0% found this document useful (0 votes)
39 views

FST Dfs Controlnet x30

The driver allows a FieldServer to emulate a single ControlNet slave station. A FieldServer can connect to a ControlNet network via BNC connectors and be scheduled by a configuration tool to exchange up to 450 bytes of data via scheduled communication. It supports common data types like integers, floats, and bits for transferring data to and from a ControlNet master via input and output buffers.

Uploaded by

Eric Dunn
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views

FST Dfs Controlnet x30

The driver allows a FieldServer to emulate a single ControlNet slave station. A FieldServer can connect to a ControlNet network via BNC connectors and be scheduled by a configuration tool to exchange up to 450 bytes of data via scheduled communication. It supports common data types like integers, floats, and bits for transferring data to and from a ControlNet master via input and output buffers.

Uploaded by

Eric Dunn
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Protocol Driver

FieldServer Driver - Fieldbus


FS8700104

ControlNet X30 Adapter Driver


Description The FieldServer ControlNet X30 Adapter driver can be used to emulate a single slave station on a ControlNet network. ControlNet scanners can open a connection of up to 450 Bytes in each direction to the FieldServer. Data transfers are via Scheduled Communication and therefore the FieldServer has to be scheduled on the ControlNet network with the use of a Network Configuration Tool such as RSNetWorx or RSLogix. The minimum supported network update time (NUT) is 5ms. Connection to the ControlNet network is via two standard BNC connector ports. The connection may be to either one or both of the ControlNet ports. A connection to both ports provides dual redundant operation. A Network Access Port (NAP) is also provided for the temporary connection of a Network Configuration Tool. Fieldserver Mode Server Nodes 1 Comments The FieldServer can only emulate one ControlNet Slave station

Formal Driver Type Fieldbus Server Only Compatibility Matrix FieldServer Model FS-x2010 FS-x2011 FS-x40 FS-x30 Connection Information Connection type: Baud Rates: Hardware interface: Proprietary 5 Mbit/s Anybus-S ControlNet Compatible with this driver No No No Yes

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: [email protected] Website: www.fieldserver.com Page 1 of 4

Protocol Driver

Proprietary Physical Interfaces Supported Fieldserver Model FS-x30 Devices tested Device SST-5136-CN-ISA Connection configurations Tested (FACTORY, SITE) FieldServer Technologies Adapter Model # Anybus-S ControlNet Vendor HMS Networks Physical Medium 75 Co-ax

Connection Notes Recommended cable is RG-6 quad shield Co-ax.

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: [email protected] Website: www.fieldserver.com Page 2 of 4

Protocol Driver

Communications functions - Supported functions at a glance: Data Types Supported FieldServer Data Type 2-byte Integer ( Signed and Unsigned ) 8-bit Byte 4-byte Float Bit Data Operations supported FieldServer as a ControlNet Slave Accept Output Buffer Data from a ControlNet Master (Scanner) Provide Input Buffer Data to a ControlNet Master (Scanner) Unsupported Functions and Data Types Function Programming messages Reason FieldServer is a data transfer device, and as such, programming messages are not required Description (or Device Data Type) Buffer arranged as WORDS Buffer arranged as BYTES Buffer arranged as DWORDS Buffer arranged as BYTES