Nonlinear Control of UPFC in Power System For Damping Inter Area Oscillations
Nonlinear Control of UPFC in Power System For Damping Inter Area Oscillations
Abstract: This paper introduces a new nonlinear control Therefore developing suitable control strategies is
of flexible ac transmission systems (FACTS) controllers for a requirement before FACTS can be confidently utilized in
the purpose of damping interarea oscillations in power the power system. Several authors have investigated
systems. FACTS controllers consist of series, shunt, or a utilizing FACTS, especially UPFCs to damp interarea
combination of series-shunt devices which are interfaced oscillations using a variety of control approaches [1]–[10].
with the bulk power system through injection buses. Interarea oscillations can occur in a system because of
Controlling the angle of these buses can effectively damp contingencies such as sudden load changes or faults. In [1]–
low frequency interarea oscillations in the system. The [5], oscillation damping is based on a linear control
proposed control method is based on finding an equivalent approach to the UPFC and power system, whereas other
reduced affine nonlinear system for the network from which authors consider nonlinear control systems theory and
the dominant machines are extracted based on dynamic Lyapunov Energy Functions [6]–[10]. Typically, nonlinear
coherency. It is shown that if properly selected, approaches are more effective for large perturbations or
measurements obtained from this subsystem of machines when the power system state strays significantly from the
are sufficient inputs to the FACTS controllers to stabilize initial operating point.
the power system. The effectiveness of the proposed method
on damping interarea oscillations is validated on the 68 The approach proposed in this paper provides
bus, 16 generator system of the New England/New York a general nonlinear method for using multiple FACTS
network. controllers in a power network for the purpose of damping
interarea oscillations. In this paper, it is shown that any
IndexTerms: Coherent groups, dominant machines, FACTS device capable of changing its interface bus
flexible ac transmission systems (FACTS), interarea angle(s) with the network can be used to mitigate power
oscillation, nonlinear control, phasor measurement unit system oscillations. Using this method, it will be shown that
(PMU), wide-area control. both shunt and series FACTS controllers can be used for
this purpose. The control method is based on finding a
I. INTRODUCTION reduced nonlinear affine state space system for the network
which can be controlled by feedback of selected
AS high voltage power electronics become less measurements of rotor frequencies. While frequency
expensive and have a wider-range of operation, flexible ac measurements (such as from FNET [11]) have made wide
transmission systems (FACTS) controllers will become area control of the power networks feasible, it is still not
more prevalent in the transmission system to control active reasonable to expect that the full set of frequency
power flow across congested corridors and ensure voltage measurements is available for controller use. Therefore, an
security. In addition, FACTS controllers can provide approach is proposed to use a reduced set of measurements
promising solutions to many of the stability problems that from a subset of machines in the system.
occur within the bulk power system. FACTS controllers can II. UPFC MODEL
be categorized into three major groups: shunt devices such
as the Static Synchronous Compensator (STATCOM), The UPFC is the most versatile FACTS device. It
series devices such as the static synchronous series consists of a combination of a shunt and series branches
compensator (SSSC) and series shunt devices such as the connected through the DC capacitor as shown in Fig. 1.
unified power flow controller (UPFC). In addition to Models for the STATCOM and SSSC can be easily
steady-state solutions such as power flow and voltage extracted from the UPFC model by considering the shunt
control, an added benefit of FACTS controllers deployed in and series converters individually. The series connected
the transmission system is that they can also effectively inverter injects a voltage with controllable magnitude and
Control active power oscillations that can damage phase angle in series with the transmission line, therefore
generators, increase line losses, and increase wear and tear providing active and reactive power to the transmission
on network components. line. The shunt-connected inverter
For control development purposes, several The controller design consists of three stages.
initial assumptions are made. The first assumption is that A. Stage I
the system loads are modeled as constant impedance loads The objective of the first design stage is to find
the desired changes in mechanical powers required to
and can therefore be absorbed into the bus admittance
matrix. Second, the generators are modeled as the classical stabilize the system. To obtain the amount of mechanical
―transient reactance behind constant voltage‖ model. Note power required, it is initially assumed that the mechanical
that these assumptions are for control development only— powers ,are inputs into the system model. Note that
the proposed control is validated with the full nonlinear 10- this is only for controller development; in the final control,
th order power system model given in the Appendix [13]. it is not required that the generator mechanical powers
In addition, the proposed control is developed for the actually vary.
UPFC; control development for the STATCOM and SSSC Under this assumption, the system models are
follows a similar procedure and is therefore not explicitly ……………………… (5)
detailed.
