service module and together they are installed in slot 1 and 2,
16
24V
48V
125V
17
IRIG-B Module
The optional IRIG-B Module is used for External time synchronization of the SER Option. This must be installed in Card Slot 5 of the CSM Cell. (When used, the Integral Power Supply must be moved to a different cell.)
JP1, JP2
AC/DC 1 2 3
Jumper Position
JP1 JP2 JP1 JP2 1 1 1 1 2 2 2 2 3 3 3 3
INPUT TYPE
Modulated(AC) Demodulated (DC)
18
INSTALLATION
MOUNTING
The system is designed for Panel Mounting and 19 Rack Mounting, Other mounting methods such as NEMA Enclosures and Surface or Wall Mounting will have additional details and drawings provided by the factory. Caution must be exercised when installing this, or any other type of equipment into racks or panels. Ensure that all equipment is properly secured using the specified hardware in accordance with equipment manufacturers specifications.
The dimensions given in the tables below refer to the size of the panel cut out required for mounting and the front bezel height and width. The height and width are related to the number of cells in the system. Dimensions shown are in inches (mm).
# of Cells High
1 2 3 4 5 6 7 8 9 10 11
# of Cells Wide
--2 3 4 5 6 7 8 9 10 11
12
13
12
13
43.16 (1096)
46.63 (1184)
42.22 (1072)
45.69 (1161)
19
Example: A 3H x 4W Annunciator has a cutout height of 11.0 and a cutout width of 14.47. Annunciator Depth (Behind Panel) Maximum depth w/out rear cover Maximum depth w/ rear cover Inches 6.75 10.00 Mm 171 254
Minimum mounting panel thickness: 18 GA Galvanneal, 0.072 inches, 1.83 mm. For system installation perform the following steps: 1 Mark cutout dimensions on the surface where the annunciator is to be mounted, keeping in mind that the assembly may rest on the sill of the cutout. NOTE: Allow a minimum of 6 inches (150 mm) above the unit and behind the panel for proper ventilation. 2 3 Cut out and remove panel material. Temporally remove the panel mounting clamps and Install the annunciator assembly through the panel cut-out (from the front of the panel). Position the annunciator within the cut-out so that the weight is taken at the bottom of the unit. From the rear of the panel, replace the annunciator mounting clamps along the bottom then top and sides screws to finger tight check the front of panel alignment on panel face etc Fully tighten the mounting clamps.
20
For system installation, perform the following steps: Allow a minimum of 6 inches (150 mm) above the unit and behind the panel for proper ventilation. 1 Slide the annunciator assembly into the rack (from the front of the rack). 2 Secure using the recommended fixing screws into the rack mount rails.
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 21
Side view
'E'
Optional Horn, Not available on all sizes)
10.00
'B'
'K'
1.50
'J'
PART # 1 or 2 H X 3 or 4W 1 or 2 H X 5 or 6W 1 or 2 H X 7 or 8W 3 or 4 H X 3 or 4W 3 or 4 H X 5 or 6W 3 or 4 H X 7 or 8W 5 or 6 H X 3 or 4W 5 or 6H X 5 or 6W 5 or 6H X 7 or 8W
16.00 22.00 16.00 30.00 16.00 36.00 24.00 22.00 24.00 30.00 24.00 36.00 32.00 22.00 32.00 30.00 32.00 36.00
7.09 14.25 3.25 14.25 12.13 4.63 7.09 14.25 4.31 21.19 12.13 4.63
6.75 14.25 3.47 28.03 19.63 4.63 8.15 21.19 8.15 21.19 7.75 21.19 3.25 14.25 12.13 4.63 4.31 21.19 12.13 4.63
22
Refer to the following chart and the figures on the following page for mounting dimensions. ANNUNCIATOR SIZE Dimension
A B C D E F G H 1H 3.65 4.93 0.40 1.90 ------------------2.23 2H 7.12 8.40 1.12 4.59 ------------------5.70 3H 10.59 11.87 1.12 4.59 8.05 ------------9.17 4H 14.06 15.34 1.12 4.59 8.05 11.52 12.64 5H 17.53 18.81 1.12 4.59 8.05 11.52 14.99 16.11 2W 3W 4W 5W
Dimension
J K L
23
1.620
1.620
G F E D
9.93 8.87
1.5
Right side
#6 CUP WASHER
24
25
.50 TYP
.50
2.19 TYP
clips shown for NCB option Only one clip, centered, for NCT option
F
D
# OF CELLS HIGH 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3
# OF CELLS WIDE 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10
DIM A 8.38 8.38 8.38 8.38 8.38 8.38 8.38 8.38 8.38 11.84 11.84 11.84 11.84 11.84 11.84 11.84 11.84 11.84 15.31 15.31 15.31 15.31 15.31 15.31 15.31 15.31 15.31
DIM B 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59
DIM C 7.38 7.38 7.38 7.38 7.38 7.38 7.38 7.38 7.38 10.84 10.84 10.84 10.84 10.84 10.84 10.84 10.84 10.84 14.31 14.31 14.31 14.31 14.31 14.31 14.31 14.31 14.31
DIM D 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59
DIM E 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 4.00 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 7.47 10.94 10.94 10.94 10.94 10.94 10.94 10.94 10.94 10.94
DIM F 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22
26
# OF CELLS HIGH 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 6 6 6 6 6 6 6 6 6 7 7 7 7 7 7 7 7 7 8 8 8 8 8 8 8 8 8 9 9 9 9 9 9 9 9
# OF CELLS WIDE 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9
DIM A 18.78 18.78 18.78 18.78 18.78 18.78 18.78 18.78 18.78 22.25 22.25 22.25 22.25 22.25 22.25 22.25 22.25 22.25 25.72 25.72 25.72 25.72 25.72 25.72 25.72 25.72 25.72 29.19 29.19 29.19 29.19 29.19 29.19 29.19 29.19 29.19 32.66 32.66 32.66 32.66 32.66 32.66 32.66 32.66 32.66 36.13 36.13 36.13 36.13 36.13 36.13 36.13 36.13
DIM B 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59 11.84 15.31 18.78 22.25 25.72 29.19 32.66 36.13
DIM C 17.78 17.78 17.78 17.78 17.78 17.78 17.78 17.78 17.78 21.25 21.25 21.25 21.25 21.25 21.25 21.25 21.25 21.25 24.72 24.72 24.72 24.72 24.72 24.72 24.72 24.72 24.72 28.19 28.19 28.19 28.19 28.19 28.19 28.19 28.19 28.19 31.66 31.66 31.66 31.66 31.66 31.66 31.66 31.66 31.66 35.13 35.13 35.13 35.13 35.13 35.13 35.13 35.13
DIM D 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59 10.84 14.31 17.78 21.25 24.72 28.19 31.66 35.13
DIM E 14.41 14.41 14.41 14.41 14.41 14.41 14.41 14.41 14.41 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 17.88 21.34 21.34 21.34 21.34 21.34 21.34 21.34 21.34 21.34 24.81 24.81 24.81 24.81 24.81 24.81 24.81 24.81 24.81 28.28 28.28 28.28 28.28 28.28 28.28 28.28 28.28 28.28 31.75 31.75 31.75 31.75 31.75 31.75 31.75 31.75
DIM F 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22 7.47 10.94 14.41 17.88 21.34 24.81 28.28 31.75
27
# OF CELLS HIGH 9 10 10 10 10 10 10 10 10 10
# OF CELLS WIDE 10 2 3 4 5 6 7 8 9 10
DIM A 36.13 102 39.59 39.59 39.59 39.59 39.59 39.59 39.59 39.59
DIM B 39.59 102 15.31 18.78 22.25 25.72 29.19 32.66 36.13 39.59
DIM C 35.13 102 38.59 38.59 38.59 38.59 38.59 38.59 38.59 38.59
DIM D 38.59 102 14.31 17.78 21.25 24.72 28.19 31.66 35.13 38.59
DIM E 31.75 102 35.22 35.22 35.22 35.22 35.22 35.22 35.22 35.22
DIM F 35.22 102 10.94 14.41 17.88 21.34 24.81 28.28 31.75 35.22
28
29
WIRING
All wiring connections are made to the rear of the unit using barrier style terminal blocks. All Field Contact Inputs, Relay Outputs and Power Connections are made to Terminal Blocks that have a #6 screw, which will accept a solid or stranded wire from 12-22 AWG, with or without ring & spade lugs. The Pushbutton Controls and Flash Synchronization connections are made to Terminal Blocks that have a #6 screw which will accept a solid or stranded wire from 14-22 AWG, with or without ring & spade lugs. Ensure that a proper earth ground connection is made to the protective earth ground stud.
Note for Relay Output Wiring: When option RR (Repeat relay) is installed, and 120 Vac is switched by the contact. All output wiring in any individual cell must be wired to the same phase of the service.
Input Wiring
The input wiring is determined by the number of alarms (or windows per cell) and the number of I/O Cards. The available configurations are:
FULL SIZE WINDOW
(1 MODULE)
1 1 2
1 2 3
1 3
2 4
The I/O cards can support up to two inputs, however, certain options limit that to one input per card as shown with the Half Size Window above.
31
TB1
1 2 3 4 5 6 7 8
Power Supply Terminal Block (only used with Integral Power Supplies)
2 3 4 5
(Front View)
+(L) -(N)
TB1
Input 1 + FCV
1 2 3 4
TB1
Input 1 - FCV
1 2 3 4
Option RR Single Repeat Relay Per Input (Form A or B) Option 2RR Two Repeat Relays Per Input (Form A or B)
5 6 7 8
5 6 7 8
32
Input/Relay Wiring For Half Size Windows (using one I/O Card)
Model Code Window Size 2
TB5
1
TB1
1 2 3 4 5 6 7 8
Power Supply Terminal Block (only used with Integral Power Supplies)
2 3 4 5
(Front View)
INPUT WIRING
Common FCV
TB1
Input 1
+ FCV 1 2 3 4 5 6 7 8 Customer Field Contact
INPUT WIRING
Isolated FCV
TB1
Input 1 - FCV Input 2 - FCV
1 2 3 4 5 6 7 8 +(L) -(N) +(L) -(N)
24,48,125 VDC 120VAC, 60Hz Customer FCV 24,48,125 VDC 120VAC, 60Hz Customer FCV
Input 2
+ FCV
+ FCV is internally bussed throughout the system to all TB1 Terminal Blocks.
TB1
Input 1 + FCV
1 2 3 4 5
6 7 8
33
Input/Relay Wiring For Half Size Windows (using one I/O Card)
Model Code Window Size 2E
TB5 TB2
1 1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7 8
Terminal Block TB2. No connections. E Option: Used for expanding up to 4
Power Supply Terminal Block (only used with Integral Power Supplies)
2 3 4 5
Input/Relay
(Front View)
INPUT WIRING
Common FCV
TB1
Input 1
+ FCV 1 2 3 4 5 6 7 8 Customer Field Contact
INPUT WIRING
Isolated FCV
TB1
Input 1 - FCV Input 2 - FCV
1 2 3 4 5 6 7 8 +(L) -(N) +(L) -(N)
24,48,125 VDC 120VAC, 60Hz Customer FCV 24,48,125 VDC 120VAC, 60Hz Customer FCV
Input 2
+ FCV
+ FCV is internally bussed throughout the system to all TB1 Terminal Blocks.
TB1
Input 1 + FCV
1 2 3 4 5
6 7 8
34
TB1
1 2 3 4 5 6 7 8
Power Supply Terminal Block (only used with Integral Power Supplies)
2 3 4 5
(Front View)
INPUT WIRING
Common FCV
TB2
Input 2 + FCV
1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7
INPUT WIRING
Isolated FCV
Customer Field Contact +(L) -(N) 24,48,125 VDC 120VAC, 60Hz Customer FCV Input 1 - FCV
8 Customer
Field Contact
TB2
Input 2 - FCV
1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7 8
+(L) -(N)
35
Repeat Relay Wiring for Half Size Windows (using two I/O Cards)
TB1
1 2 3 4 5 6 7 8
2 3 4 5
(Front View)
TB2
Input 2 FCV
1 2 3 4
TB1
1 2 3 4
Option RR Single Repeat Relay Per Input (Form A or B) Option 2RR Two Repeat Relays Per Input (Form A or B)
5 6 7 8
Option RR Single Repeat Relay Per Input (Form A or B) Option 2RR Two Repeat Relays Per Input (Form A or B)
5 6 7 8
TB2
1 2 3 4 5 6 7 8
TB1
Option FRC
Input 1 FCV
1 2 3 4 5
6 7 8
36
Input/Relay Wiring for Third Size Windows (using two I/O Cards)
TB1
1 2 3 4 5 6 7 8
(Front View)
INPUT WIRING
Common FCV
TB2
Input 3 + FCV + FCV is internally bussed throughout the system to all TB1-2 Terminal Blocks. (reference power supply wiring for main FCV connections)
1 2 3 4 5 6 7 8 Customer Field Contact
TB1
Input 1 + FCV Input 2 + FCV
1 2 3 4 5 6 7 8
INPUT WIRING
Isolated FCV
TB2
Input 3 - FCV
1 2 3 4 5 6 7 8
Customer Field Contact +(L) -(N) 12, 24, 48, 125 VDC 120VAC, 60Hz Customer FCV Input 1 - FCV Input 2 - FCV
TB1
1 2 3 4 5 6 7 8
Customer Field Contact +(L) -(N) +(L) -(N) 12,24,48,125 VDC 120VAC, 60Hz Customer FCV 12,24,48,125 VDC 120VAC, 60Hz Customer FCV
TB1
Input 1 - FCV Input 2 - FCV Option RR Single Repeat Relay Per Input (Form A or B) Option RR Single Repeat Relay Per Input (Form A or B)
1 2 3 4 5 6 7 8
37
TB2
1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7 8
(Front View)
INPUT WIRING
Common FCV
TB2
Input 3 + FCV Input 4
+ FCV 1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7 8
+ FCV is internally bussed throughout the system to all TB1-2 Terminal Blocks. (reference power supply wiring for main FCV connections)
INPUT WIRING
Isolated FCV
TB2
Input 3 - FCV Input 4 - FCV
1 2 3 4 5 6 7 8
Customer Field Contact +(L) -(N) +(L) -(N) 12,24,48,125 VDC 120VAC, 60Hz Customer FCV 12,24,48,125 VDC 120VAC, 60Hz Customer FCV Input 1 - FCV Input 2 - FCV
Customer
TB1
1 2 3 4 5 6 7 8
12,24,48,125 VDC 120VAC, 60Hz Customer FCV 12,24,48,125 VDC 120VAC, 60Hz Customer FCV
TB2
Input 3 - FCV Input 4 - FCV 1 2 3 4 5 6 7 8
TB1
1 2 3 4 5 6 7 8
Option RR Single Repeat Relay Per Input (Form A or B) Option RR Single Repeat Relay Per Input (Form A or B)
38
TB5
1 2 3 4 5 J2 J1
TB4
1 2 3 4 5 6 7
TB3
1 2 3 4 5 6 7 8
SIL
ACK
TEST
RESET
J3
SYSTEM STATUS
FAIL
REMOTE COMM
GROUND FAULT
(front view)
(rear view)
CSM WIRING
Common Service Relay Wiring
TB3
CSM Relay #1 (Form A or B) CSM Relay #2 (Form A or B) CSM Relay #3 (Form A or B) CSm Relay #4 (Form A or B)
1 2 3 4 5 6 7 8
Customer Pushbuttons
CSM Relay K2
Option RLY
Note: TB4-7 can be used as a second Configurable Input when the LED Flash Synchronization Option is not used.
RS-485
TX/RX TX/RX + Ground
Customer Power Input 24, 48 125 VDC 120/240 VAC, 50/60HZ Field Contact Voltage (FCV) 24, 48, 125 VDC 120 VAC, 60HZ (no connection required if the FVC is supplied through the Intergral Power Supply)
+ E
1 2 3 4 5 6 7 8 9
BNC Connector
RJ 45 Connector
J3
J2
IRIG-B
Ethernet
NOTE: When wiring an external horn or other audible device to the CSM output relays, it is recommended that the interconnect wires be physically isolated from any other input or output wiring.
39
(1 I/O Card)
OR
TB4
1 2 3 4 5 6 7 8
TB3
1 2 3 4 5 6 7 8
(rear view)
1 2 3 4 5 6 7 8
Customer Pushbuttons
CSM Relay K2
Option RLY
Configurable Input
Note: TB4-7 can be used as a second Configurable Input when the LED Flash Synchronization Option is not used.
Communications Wiring
RS-232 RS-485
TX/RX TX/RX + Ground
Connector DB9 (F) Shown w/Isolated FCV 24,48,125 VDC J1 120VAC, 60Hz
Customer FCV
1 2 3 4 5 6 7 8 9
RJ 45 Connector
J2
Ethernet
NOTE: When wiring an external horn or other audible device to the CSM output relays, it is recommended that the interconnect wires be physically isolated from any other input or output wiring.
40 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
CONNECTING POWER
The SERIES 90A Annunciator operates from a selection of AC and DC Voltages. The Annunciator uses Power Supplies to provide the necessary 5VDC Logic and LED Power. If the Field Contact Voltage (FCV) needs to be provided from the Annunciator, separate FCV Supplies are provided. For 24 and 48 VDC Input Power, an Integral Power Supply will always be used. In some cases, multiple supplies will be located in the system to accommodate the quantity of inputs specified. For 120/230 VAC and 125 VDC Input Power, the quantity of inputs, window sizes and other options determines whether the Power supplies can be self contained within the Annunciator (Integral Power Supply) or external to the Annunciator.
The Field Contact Voltage (FCV) can be provided externally by the user or can be provided by the Field Contact Voltage Supply.
41
POWER REQUIREMENTS
External AC supply:
(Watts @ Annunciator power input per point)
Annunciator Window Size Full (1 per Cell) Half (2 per Cell) Third (3 per Cell) Quad (4 per Cell) I/O Cards with Repeat Relays 1.7 1.0 0.7 0.7 I/O Cards with no Repeat Relays 1.4 0.7 0.4 0.4
Integral AC supply:
(Watts @ Annunciator power input per point)
Annunciator Window Size Full (1 per Cell) Half (2 per Cell) Third (3 per Cell) Quad (4 per Cell) I/O Cards with Repeat Relays 2.2 1.3 1.0 0.9 I/O Cards with no Repeat Relays 1.8 0.8 0.5 0.5
42
Based on the size of the system, there could be several integral power supplies within the Annunciator. The location of integral power supplies within the Annunciator can be noted by the five position terminal block, TB5.
43
Systems that exceed these quantities shall use an External Power Supply.
44
Systems that exceed these quantities shall use an External Power Supply.