−3𝐿1 ∗ 𝑅 𝐿1 𝑉2 cos 𝜃2
𝑢3 = 𝑖 − 𝑖𝑑2 + 1 𝑖𝑑2 − 𝑖 + −
𝜔 𝑠 𝑣𝑑𝑐 𝑇 𝑑 2 𝑉 𝑑𝑐 𝑉 𝑑𝑐 𝑞2 𝑉 𝑑𝑐
𝑉 cos 𝜃1 𝐿2 𝑑 ∗
+ 1 𝑖 ……..(25)
𝑉 𝜔 𝑉 𝑑𝑡 𝑑2
𝑑𝑐 𝑠 𝑑𝑐
−3𝐿2 𝑅 𝐿 𝑉2 sin 𝜃2
𝑢4 = 𝜔 ∗
𝑖𝑞2 − 𝑖𝑞2 + 𝑉 2 𝑖𝑞2 − 𝑉 2 𝑖𝑑2 + − Fig. 3. Three stage control process.
𝑠 𝑣𝑑𝑐 𝑇 𝑑𝑐 𝑑𝑐 𝑉 𝑑𝑐
𝑉1 sin 𝜃1 𝐿1 𝑑 ∗
+𝜔 𝑖 𝑞1 ……..(26) 𝑢2
𝑉 𝑑𝑐 𝑠 𝑉 𝑑𝑐 𝑑𝑡 𝛼1 = tan−1 ………(28)
𝑢1
These inputs are then translated into the control inputs for 𝑘2 = 𝑢32 + 𝑢42 ……(29)
−1 𝑢 4
the UPFC 𝛼2 = tan ………….(30)
𝑢3
𝑘1 = 𝑢12 + 𝑢22 …………..(27)
The three stage control process and outcomes of each
stage are summarized in Fig.3
𝑋𝑄+1,𝑄+1 ⋯ 𝑋𝑄+1,𝑁
∆𝛿𝑄+1
⋮ ⋱ ⋮ ⋮ =
𝑋𝑁,𝑄+1 ⋯ 𝑋𝑁,𝑁
∆𝛿𝑁
𝑄 𝑁+𝑛
𝑘=1 𝑋𝑄+1,𝑘 ∆𝛿𝑘 − 𝑘=𝑁+1 𝑋𝑄+1,𝑘 ∆𝛿𝑘
⋮ ….(31)
𝑄 𝑁+𝑛
𝑘=1 𝑋𝑁,𝑘 ∆𝛿𝑘 − 𝑘=𝑁+1 𝑋𝑁,𝑘 ∆𝛿𝑘
Where
Fig. 4. The 68 bus, 16 generator test system
𝜇 𝑖𝑗
𝑥𝑖,𝑗 = ……………(32)
𝜇 𝑖𝑖
V. SELECTIVEFEEDBACKMEASUREMENTS And
BASEDON DOMINANT MACHINES 𝜇𝑖𝑗 = −𝐸𝑖 𝐸𝑗 𝑌𝑖𝑗 sin(𝛿𝑖 − 𝛿𝑗 − 𝜑𝑖𝑗 ) i≠j …..(33)
The control method proposed in the previous 𝑁+𝑛
𝜇𝑖𝑖 = − 𝑘≠𝑖 𝐸𝑖 𝐸𝑗 𝑌𝑖𝑗 sin(𝛿𝑖 − 𝛿𝑗 − 𝜑𝑖𝑗 ) i=j ……….(34)
section requires generator rotor frequencies to be
implemented. Although with recent advances in wide area
frequency measurement (FNET) it may be possible to Note than when only the dominant machines are
provide synchronized global measurements, it is still not selected for the control action, only the rows corresponding
feasible to assume that all generator rotor frequencies are to the dominant machines will be used thereby reducing
simultaneously available. However, it is reasonable to the order of the system. This is advantageous since the
assume that a subset of the measurements are available for pseudo-inverse required to solve the set of equations is
feedback and the remainder of the states can be estimated more nearly square providing better convergence.
based on the available measurements. The most probable
machines to obtain measurements from are those machines VI. EXAMPLE AND RESULTS
which dominate coherent groups.
There are numerous methods for calculating Although the control has been developed
coherent groups in the literature [15]–[18]. In [18], the using the classical generator model, the control approach
coherency identification method is based on modal will be validated using the full 10th order model which
analysis and Gaussian elimination with full pivoting on the includes an exciter/AVR, turbine, and governor dynamics.
selected eigenvectors of the system to find the reference The model is given in the Appendix. The proposed control
generators and their group members. is validated on the 68 bus, 16 generator New England/New
The selected eigenvectors are chosen based on the York test system shown in Fig. 4. The coherent groupings
lowest oscillatory modes of the system. Once the dominant corresponding to the five slowest modes are indicated by
machines are found, a reduced order system is computed the dashed lines in Fig. 4. The network data and coherent
which captures the ―slow‖ dynamics of the original system. groupings are the same as in [19]. The transmission tie
In this process, the remaining unmeasured states of the lines are shown with bold lines. The reference generators
system can be estimated based on the states which are for the five areas are G5, G13, G14, G15, and G16.
measured via singular perturbation [13]. Let the dominant