+
P1 6 T3 CR5 1 1
C4
F1 R9 Q6 R10
Q5
L1
PS1 PS2
CR6
R3
P12
R4
aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa aaaaaaaaaaaaaaaaaaaaaaaaaaaaaaa
+
BR3
R2
F2 R1 C20 R5
45
(Rear View)
(Rear View)
(Rear View)
120/240 VAC 50/60 Hz Power Input 24, 48 OR 125VDC FCV Field Contact Voltage
46
Quantity of Inputs per FCV Supply Systems that exceed these quantities can use multiple integral FCV Supplies
47
Note: In order to maintain a UL listing or CE Certification, any customer power supply used to provide 24VDC or 48VDC to the Annunciator shall be UL recognized or CE Certified, and provide basic insulation.
48
(Rear View)
(Rear View)
(Rear View)
49
For Field Contact Voltage, 24VDC can be derived from the External Power Supply 24VDC Output. For 125VDC, the Integral 24VDC Supply will be used. 120/230VAC
125VDC
+ + - -
Phoenix Quint-PS-100
L NE
+ + - -
TB5 24 VDC Power Input 24, 48 OR 125 VDC FCV (internally bussed to TB1,TB2 - 2 & 4) + + 1 2 3 4 5
Phoenix Quint-PS-100
L NE
+ E
51
L N E
6 5 4 3 2 7 1
L N E
6 5 4 3 2 7 1
Meanwell S-150
52
SOFTWARE CONFIGURATION
APPLICATION
The SERIES 90A Annunciator Configurator application is used to create, edit and download annunciator configurations from a PC. The PC Comm Port connects directly to the annunciator via a serial port on the front of the CSM module. A configuration may be created on the PC without a connection to the annunciator and then downloaded later. The configuration information is held as a file on the PC, which may be edited if a change is required. An exception to this is the physical size of the annunciator, which includes the number of input modules, and the size of each module, which is factory configured. If a configuration is edited, checks are made to ensure that the correct file is downloaded to the annunciator. If more than one version of the SERIES 90A configuration software is used then more than one version of the configuration file can exist. It is up to the user to ensure that copies of the configuration are kept up to date. If the application detects that the local and remote copies of a configuration are different the user can update either. The application also includes a function to enable the configurable options in the annunciator, such as Modbus and DNP communications.
SOFTWARE INSTALLATION
The SERIES 90A configuration software should be installed onto a PC with the following minimum configuration: 300MHz Pentium II CPU Windows 98/2000/XP 64Mbytes RAM 20Gbytes hard disk Insert the AMETEK SERIES 90A Configuration CD in the CD-ROM drive. This will automatically start the installation process. If this does not happen choose Run from the Start menu then browse to the CD-ROM drive and click on Autorun.exe. During the installation, you will be prompted to select the type of Annunciator you wish to configure. Select only the models you wish to use to avoid confusion with extra choices.
53
prompted. Select Connections, Configuration, Write Configuration. When it is complete, select Connection, Disconnect. Press the TEST pushbutton to verify that everything is functioning correctly.
55
File Menu
The program manages configuration files through the File Menu. From this menu, you can open, save, and delete configuration files. The File Menu also provides you access to a new "default" configuration as a point of reference.
Options Menu
This menu provides functionality to alter the way your program behaves and appears.
View Menu
Here you can select what you see in main window. Status bar, Tool bar etc.
Connections Menu
Connections menu performs the actual communication with the annunciator to download or retrieve configurations.
Help Menu
The Annunciator Configurator is equipped with a Help Menu to provide the user with assistance for each screen and program function.
56
File
In the File menu you will find the following menu options: New Clicking on this will create and open a new configuration. As only one configuration can be open at a time, any previous configuration that is open will be closed. You will be prompted to save any changes before the configuration is closed. New configurations are set to the defaults. Open Here you can browse available locations on your system to open existing configuration files. (file extension "anc").
Save Allows you to save the active configuration file. If the configuration file has already been saved, it will automatically write over the old version. Save As Allows you to save the active configuration file. When clicked, it will ask you for a filename before proceeding. If the filename already exists, it will ask you if you want to overwrite the old version.
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 57
Create Duplicate This will create and open a new configuration file; the parameters will be copied from the active (open) configuration and not set to defaults. This allows the same configuration settings to be downloaded to two annunciators. Print This allows you to print the configuration in a text form so that you can see all the parameters. The printout is marked with the time and date of printing. Print Setup This allows you to change your printer settings. Start Wizard This will start the configuration wizard, which will guide you through a set of screens to simply setup your annunciator. Recent Files At the bottom of the file menu, you will also find a list of you most recent configuration files. You can simply click on one of these to open it.
58
Options
Preferences In the preferences menu you can change the color setup of the whole application, and tell the program how you want the wizard to behave. View Configuration This is a textual overview of the complete configuration. Upgrade This menu option will allow you to add extra functionality to your annunciator and the configurator. Preferences
Colors The colors used to indicate various selections used in the configuration software may be changed. This may be required if they conflict with colors used in the Windows desktop. For most installations the default colors will be acceptable. To change a color first select its usage from the list then click on Change Color and select the new choice from the palate. General If the box beside "Start wizard when opening file" is checked, the wizard will automatically appear every time a new or existing document is opened. As the last open configuration is loaded when the application starts it means that the wizard will also automatically start at this point.
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 59
Copy to clipboard You can use the mouse to select a portion of the configuration and then copy the selection to the clipboard so you can paste it into other documents. If you do not select any text the whole configuration is then copied. Print This will print the complete configuration. Upgrade
The application also includes a function to enable the configurable options in the annunciator. One such is Modbus communications. To enable any of these options you must contact AMETEK Power Instruments with your annunciator serial number that you will find in the Upgrade dialog. You will be given a unique key, which you must type into the box (shown above) and then click upgrade. If you are connected to an annunciator the upgrade will be performed right away. If you are not connected then you must save the configuration and upload it at a later date.
60 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Note: To successfully obtain the serial number of the annunciator you must have uploaded the configuration at least once. If the configuration has never been uploaded to an annunciator you will get the following message where your serial ID should be. "This configuration has not been uploaded to an annunciator." Connections
Connect & Disconnect From the connections menu you will be able to connect to or disconnect from your annunciator using the Connect and Disconnect menu options. Configuration Once you have successfully connected to your annunciator you will be able to select the Configuration menu option. This will allow you to read and write configurations to and from the annunciator. Settings Here you change your computer's settings to tell it how to connect to your annunciator. N.B. The annunciator functions will not operate while the configurator is connected to the SERIES 90A. Configuration
Read Configuration This copies the configuration from the annunciator into the active configuration. It is recommended that you save any configuration changes before reading a configuration. If you wish to discard your changes you can open another document or close the application opting not to save.
61
Write Configuration This will copy the active configuration to the annunciator. It is recommended that you save any configuration changes before writing to the annunciator. Note: When a configuration is written to an annunciator the file is, from then on associated with that specific annunciator. As a result of this association, on subsequent sessions there are certain configuration options, which will be disabled. They are listed below. System Name Number of rows Number of columns Alarms per module Number of hardwired inputs Input delay resolution They can only be changed when creating a New Configuration. Note: Changing the system size or window style to something different than your actual Annunciator can cause problems. Communication Settings From this dialog you can select the Com port wish to use to connect and the baud rate and parity of the connection, and the address of the annunciator. These values are stored independently of the annunciator hence care must taken be as if you have more that one annunciator they may not all have the same settings.
Connect Status This option can be used when connected to retrieve the serial ID, the Hardware version and the system description. When nothing is connected the menu option is disabled. This can be used as an indicator to a successful connection.
62
Configuration Mismatch
When you connect to an annunciator the program checks to see if the active file was the last configuration to be downloaded to the annunciator, if this is not the case then the message shown above will be displayed. A Configuration mismatch may occur as a result of the following: 1) You have opened the wrong configuration file. 2) Someone else has downloaded a different configuration to the annunciator. If you choose the first option "Download configuration from annunciator" this will copy the configuration from the annunciator in to the active file. If you choose the second option "Overwrite configuration on annunciator with configuration....." this will copy the configuration in the active file to the annunciator. In the case of a configuration mismatch it is recommended that you select the first option and then save this configuration to another location as a backup.
63
Serial ID Mismatch
A serial ID mismatch occurs when you try to upload a configuration that has already been uploaded to another annunciator. When you upload a configuration, a note is kept of which annunciator it "belongs to". Every time you connect to an annunciator the stored serial ID is checked to make sure that it matches the annunciator you are connected to. In the case of a serial ID mismatch if you hit continue you will be able to read the configuration from the annunciator but you will not be able to write the active one to the annunciator. To rectify this situation you should click "No" and then open the correct configuration file, or create a new configuration.
64
Configuration Wizard
The configuration of an SERIES 90A is defined in a number of sections, which are displayed on separate pages. The pages may be selected by clicking on the labeled tabs at the top of each page. When a system is configured for the first time the Next >> button may be used to move through all the sections. This will ensure that no sections are missed. The << Back button may be used to go to the previous page if required. A graphical representation of the annunciator is used to simplify the configuration. This mimic diagram may be given the same window colors as the actual unit to make correct input selection easy. Individual or groups of inputs or modules can be selected by clicking on them. (To select a group of inputs, select an input with the mouse and hold & drag across other cells. You can also use the Ctrl key to pick a group of inputs.) The Configuration Wizard Screens and their functions are detailed below: System: Used to configure System Size (High x Wide), Window size per cell and other system-wide features. Once configured and downloaded it will be locked to prevent any further changes. Input Configuration: Used to select individual settings per input, such as input delays, repeat relay operation, critical/non-critical alarms, alarm sequence groups. These settings can be edited or changed at any time. Lamp Configuration: Used to configure flash rates for slow, fast and intermittent speeds as determined by the operating sequence. Sequence: Selection of the operating sequence for each alarm group. CSM: Switch Input: Modbus: DNP: Set-up of auxiliary relays and other system-wide functions. Set up for optional external switch inputs and Test Pushbutton operation. Modbus set-up configuration. (Only shown when option is enabled.) DNP set-up configuration. (Only shown when option is enabled.)
65
System
The hardware configuration is defined in this page. The values must match the actual size of the SERIES 90A. A mimic diagram of the annunciator is shown on the left hand side. The blank section on the bottom right of the annunciator is the Common Service Module (CSM).
Note: After the configuration is uploaded to the annunciator for the first time the system parameters cannot be edited. The controls will be disabled. Care should be taken that the System values are correct. To make a change, you must create a new configuration. System Name (ID) This name is used to uniquely identify the annunciator. Up to 16 characters may be used.
66
Rows and Columns of Modules Use the up or down arrows to the right of each value to set the actual number of modules. The AN3100D annunciators are limited to 13 rows or 13 columns and a maximum of 200 alarms or 50 Cells. (Example: a 13 x 4 system is not allowed, but a 5 x 10 is.) Alarm points per module There may be 1, 2 or 4 points per module as determined by your window size. Quad size windows use 4 points per cell, Triple Size windows use 3 per cell, Dual or Half Size windows use 2 per cell and Single or Full Size windows use 1 point per cell. By default all modules have the same number of points. If different numbers of points per module are required (Option IMW) click on the Advanced button. Hardwired inputs The default is that all inputs are hardwired, which refers to the field contacts wired to the back of the annunciator. On the mimic diagram the hardwired inputs are shown with a dot at the center. Non-hardwired inputs refers to inputs that are received via the serial communications. Non hard-wired inputs do not respond to the I/O cards or field contact inputs. Note: Serial Communications may be used for both Hardwired and NonHardwired systems. Input delay resolution This determines the system-wide increment value for the input delay (or response) for each alarm. It is used in conjunction with the individual input delay setting in the Input Configuration Screen. The setting is based on whether your maximum input delay will be 12.5 seconds or 250 seconds. You have 255 increments of the value selected. For the 50ms setting, you can have a selectable software delay in 50 msec increments up to 12.5seconds. For the 1sec setting, you have a selectable software delay in 1 second increments up to 250 seconds. Each input can have its own delay assigned as shown in the Input Configuration page, however, this system setting (50msec or 1 sec) is applied across the whole system. Integral Push Buttons (Option INTB, NPB) These are the pushbuttons located in the lower right cell of the Annunciator System. They include Annunciator Functions: Test, Acknowledge, Silence and Reset. They are provided when specified in the model number, using model code INTB. When model code NPB is specified, the integral pushbuttons are not installed and the software box should be unchecked, to allow up to two active alarm windows in this position. For either selection (INTB or NPB), external pushbuttons can be connected to the Annunciator terminal blocks with the same functionality. Single Input I/O board (Option 2S)
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 67
This is selected whenever window size option 2S (two point windows with single input per I/O board) is selected. The standard I/O board has two inputs available, but in certain configurations, as listed above, it is necessary to only activate a single input on this module. Dual Relay (Option 2RR) This will provide two repeat relay outputs (each selectable for Form A or Form B operation) for every input. This is only available whenever window size option 1 (single point windows) or 2S (two point windows with single input per I/O board) are selected. Flash Synch Master (Option FS) A software selection box is provided for flash synchronization between several different SERIES 90A Annunciators. In systems that require flash synchronization, one Annunciator is configured as the Master (box checked) and all others are configured as the Slave (unchecked). Wiring between the Annunciators is required to share the flash signals. (Reference the Common Service Cell Wiring diagrams.) In systems that don't require flash synchronization, the Flash Sync Master box must be checked. When setting up a system for flash synchronization, the flash lamp rates should be configured as follows: (reference the Lamp Configuration Screen) Master and Slave Lamp Flash Rates should be identical except, on the Slave units, set the Slow Flash On time approximately 0.1 sec lower than the Master. This ensures the slave unit is ready and waiting for the sync edge from the master. Set the Slow and Fast rates in even multiples. (Example: Slow Flash = 1.0 sec, Fast Flash = 0.5 sec). Use of intermittent flash is not recommended. Use alarm sequences that are either identical between master/slave units or ones that share the same flash rates (slow, fast, etc.) Note: If a Slave unit does not receive the flash synchronization signal from the Master unit, the slow flash will become steady on.
68
Input Configuration
The configuration of each alarm input is defined in this page. To simplify this procedure a number of similar inputs may be selected at the same time and common parameters set. An individual input is selected by clicking on it. The input will change color when selected. The input number will be shown in the Alarms list. To select a number of inputs hold down the Ctrl key while clicking on the inputs. To de-select an input press the Ctrl key and click on the input again. To select a rectangular block of inputs click on the top left hand one then drag down to the bottom right. When one or a number of inputs has been selected the parameters for those inputs may be set.
Alarm Numbering
The inputs are numbered left to right and top to bottom. The inputs within a module are numbered in sequence followed by the next module. So, for example, the top row of inputs of modules with four inputs each are:1, 2, 5, 6, 9, 10,
69
Relay Mode (optional) If the repeat relay option has been included with your system, you may select the Relay Mode for each input as follows:-
Follows Input Contact Normally Energized The repeat relay will follow the status of the field contact, regardless of the pushbuttons pressed. In this mode, the relay coil is energized in the normal (nonalarm) state. Follows Input Contact Normally De-Energized The repeat relay will follow the status of the field contact, regardless of the pushbuttons pressed. In this mode, the relay coil is de-energized in the normal (non-alarm) state. Latched Alarm till ACK Normally Energized The repeat relay will change state during an alarm and latch on until the acknowledge pushbutton is pressed, which returns the relay to the normal state. In this mode, the relay coil is energized in the normal (non-alarm) state. Latched Alarm till ACK Normally De-Energized The repeat relay will change state during an alarm and latch on until the acknowledge pushbutton is pressed, which returns the relay to the normal state. In this mode, the relay coil is de-energized in the normal (non-alarm) state. Latched Alarm till Reset Normally Energized The repeat relay will change state during an alarm and latch on until the reset pushbutton is pressed, which returns the relay to the normal state. In this mode, the relay coil is energized in the normal (non-alarm) state. Latched Alarm till Reset Normally De-Energized
70 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
The repeat relay will change state during an alarm and latch on until the reset pushbutton is pressed, which returns the relay to the normal state. In this mode, the relay coil is de-energized in the normal (non-alarm) state. Follows Lamp Display Normally De-Energized The repeat relay will follow the state of the lamp display for that input. When the display is flashing on and off, it will toggle open and closed at the slow flash rate. When the lamp display is on steady, the repeat relay contact will be closed. It will open when the lamp turns off. Note: In addition to these configurations, the repeat relay contact may be selected as a Form A or (Normally Open) or Form B (Normally Closed) using the I/O jumpers described in the previous section. Alarm Group Each input belongs to one of 4 groups. The groups define the alarm sequences that are set in the 'Group page. This allows up to 4 first out groups per system or four different sequences. Input delay This is also referred to as the input response time, which is the amount of time an input must be in the alarm state before it is recognized as a valid alarm. Each input may be set from 1 second to 250 seconds in 1 second increments or from 50 msec to 12.5 seconds in 50 milliseconds increments. The system wide input delay resolution (50ms or 1sec) is set on the System page. Systems with FR Option enabled (1 msec response) will have an additional software selection shown for 1 msec input. Note: The Input Delay is the total delay including hardware and software filtering. For AC Inputs, there will be an additional 40 msec hardware filtering delay added to these numbers. Critical alarm Alarms may be selected as critical or non-critical for segregating inputs into a common alarm relay output on the CSM. The CSM has separate relays for critical or non-critical horns, reflash and fault outputs. Any input in the system selected for critical or non-critical will activate the respective CSM relay output. By default, all alarms are set as non-critical. Modbus Transmit or Receive (Optional) If the Modbus option is included with your system, every input is defined for Transmit or Receive by clicking on the button. Transmit implies that the alarm status from hardwired contacts are sent serially to some other device. Receive implies that some other serial device is providing the status of the alarm and the Annunciator will respond as if it were a field contact input. You may choose
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 71
combinations of transmit and receive, but a single input cannot do both. You may also set up an input as receive while providing a hard-wired contact input to the same point. In this case, the Annunciator will respond to alarms from either the contact or serial input in a logic OR arrangement. If the option is not available this button is not displayed. It may also not be displayed if creating a new configuration. You must connect to your Annunciator to enable the serial Modbus configuration. Note: Systems with Serial Inputs only (not Hardwired) cannot be set to transmit. Panel Colors The color of each input in the mimic diagram may be changed to match the actual annunciator. To do this, select all the inputs with the same color as described above then click on Panel Colors'. From the color selector dialog choose any color. The custom colors represent the available window colors. Repeat this for each color. Table View Click on the Table View button to display the current input configuration in a table format. This is designed to be a summary of all the input configuration, but by clicking on the individual items you can change the selection from the table. The column widths may be adjusted by clicking and dragging on the vertical separators between the column titles.
72
Lamp Configuration The lamp flash rates are defined in this page. The operational sequence chosen determines whether a slow, fast or intermittent flash rate is used. For example; Sequence TFS uses all three rates while Sequence AF uses only the slow flash rate. Click on the up or down arrows beside each number to increment or decrement it. Click and hold on the arrows to scroll up or down. Click on the Test button to check the appearance of each flash rate. Fast & Slow flash rates The ON and OFF times are set up with a resolution of 0.1s. The maximum times are 4s. Intermittent rate The Intermittent period values will be automatically adjusted to ensure they are integer multiples of the sum of the Intermittent ON and OFF times. The maximum Intermittent Period ON and OFF values are 25s. Note: The intermittent on period may be adjusted automatically by the wizard so that it is set to at least one full intermittent on - off cycle.
73
Sequence
The alarm sequence for each input group is defined in this page. The Input Configuration page was used to indicate which of the four available groups was assigned to each input. This page identifies the sequence chosen for each group. Note: The four available groups can be set up for the same First-Out Sequence, but each group is treated separately as its own first out group. To change the alarm sequence, click on the entry then choose the sequence from the list. LN Automatic reset, non-locking, no flash, no audible, no PB AO Automatic reset with lock-in of alarms, no flash AONL Automatic reset, non locking, no flash AF Automatic reset with lock-in of alarms AFNL Automatic reset, non locking FR Automatic reset with lock-in of alarms, flash reset AM Manual Reset with lock-in of alarms FRM Manual Reset with lock-in of alarms, flash reset AS First out fast flash, subsequent alarm steady, auto reset ASFR First out fast flash, subsequent alarm steady, auto reset, w/ silence ASFRM First out fast flash, subsequent alarm steady, first out reset, w/ silence TFS First out, triple flash, first out reset TFSFRM First out, triple flash, first out reset, flash reset, reset TFSM First out, triple flash, first out reset, reset ARR Ringback, dual flash, lock-in of alarms until acknowledged FRR Ringback, dual flash, lock-in of alarms until acknowledged, flash reset VS First out, dual color, single flash, with first out reset VSRR First out with ringback, dual color, dual flash, with first out reset, reset MC Motor Control
74 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
The functions of the CSM are defined in this page. Common Relay There are 2 relays in the CSM and an additional 2 can be provided with option RLY. Each relay mode may be defined as either Energized or De-Energized, with respect to the power on, normal state. For example, a Energized Relay has a coil that is energized when power is applied and there is no alarm. When the output is activated, the coil will de-energize, transferring the contact output. The Standard relay functions may be selected from:Critical horn Auxiliary horn output driven by any alarm selected as critical. The horn relay output will return to its normal state upon activation of the silence or acknowledge pushbutton. Non-critical horn Auxiliary horn output driven by any alarm selected as noncritical. The horn relay output will return to its normal state upon activation of the silence or acknowledge pushbutton. Note: If a critical horn is used in addition to the non-critical horn, the critical horn has priority. For example; if the non-critical alarm is on and the Annunciator receives a critical alarm, the non-critical horn will turn off and the critical horn will turn on. When the critical horn is silenced, any new non-critical alarms will activate the non-critical horn. This operation can be changed in the common functions below. Ringback (clear horn) An output driven by the return to normal of an alarm input. Operated by sequences ARR, FRR, and VSRR only. The following functions are included with the RLY Relay Option: Critical Reflash Grouped output driven by any alarm selected as critical. Upon a critical alarm, the relay output changes state. Every new critical alarm will pulse the relay output for approximately second. The relay output will return to
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL 75
its normal state when all critical alarms have returned to normal. Non-Critical Reflash Grouped output driven by any alarm selected as noncritical. Upon a non-critical alarm, the relay output changes state. Every new noncritical alarm will pulse the relay output for approximately second. The relay output will return to its normal state when all critical alarms have returned to normal. Critical Fault This relay output will change state when any critical input is in the alarm state. The relay output will only return to its normal state when all critical alarms have returned to normal. The relay output is not affected by the silence or acknowledge pushbutton. Non-Critical Fault This relay output will change state when any non-critical input is in the alarm state. The relay output will only return to its normal state when all non-critical alarms have returned to normal. The relay output is not affected by the silence or acknowledge pushbutton. Power Fail This relay output will change state when the Power is lost. The relay coil is energized upon start-up and the contacts will transfer upon a loss of power. Ground Fault This relay output will change state when a ground fault condition is detected. (Note: Must have Ground Fault Detector Option GF) The ground fault can be either a positive ground (+FCV wire to ground) or a negative ground (FCV return wire to ground). Watchdog System healthy output. It will activate when the system is not processing alarms, like during the configuration process or when there is a system failure. The Watchdog will detect when there is a remote communication failure, if Modbus or DNP are used. The communication failure would activate after a period of inactivity, including a disconnected or broken cable. The Configuration Screen will show a summary of the Common Relay functions to the right. To select a relay to edit use the up or down arrows beside the relay number or click on the entry in the summary. Note: In addition to these configurations, the repeat relay contact may be selected as a Form A or (Normally Open) or Form B (Normally Closed) using the I/O jumpers described in the previous section. Common Functions A number of system-wide functions are available through the Common Service Module. To select a function click on the white box to the right of the name so as a tick mark appears. To turn the function off click on the box again so as the tick is removed. The available functions are:Enable Internal Horn (Option HN) When selected, this will activate the internal audible device upon any non-critical or critical horn condition.
76 SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
Internal Horn Silence (option AS) The internal horn (option HN) may be automatically silenced after a fixed time. To do this use the up and down arrows to the right of the value box to set the required time. The maximum value is 240s and the resolution is 1.0s. Note: A setting of 0 indicates that the auto-silence is not activated. External Horn Silence (Option AS) This will silence any external horn if selected for CSM Relay #1-4 in the time increment selected. This will automatically silence the Critical, Non-Critical or Ringback Horn when this option is included with the system. The maximum value is 240s and the resolution is 1.0s. Note: A setting of 0 indicates that the auto-silence is not activated. Auto Reset This will activate the Reset function continuously, eliminating the need to manually press this. (Note: this only applies to alarm sequences that require the reset function.) Critical Audible has no affect on non-critical This will make the operation of the non-critical horn independent of the critical horn. See the previous section on the operation of the non-critical audible. Critical Audible Pulsed This will pulse the critical audible output upon an alarm. Non-critical Audible Pulsed This will pulse the non-critical audible output upon an alarm. Ringback Audible Pulsed This will pulse the ringback audible output upon an alarm.
77
Switch Inputs
This screen is used to set up the optional External Switch Inputs (Option SW). The External Switch Inputs provide several inhibit functions that are commonly used when the system is left in a in-manned state and there is no need to flash alarms or sound horns. There are other configurations available on this page to configure the Test Pushbutton Operation.
Inhibit all CSM Relay Outputs If selected, whenever the switch is closed, all CSM Repeat Relay Outputs (Horns, Reflash and Fault) will be disabled. If the operational sequence chosen latches the alarm (AO, AM, etc.), any alarms that occurred while the inhibit switch was enabled as well as any current alarms will operate as soon as the switch returns to the off position.
Test Configuration
The following functions can be activated when the Test Pushbutton is used. It applies to the Integral Test Pushbutton on the CSM Module (Option INTB) and to an external Test Pushbutton wired into the Annunciator. 1. Audible If selected, the audible outputs (critical, non-critical and ringback horn) will be activated during the Test Function. The LED Lamps will always be activated during the Test Pushbutton. There is no selection to de-activate this.
2.
LED Lamps:
3.
Repeat Relays: If selected, the Repeat Relay outputs will be activated during the Test Function.
79
Modbus
Note: These options will only be available if the Modbus functionality has been purchased from AMETEK. Default values of the Modbus settings are given in Appendix B
The configuration application will always use the parity defined for the SERIES 90A. If the parity is changed it will not take affect until the current configuration session is complete. Baud Rate The Modbus baud rate may be selected from :1200 2400 4800 9600 19200
The configuration application will always use the baud rate defined for the SERIES 90A. If the baud rate is changed it will not take affect until the current configuration session is complete. Modbus Mode The Modbus Mode may be selected from:Master Slave
A Master unit may issue command functions and a slave unit responds to them. When the SERIES 90A configuration application is being used the SERIES 90A will be in slave mode independent of its Mode setting.
81
Data Type The Modbus Data Type may be selected from:AN3135 Point State Point State
Reference Appendix A for a complete description of these Data Types. Slave Address This is used when the SERIES 90A is selected as a Modbus Master. The Slave Address refers to the device that the Master is communicating to. Valid addresses are from 1 to 255. Transmit Controls If this option is selected, Acknowledge and Reset Pushbutton controls will be transmitted along with point data. (When communicating between two Annunciators, only one Annunciator may be set to Transmit Controls. As a default, the Annunciator will always accept or receive pushbutton controls from another device regardless if the Transmit Controls option is selected. Modbus Type This is a format in which the data is transmitted. Can be set to ASCII or RTU.
82
DNP3.0
Note: These options will only be available if the DNP3.0 functionality has been purchased from AMETEK. The DNP3.0 option is currently only available on the SERIES 90A annunciators. The default DNP settings are given in Appendix C.
84
Hot Keys
85
SYSTEM SPECIFICATIONS
INPUTS
Field Contacts Normally Open (N.O.) or Normally Closed (N.C.) Input selection through Software or Field Selectable Jumper Wet (voltage supplied) or dry (voltage free) contacts Field Contact Voltage (FCV) Common FCV or FCV Isolated Input to Input (Jumper Selectable) 12, 24, 48, 125 VDC, 120 VAC or 24VDC open collector Input Current Requirement: 0.0018 mA per input FCV Disconnect for an alarm when the I/O Module is removed (other alarms unaffected) Input Isolation Each input is optically isolated Input Response 1 millisecond 50 milliseconds 50 msec to 250 seconds (Fast Response, Option FR. Also used with SER option) Standard Response Adjustable in Software in 50 msec or 1 second increments
Display
Window Sizes Full Size (1 per Cell): Half Size (2 per Cell): Third Size (3 per Cell): Quad Size (4 per Cell): Illumination White LED 20 mA @5VDC Full Size Windows 8 LEDs / Input Half Size Windows 4 LEDs / Input Third Size Windows 2 LEDs / Input Quad Size Windows 2 LEDs / Input Window Color White, Red, Yellow, Amber, Green, Blue Legends Laser printed on transparency film or Engraved 3.0 x 3.0 (76 x 76mm) 1.5 x 3.0 (38 x 76mm) 1.0 x 3.0 (25 x 76mm) 1.5 x 1.5 (38 x 38mm)
87
88
Alarm Sequence
Sequence Selections LN AO AONL AF AFNL FR AM FRM AS ASFR ASFRM TFS TFSFRM TFSM ARR FRR VS VSRR MC Up to 4 Sequences per system (configured in software by input) Automatic reset, non-locking, no flash, no audible, no PB Automatic reset with lock-in of alarms, no flash Automatic reset, non locking, no flash Automatic reset with lock-in of alarms Automatic reset, non locking Automatic reset with lock-in of alarms, flash reset Manual Reset with lock-in of alarms Manual Reset with lock-in of alarms, flash reset First out fast flash, subsequent alarm steady, auto reset First out fast flash, subsequent alarm steady, auto reset, w/ silence First out fast flash, subsequent alarm steady, first out reset, w/ silence First out, triple flash, first out reset First out, triple flash, first out reset, flash reset, reset First out, triple flash, first out reset, reset Ringback, dual flash, lock-in of alarms until acknowledged Ringback, dual flash, lock-in of alarms until acknowledged, flash reset First out, dual color, single flash, with first out reset First out with ringback, dual color, dual flash, with first out reset, reset Motor Control
Customized flash rates 100 millisecond increments (Selectable in Software) First Out Groups Up to 4 first out groups per system 5 millisecond First Out Discrimination Lamp Synchronization Synchronize other displays to same flash rate. Master system outputs a pulse at the slow flash rate. Slaves re-sync to incoming lamp off edge. A master system may drive up to 5 slave units.
89
Controls
Pushbuttons Integral Pushbutton Option (INTB): Test, Acknowledge, Silence and Reset (4) External Pushbutton Inputs:Test, Acknowledge, Silence and Reset 5VDC @0.002 mA per Pushbutton (provided by Annunciator) Switch Input (Option SW) Software configurable for: Inhibit of LED Lamps, Horn, Repeat Relay Outputs or CSM Common Relay Outputs 5VDC @0.002 mA (provided by Annunciator)
System Relays
Alarm Grouping Critical or Non-Critical Alarms: Selectable in software per input Used to provide separate horns, or other relay outputs Critical Alarms have priority over Non-Critical (can be disabled) Standard Relays (2) Relays Software Configurable for: Critical or Non-Critical Horn, Ringback Horn Energized or De-Energized Relay Coil, selectable in Software Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper Optional Relays (Option RLY) (2) Additional Relays Software Configurable for: Critical or Non-Critical Horn, Ringback Horn, Critical or Non-Critical Reflash, Critical or Non-Critical Fault, Power Fail, System Watchdog, or Ground Fault Detect) Energized or De-Energized Relay Coil, selectable in Software Form A or Form B (N.O. or N.C.) Contact, Selectable by Jumper Relay Ratings: 24VDC @ 3.0 Amps 110VDC @ 0.1 Amps 120VAC @ 3.0 Amps Resistive Load
Audible Devices
Internal 80db @ 30cm audible device (option HN) External Audible Devices available
90
Communications
Communication Options
Option SIM Modbus Input Only No Yes Yes Yes Yes Yes Yes Yes Yes Option MB Modbus Input & Output Yes Yes Yes Yes Yes Yes Yes Yes Yes Option DNP DNP Output Yes No N/A No Yes Yes Yes Yes Yes Option SD Serial ASCII Output Time stamped alarms only No N/A N/A N/A No No Yes Yes
Function
Transmit Alarm Status via Serial Data Receive Alarm Status via Serial Data RTU or ASCII Mode Master Mode Slave Mode Transmit Local Pushbutton Controls Receive Remote Pushbutton Controls RS-232 / 485 Ethernet (Option ET)
Power Requirements
Input Power 19-29 VDC (Option F 24VDC) 38-58 VDC (Option E 48VDC) 100-250 VDC (Option C 125VDC) 88-132 VAC, 60 Hz (Option B 120VAC) 176-264 VAC, 50 Hz (Option A 230VAC) Input Burden: Maximum 2.2 Watts/point (depends on window size and options selected)
91
Mechanical
Enclosures: Semi-flush Panel Mount, 19 Rack Mount, Surface (wall) mount, NEMA Enclosures Depends on Annunciator Configuration (# of cells high x wide)
Size:
Connections / terminations
Field Contact Input, Relay Output, Power Input Terminals -Barrier Terminal Block, #6-32 screw. Accepts Ring, Spade Lug or Bare Wire -Wire size: 12-22 AWG Pushbutton/Switch Input, Lamp Synchronization Terminals -Barrier Terminal Block, #6-32 screw. Accepts Ring, Spade Lug or Bare Wire -Wire size: 14-22 AWG Serial Communication Port(s) 9 Pin Female D connector Ethernet Communication Port -RJ45 connector IRIG-B Time Synchronization Input -BNC connector
92
Environment
Operating Temperature Range: Storage Temperature Range: Humidity: -20 TO 50 OC (-4 to 122oF) -20 TO 80 OC (-4 to 176oF) 20-95% RH
Electrical
Surge Withstand: ANSI C37.90.1 (Oscillatory portion) Electrical Fast Transient/Burst Immunity: IEC 61000-4-4 (2kV DC Power, 1kV I/O) Surge Immunity: IEC 61000-4-5 (1kV Common Mode, line-to-ground) Dielectric Withstand: 1400 Vac or 2050 Vdc Inputs to Digital (test @ configuration port) 1400 Vac or 2050 Vdc Outputs to Digital (test @ configuration port) 1450 Vac or 2150 Vdc AC Integral Power Input to Digital (test @ configuration port) 350 Vac or 500 Vdc DC Integral Power Input to Digital (test @ configuration port) 1400 Vac or 2000 Vdc from Inputs to Outputs 1400 Vac or 2000 Vdc from Inputs to Power Input 250 V RMS from Input to Input when configured for Isolated Inputs 1400 Vac or 2000 Vdc from Outputs to Power Input 1200 Vac or 1700 Vdc from Output to Output 1400 Vac or 2000 Vdc from Inputs to Case 1200 Vac or 1700 Vdc from Outputs to Case 1400 Vac or 2000 Vdc from Integral AC Power to Case 350 Vac or 500 Vdc from Integral DC Power to Case 350 Vac or 500 Vdc from Communications Ports to DC Power 1450 Vac or 2150 Vdc from Communications Ports to AC Integral Power Input Radiated RFI Immunity: Conducted RFI Immunity: Radiated Emissions: Conducted Emissions: Radiated Power Frequency: ESD Effects: IEC 61000-4-3 10 V/m IEC 61000-4-6 3V
EN 61000-6-4 (EN55011) EN 61000-6-4 (EN55011) IEC 61000-4-8 IEC 61000-4-2 30 A/m Magnetic Field 4kV contact 8kV air
93
Certifications
CE: FM 1 FM-C1 UL: ULC: ULR CSA Low Voltage Directive 73/23/EEC: EN 61010-1:2001 EMC Directive 89/336/EEC: EN 61326:1998 Class 1, Division 2, groups A, B, C, and D (FM Canada) 2017 (UL Canada)
Requires FM option (refer to option codes). The required door may be supplied by Ametek, a panel shop or the customer. The door must meet the FM standard for requiring a tool to open or remove the door to allow access to the front of the Annunciator.
SERIES 90A ANNUNCIATOR INSTALLATION AND CONFIGURATION MANUAL
94
Servicing
Ensure that the power supply to the unit is switched off before servicing.
MODULE REMOVAL
When removing a module for replacement or configuration, it is best to shut off the power to prevent any false alarms or electric shock. When replacing any board, note the jumper settings and transfer them to the replacement module. If in doubt, refer to the module set-up instructions in this manual.
CAUTION
Note and record the window positions when removed from the chassis so as to ensure that the windows are replaced in their original locations Severe problems/damage could occur to monitored plant/equipment should windows be replaced in incorrect positions causing erroneous indication of alarms Only remove one window assembly at a time to minimise the possible incorrect repositioning of alarm display windows
95
ESD
ESD (Electrostatic Discharge) can damage sensitive electronics when they are being handled or touched. The Annunciator has been protected against certain levels of ESD when touching the outside case or terminals. The internal electronics may be susceptible to ESD when handled, so proper care should be given to any exposed electronics or circuit boards. The following guidelines should be used to prevent any build-up of ESD and to minimize the products exposure to it. 1. Prevent static build-up by using conductive paints, carpeting, mats and metal surfaces. Use appropriate grounding techniques, including wrist and heel straps for personnel. 2. Store or transport electronic devices, parts and assemblies in conductive bags or bins. 3. Only perform repairs at an appropriate repair station. 4. When handling electronic assemblies or printed circuit boards try to avoid touching traces on the printed circuit board or the static sensitive devices. 5. Remember that tools are a source of static electricity. Only use grounded soldering irons. Ground tools before using them to bleed off any charge buildup. 6. Discharge yourself before touching or handling any electronic assembly or device. This can be done by touching a good ground point before touching any electronic devices or assemblies. Preferably, discharge any static charge through a high impedance such as a wrist or heel strap.
96
APPENDIX A
OPERATIONAL SEQUENCES
The following are summary sequence descriptions provided for guidance.
AUTO RESET, NON LOCKING STATUS ONLY INDICATION, NO AUDIBLE
SEQUENCE CODE ALARM DEVICE NORMAL ALARM RETURN TO NORMAL
LN
ISA-A-4-5-6
VISUAL
AUDIBLE
AO
ISA-A-5
VISUAL
AUDIBLE
AONL
ISA-A-4-5
VISUAL
AUDIBLE
AF
ISA-A
VISUAL
AUDIBLE
97
AFNL
ISA-A-4
VISUAL
AUDIBLE
FR
VISUAL
AUDIBLE
AM
ISA-M
VISUAL
AUDIBLE
FRM
VISUAL
AUDIBLE
98
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
AS
ISA-F1-A
VISUAL
FAST FAST
AUDIBLE
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
ASFR
ISA-F1-A
VISUAL
FAST FAST FAST
AUDIBLE
FIRST OUT, FAST FLASH, LOCKING, FIRST OUT RESET WITH SILENCE
SEQUENCE CODE ALARM DEVICE NORMAL ALARM SILENCE ACKNOWLEDGE RETURN TO NORMAL RETURN TO NORMAL BEFORE ACK. INITIAL NEXT ACKNOWLEDGE RESET
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
RESET
ASFRM
ISA-F2M-1
VISUAL
FAST FAST FAST
AUDIBLE
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
RESET
TFS
ISA-F3A
VISUAL
SLOW INT. FAST FAST SLOW INT. FAST FAST SLOW
AUDIBLE
99
TFSFRM
VISUAL
INT. FAST FAST INT. FAST FAST SLOW
AUDIBLE
Note: The RESET and FIRST OUT RESET Pushbuttons are combined together at the same terminal.
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
RESET
TFSM
VISUAL
INT. FAST FAST SLOW
AUDIBLE
Note: The RESET and FIRST OUT RESET Pushbuttons are combined together at the same terminal.
ARR
ISA-R
VISUAL
FAST SLOW
AUDIBLE
Ringback Audible
100
FRR
VISUAL
FAST FAST SLOW
AUDIBLE
Ringback Audible
FIRST OUT, SINGLE FLASH DUAL COLOR WITH FIRST OUT RESET
SEQUENCE CODE ALARM DEVICE NORMAL ALARM ACKNOWLEDGE RETURN TO NORMAL FIRST OUT RESET FO RESET
INITIAL
NEXT
INITIAL
NEXT
INITIAL
NEXT
VS
VISUAL
LAMP 1 LAMP 2 LAMP 1 LAMP 2 LAMP 1 LAMP 2
AUDIBLE
Dual Lamp Sequences use only one input on each input card for a maximum of 2 alarms per window cell. Window Size 2 provides 1 alarm/cell, size 2S,2E & 4 provide 2 alarms/cell.
FIRST OUT, DUAL FLASH, DUAL COLOR, FIRST OUT RESET, RESET
SEQUENCE CODE ALARM DEVICE NORMAL ALARM ACKNOWLEDGE RETYURN TO NORMAL RESET FIRST OUT RESET NEXT FO RESET
INITIAL FAST
NEXT
INITIAL
NEXT
INITIAL SLOW
NEXT SLOW
INITIAL
FAST
VSRR
VISUAL
LAMP 1 LAMP 2 LAMP 1 LAMP 2 LAMP 1 LAMP 2 LAMP 1 LAMP 2
AUDIBLE
Ringback Audible
Dual Lamp Sequences use only one input on each input card for a maximum of 2 alarms per window cell. Window Size 2 provides 1 alarm/cell, size 2S,2E & 4 provide 2 alarms/cell.
101
MOTOR CONTROL
SEQUENCE CODE ALARM DEVICE MOTOR ON ALARM ACKNOWLEDGE MOTOR RESTART MANUAL STOP
MC
VISUAL
FAST SLOW
AUDIBLE
Note: The Manual Stop function is provided through the Reset Pushbutton. It is a common control for the entire system and provides a manual stop indication (lamps and horn off) to all inputs in the alarm state.
LEGEND
LAMP OFF
LAMP FLASHING
LAMP ON
HORN OFF
HORN ON
102
APPENDIX B
MODBUS DATA FORMATS
The system has the capability of operating with three distinct data formats: fault mode, alarm state mode and AN3135 mode. The latter is designed to be compatible with existing AN-3100C Modbus installations. All these formats are embedded within Modbus data registers for transmission and reception. A selection of Modbus function may be used and these vary depending on the whether the SERIES 90A is operating as Modbus master or slave.
Data Direction Function Description Data Units Master Slave Input 3 Read Holding Registers Words Output Output 6 Preset Single Register Words Input Input 7 Read Exception Status Bytes Output Preset Multiple Output 16 Registers Words Input Input 17 Report Slave ID Bytes Output SERIES 90A Supported Mode Master or slave Slave only Slave only Master or slave Slave only
A function value of 03 (Read Holding Registers) is set to read alarm data from the system (in slave configuration). Function values 06 (Preset Single Register) and 16 (Preset Multiple Registers) are used to write fault and control data. Single and multiple register writes are supported. Exception status responses (function 07) and Slave ID (function 17) are also supported. Exception codes for unrecognized received messages are also included. The Modbus functions are enabled by a software switch and require a key to enable them, which is supplied by AMETEK. This may be done prior to delivery or retrofitted to installed systems.
103
Point Mode
The system can present or accept (transmit or receive) raw field input point data plus alarm controls. Single and multiple register writes are supported. Data is again presented in a 16 bit register format. The last word of a transfer of input data may optionally contain control data. The data layout for a sample system configured for point data will be as below.
Word 1 .. 15 16 Bit15 AP 16 .. AP 240 . . Bit6 .. .. .. Bit5 .. .. .. Bit4 .. .. .. Bit3 .. .. .. Ack Rec Bit2 .. .. .. Rst Rec Bit1 .. .. .. Ack Tran Bit0 AP 01 .. AP 225 Rst Tran
AP refers to Alarm Point Channel. ACK refers to the Acknowledge Pushbutton and RST refers to the RESET Pushbutton. The local pushbutton controls (on the front of the Annunciator and other ones connected to the external pushbutton inputs) can be transmitted (Tran) to a remote device using Ack Tran and Rst Tran as shown. The Annunciator can also receive (Rec) the pushbutton controls from the remote device using Ack Rec and Rst Rec as shown.
104
AN3135 Mode
The system has the capability of mimicking the existing AN-3100C Modbus functionality. The object is to provide a system that is backwards compatible with the existing AN-3135 Modbus Module used on AN-3100C systems. The AN3135 mode is restricted to the default Functions of 03 to read alarm data and 06 and 16 being used to write fault and control data. The principal difference between this and the point mode above is that the AN3135 mode is restricted to 64 points. The data layout for a sample system configured for point data will be as below.
Word
1 .. 4 5
Bit15
AP 16 .. AP 64
Bit6
.. .. ..
Bit5
.. .. ..
Bit4
.. .. ..
Bit3
.. .. .. Ack Rec
Bit2
.. .. .. Rst Rec
Bit1
.. .. .. Ack Tran
Bit0
AP 01 .. AP 49 Rst Tran
AP refers to Alarm Point Channel. ACK refers to the Acknowledge Pushbutton and RST refers to the RESET Pushbutton. The local pushbutton controls (on the front of the Annunciator and other ones connected to the external pushbutton inputs) can be transmitted (Tran) to a remote device using Ack Tran and Rst Tran as shown. The Annunciator can also receive (Rec) the pushbutton controls from the remote device using Ack Rec and Rst Rec as shown.
105
Event Data
Event data may be read in blocks of 10 events at a time. These appear in a block of 60 registers (6 per event) located at the configured Start Address plus 1000 i.e. if the Start Address is set to 40001 then the events appear at 41001-41060. Once ten events are read then the registers are reloaded with any subsequent ones from the 500 event buffer. If no event has occurred, then all 12 bytes are filled with FF HEX. The event data format is as shown below:
Word 1 2 3 4 5 6 MSB Year Day Minute Millisecond (0-999) 0x00 IRIG-B Sync LSB Month Hour Second Input Point No. 1 = Point on 0 = Point off
10th Event
Year (0-99) high byte / Month (1-12)low byte Day of month (1-31)high byte /Hours (0-23) low byte Minutes (0-59) high byte / Seconds (0-59) low byte Milliseconds (0-999) two bytes SERIES 90A Point Number (1-198) IRIG-B Sync high byte / Point Status (1 = A, 0 = N) low byte
106
Modbus Addresses
Conventional addresses are included in the configuration. The input and output functions here are the most commonly used and refer to a system in slave configuration.
Conventional Start address 00000 10000 30000 40000* 60000 Data Output Coils Discrete Inputs Input Registers Holding (output) Registers Extended Memory Input Functions 05,15 Output Functions 01 02 04 03
06,16
Default Values
Designation Modbus Address Receive Start Address Transmit Start Address Modbus Mode Data type Baud rate Parity Transmit controls Data direction Modbus format Options 0-255 40001-49999 40001-49999 Master/Slave AN3135 /Point/State 2400/4800/ 9600/19200 Odd/Even/none Yes/No Input/output ASCII/RTU Default 01 40001 40001 Slave Point 9600 None Output RTU Parity type Send alarm control (ACK, RST) data 1 bit per point to designate Tx/Rx data Comments Register address entry.
107
APPENDIX C
DNP DATA FORMATS
The DNP Communication option is used to transmit point status (Binary Inputs) to other devices. When the SER time-stamped alarms option is enabled, a historical record of binary input change events and the time at which they occurred can also be sent. The DNP Communications work in a slave mode and operate over RS-232/485 or Ethernet. The DNP implementation is outlined in the Device Profile Document.
DNP V3.0
DEVICE PROFILE DOCUMENT
Vendor Name: AMETEK Power Instruments Device Name: AN3100D, using the Triangle MicroWorks, Inc. DNP3 Multi-Port Slave Source Code Library Highest DNP Level Supported: Device Function: For Requests: Level 2 Slave For Responses: Level 2 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the complete list is described in the attached table): For static (non-change-event) object requests, request qualifier codes 00 and 01 (start-stop), and 17 and 28 (index) are supported in addition to request qualifier code 06 (no range or all points). Static object requests received with qualifiers 00, 01 or 06, will be responded to with qualifiers 00 or 01. Static object requests received with qualifiers 17 or 28 will be responded to with qualifiers 17 or 28. For change-event object requests, qualifier codes 06 (no range) and 07 and 08 (limited quantity) are supported. Qualifiers 17 or 28 are always returned. Maximum Data Link Frame Size (octets): Transmitted: 292 Received 292 Maximum Data Link Re-tries: Configurable from 0 to 255 Maximum Application Fragment Size (octets): Transmitted: 170 Received 50 Maximum Application Layer Re-tries: None
Requires Data Link Layer Confirmation: Configurable as: Never, Only for multi-frame messages, or Always Requires Application Layer Confirmation: When sending multi-fragment responses (Slave devices only) Sometimes
108
DNP V3.0
DEVICE PROFILE DOCUMENT
Timeouts while waiting for: Data Link Confirm: Configurable. Complete Appl. Fragment: None Application Confirm: Configurable. Complete Appl. Response: None Others: Transmission Delay, configurable Inter-character Timeout, 1 second Need Time Delay, configurable
Never Never Never Never Never Never Never Never Never Never Never Reports time-tagged Binary Input Change Events when no specific variation requested: Never Sends Static Data in Unsolicited Responses: Never No other options are permitted. Counters Roll Over at: No Counters Reported
Reports Binary Input Change Events when no specific variation requested: Never Sends Unsolicited Responses: Never Default Counter Object/Variation: Default Object 1 Default Variation: 1
Yes
IMPLEMENTATION TABLE
OBJECT
Object Numbe r 1 Variation Number 1 Description
REQUEST
Function Codes (decimal) 1 (read)
RESPONSE
Function Codes (decimal) 129 (response) Qualifier Codes (hex) 00, 01 (startstop)
Binary Input
109
PUSHBUTTON CONTROLS
Pushbutton activation can be transmitted from the Annunciator via a Binary input to indicate whenever a pushbutton is activated locally at the Annunciator. (Reference the Binary Input Data Map for location of the pushbutton indications.) Pushbutton controls can be sent to the Annunciator using a Control Relay Output block, as detailed below. Control Relay Output Block (Object 12, variation 2) DNP Object Index #
00 Object Numbe r 10 Variation Number 02
LON, Reset Pushbutton LOFF * LON, 01 10 02 Acknowledge Pushbutton LOFF * For proper pushbutton operation, transmit a single LON (latch on) followed by a single LOFF (latch off). Allow a few seconds in between commands to ensure the Annunciator receives the pushbutton controls. Mode: Direct 16 Bit Index The Pushbutton Control Status can be checked by issuing a Binary Output Status, Object 10, variation 2. Binary Output Status (Object 10, Variation 2) DNP Object Index #
00 01 Object Number 10 10 Variation Number 02 02
Description
Reset Pushbutton Acknowledge Pushbutton
110
Description
Point 1 Digital Contact Alarm Point 2 Digital Contact Alarm Point 3 Digital Contact Alarm Point 4 Digital Contact Alarm Point 5 Digital Contact Alarm Point 6 Digital Contact Alarm Point 7 Digital Contact Alarm Point 8 Digital Contact Alarm Point 9 Digital Contact Alarm Point 10 Digital Contact Alarm Point 11 Digital Contact Alarm
01 01 01 01 01 01
00 00 00 00 00 00
Point 197 Digital Contact Alarm Point 198 Digital Contact Alarm Point 199 Digital Contact Alarm Point 200 Digital Contact Alarm Acknowledge Pushbutton Reset Pushbutton
Description
Digital Contact Alarm w/time of event
111
APPENDIX D
WINDOW ASSEMBLY DETAILS
The Annunciator uses a common window assembly for all window configurations. The different window options are created using dividers (for the 4 window sizes) and colored filters for the different window colors (white, red, blue, green, amber, yellow). The assembly drawings on the next page identify the different options available. A typical window consists of the following parts: Transparency film with Legends Colored Filter if required (red, blue, green, amber, yellow) White Diffusers (to eliminate LED hotspots)
All of these parts are pressed into the clear window, which is inserted into the window frame.
Window Legends
The Annunciator Window Legends are typically printed on clear transparency film, which is provided with the Annunciator. There is an option to engrave these legends directly on the window (Option E). For printing of legends on the transparency film, the Software CD will include a template in Microsoft Excel. You type the legend in the window template that matches your size window and print on a suitable printer. (A laser printer is recommended or any type that is compatible with printing on Transparency film.)
Window Colors
The Annunciator Window Colors are provided through colored filters, which are provided with the Annunciator. In cases where several different window colors are required for an individual Cell (option IMC), the laser printed transparency will be colored in place of the color filters. In these cases, color Laser Printer should be used. Note: All legends and pre-printed colors will be provided with the Annunciator if the details are provided before the unit ships.
112
TWO WHITE DIFFUSERS, ONE COLOR DIFFUSER, ONE CLEAR LEGEND TWO WHITE DIFFUSERS. ONE CLEAR LEGEND
TOUCHPAD TWO DIVIDERS USED TO SUPPORT TOUCHPAD SUPPORT
MEMBRANE TOUCHPAD
ENGRAVED LEGEND
FIGURE 3
10 SEE NOTE 1
12
INDEXPART NUMBER
8 9 10 11 1085-252 1085-394 1085-400 1085-396 12 1085-397 13 14 16 1085-398 1085-399 1085-389
DESCRIPTION
Window Assembly
9 10 SEE NOTE 1 THIS VIEW SHOWN WITH ALL PARTS FOR ANY CONFIGURATION.
WINDOW, MOLDED
WINDOW FRAME
NOTES: 1. DIVIDER QUANTITY AND LOCATION IS DEPENDANT ON CELL ALARM CONFIGURATION. 2. SEE FIGURES 1, 2, AND 3 FOR WINDOW CONFIGURATIONS. FIG 1A: THESE THREE ITEMS ARE USED TOGETHER FOR THE PRINTED LEGEND WITH WHITE WINDOWS
14
FIG 1B: THESE FOUR ITEMS ARE USED TOGETHER FOR THE PRINTED LEGEND FOR COLORED WINDOWS FIG 2: THIS ITEM IS USED WITH A CELL MEMBRANE TOUCHPAD OPTION. FIG 3: THIS ITEM IS USED FOR THE ENGRAVED LEGEND OPTION.
113
APPENDIX E
TELEPHONE / FAX NUMBER LIST
This errata sheet provides an easy-to-use reference for all major departments. Use these numbers for ordering equipment, application assistance, technical support, and scheduling field service Please Note: Your instruction manual may contain other phone and fax numbers; this list will take precedence. MAIN OFFICE AMETEK Power Instruments Rochester 255 North Union St., Rochester, NY 14605
DEPARTMENT/PRODUCT LINE MAIN PHONE FIELD SERVICE REPAIRS/RETURNS SALES SUPPORT TELEPHONE 585-263-7700 800-374-4835 888-222-6282 800-950-5503 FAX 585-262-4777 585-238-4945 585-238-4945 585-454-7805
UK OFFICE
AMETEK Power Instruments Unit 20, Ridgeway Donibristle Industrial Estate Dunfermline, UK Tel: 1383-825630 Fax: 1383-825715
115
Name and telephone number of person to contact if questions arise. Enclose the information with the equipment and pack in a commercially accepted shipping container with sufficient packing material to insure that no shipping damage will occur. Mark the outside of the container with the RMA number. Ship to the appropriate location
Attention: Repair Department AMETEK Power Instruments 255 North Union Street Rochester, New York 14605 USA Tel: (888) 222-6282 Fax: (585) 238-4945
Your emergency equipment will be tested, repaired and inspected at the factory. Factory turnaround is ten working days or less (excluding shipping time). For emergency service or repair status information, please contact the AMETEK Repair Sales Engineer at (800) 374-4835.
WARRANTY
AMETEK warrants equipment of its own manufacture to be free from defects in material and workmanship, under normal conditions of use and service. AMETEK will replace any component found to be defective, upon its return, transportation charges prepaid, within one year of its original purchase. AMETEK will extend the same warranty protection on accessories that is extended to AMETEK by the original manufacturer. AMETEK assumes no responsibility, expressed or implied, beyond its obligation to replace any component involved. Such warranty is in lieu of all other warranties expressed or implied.
117